0% found this document useful (0 votes)
51 views

FM Approval Guide Sample 00

This document provides details on FM Approved wall and ceiling products, including their class numbers, primary classes of work, acceptable uses, and installation requirements. It lists the JNFM-H, JNFM-L, JNFM-N, and JNFM-V products, specifying their panel thickness, core material, dimensions, facer materials, and interior and exterior installation requirements.

Uploaded by

cmedxb1
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views

FM Approval Guide Sample 00

This document provides details on FM Approved wall and ceiling products, including their class numbers, primary classes of work, acceptable uses, and installation requirements. It lists the JNFM-H, JNFM-L, JNFM-N, and JNFM-V products, specifying their panel thickness, core material, dimensions, facer materials, and interior and exterior installation requirements.

Uploaded by

cmedxb1
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Walls and Ceilings (FM Approval Class Numbers 4411, 4650, 4651, 4840, 4880, 4881, 4882)

Under this section an FM Approved product/assembly will only be located/reference for its’ Primary Class of Work as detailed below:

Primary Class of Work Subsections/ Approval Guide Location(s) Approval Includes


4880 Interior Use Only (Class 4880) 4880
4881 Interior and Exterior Use (Class Number 4881) 4880 and 4881
Smoke Sensitive Occupancies Interior Use Only (Class 4882) 4880 and 4882
4882
Smoke Sensitive Occupancies Interior and Exterior Use (Class 4882) 4880, 4881, and 4882
4651 Suspended Plastic Ceilings 4651

The heading of the subsections (shown above) details all acceptable uses/applications for the Approved product/assembly. One or
multiple uses maybe listed and would included the following;
• Interior use,
• Exterior use,
• Smoke Sensitive Occupancies,
• Suspended Plastic Ceilings
See each subsections and listing detail for additional installation requirements and ratings.
The listed assemblies are not intended as long-term fire walls or barriers since fire endurance was not evaluated. See
SPECIFICATION TESTED PRODUCTS, ASTM E119 Standard, for hourly rated systems.

Interior and Exterior Use (Class Number 4881)


This section contains FM Approved building assemblies for an interior and exterior use application. All assemblies have been
examined per the following FM Approvals Standards;
• Class 4881, Approval Standard for Class 1 Exterior Wall Systems, and
• Class 4880, Approval Standard for Class 1 Fire Rating of Building Panels or Interior Finish Materials
All building assemblies are FM Approved with:
• Acceptable application’s for walls and/or ceilings,
• Class 1 type/ratings,
• Height restrictions,
• Wall/ceiling product specifications,
• Interior installation requirements, and
• Exterior installation requirements and ratings
Products listed as ceiling applications are not necessarily Approved for use as roofs. For approved roofing products and
assemblies, please click here for www.roofnav.com

Exterior installation requirements and ratings include;


• a wind zone category of;
o Non-Tropical Cyclone (NTC)
o Tropical Cyclone (TC), or
o Tropical Cyclone Missile (TCM)
• a wind pressure rating expressed as the maximum inward and outward pressures (+P/-P) Approved and does not include a safety
factor, and
• a hail resistance rating of either;
o Moderate (MH),
o Severe (SH), or
o Very Severe (VSH)

The FM Global Property Loss Prevention Data Sheets 1-28 shall be used to determine which ratings applies for to a particular location.

Exterior wall systems with unequal (+P/-P) values were Approved via the previous version of Standard 4881. Per Section 1.6 of the
current version of Standard 4881, these systems did not require re-examination and the ratings remain valid.

JNFM-H, JNFM-L, JNFM-N, JNFM-V

Product Summary
Primary
Green Class 1 Height Listing Certification
Product Class of Application
Product Type/Rating Restriction Country Type
Work

© 2007-2020 FM Approvals. All rights reserved. Page 1 of 3


JNFM-H,
JNFM-L, Walls and Inert-Faced with No Height
4881 China FM Approved
JNFM-N, Ceilings Combustible Core Restriction
JNFM-V

Product Specification
Min Min Interior Min Exterior
Panel Panel
Core Panel Facer Facer Facer
Product Thickness Width
Material Length Thickness Thickness Material
in (mm) in (mm) ft (m) in (mm) in (mm)
Galvanized or
(51 ‑
JNFM-L 2-7.9 PIR 39.4 (1001) 8 (2.4) 0.024 (0.61) 0.024 (0.61) Stainless Steel
201)
*
Galvanized or
(51 ‑
JNFM-N 2-7.9 PIR 39.4 (1001) 8 (2.4) 0.024 (0.61) 0.024 (0.61) Stainless Steel
201)
*
Galvanized or
(51 ‑
JNFM-V 2-7.9 PIR 39.4 (1001) 8 (2.4) 0.024 (0.61) 0.024 (0.61) Stainless Steel
201)
*
Galvanized or
(51 ‑
JNFM-H 2-7.9 PIR 39.4 (1001) 8 (2.4) 0.024 (0.61) 0.024 (0.61) Stainless Steel
201)
*

*optional prefinished coating/paint

Interior Installation Requirements


Flashing Minimum 50 by 50 mm (2 by 2 in.) flashing fastened maximum 300 mm (12 in.) on center
Aluminum silicone fiber is placed between each joint including the ceiling and between and on the top
Sealant/Gasket/Caulking and bottom of the flashing. HAOFENGLI self adhered tape will be used on both top and bottom side
of the flashing prior to placing the Aluminum silicone fiber.

Exterior Installation Requirements and Ratings


Max Min Min
Panel Wind Support Support Support
Hail Pressure
Product Thickness Securement Steel Steel Steel Yield
Rating Rating and Spacing Thickness Stress
Zone
in (mm) in (mm) in (mm) ksi (MPa)
JNFM-V, (51 ‑ Fastening Severe +90/-126 Zone
2-7.9 36 (914) 0.07 (1.78) 50 (345)
JNFM-H 201) System A (SH) TC
JNFM-V, (51 ‑ Fastening Severe +40/-56 Zone
2-7.9 72 (1829) 0.07 (1.78) 50 (345)
JNFM-H 201) System B (SH) TC
JNFM-L, (51 ‑ Fastening Severe +50/-70 Zone
2-7.9 72 (1829) 0.07 (1.78) 50 (345)
JNFM-N 201) System C (SH) TC

Fastening System A - Panels are secret fastened in joint (maximum 1000 mm (39.4 in.) oc) along every girt (915 mm (36 in.) oc) with
three 1/4 -14-4 Atlas and Bolt Company fasteners and one washer or three Buildex - CTEKS 14-20x65 and a washer. Panel
additionally secured with 4.8 mm (3/16 in.) diameter Steel Fastenel SBL6-8 Blind Rivets attached 150 mm (6 in.) o.c (8 rivets/panel
width) starting from the edge. Rivets holes are pre-drilled and used to secure the internal side of the panels.
Fastening System B - Panels are secret fastened in joint (maximum 1000 mm (39.4 in.) oc) along every girt (1830 mm (72 in.) oc)
with three 1/4 -14-4 Atlas and Bolt Company fasteners and one washer or three Buildex - CTEKS 14-20x65 and a washer. Panel
additionally secured with 4.8 mm (3/16 in.) diameter Steel Fastenel SBL6-8 Blind Rivets attached 500 mm (20 in.) o.c (3 rivets/panel
width) starting from the edge. Rivets holes are pre-drilled and used to secure the internal side of the panels.
Fastening System C - Panel are through fastened with Hexagon Head Higrip with seal #14 ITW Buildex fasteners along girts
(fasteners rows spaced 1830 mm (73.2 in.) oc) and across panel facer spaced 100,266,266,266 and 100 mm (3.9, 5.9, 5.9, 5.9 and
3.9) oc (4 fasteners per panel/girt interface).

© 2007-2020 FM Approvals. All rights reserved. Page 2 of 3


Company Name: Jiangsu Jingxue Insulation Technology Co Ltd
Company Address: No. 18, Fengze Road , Wujin District, Changzhou, Jiangsu, China
Company Website: http://www.Jingxue.com
New/Updated Product Listing: No
Green Product: No
Application: Walls and Ceilings
Class 1 Type/Rating: Inert-Faced with Combustible Core
Height Restriction: No Height Restriction
Listing Country: China
Certification Type: FM Approved
Class of Work: 4881-Exterior Wall Systems

© 2007-2020 FM Approvals. All rights reserved. Page 3 of 3