100% found this document useful (1 vote)
788 views30 pages

EN 12255 4 Wastewater Treatment Plants P

This European standard provides requirements and guidance for the design, construction, and operation of primary treatment systems in wastewater treatment plants. It covers the planning and design considerations for primary treatment, including required data and information as well as the advantages and disadvantages of different primary treatment systems.

Uploaded by

Hoài An Lê
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
788 views30 pages

EN 12255 4 Wastewater Treatment Plants P

This European standard provides requirements and guidance for the design, construction, and operation of primary treatment systems in wastewater treatment plants. It covers the planning and design considerations for primary treatment, including required data and information as well as the advantages and disadvantages of different primary treatment systems.

Uploaded by

Hoài An Lê
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 30

BS EN 12255‑4:2023

m /
. c o
ge s
a - gau
n
w .chi
BSI Standards Publication/ w w
tp : /
ht

Wastewater treatment plants

Part 4: Primary treatment


BS EN 12255‑4:2023 BRITISH STANDARD

National foreword

/
This British Standard is the UK implementation of EN 12255‑4:2023. It
m
supersedes BS EN 12255‑4:2002, which is withdrawn.
. c o
e s
The UK participation in its preparation was entrusted to Technical
g
gau
Committee B/505/40, Wastewater Treatment Plants > 50 PT.

n a -
A list of organizations represented on this committee can be obtained on

chi
request to its committee manager.

.
Contractual and legal considerations
w
w w
This publication has been prepared in good faith, however no
/
: /
representation, warranty, assurance or undertaking (express or

h ttp
implied) is or will be made, and no responsibility or liability is or will be
accepted by BSI in relation to the adequacy, accuracy, completeness or
reasonableness of this publication. All and any such responsibility and
liability is expressly disclaimed to the full extent permitted by the law.
This publication is provided as is, and is to be used at the
recipient’s own risk.
The recipient is advised to consider seeking professional guidance with
respect to its use of this publication.
This publication is not intended to constitute a contract. Users are
responsible for its correct application.
© The British Standards Institution 2023
Published by BSI Standards Limited 2023
ISBN 978 0 539 14384 3
ICS 13.060.30
Compliance with a British Standard cannot confer immunity from
legal obligations.
This British Standard was published under the authority of the
Standards Policy and Strategy Committee on 31 March 2023.

Amendments/corrigenda issued since publication


Date Text affected
BS EN 12255‑4:2023

EUROPEAN STANDARD EN 12255-4


NORME EUROPÉENNE
EUROPÄISCHE NORM March 2023

m /
ICS 13.060.30
. co
Supersedes EN 12255-4:2002
s
a u
English Version
ge
a g
-Primary treatment
i
Wastewater treatment plants - Part
h n4:
w. c
Stations d'épuration - Partie 4 : Traitement primaire Kläranlagen - Teil 4: Vorklärung

/ w w
p : /
This European Standard was approved by CEN on 9 January 2023.
t
ht
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.

EUROPEAN COMMITTEE FOR STANDARDIZATION


COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels

© 2023 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 12255-4:2023 E
worldwide for CEN national Members.
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

Contents
m / Page

s . co
European foreword....................................................................................................................................................... 3

u ge
Introduction .................................................................................................................................................................... 5
a
1 - g
Scope .................................................................................................................................................................... 6
a
2
hi n
Normative references .................................................................................................................................... 6
3
w.c
Terms and definitions ................................................................................................................................... 6
4
/ w w
Symbols and abbreviations ......................................................................................................................... 7
: /
5
5.1 h ttp
Requirements ................................................................................................................................................... 7
General ................................................................................................................................................................ 7
5.2 Planning .............................................................................................................................................................. 8
5.2.1 Required Data and Information ................................................................................................................. 8
5.2.2 Advantages and Disadvantages of Primary Treatment Systems ................................................ 10
5.2.3 Performance .................................................................................................................................................. 11
5.3 Design ............................................................................................................................................................... 12
5.3.1 General ............................................................................................................................................................. 12
5.3.2 Specifications ................................................................................................................................................. 12
5.3.3 Required Capacity ........................................................................................................................................ 12
5.3.4 Systems for primary treatment............................................................................................................... 12
5.3.5 Materials.......................................................................................................................................................... 17
5.3.6 Control and Automation ............................................................................................................................ 17
5.3.7 Operation and Maintenance ..................................................................................................................... 17
5.3.8 Health and Safety.......................................................................................................................................... 17
Annex A (informative) Illustrations of typical clarifiers ............................................................................. 18
Annex B (normative) Dimensions and tolerances for the structures of clarifiers ............................ 26
Bibliography ................................................................................................................................................................. 27

2
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

European foreword

m
This document (EN 12255-4:2023) has been prepared by Technical Committee CEN/TC 165 “Waste
/
water engineering”, the secretariat of which is held by DIN.
s . co
u ge
This European Standard shall be given the status of a national standard, either by publication of an
a
shall be withdrawn at the latest by September 2023. a - g
identical text or by endorsement, at the latest by September 2023, and conflicting national standards

hi n
.c
Attention is drawn to the possibility that some of the elements of this document may be the subject of
w
/ w w
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.

: /
ttp
This document supersedes EN 12255-4:2002.

h
It is the fourth part prepared by the Working Group CEN/TC 165/WG 40 relating to the general
requirements and processes for treatment plants for a total number of inhabitants and population
equivalents (PT) over 50.

The EN 12255 series, Wastewater treatment plants, consists of the following parts:

— Part 1: General construction principles

— Part 2: Storm management systems

— Part 3: Preliminary treatment

— Part 4: Primary treatment

— Part 5: Lagooning processes

— Part 6: Activated sludge process

— Part 7: Biological fixed-film reactors

— Part 8: Sludge treatment and storage

— Part 9: Odour control and ventilation

— Part 10: Safety principles

— Part 11: General data required

— Part 12: Control and automation

— Part 13: Chemical treatment — Treatment of wastewater by precipitation/flocculation

— Part 14: Disinfection

— Part 15: Measurement of the oxygen transfer in clean water in aeration tanks of activated sludge
plants

— Part 16: Physical (mechanical) filtration

3
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

NOTE 1 Part 2 is under preparation.

NOTE 2 For requirements on pumping installations at wastewater treatment plants, see EN 752, Drain and

outside buildings — Pumping systems. m /


sewer systems outside buildings — Sewer system management and EN 16932 (all parts), Drain and sewer systems

s . co
ge
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
g a u
a -
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
n
.c hi
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland,
w
Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of
w
United Kingdom. : / w
North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and the
/
h ttp

4
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

Introduction

/
Differences in wastewater treatment throughout Europe have led to a variety of systems being
m
co
developed. This document gives fundamental information about the systems; this document has not
.
attempted to specify all available systems. A generic arrangement of wastewater treatment plants is
s
illustrated below in Figure 1:

a u ge
a - g
hi n
w.c
/ w w
: /
h ttp

Key
1 preliminary treatment
2 primary treatment
3 secondary treatment
4 tertiary treatment
5 additional treatment (e.g. disinfection or removal of micropollutants)
6 sludge treatment
7 lagoons (as an alternative)
A raw wastewater
B effluent for re-use (e.g. irrigation)
C discharged effluent
D screenings and grit
E primary sludge
F secondary sludge
G tertiary sludge
H stabilized sludge
I digester gas
J returned water from dewatering

Figure 1 — Schematic diagram of wastewater treatment plants

Detailed information additional to that contained in this document can be obtained by referring to the
bibliography.
The primary application is for wastewater treatment plants designed for the treatment of domestic and
municipal wastewater.

5
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

1 Scope
This document specifies the design requirements for plant and equipment to remove solids, other than
screenings and grit, from raw wastewater, at wastewater treatment plants for over 50 PT.
m /
It includes primary treatment with sedimentation, fine screens and micro-screens.
s . co
NOTE 1 The removal of screenings and grit is covered in EN 12255-3.

a u ge
NOTE 2
- g
Dissolved air flotation (DAF) is not covered in detail in this document because it is not commonly used
a
for primary treatment in municipal wastewater treatment plants. It can be used for primary treatment of

hi n
industrial wastewater, but then the design is specific to the application.

2 Normative references w.c


/ w w
: /
ttp
The following documents are referred to in the text in such a way that some or all of their content

h
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 12255-1, Wastewater treatment plants - Part 1: General construction principles

EN 12255-10, Wastewater treatment plants - Part 10: Safety principles

EN 16323:2014, Glossary of wastewater engineering terms

3 Terms and definitions


For the purposes of this document, the terms and definitions given in EN 16323:2014 and the following
apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https://www.iso.org/obp

— IEC Electropedia: available at https://www.electropedia.org/

3.1
dissolved air flotation
DAF
separation of solids from wastewater whereby air is dissolved in recirculated wastewater under
pressure, generates micro-bubbles when the pressure is released within a tank, which attach to
particles and floats them to the wastewater surface as scum

3.2
lamella separator
device comprising regularly spaced, inclined plates or tubes designed to increase the effective settling
area

[SOURCE: EN 16323:2014, term number 2.3.2.6]

3.3
micro-screen
screen with a typical mesh size between 0,1 mm and 1,0 mm

6
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

3.4
fine screen
screen with a slot or perforation diameter between 1 mm and < 8 mm

m /
[SOURCE: EN 12255-3]
s . co
4 Symbols and abbreviations
a u ge
BOD Biochemical Oxygen Demand
a - g
COD Chemical Oxygen Demand
hi n
FOG Fat, Oil and Grease
w.c
rbdCOD
/ w
readily biodegradable COD w
: /
Ptot
TKN http
Total Phosphorus
Total Kjeldahl Nitrogen
TS Total Solids
TSS Total Suspended Solids

5 Requirements
5.1 General

Primary treatment has the objective of removing solids and the associated organic load from raw
wastewater (solid-liquid separation). Retained solids are removed continuously or on a regular basis in
the form of primary sludge. The kind of solids removed depends on the process employed: primary
clarifiers and lamella separators remove solids depending on their size and density by sedimentation
(settable solids) or by flotation (fat, oil and grease), but they do not effectively remove solids with a
density close to that of the wastewater. Screens remove solids from wastewater based on their particle
size and rigidity, independent of their density.
The type and size of units employed will depend on the overall system, on the inflow and solids load
and their variabilities, on the available space and ground conditions.
Primary treatment can include the following units:
a) Primary clarifier (settling tank or lamella separator):

— upward flow;

— horizontal flow;

— clarifier/sludge storage tank combination;

— lamella separator;

— imhoff tank.

Figure A.1 to A.6 in Appendix A show sketches of typical gravity clarifiers and lamella separators.

7
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

b) Micro-screen:

— rotating cylindrical screens with flow from the inside out;

m /
— continuous belt screen which is horizontal or slightly sopped upwards;

s . co
— other micro-screens which might be developed.

a u ge
a - g
Figure A.7 in Appendix A shows sketches of typical micro-screens, i.e. of a belt and drum screen.
c) Dissolved air flotation:
hi n
w.c
— system with or without addition of coagulants or flocculants;

/ w w
: /
— system with or without lamella separators.

h ttp
Figure A.8 in Appendix A shows a sketch of a typical dissolved air flotation unit.
Primary treatment is not required where secondary wastewater treatment and simultaneous aerobic
sludge stabilization is achieved. However, upstream preliminary treatment with fine screens for the
removal of solids and grit removal is always required if there is no primary treatment with
sedimentation.
Primary treatment can be enhanced through coagulant and flocculant (polymer) addition.
5.2 Planning
5.2.1 Required Data and Information

Performance requirements shall be determined considering the following factors:


— the nature and quantity of flow, including its variation (in particular storm events);

— chemical Oxygen Demand (COD) and Suspended Solids (TSS) loads and their variations;

— ratio of dissolved (or particulate) COD to total COD;

— ratio of readily biodegradable COD (rbdCOD) to total COD; knowledge of this ratio is required
where biological Nitrogen removal is performed during subsequent biological treatment; the ratio
of Biochemical Oxygen Demand (BOD) to COD may be used as a substitute;

— total Kjeldahl Nitrogen (TKN) load; this parameter is also required where biological Nitrogen
removal is performed during subsequent biological treatment;

— slot or perforation width of the headworks screens; lamella separators and micro-screens require
fine screens (see Part 3) with a maximum slot width of 4 mm or a perforation diameter of
maximum 6 mm;

— the quantity and quality of primary sludge generated, including its peak during storm events, which
depends on the quality and operation of the sewer system;

— type of sludge stabilization and requirements concerning the primary sludge solids concentration
(gravity or mechanical sludge thickening is usually needed);

— the quantity and quality of the effluent and its variation; where nitrogen removal is required, the
COD/TKN-ratio of the effluent should not be below 6:1 so that enough rbdCOD for denitrification

8
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

remains in the effluent. More specifically, the ratio of rbdCOD to TKN in the effluent should not be
lower than 1:1,2;

— redundancy requirements;
m /
— health and safety requirements;
s . co
u ge
— concentrations of Sulfide and Chloride in the influent (they can cause concrete and metal
a
corrosion).
a - g
hi n
Figure 2 shows the composition of COD and TSS in raw wastewater. Typical average specific loads are
.c
shown, but they can vary depending on local conditions. It should be noted that 85-Percentiles of the
w
specific loads are about 20 % higher.
/ w w
: /
h ttp

Figure 2 — Typical composition of COD and TSS

9
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

5.2.2 Advantages and Disadvantages of Primary Treatment Systems

Lamella separators have the following pros and cons in comparison with conventional clarifiers:
Pros:
m /
— their footprint is about half that of primary clarifiers;
s . co
— savings of construction costs;
a u ge
— better flow distribution. a - g
hi n
Cons:
w.c
/ w w
— additional costs of mechanical equipment and its maintenance;
: /
— need for regular cleaning;
h ttp
— inconsistent performance due to more frequent blockages from fat and rags which can be mitigated
by good preliminary treatment (see Part 3).

Lamella separators are typically taken into consideration where:


— existing primary clarifiers need upgrading; or

— where the available footprint for conventional primary clarifiers is insufficient.

Micro-screens have the following pros and cons in comparison with conventional clarifiers:
Pros:
— they require only about 10 % of the footprint of primary clarifiers;
— savings of construction and investment costs;

— smaller variation of removal ratios depending on flow [1];

— removal ratios can be adjusted by changing the mesh;

— removal of fibres and thus protection of subsequent treatment stages from cording;

— removal of micro-plastic;

— can be used to thicken primary sludge (saving pre-thickening storage and separate thickeners).

Cons:
— micro-screens typically generate a head loss of up to 0,4 m and thus can need inflow pumping (this
can be comparable to a flow splitter chamber and traditional clarifiers); however, pumping offers
the benefit of flow control;

— power consumption is higher;

— need for redundancy: Failure of one unit shall not result in total loss of primary treatment capacity;

— increased reliance on mechanical equipment which requires maintenance.

10
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

Micro-screens are typically taken into consideration where:


— an existing primary clarifier needs upgrading; instead a portion of the inflow can be mechanically
treated by micro-screening;
m /
— there is a lack of available space for a conventional clarifier;
s . co
a u ge
— a wastewater plant with aerobic sludge stabilization is changed into a plant with anaerobic sludge
stabilization and it is difficult to add a primary clarifier (lack of space or requirement for pumping);
a - g
hi n
— sea or river outflows need mechanical treatment (with or without prior coagulation or
flocculation).
w.c
5.2.3 Performance
/ w w
: /
h ttp
In a primary clarifier the removal rate depends on the mean retention period, as shown in Table 1.
Table 1 — Removal Efficiencies of primary clarifiers (DWA-A 131 modified)

Removal effectivity η in %
Retention period in primary
clarifier calculated with the 0,75 h − 1 h 1 h − 1,5 h 1,5 h − 2 h 2 h − 2,5 h > 2,5 h
average dry weather flow
COD 30 % 32,5 % 35 % 37,5 % 40 %
Particulate COD 45 % 50 % 55 % 57,5 % 60 %
TSS 50 % 55 % 60 % 62,5 % 65 %
TKN 10 %
Ptot 10 %

Where nitrogen is to be removed during subsequent biological treatment, the mean retention period
during dry weather conditions in a clarifier should be between 0,5 h and 1,5 h. Where this is not the
case, a dry weather retention period between 1,5 h and 2,5 h may be used.
Primary clarifiers for wastewater treatment plants serving a total population of up to 1 000 PT should
have a retention period, based on the design flow, of minimum 2 h. In such cases the primary clarifier
can also serve as primary sludge storage tank. Its volume shall be calculated accordingly. The primary
sludge should be removed in such intervals that it does not become septic. The primary sludge can be
transferred to a larger plant where it can be stabilized (e.g.in an anaerobic digester).
Micro-screens with a mesh size of 0,3 mm and without prior flocculation can remove about 70 % of the
TSS and 50 % of the COD [1]. After prior flocculation up to 90 % of the TSS can be removed.
Micro-screens can also be used for mechanical treatment at sea and river outfalls. In such cases prior
flocculation should be provided.
Where no subsequent nitrogen removal is required, the TSS- and COD-removal rate should be as high as
reasonably possible and therefore mesh sizes between 0,1 mm and 0,25 mm should be used. This raises
the ratio of primary to secondary sludge, increasing the gas production of anaerobic digesters, reduces
the volatile solids ratio of stabilized sludge, and improves its dewaterability.
However, where subsequent biological nitrogen removal is required, the denitrification capacity
depends on the availability of rbdCOD and the COD/TKN-ratio should not drop below 6:1. In such cases
the mesh size of very fine screens should be in a range between 0,2 mm and 0,5 mm, so that about 25 %
of the COD and about 60 % of the TSS are removed.

11
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

Where only a single clarifier or micro-screen is provided, the primary clarifier and micro- screen shall
be provided with a bypass permitting control of the removal ratio and allowing maintenance work.
Waste activated sludge or excess sludge from biofilm plants can be returned to primary treatment. At
plants serving a total population of 10 000 or more, separate sludge thickening (by gravity or
m /
mechanically) shall be considered.
s . co
5.3 Design
a u ge
5.3.1 General
a - g
hi n
Solids removal rates shall be in accordance to the needs of any downstream process.

w.c
Flow distribution to parallel units shall be as equal as reasonable possible. This should be by symmetric

/ w w
proportional length distribution weirs in a chamber. Pipelines or channels, or provision of nozzles
: /
which are controlled by flow meters used to distribute flows are less accurate and rely on mechanical
equipment that requires maintenance.
h ttp
A bypass of the mechanical treatment stage (a microscreen) shall be provided. The bypass can be used
to control the removal ratios but this will allow coarse solids to cause blockages in downstream process
units and increased energy consumption.
The general construction principles of Part 1 of this standard series (EN 12255-1) apply. Part 1 includes
information on scrapers and wheel tracks.
5.3.2 Specifications

Specification documents shall include the following information:


1) maximum, minimum and average flow;

2) maximum, minimum and average solids load;

3) information on industrial influents in respect to quantity and quality;

4) information on site conditions, including space and geological conditions;

5) information on hydraulic restrictions;

6) redundancy requirements;

7) material specifications.

5.3.3 Required Capacity

The system’s capacity shall be designed for the maximum flow and load. The TSS- and COD removal
ratios and their remaining loads shall be determined or estimated for design (maximum), average and
minimum loads and flows.
5.3.4 Systems for primary treatment

5.3.4.1 Primary Clarifiers

The mean retention period during dry weather flow should be between 0,5 h and 2,5 h, depending on
subsequent nitrogen removal requirement (see 5.2.3) In general, with appropriate sludge removal
practices, the longer the retention period, the better is the removal ratio (see Table 1). In order to
prevent too much removal, the retention period upstream of activated sludge systems with nitrogen
removal should remain between 0,75 h and 1,5 h under normal circumstances.

12
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

The flow over overflow weirs at maximum flow shall not exceed 150 m3/(m∙h).
Clarifiers with a surface of up to 30 m2 can be designed for upward flow. Such Dortmund tanks have a

m /
side wall and a conical or pyramidal shape with a minimum 60 ° slope and no scraper. Their use is
limited by their depth. Settled sludge is removed from the bottom tip of the cone or pyramid through a
. co
rising pipe. The inflowing wastewater is radially distributed via a stilling device at a level about 2/3rd
s
ge
of the tank’s depth. It flows radially upward to a circumferential overflow weir.

g a u
Larger clarifiers are designed for essentially horizontal flow and provided with sludge hoppers and
bottom scrapers. They are circular or rectangular tanks.
na -
.c hi
Such clarifiers shall be provided with one or several sludge hoppers, dependent on their size and
geometry. Sludge hoppers can be circular or square. The slope of the hopper walls should not be less
w
than 60 °, unless they are provided with a scraper.
w
/ / w
Table 2 shows design dimensions for horizontal and vertical flow clarifiers. At small plants (≤1 000 PT)
:
h ttp
the primary clarifier can also serve as storage tank for primary and secondary sludge if the settled
sludge is removed every few months and treated at a larger plant. The volume of the sludge storage
tank shall be sufficient to store primary sludge of 3 % Dry Solids content for at least 4 weeks.

13
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

Table 2 — Typical design data for primary clarifiers for design flow

Design Parameter for Clarifier + sludge


Horizontal flow Vertical flow
New Builds storage combination
m /
Max. surface area 1 250 m2
(circular) and
400 m2 (rectangular)
Up to 80 m2 Up to 30
s
m2
. co
Tank dimensions 20 m to 40 m diameter 10 m
a u ge
e.g. 5 m × 6 m
or 2 m to 10 m width
a - g
and 20 m to 40 m length
i n
Minimum Side Wall
Depth
2m
.
0,75 m
w ch 2,5 m

/ w w
Minimum Diffuser
:
10 % but preferably
/ 20 % of tank diameter N/A
Drum Diameter
ttp
about 20 % of tank
diameter h
Diffuser Drum Min. 1,0 m Approx. 2/3rd of depth N/A
Submergence
Minimum Diffuser 0,3 m 0,3 m
Drum Freeboard
Inflow velocity 0,3 m/s to 0,4 m/s same same
(Horizonal velocity during dry weather
component of the conditions
inflow into the tank)
Floor Slope min. 3° (circular) and min. 60° N/A
min 0,5° (rectangular)
Minimum Central 60° integral N/A
Hopper Slope
Central Hopper Sufficient to retain up to Sufficient to retain up Sufficient to retain
Volume/sludge storage 4 h sludge at 3 % TS and to 4 h sludge at 3 % TS min. 1 week sludge at
volume average production and average 3 % TS
rates production rates
Retention period (tR) 0,5 h to 2,5 h 0,5 h to 2,5 h Min 1,5 h above sludge
at dry weather storage volume
conditions depending
on the requirement for
nitrogen removal
Maximum Upflow Rate 0,8 m/h to 1,5 m/h 0,8 m/h to 1,5 m/h 0,8 m/h to 1,5 m/h
(qA)
Weir overflow rate 30 m3/(h∙m) to 30 m3/(h∙m) to N/A
60 m3/(h∙m) during dry 60 m3/(h∙m) during
weather conditions and dry weather conditions
max. 150 m3/(h∙m) at and max. 50 m3/(h∙m)
peak flow at peak flow

Where several sludge hoppers are provided, the primary sludge should be sequentially removed from
individual hoppers over short time intervals to mitigate water funnelling through the hopper. TS-
probes can be provided. Flow meters or sludge level detectors can be provided to detect blockage.

14
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

Sludge is removed from the hoppers through pipes. They may be directly connected to sludge pumps
(usually redundant pumps are required) or connected to a primary sludge tank wherefrom the sludge is
forwarded via pumps. Where there are several sludge hoppers, each pipe shall be provided with a shut
/
off device (usually automated). Where the sludge hoppers are connected to a primary sludge tank, the
m
head shall be 1,5 m to 2,0 m to guarantee sufficient flow.
s . co
ge
Wastewater shall enter the tank through a stilling device, reducing the kinetic energy of the inflow and

g a u
evenly distributing it. The inflow velocity shall be reduced to below 0,5 m/s. A vertically installed very
coarse perforated screen can be provided for this purpose if it can easily be cleaned.

na -
The introduced and stilled wastewater flows longitudinally or radially upwards to an overflow weir.
The freeboard shall be minimum 0,3 m.
.c hi
w w
The length to width ratio of rectangular clarifiers with horizontal flow shall be minimum 3:1. Their ratio
/ / w
of length to the average water depth should not exceed 20:1.
:
h ttp
A scum board and scum scraper should be provided, driving scum over a ramp to a scum hopper or
channel. The scum scraper is usually integral with the bottom scraper.
Overflow weirs should have a serrated shape to equalize the overflow. Their height should be
adjustable.
Scum boards shall have a distance of minimum 300 mm from overflow weirs. The lower edge of scum
boards shall be minimum 200 mm below the water surface.
It shall be considered how equipment for inflow distribution, baffles and overflow weirs, as well as
channels can be cleaned. Mechanical cleaning equipment can be provided, e.g. brushes attached to a
scraper.
Structural tolerances of clarifiers with scrapers are listed in EN 12255-1.
It shall be considered whether scrapers should run on rails or on wall tracks. Structural requirements
on wheel tracks are included in EN 12255-1.
Bottom scrapers in circular clarifiers are usually shield scrapers. In rectangular tanks bar and chain
scrapers can be used as an alternative.
Requirements on scraper design are included in EN 12255-1.
Imhoff tanks are horizontal clarifiers with an unheated anaerobic sludge digestion zone underneath
wherefrom digester gas is collected. Imhoff tanks are no longer built in Europe, but could be useful in
warm climates.
Examples of primary clarifiers are shown in Annex A.
5.3.4.2 Lamella Separators

The raw wastewater flow enters the space between the lamella either at their bottom ends or laterally.
Settling solids collect at the upper face of the lamellae while floating material collects at their lower
faces. The angle of the lamellae shall be minimum 60° to ensure that settled solids can slide down on the
upper faces and that scum can slide up on the lower faces.
The surface flow rate is about double that of conventional clarifiers (see 5.3.3).
The distance between lamella surfaces or the internal diameter of tubes shall not be below 50 mm to
prevent clogging.
One or several sludge hoppers shall be provided below the lower end of the lamellae and one or several
scum hoppers shall be provided near the upper end of the lamella. Scrapers for sludge and scum can be
needed. Bar and chain scrapers are typically used.

15
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

Even distribution of the raw wastewater to the spaces between the lamella is essential. A vertical very
coarse perforated screen can be provided for this purpose, provided it can easily be cleaned.
5.3.4.3 Micro-screens
m /
There are various kinds of micro screens which can be used for primary treatment. The dry solids
s .
concentration of removed primary sludge can vary in a wide range between 2 kg/m3 and 60 kg/m3, co
sludge to between 20 % and 40 % dry solids. a u ge
depending on local conditions. An optional screw press can be used for dewatering of the removed

a - g
Micro-screens shall be provided with sensors determining their head loss and controlling their cleaning
cycles.
hi n
w.c
The capacity of micro-screens is reduced by fat, oil and grease (FOG). For this reason, high pressure
spray washing should be provided.
/ w w
: /
h ttp
Regular chemical cleaning is usually not necessary.
For a mesh size between 0,2 mm and 0,3 mm the surface specific design flow rate should be within a
range of 25 to 50 m3/(m2∙h) which is equivalent to between 25 and 50 m/h.
5.3.4.4 Rotary drum screens

The screen should generally be made of a stainless steel mesh. The wastewater flows from the inside
out. The drum is partially immersed in the effluent.
When the head loss through the screen and thus the water level inside the drum rises above a certain
level, the drum rotates lifting the retained solids out of the wastewater.
The retained solids are flushed with spray water at the high point of the screen, so that the solids drop
into a channel conveying them into a positive displacement forwarding pump.
Regular flushing is done with low-pressure plant effluent for around 50 % of the filtration time. The
pressure is around 0,6 MPa. The flushing water consumption is within a range of 2 % to 4 % of the
wastewater flow.
High-pressure water flushing with a travelling nozzle, a pressure of ca. 12 MPa and a water flow of
about 0,25 l/s should be done once or twice per day for 5 min to 10 min.
5.3.4.5 Belt screens

The screen removes solids with a continuous-loop fine-mesh belt, made of a flexible and durable
material (e.g. woven nylon filaments). The wastewater flows from top to bottom through the moving
mesh. As the belt is usually slightly inclined, it acts like a conveyor and lifts retained solids out of the
incoming wastewater. A cleaning system removes the solids from the belt and they drop into a hopper
or channel. On the returning belt a laterally moving high-pressure water spray can be provided to
periodically remove oil and grease that can block the belt. Chemical cleaning of the belt could be
required from time to time because oil and grease can be trapped between filaments of the belt.
5.3.4.6 Information from micro-screen suppliers

Suppliers of micro-screens shall provide the following data:


1) dimensions of the tank or channel wherein the screen can be installed;

2) weight of the complete screen;

3) minimum and maximum water level upstream the screen;

4) minimum and maximum head loss of the entire unit;

16
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

5) net screening area at minimum and maximum head;

6) mesh size and material of the screen;

m /
7) area specific design flow rate;

s . co
consumptions;
a u ge
8) spray water and air pressure (where provided) as well as average and peak spray water and air

a - g
9) power consumption of all pumps and drives during average and peak load (including the power
consumption of spray water generation);
hi n
w.c
/ w w
10) regular maintenance intervals and requirements (manpower needed and spare parts replaced).

5.3.5 Materials : /
h ttp
Materials used for the mechanical equipment (e.g. screens and scrapers, but also pipes, scum boards
and overflow weirs) shall be resistant to attack by the constituents of municipal wastewater and sludge,
aerosols, sewage gases and atmospheric influences as appropriate and consistent with the relevant
requirements. The client shall inform the equipment supplier of any special factors, such as the
presence of septic sewage. If different materials are connected, detrimental galvanic corrosion shall be
prevented. If load-bearing components are made of plastic material, detrimental effects of the
environment (e.g. UV-radiation, temperature) shall be considered.
Local conditions can require the use of particularly durable materials. Durability can be achieved by the
use of materials inherently resistant to corrosion (e.g. stainless steel of appropriate grade) or by the
application of a suitable coating.
General requirements for materials are given in EN 12255-1.
5.3.6 Control and Automation

General information is provided in EN 12255-1 and EN 12255-12.


Screens and scrapers shall be fully automated. Remote alarm shall be transmitted in case of their
failure.
5.3.7 Operation and Maintenance

General requirements for maintenance are included in EN 12255-1.


All parts requiring maintenance shall be easily accessible and exchangeable.
It shall be possible to empty all tanks. Clarifiers could be emptied through their sludge hoppers using a
pump (e.g. their sludge pump). Otherwise they shall be provided with a pump sump at their lowest
point wherein a submersible pump can be inserted.
It shall be possible to take representative samples from the in- and outflow of every unit.
It shall be possible to clean all mechanical equipment (e.g. screens, scrapers, lamellae, channels).
It should be possible to flush sludge pipes in reverse flow.
5.3.8 Health and Safety

See the EU machine regulation 206/42/EC for additional information.


Health and safety requirements in EN 12255-1 and EN 12255-10 apply.

17
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

Annex A
(informative)

Illustrations of typical clarifiers m /


s . co
a u ge
- g
Typical general arrangements of different clarifier types are illustrated in Figure A.1 to A.8.
a
hi n
w.c
/ w w
: /
h ttp

Key
1 effluent weir
2 baffle
3 influent
4 effluent
5 primary sludge withdrawal
6 sludge flow route (general)
7 wastewater flow route (general)
8 scraper with blade
9 scraper rotational direction

Figure A.1 — Circular clarifier with scraper

18
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

m /
s . co
a u ge
a - g
hi n
w.c
/ ww
: /
h ttp

Key
1 effluent weir
2 baffle
3 influent
4 effluent
5 primary sludge withdrawal
6 sludge flow route (general)
7 wastewater flow route (general)

Figure A.2 — Circular or square clarifier without scraper (Dortmund tank)

19
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

m /
s .co
a u ge
a - g
hi n
w.c
/ ww
: /
h ttp
Key
1 effluent weir
2 baffle
3 influent
4 effluent
5 primary sludge withdrawal
6 sludge flow route (general)
7 wastewater flow route (general)
8 scraper bridge
9 scum trough

Figure A.3 — Rectangular clarifier with bottom and scum scraper

20
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

m /
s . co
a u ge
a - g
hi n
w.c
/ w w
: /
h ttp

Key
1 effluent weir
2 baffle
3 influent
4 effluent
5 primary sludge withdrawal
6 sludge flow route (general)
7 wastewater flow route (general)
8 chain
9 scum trough
10 sludge and scum scraper blades

Figure A.4 — Rectangular clarifier with chain scraper

21
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

m /
s .co
a u ge
a - g
hi n
w.c
/ ww
: /
h ttp
Key
1 effluent weir
2 baffle
3 influent
4 effluent
5 primary sludge withdrawal
6 sludge flow route (general)
7 wastewater flow route (general)
8 hydraulic ram
9 scum trough
10 wedge shaped scraper blades

Figure A.5 — Rectangular clarifier with ram scraper

22
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

m /
s . co
a u ge
a - g
hi n
w.c
/ w w
: /
h ttp

Key
1 effluent weir
3 influent
4 effluent
5 primary sludge withdrawal
6 sludge flow route (general)
7 wastewater flow route (general)
8 lamella plates
9 scraper

Figure A.6 — Clarifier with lamella separators

23
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

m /
s .co
a uge
a - g
hi n
w.c
Key

/ ww
1 cleaning mechanism
: /
2
3
drive
influent h ttp
4 effluent
5 primary sludge withdrawal
6 sludge flow route (general)
7 wastewater flow route (general)
8 drum
9 belt

Figure A.7 — Belt or drum clarifier

24
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

m /
s . co
a u ge
a - g
hi n
w.c
/ w w
: /
h ttp

Key
1 effluent weir
2 baffle
3 influent
4 effluent
5 primary sludge withdrawal
6 sludge flow route (general)
7 wastewater flow route (general)
8 scum scraper
9 scum trough
10 air injection
11 milky water route
12 milky water distributer
13 pump

Figure A.8 — Dissolved air flotation clarifier

25
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

Annex B
(normative)

Dimensions and tolerances for the structures of clarifiers m /


s .co
a u ge
NOTE
- g
Annex B describes the required tolerances for civil structures of clarifiers.
a
B.1 Circular clarifiers with scrapers hi n
w.c
— internal tank diameter: ± 0,03 m;
/ w w
: /
ttp
— contour of the bottom floor: ± 0,03 m;
h
— internal and external diameter of wall track: ± 0,03 m.

B.2 Rectangular clarifiers with scrapers


— distance of the side walls from the longitudinal axis: ± 0,02 m;

— distance of side walls from each other: ± 0,02 m;

— distance of wall tracks from each other: ± 0,02 m;

— lateral contour of the bottom floor: ± 0,01 m;

— longitudinal contour of the bottom floor over length sections of 4 m: ± 0,02 m;

— vertical distance from the track to the bottom floor: ± 0,03 m (only where scrapers with fixed
shields are employed).

26
BS EN 12255‑4:2023
EN 12255-4:2023 (E)

Bibliography

m /
[1]
s . co
Kaless M., Palmowski L., Pinnekamp J. Sieving Wastewater for Energy Efficient and Resource
Saving Wastewater Treatment, Proceedings of the IWA Specialist conference on Sludge
Management, July 9 to 13, 2017
a u ge
[2] - g
DWA-A 131 (work sheet): Dimensioning of single-stage activated sludge systems, Hennef
a
(Germany) 2016
hi n
[3]
w.c
EN 752, Drain and sewer systems outside buildings - Sewer system management

/ w w
[4]
: /
Arbeitsbericht DWA-Fachausschuss KA-5 08/2003

[5] h ttp
EN ISO 14122-2:2016, Safety of machinery - Permanent means of access to machinery - Part 2:
Working platforms and walkways (ISO 14122-2:2016)

[6] EN 12255-12, Wastewater treatment plants - Part 12: Control and automation

27
NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW

British Standards Institution (BSI) /


BSI is the national body responsible for preparing British Standards and other
c o m
standards-related publications, information and services.
e s .
a
BSI is incorporated by Royal Charter. British Standards and other
g
ustandardization
products are published by BSI Standards Limited. a - g
h in
w . c
About us
/ w w Reproducing extracts

p : /
We bring together business, industry, government, consumers, innovators
t For permission to reproduce content from BSI publications contact the BSI

ht
and others to shape their combined experience and expertise into standards Copyright and Licensing team.
-based solutions.
The knowledge embodied in our standards has been carefully assembled in Subscriptions
a dependable format and refined through our open consultation process. Our range of subscription services are designed to make using standards
Organizations of all sizes and across all sectors choose standards to help easier for you. For further information on our subscription products go to bsigroup.
them achieve their goals. com/subscriptions.
With British Standards Online (BSOL) you’ll have instant access to over 55,000
Information on standards British and adopted European and international standards from your desktop.
We can provide you with the knowledge that your organization needs It’s available 24/7 and is refreshed daily so you’ll always be up to date.
to succeed. Find out more about British Standards by visiting our website at You can keep in touch with standards developments and receive substantial
bsigroup.com/standards or contacting our Customer Services team or discounts on the purchase price of standards, both in single copy and subscription
Knowledge Centre. format, by becoming a BSI Subscribing Member.

Buying standards PLUS is an updating service exclusive to BSI Subscribing Members. You will
automatically receive the latest hard copy of your standards when they’re
You can buy and download PDF versions of BSI publications, including British and revised or replaced.
adopted European and international standards, through our website at bsigroup.
com/shop, where hard copies can also be purchased. To find out more about becoming a BSI Subscribing Member and the benefits
of membership, please visit bsigroup.com/shop.
If you need international and foreign standards from other Standards Development
Organizations, hard copies can be ordered from our Customer Services team. With a Multi-User Network Licence (MUNL) you are able to host standards
publications on your intranet. Licences can cover as few or as many users as you
Copyright in BSI publications wish. With updates supplied as soon as they’re available, you can be sure your
documentation is current. For further information, email [email protected].
All the content in BSI publications, including British Standards, is the property
of and copyrighted by BSI or some person or entity that owns copyright in the Revisions
information used (such as the international standardization bodies) and has
formally licensed such information to BSI for commercial publication and use. Our British Standards and other publications are updated by amendment or revision.

Save for the provisions below, you may not transfer, share or disseminate any We continually improve the quality of our products and services to benefit your
portion of the standard to any other person. You may not adapt, distribute, business. If you find an inaccuracy or ambiguity within a British Standard or other
commercially exploit or publicly display the standard or any portion thereof in any BSI publication please inform the Knowledge Centre.
manner whatsoever without BSI’s prior written consent.
Useful Contacts
Storing and using standards Customer Services
Standards purchased in soft copy format: Tel: +44 345 086 9001
• A British Standard purchased in soft copy format is licensed to a sole named Email: [email protected]
user for personal or internal company use only.
Subscriptions
• The standard may be stored on more than one device provided that it is Tel: +44 345 086 9001
accessible by the sole named user only and that only one copy is accessed at Email: [email protected]
any one time.
• A single paper copy may be printed for personal or internal company use only. Knowledge Centre
Tel: +44 20 8996 7004
Standards purchased in hard copy format: Email: [email protected]
• A British Standard purchased in hard copy format is for personal or internal
company use only. Copyright & Licensing
Tel: +44 20 8996 7070
• It may not be further reproduced – in any format – to create an additional copy.
This includes scanning of the document. Email: [email protected]

If you need more than one copy of the document, or if you wish to share the BSI Group Headquarters
document on an internal network, you can save money by choosing a subscription
product (see ‘Subscriptions’). 389 Chiswick High Road London W4 4AL UK

This page deliberately left blank

You might also like