0% found this document useful (0 votes)
41 views4 pages

Water Calculation New

The document provides water calculation details for an ICP facility including total water requirement, waste water generation, water balance, and underground and overhead storage details. It also lists the fire protection requirements for various proposed buildings at the facility.

Uploaded by

kaushikc786
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
41 views4 pages

Water Calculation New

The document provides water calculation details for an ICP facility including total water requirement, waste water generation, water balance, and underground and overhead storage details. It also lists the fire protection requirements for various proposed buildings at the facility.

Uploaded by

kaushikc786
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Water Calculation of ICP Ghojadanga

Total Water
Perso
S.No. Description Requirement
n
LPC LPD kl/da
1 Passenger Terminal Cum Admin
Building
1.1 Employees 50 45 2250 2.25
1.2 Visitors 5 15 75 0.08
1.3 Foreign Nationals 2000 15 30000 30.00
Total for Domestic use 32.33
2 Cargo Terminal Building

2.1 Employees 35 45 1575 1.58


2.1 Visitors 15 15 225 0.23
2.3 Misc. 100 0.10
Total for Domestic use 1.90
3 Plant Quarantine Building
3.1 Employees 15 45 450 0.45
3.2 Visitors 5 15 75 0.08
3.3 Misc. 100 0.10
Total for Domestic use 0.63
4 Inspection Export
4.1 Employees 15 45 675 6.75
4.2 Visitors 5 15 75 0.08
4.3 Misc. 100 0.10
Total for Domestic use 6.93
5 Warehouse Import
5.1 Employees 15 45 675 0.68
5.2 Visitors 5 15 75 0.08
5.3 Misc. 100 0.10
Total for Domestic use 0.85

6 Driver/ Porter Rest Area Export


6.1 Visitors 150 15 2250 2.25
7 Driver/ Porter Rest Area Import
7.1 Visitors 75 15 1125 1.13
8 Motor Workshop
8.1 Visitors 15 15 225 0.23
8.2 Misc. 100 0.10
Total for Domestic use 0.33

9 Jawan Barrack
9.1 Bed 200 135 27000 27.00
9.2 Visitors 5 15 75 0.08
9.3 Permanent Employees 20 135 2700 2.70
Total for Domestic use 29.78
10 Barrack for officer
10.1 Bed 16 135 2160 2.16
10.2 Visitors 5 15 75 0.08
10.3 Permanent Employees 5 135 675 0.68
Total for Domestic use 2.92
11 Barrack For Subordinate Officer
11.1 Bed 16 135 2160 2.16
11.2 Visitors 5 15 75 0.08
11.3 Permanent Employees 5 135 675 6.75
Total for Domestic use 8.99
12 Mahila Barrack
12.1 Bed 24 135 3240 3.24
12.2 Visitors 5 15 75 0.08
12.3 Permanent Employees 5 135 675 0.68
Total for Domestic use 3.99
13 LPAI & Stakeholder quarters 3 nos
13.1 Residence 20 135 2700 2.70
14 Toilet Block (Export) 4 nos 340 person each
block
Visitors 1500 45 67500 67.50
15 Toilet Block (Import) 1 nos 400 person each
block
Visitors 500 45 22500 22.50
16 Toilet Block with Restroom (Import)
Visitors 500 45 22500 22.50
Total 207.20
Total Water Requirement
S.No Description Person

LPCD LPD kl/day


17 Miscellaneous 5.00
Total Water requirement 212.20
Say 213 KL/ Day
Waste Water Calculation (in KLD)
1 Total Water Requirement 213

2 Fresh 213
3 Waste Water Generated (80%) 170
4 STP Capacity Say 200 KLD
Water Balance Data (in KL/Day)
S. No. Description Round-off
A. Domestic Water
1 Domestic Water Requirement 213
2 Domestic water Requirement per day for Filter back wash (LS) 5
Total Domestic water 217
B. Recycled Water Reuse from STP
1 Gardening and Landscape @ 2 Liters per day per sqm for 40000 sqm. 80

2 Recycle water Requirement per day for Paved area- Mopping & washing 5
(LS)

TOTAL 85
Reclaimed Water from S.T.P @80% of Waste Water 135
Generated
Flow to external drain after treatment 50
Underground Storage
S.No. Description Capacity in
cum

(i) U.G Tanks(Fire Fighting, Raw, Domestic)


UG Fire Static Tank Capacity 100
UG Domestic water Tank Capacity 217
Total UG TANK Capacity 317
S.N. Water
Daily Calculation
Demand Over Head Storage
(kL) of ICP Ghojadanga
(kL)
Domestic Fire
1 217 217 100 317
Proposed Buildings Building Fire Fire Wet Sprinkler*
UG riser*
Categor tank OH
y T
Passenger Terminal cum D2 100000 5000 R NR R
Administrative building (G+1)
Cargo Terminal building/Plant E2 50000 5000 R NR R
quarantine (G+1)
Plant Quarantine Building (G) E1 NR 10000 NR NR NR

Bus Terminal Arrival (G) D1i NR 20000 NR NR NR

Bus Terminal Departure (G) D1i NR 20000 NR NR NR

Warehouse /Custom office , ground H2i 50000 10000 R R R


+mezz floor
Inspection shed /Custom H2i 50000 10000 R R R
office,ground +mezz floor
Drivers/ Porter area in Import A3 NR 5000 NR NR NR

Drivers/ Porter area in Export A3 NR 5000 NR NR NR

Motor Workshop (G) H2i 50000 10000 R R R

Entrance gate (G+1) E2 50000 5000 R NR R

Entrance gate (G+1) E2 50000 5000 R NR R

Jawan barrack G+2 A3i NR 5000 NR NR NR

Barrack for officer G+1 A1i NR 5000 NR NR NR

Barrack for subordinate officer, G+1 A1i NR 5000 NR NR NR

Mahila barrack , G+1 A3i NR 5000 NR NR NR

Quarter for Manager LPAI (G) A2 NR NR NR NR NR

Quarter for stakeholder (G) A2 NR NR NR NR NR

Quarter for stakeholder (G) A2 NR NR NR NR NR

*for calculation of estimate based on PAR 2020