L4
L4
INTRODUCTION
▪ A single-phase AC power system consists of a
generator connected through a pair of wires (a
transmission line) to a load. It is also known as a
single-phase two-wire system.
3
INTRODUCTION
▪ There is also a single-phase three-wire system. It
contains two identical sources (equal magnitude
and the same phase) that are connected to two
loads by outer wires and the neutral.
▪ Example, the normal household system.
4
POLYPHASE CIRCUIT
▪ Circuits or systems in which the AC sources
operate at the same frequency but in different
phases are known as polyphase.
8
BALANCED THREE PHASE
VOLTAGES
▪ The three-phase generator can supply power to
both single-phase and three-phase loads.
▪ A typical three-phase system consists of three
voltage sources connected to loads by three or four
wires (or transmission lines).
▪ The voltage sources can be either wye-connected
or delta-connected.
9
BALANCED THREE PHASE
VOLTAGES
11
WYE-CONNECTED VOLTAGES
12
WYE-CONNECTED VOLTAGES
13
WYE-CONNECTED VOLTAGES
14
WYE-CONNECTED VOLTAGES
15
WYE-CONNECTED VOLTAGES
16
THREE PHASE CONNECTED
LOADS
18
THREE PHASE CONNECTED
LOADS
▪ For a balanced wye-connected load,
19
THREE PHASE CONNECTED
LOADS
▪ Since both the three-phase source and the three-
phase load can be either wye- or delta-connected,
we have four possible connections
1. Y – Y Connection (i.e Y connected source with a
Y connected load)
2. Y - ∆ connection
3. ∆ - ∆ connection
4. ∆ - Y connection
20
POLYPHASE SYSTEM-
CONCLUSION
▪ It is appropriate to mention here that a balanced
delta-connected load is more common than a
balanced wye-connected load.
▪ This is due to the ease with which loads may be
added or removed from each phase of a delta-
connected load.
▪ This is very difficult with a wye-connected load
because the neutral may not be accessible.
▪ On the other hand, delta-connected sources are not
common in practice because of the circulating
current that will result in the delta-mesh if the three-
phase voltages are slightly unbalanced. 21
BALANCED THREE PHASE
SYSTEM
22
BALANCED WYE –WYE
CONNECTION
▪ A balanced Y-Y system is
a three-phase system
with a balanced Y-
connected source and a
balanced Y-connected
load.
▪ ZS and Zl are often very
small compared with ZL.
So we can assume that
ZY=ZL if no source or line
impedance is given
23
BALANCED WYE –WYE
CONNECTION
▪ Assuming the positive sequence, the phase voltage
(line to neutral voltages) are
24
BALANCED WYE –WYE
CONNECTION
25
BALANCED WYE –WYE
CONNECTION
▪ By applying KVL to each phase on the below figure
below, we obtain the line current as
26
BALANCED WYE –WYE
CONNECTION
27
BALANCED WYE –WYE
CONNECTION
▪ Phasor diagrams illustrating the relationship
between line voltages and phase voltages.
28
BALANCED WYE –WYE
CONNECTION
▪ The neutral line can thus be removed without
affecting the system. In fact, in long-distance power
transmission, conductors in multiples of three are
used with the earth itself acting as the neutral
conductor.
▪ Power systems designed in this way are well-
grounded at all critical points to ensure safety.
▪ In the Y-Y system, the line current is the same as the
phase current
29
BALANCED WYE –DELTA
CONNECTION
▪ A balanced Y- ∆
system consists
of a balanced Y-
connected source
feeding a
balanced ∆ -
connected load.
▪ Assuming the
positive
sequence, the
phase voltages
30
BALANCED WYE –DELTA
CONNECTION
▪ Assuming the positive sequence, the line voltages
31
BALANCED WYE –DELTA
CONNECTION
▪ The magnitude of the line current is times the
magnitude of the phase current.
▪ An alternative way of analyzing the circuit is to
transform the ∆ - connected load to an equivalent
Y-connected load. Using the transformation formula
32
BALANCED WYE –DELTA
CONNECTION
33
ASSIGNMENT
Read on:
1. Balanced Delta – Delta Connection
2. Balanced Delta – Wye Connection
34
POWER IN A BALANCED SYSTEM
35
POWER IN A BALANCED SYSTEM
36
POWER IN A BALANCED SYSTEM
37
POWER IN A BALANCED SYSTEM
39
POWER IN A BALANCED SYSTEM
40
POWER IN A BALANCED SYSTEM
41
TUTORIAL QUESTIONS
END
42
UNBALANCED THREE PHASE
SYSTEMS
▪ An unbalanced system is due to unbalanced
voltage sources or an unbalanced load.
▪ An unbalanced system is caused by two possible
situations:
(1) The source voltages are not equal in magnitude
and/or differ in phase by unequal angles, or
(2) load impedances are unequal
▪ To simplify analysis, we will assume balanced
source voltages, but an unbalanced load.
▪ Unbalanced three-phase systems are solved by
direct application of mesh and nodal analysis 43
UNBALANCED THREE PHASE
SYSTEMS
▪ Consider the given
unbalanced load three phase
system. Since load is
unbalanced ZA, ZB and ZC are
not equal.
▪ The line currents are
determined by Ohm’s law as
44
UNBALANCED THREE PHASE
SYSTEMS
▪ This set of unbalanced line currents produces
current in the neutral line, which is not zero as in a
balanced system.
▪ Applying KCL at node N gives the neutral line
current as
45
UNBALANCED THREE PHASE
SYSTEMS
▪ To calculate power in an unbalanced three-phase
system requires that we find the power in each
phase.
▪ The total power is not simply three times the power
in one phase but the sum of the powers in the three
phases.
46
UNBALANCED THREE PHASE
SYSTEMS
47
UNBALANCED THREE PHASE
SYSTEMS
Class work: The unbalanced Delta connected loads
of the figure below is supplied by balanced line to line
voltages of 440V in the positive sequence. Find the
line currents. Take Vab as reference.
48
UNBALANCED THREE PHASE
SYSTEMS
49
SINGLE PHASE POWER
MEASUREMENT
▪ The average power absorbed by a load is measured
by an instrument called the wattmeter
▪ A wattmeter that consists essentially of two coils:
the current coil and the voltage coil
▪ A current coil with very low impedance (ideally zero)
is connected in series with the load and responds to
the load current.
▪ The voltage coil with very high impedance (ideally
infinite) is connected in parallel with the load as
shown and responds to the load voltage
50
SINGLE PHASE POWER
MEASUREMENT
▪ The current coil acts like a short circuit because of
its low impedance; the voltage coil behaves like an
open circuit because of its high impedance
▪ As a result, the presence of the wattmeter does not
disturb the circuit or affect the power measurement
51
SINGLE PHASE POWER
MEASUREMENT
52
SINGLE PHASE POWER
MEASUREMENT
▪ The wattmeter measures the average power given
by
53
SINGLE PHASE POWER
MEASUREMENT
Example 10: Find the wattmeter reading of the circuit
in the figure below
54
THREE PHASE POWER
MEASUREMENT
55
THREE PHASE POWER
MEASUREMENT
Three Wattmeter Method
▪ The three wattmeter method of power
measurement, work regardless of whether the load
is balanced or unbalanced, wye or delta-connected
56
THREE PHASE POWER
MEASUREMENT
Three Wattmeter Method
▪ The three-wattmeter method is well suited for power
measurement in a three-phase system where the
power factor is constantly changing.
▪ The total average power is the algebraic sum of the
three wattmeter readings
57
THREE PHASE POWER
MEASUREMENT
Two Wattmeter Method
▪ The two-wattmeter method is the most commonly
used method for three-phase power measurement
▪ The two wattmeter's must be properly connected to
any two phases as shown in the figure below
58
THREE PHASE POWER
MEASUREMENT
Two Wattmeter Method
▪ The current coil of each wattmeter measures the
line current, while the respective voltage coil is
connected between the line and the third line and
measures the line voltage.
▪ The algebraic sum of the two wattmeter readings
equals the total average power absorbed by the
load, regardless of whether it is wye- or delta-
connected, balanced, or unbalanced.
▪ The total real power is equal to the algebraic sum of
the two-wattmeter readings
59
THREE PHASE POWER
MEASUREMENT
Two Wattmeter Method
▪ How two Wattmeter Method measure power in a
three phase system.
▪ Consider the balance, wye-connected load in figure
below
60
THREE PHASE POWER
MEASUREMENT
61
THREE PHASE POWER
MEASUREMENT
63
THREE PHASE POWER
MEASUREMENT
64
THREE PHASE POWER
MEASUREMENT
Two Wattmeter Method
▪ The two-wattmeter method cannot be used for
power measurement in a three-phase four-wire
system unless the current through the neutral line is
zero.
▪ We use the three-wattmeter method to measure the
real power in a three-phase four-wire system
65
END OF LECTURE 05
67