Midea Msv1 XX SM
Midea Msv1 XX SM
MSV1-09CR-QB8F MSV1-09HR-QB8F
MSV1-12CR-QB8F MSV1-12HR-QB8F
MSV1-18CR-QB8F MSV1-18HR-QB8F
MSV1-07CR-NC2F MSV1-07HR-NC2F
MSV1-09CR-NC2F MSV1-09HR-NC2F
MSV1-12CR-NC2F MSV1-12HR-NC2F
MSV1-18CR-QB8F MSV1-18HR-QB8F
Content
Content
1 Precaution............................................................................................................................1
1.1 Safety Precaution ...................................................................................................................................... 1
1.2 Warning ..................................................................................................................................................... 1
2 Function ...............................................................................................................................4
3 Dimension............................................................................................................................5
4 Specification........................................................................................................................6
5 Refrigerant cycle diagram ................................................................................................10
6 Operation limits ................................................................................................................. 11
7 Wiring diagram ..................................................................................................................12
8 Installation details .............................................................................................................16
8.1 Wrench torque sheet for installation........................................................................................................ 16
8.2 Connecting the cables............................................................................................................................. 16
8.3 Pipe length and the elevation.................................................................................................................. 16
8.4 Air purging of the piping and indoor unit ................................................................................................. 17
8.5 Pumping down (Re-installation) .............................................................................................................. 18
8.6 Re-air purging (Re-installation) ............................................................................................................... 19
8.7 Balance refrigerant of the 2-way, 3-way valves ...................................................................................... 20
8.8 Evacuation............................................................................................................................................... 21
8.9 Gas charging ........................................................................................................................................... 22
9 Electronic function............................................................................................................23
9.1 Electronic control working environment .................................................................................................. 23
9.2 Proper symbols and their meaning ......................................................................................................... 23
9.3 Function................................................................................................................................................... 24
9.4 Protection ................................................................................................................................................ 24
9.5 Fan only mode......................................................................................................................................... 25
9.6 Cooling mode .......................................................................................................................................... 25
9.7 Dehumidifying mode................................................................................................................................ 26
9.8 Heating mode .......................................................................................................................................... 26
9.9 Defrosting mode(available for heating mode)......................................................................................... 27
9.10 Auto mode ............................................................................................................................................. 28
9.11 Force cooling function ........................................................................................................................... 28
9.12 Sleep mode ........................................................................................................................................... 28
9.13 Auto restart function .............................................................................................................................. 29
9.14 Ionizer (air clean) function..................................................................................................................... 29
9.15 Follow me function ................................................................................................................................ 30
9.16 Self-clean function................................................................................................................................. 30
9.17 Turbo ..................................................................................................................................................... 30
10 Model and Parameters ......................................................................................................32
11 Troubleshooting.................................................................................................................34
11.1 LCD Display board ................................................................................................................................ 34
11.2 Indoor Unit Error Display ....................................................................................................................... 35
11.3 Diagnostic chart ..................................................................................................................................... 36
-1-
Content
11.4 Resetting phenomenon often occurs during operation. ........................................................................ 37
-2-
Service manual
1 Precaution
§ To prevent injury to the user or other people and property damage, the following instructions
must be followed.
§ Incorrect operation due to ignoring instruction will cause harm or damage.
§ Before service unit, be sure to read this service manual at first.
1.2 Warning
Ø Installation
§ Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated
circuit.
There is risk of fire or electric shock.
§ For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized service
center.
Do not disassemble or repair the product, there is risk of fire or electric shock.
§ Always ground the product.
There is risk of fire or electric shock.
§ Install the panel and the cover of control box securely.
There is risk of fire of electric shock.
§ Always install a dedicated circuit and breaker.
Improper wiring or installation may cause fore or electric shock.
§ Use the correctly rated breaker of fuse.
There is risk of fire or electric shock.
§ Do not modify or extend the power cable.
There is risk of fire or electric shock.
§ Do not install, remove, or reinstall the unit by yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
§ Be caution when unpacking and installing the product.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser and
evaporator.
§ For installation, always contact the dealer or an Authorized service center.
There is risk of fire, electric shock, explosion, or injury.
§ Do not install the product on a defective installation stand.
It may cause injury, accident, or damage to the product.
§ Be sure the installation area does not deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal
injury.
§ Do not let the air conditioner run for a long time when the humidity is very high and a door or
windows is left open.
Moisture may condense and wet or damage furniture.
§ Take care to ensure that power cable could not be pulled out or damaged during operation.
There is risk of fire or electric shock.
-1-
Service manual
§ Do not place anything on the power cable.
There is risk of fire or electric shock.
§ Do not plug or unplug the power supply plug during operation.
There is risk of fire or electric shock.
§ Do not touch (operation) the product with wet hands.
There is risk of fire or electric shock.
§ Do not place a heater or other appliance near the power cable.
There is risk of fire and electric shock.
§ Do not allow water to run into electric parts.
It may cause fire, failure of the product, or electric shock.
§ Do not store or use flammable gas or combustible near the product.
There is risk of fire or failure of product.
§ Do not use the product in a tightly closed space for a long time.
Oxygen deficiency could occur.
§ When flammable gas leaks, turn off the gas and open a window for ventilation before turn the
product on.
Do not use the telephone or turn switches on or off.
There is risk of explosion or fire.
§ If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect
the power supply cable.
There is risk of electric shock or fire.
§ Stop operation and close the window in storm or hurricane. If possible, remove the product
from the window before the hurricane arrives.
There is risk of property damage, failure of product, or electric shock.
§ Do not open the inlet grill of the product during operation. (Do not touch the electrostatic
filter, if the unit is so equipped.
There is risk of physical injury, electric shock, or product failure.
§ When the product is soaked (flooded or submerged), contact an Authorized service center.
There is risk of fire or electric shock.
§ Be caution that water could not enter the product.
There is risk of fire, electric shock, or product damage.
§ Ventilate the product from time to time when operating it together with a stove, etc.
There is risk of fire or electric shock.
§ Turn the main power off when cleaning or maintaining the product.
There is risk of electric shock.
§ When the product is not be used for a long time, disconnect the power supply plug or turn off
the breaker.
There is risk of product damage or failure, or unintended operation.
§ Take care to ensure that nobody could step on or fall onto the outdoor unit.
This could result in personal injury and product damage.
Ø CAUTION
§ Always check for gas (refrigerant) leakage after installation or repair of product.
Low refrigerant levels may cause failure of product.
§ Install the drain hose to ensure that water is drained away properly.
A bad connection may cause water leakage.
§ Keep level even when installing the product.
To avoid vibration of water leakage.
§ Do not install the product where the noise or hot air from the outdoor unit could damage the
neighborhoods.
It may cause a problem for your neighbors.
-2-
Service manual
§ Use two or more people to lift and transport the product.
Avoid personal injury.
§ Do not install the product where it will be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause
product malfunction or inefficient operation.
Ø Operational
§ Do not expose the skin directly to cool air for long periods of time. (Do not sit in the draft).
This could harm to your health.
§ Do not use the product for special purposes, such as preserving foods, works of art, etc. It is
a consumer air conditioner, not a precision refrigerant system.
There is risk of damage or loss of property.
§ Do not block the inlet or outlet of air flow.
It may cause product failure.
§ Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
§ Do not touch the metal parts of the product when removing the air filter. They are very sharp.
There is risk of personal injury.
§ Do not step on pr put anything on the product. (outdoor units)
There is risk of personal injury and failure of product.
§ Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
§ Do not insert hands or other object through air inlet or outlet while the product is operated.
There are sharp and moving parts that could cause personal injury.
§ Do not drink the water drained from the product.
It is not sanitary could cause serious health issues.
§ Use a firm stool or ladder when cleaning or maintaining the product.
Be careful and avoid personal injury.
§ Replace the all batteries in the remote control with new ones of the same type. Do not mix old
and mew batteries or different types of batteries.
There is risk of fire or explosion.
§ Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
They may burn of explode.
§ If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do
not use the remote of the batteries have leaked.
The chemical in batteries could cause burns or other health hazards.
-3-
Service manual
2 Function
20. Ionizer
Ø Indoor unit The function is operated by remote controller.
1. Operation ON/OFF by remote controller
21.Follow me.
2. Sensing by room temperature
Room temperature sensor. Pipe temperature The function is operated by remote controller.
sensor. 22. Self-clean
3. Room temperature control Function used after the Shut Down of cooling
Maintain the room temperature in accordance with operation to clean the Evaporator and keep it as fresh
the setting temperature. for the next operation. The function is operated by
4. Starting temperature control remote controller..
Indoor fan is delayed for 5 sec at the starting.
23.Turbo
5. Time Delay Safety control
Restarting is for approx. 3 minutes. This function enables the unit to reach the preset
6. Indoor fan speed control temperature in the shortest time under cooling mode
High, med, low.
7. Operation indication LCD
Ø Outdoor unit
Light up in the LCD for each operation mode. 1. Power relay control
8. Two-direction air vane The unit has 3 mins delay between continuously
The unit will decide the louver direction according ON/OFF operations.
to operation mode. 2. Low noise air flow system
9. Sleep mode auto control Bird tail propeller fan makes the outdoor unit run
The fan is turn to low speed (cooling/heating). more quietly
The unit will be turn off after seven hours. 3. Hydrophilic aluminum fin
10. Independent dehumidification The hydrophilic fin can improve the heating
The function is usually used in rainy days in efficiency at operation mode.
springtime or damp areas 4. 4 way valve control
11. Self-diag. function It is only operated in the heating operation mode
The function will be operate in any operation mode. except defrosting operation.
12. Air flow Direction control 5. Anti-rust cabinet
The louver can be set at the desired position or Made from electrolytic zinc steel sheet and anti-rust
swing up and down automatically coated components.
13. Auto mode 6. Valve protection cover
The unit can be change by the room temperature. It protects the valves and prevents water from
14. Anti-cold function dripping.
Prevent the cold wind at the beginning of unit start. 7. Discharge pipe temperature
15. Temp. Compensation
16. Defrost mode
17. Auto-restart function
18. Flexible wiring connection
19. Self-Clean
-4-
Service manual
3 Dimension
Indoor unit
Di mensi on
W H D
Mode
7K 795 270 165
9K 795 270 165
12K 845 286 165
18K 995 292 194
outdoor unit
Dimension
W H D L1 L2
Mode
7K 700 535 285 458 250
9K(50Hz) 700 535 285 458 250
9K(60Hz) 780 540 250 549 266
12K 780 540 250 549 266
18K 845 695 335 560 360
-5-
Service manual
4 Specification
Model MSV1-07CR-QB8F MSV1-07HR-QB8F MSV1-07CR-NC2F MSV1-07HR-NC2F
Power supply Ph-V-Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz 1, 220-230V~, 60Hz 1, 220-230V~, 60Hz
Capacity Btu/h 7000 7000 7000 7000
Input W 730 730 660 660
Cooling
Rated current A 3.3 3.3 3 3
EER Btu/w.h 9.55 9.55 10.9 10.9
Capacity Btu/h —— 8000 —— 8000
Input W —— 780 —— 730
Heating
Rated current A —— 3.5 —— 3.3
COP W/W —— 10.2 —— 10.9
Max. current A 5 5 5 5
Starting current A 14 14 21 21
Model 2P14C225ANA 2P14C225ANA 2R12S3R236A6B 2R12S3R236A6B
Type ROTARY ROTARY ROTARY ROTARY
Brand Matsushita Matsushita Matsushita Matsushita
Capacity Btu/h 7455 7455 7933 7933
Input W 725 725 737 737
Compressor
Rated current(RLA) A 3.4 3.4 3.3 3.3
Locked rotor Amp(LRA) A 14 14 21 21
Thermal protector External External External External
Capacitor uF 25 25 15 15
Refrigerant oil ml 270 270 550 550
Model RPG20D RPG20D RPG13B RPG13B
Brand Welling Welling Welling Welling
Indoor
Input W 32 32 32 32
fan motor
Capacitor uF 1.2 1.2 1.2 1.2
Speed(hi/mi/lo) r/min 1040/900/800 1040/900/800 1040/900/800 1040/900/800
Indoor air flow (Hi/Mi/Lo) m3/h 450 450 450 450
Indoor noise level (Hi/Mi/Lo) dB(A) 36/33/30 36/33/30 36/33/30 36/33/30
Model YDK24-6T YDK24-6T YDK20-6B YDK20-6B
Brand Welling Welling Welling Welling
Outdoor
Input W 56 56 58 58
fan motor
Capacitor uF 2.5 2.5 2.5 2.5
Speed r/min 800 800 750 750
Outdoor air flow m3/h 1500 1500 1500 1500
Outdoor noise level dB(A) 50 50 54 54
Refrigerant type R22 g 530 570 730 730
Design pressure MPa 2.6 2.6 2.6 2.6
Liquid side/ Gas side mm Ф 6.35/Ф 9.53 Ф 6.35/Ф 9.53 Ф 6.35/Ф 9.53 Ф 6.35/Ф 9.53
Refrigerant
Max. refrigerant pipe length m 10 10 10 10
piping
Max. difference in level m 5 5 5 5
Operation temp ℃ 17-30 17-30 17-30 17-30
Ambient temp ℃ 18-45 -7-45 18-45 -7-45
Application area m2 10-14 10-14 10-14 10-14
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are
normally somewhat different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product
improvement.
-6-
Service manual
Model MSV-09CR-QB8F MSV-09HR-QB8F MSV-09CR-NC2F MSV-09HR-NC2F
Power supply Ph-V-Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz 1, 220-230V~, 60Hz 1, 220-230V~, 60Hz
Capacity Btu/h 9000 9000 9000 9000
Input W 940 940 820 820
Cooling
Rated current A 4.2 4.2 3.7 3.7
EER Btu/w.h 9.55 9.55 10.9 10.9
Capacity Btu/h ___________ 10000 ___________ 10000
Input W ___________ 980 ___________ 910
Heating
Rated current A ___________ 4.4 ___________ 4.1
COP W/W ___________ 10.2 ___________ 10.9
Max. current A 6.3 6.3 6 6
Starting current A 19.8 19.8 26 26
Model 2P18S225ANK 2P18S225ANK 2P14S236A1E 2P14S236A1J
Type Rotary Rotary Rotary Rotary
Brand Matsushita Matsushita Matsushita Matsushita
Capacity Btu/h 9912 9912 9161 9195
Input W 970 970 845 850
Compressor
Rated current(RLA) A 4.5 4.5 3.8 3.8
Locked rotor Amp(LRA) A 19.8 19.8 26 26
Thermal protector External External External External
Capacitor uF 30 30 30 30
Refrigerant oil ml 350 350 270 350
Model RPG20D RPG20D RPG13B RPG13B
Brand Welling Welling Welling Welling
Indoor
Input W 32 32 32 32
fan motor
Capacitor uF 1.2 1.2 1.2 1.2
Speed(hi/mi/lo) r/min 1040/900/800 1040/900/800 1040/900/800 1040/900/800
Indoor air flow (Hi/Mi/Lo) m3/h 550 550 550 550
Indoor noise level (Hi/Mi/Lo) dB(A) 38/35/32 38/35/32 38/35/32 38/35/32
Model YDK24-6T YDK24-6T YDK25-6B YDK24-6FB
Brand Welling Welling Welling Welling
Outdoor
Input W 70 70 82.5 72
fan motor
Capacitor uF 3 3 2.5 2.5
Speed r/min 850 850 950 830
Outdoor air flow m3/h 1800 1800 1800 1800
Outdoor noise level dB(A) 52 52 54 54
Refrigerant type R22 g 580 800 900 1000
Design pressure MPa 2.6 2.6 2.6 2.6
Liquid side/ Gas side mm Ф 6.35/Ф 9.53 Ф 6.35/Ф 9.53 Ф 6.35/Ф 9.53 Ф 6.35/Ф 9.53
Refrigerant
Max. refrigerant pipe length m 10 10 10 10
piping
Max. difference in level m 5 5 5 5
Operation temp ℃ 17-30 17-30 17-30 17-30
Ambient temp ℃ 18-45 -7-45 18-45 -7-45
Application area m2 14-21 14-21 14-21 14-21
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are
normally somewhat different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product
improvement.
-7-
Service manual
-8-
Service manual
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are
normally somewhat different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product
improvement.
-9-
Service manual
Ø Cooling only
- 10 -
Service manual
6 Operation limits
Cooling operation
Note: The chart is the result from the continuous operation under constant air temperature
conditions. However, excludes the initial pull-down stage.
Heating operation
Note: The chart is the result from the continuous operation under constant air temperature
- 11 -
Service manual
conditions. However, excludes the initial pull-down stage.
7 Wiring diagram
MSV1-18CR-QB8F
Indoor unit:
( I NDOOR UNI T)
Y/ G ANI ON GENERATOR SWI TCH BOARD SWI NG MOTOR M1 CONTROL TOP AI R
POWER SUPPLY I NDOOR MOTOR
M 5 5 I N LET LOUVER
BROWN( OR BLACK) M2
BLUE( OR WHI TE) M 3 5
Y/ G( OR GREEN)
1 2 1 3 5 3 2 1 3 2 1 123 4 5 1 2 34 5
1 2 1 3 5 3 2 1 3 2 1 12 3 45 1 2 34 5
CN14 CN8 CN12 CN4 CN3
7 6 5 4 3 21
CN7
DI SPLAY
P3 CN11 BOARD
CURRENT I NDUCTOR
MAI N BOARD
CN2
21
21
COMPRESSOR RELAY
AMBI ENT SENSOR
CN9 CN15 CN1
21
21
1234 1 2
12 3 4 1 2 EVAPORATOR SENSOR
RED BLACK
Y/ G
- 12 -
Service manual
1 2( N)
YELLOW/ GREEN
BLACK
OVERLOAD
RELAY
( I NTERNAL/ RED BLACK RED
EXTERNAL
DEPENDI NG BLACK
ON MODELS) C RED FAN RED
COMPRESSON M R
M BLUE
~ BLUE
S
COMPRESSON ~ FAN CAPACI TON
CAPACI TON
YELL OW/GREEN
MSV1-18CR-QB8F
outdoor unit:
- 13 -
Service manual
MSV1-18HR-QB8F
Indoor unit:
( I NDOOR U
NI T)
Y/ G ANI ON GENERATOR SWI TCH BOARD SWING MOTOR M1 CONTROL TOP AI R
POWER SUPPLY INDOOR MOTOR
M 5 5 I N LET LOUVER
BROWN( OR BLACK) M 3 5
M2
BLUE(OR WHI TE)
Y/ G( OR GREEN)
1 2 1 3 5 3 2 1 3 2 1 1 2 34 5 12 345
1 2 1 3 5 3 2 1 3 2 1 1 23 4 5 12 345
CN7 CN14 CN8 CN12 CN4
7 6 5 4 3 21
CN3 DI SPLAY
P3 CN11 BOARD
CURRENT I NDUCTOR
MAI N BOARD
CN2
21
21
P5
COMPRESSOR RELAY
AMBI ENT SENSOR
P4 CN9 CN15 CN1
21
21
YELLOW 12 34 1 2
12 3 4 1 2 EVAPORATOR SENSOR
RED BLACK BLUE
Y/ G
- 14 -
Service manual
I NDOOR UNI T
OUTDOOR UNI T
1 2(N) 3 4
BL UE
Y&G
4- WAY
OVERLOAD BL ACK
RELAY BL UE
BL ACK
C BL ACK RED
COMPRESSOR
R( M) RED
RE D RED
FAN
S MOTOR
Y&G BL UE BL UE
COMPRESSOR
CAPACI TOR FAN CAPACI TOR
MSV1-18HR-QB8F
outdoor unit:
- 15 -
Service manual
8 Installation details
The power cord of connect should be selected according to the following specifications sheet.
Grade
Amp 10 15 20
mm2 1.0 1.5 2.5
Standard
Max. Max. Additional
length
Capacity Pipe size
(m) Elevation Elevation refrigerant
Btu/h GAS LIQUID B (m) A (m) (g/m)
3/8’’ (φ9.52) 1/4’’ (φ6.35) 5 5 10 30
7k~12K
1/2’’ (φ12.7) 1/4’’ (φ6.35) 5 5 10 30
1/2’’ (φ12.7) 1/4’’ (φ6.35) 5 8 15 30
16K~28K 5/8’’ (φ15.88) 1/4’’ (φ6.35) 5 10 20 30
5/8’’ (φ15.88) 3/8’’ (φ9.52) 5 10 20 65
5/8’’ (φ15.88) 3/8’’ (φ9.52) 5 15 30 65
30K~36K
3/4’’ (φ19.05) 3/8’’ (φ9.52) 5 15 30 65
Caution:
Capacity is base on standard length and maximum allowance length is base of reliability.
Oil trap should be install per 5-7 meters.
- 16 -
Service manual
Required tools:
Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak
detector.
Note:
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration
piping, it will affect the compressor, reduce the cooling capacity, and could lead to a malfunction
of unit.
Be sure, using a torque wrench to tighten the service port cap (after using the service port), so
that it prevents the gas leakage from the refrigeration cycle.
Procedure:
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the opened position.
Remove the valve stem caps and confirm that the valve stems are in the opened position.
Be sure to use a hexagonal wrench to operate the valve stems.
2. Operate the unit for 10 to 15 minutes.
3. Stop operation and wait for 3 minutes, then connect the charge set to the service port of the 3-way
valve.
Connect the charge hose with the push pin to the gas service port.
4. Air purging of the charge hose.
Open the low-pressure valve on the charge set slightly to purge air from the charge hose.
5. Set the 2-way valve to the close position.
6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
7. Immediately set the 3-way valve to the closed position.
- 18 -
Service manual
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
8. Disconnect the charge set, and amount the 2-way and 3-way valve’s stem nuts and service port
caps.
Use a torque wrench to tighten the service port cap to a torque of 1.8 kg.m.
Be sure to check for gas leakage.
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the closed position.
2. Connect the charge set and a charging cylinder to the service port of the 3-way valve.
3. Leave the valve on the charging cylinder closed.
4. Air purging.
5. Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare
nut on the 2-way valve approximately 45’ for 3 seconds then closing it for 1 minutes; repeat 3 times.
6. After purging the air, use a torque wrench to tighten the flare nut to on the 2-way valve.
7. Check the gas leakage.
8. Check the flare connections for gas leakage.
9. Discharge the refrigerant.
10. Close the valve on the charging cylinder and discharge the refrigerant until the gauge indicate 0.3
to 0.5 Mpa.
11. Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the
open position.
12. Be sure to use a hexagonal wrench to operate the valve stems.
13. Mount the valve stems nuts and the service port cap.
Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.
Be sure to check the gas leakage.
- 19 -
Service manual
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the open position.
2. Connect the charge set to the 3-way valve’s service port.
Leave the valve on the charge set closed.
Connect the charge hose with the push pin to the service port.
3. Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge indicates
0.05 to 0.1 Mpa.
If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running is higher than
0.1Mpa, discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa. If this is the case, it will not be
necessary to apply a evacuation.
Discharge the refrigeration gradually; if it is discharged too suddenly, the refrigeration oil sill be discharged.
- 20 -
Service manual
8.8 Evacuation
Procedure:
1. Connect the vacuum pump to the charge set’s centre hose.
2. Evacuation for approximately one hour.
Confirm that the gauge needle has moved toward -0.1 Mpa (-76 cmHg) [vacuum of 4 mmHg or less].
3. Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge
needle does not move (approximately 5 minutes after turning off the vacuum pump).
4. Disconnect the charge hose from the vacuum pump.
Vacuum pump oil, if the vacuum pump oil becomes dirty or depleted, replenish as needle.
- 21 -
Service manual
Procedure:
1. Connect the charge hose to the charging cylinder.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the
cylinder.
2. Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be
careful of the liquid refrigerant).
3. Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
If the system cannot be charge with the specified amount of refrigerant, if can be charged with a little at a time
(approximately 150g each time0 while operating the air conditioner in the cooling cycle; however, one time is not
sufficient, wait approximately 1 minute and then repeat the procedure.(pumping down-pin).
4. Immediately disconnect the charge hose from the 3-way valve’s service port.
Stopping partway will allow the refrigerant to be discharged.
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air
conditioner before disconnecting the hose.
5. Mounted the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
- 22 -
Service manual
9 Electronic function
- 23 -
Service manual
9.3 Function
Remote receiving
Testing and forced running
Position set for indoor unit wind vane
LCD displaying and alarm
Timer On or off
Protection for the compressor
Current protection
High temperature protection of indoor heat exchanger at heating mode
Auto defrosting and heating recovery at heating mode
Anti cold air at heating mode
Anti frozen at cooling mode
Auto restart
Self-Clean
Ionizer
Follow me
Auto clean
9.4 Protection
If compressor turns off for continuously 4 times due to current protection in 5 minutes from Compressor
On, the unit stops and LCD displays failure information and can’t returns to normal operation
automatically.
- 24 -
Service manual
- 25 -
Service manual
9.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve
must delay 2 minutes compared with compressor if the compressor changed into non-heating mode or
turned off. 4-way valve doesn't delay in dehumidifying mode.
9.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except
for the defrosting mode or the end of defrost.
9.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes
after starting and then judge temperature. Meanwhile other protections are still valid.
Med fan
High fan
0 2 T-Ts
- 26 -
Service manual
9.8.6 Indoor evaporator high-temperature protection at heating mode
(T=indoor exchanger temp.)
The louver opens to Standard Angle ANGLHEAT when power is on for the first time
Defrost 10 or 6 minutes
Compressor 25s
5s
4-way valve
2s
Outdoor fan
Indoor fan
10s
Remark: when the evaporator pipe temperature sensor more than TE16, the indoor fan start to run.
- 27 -
Service manual
9.10.1 The air conditioner automatically selects one of the following operation modes: cooling, heating or
fan only according to the temperature difference between room temperature (TA) and set temperature
(TS).
9.10.3 The motion of indoor fan’s blade should accord with the selected operation mode;
9.10.4 One mode should be carried out for at least 15 minutes once selected. If the compressor cannot
start for 15 minutes, reselect the operation mode according to the room temp. and set temp., or reselect
when the set temp. varies
9.11.1 Select forced cooling function with the forced cooling button or the switch
9.11.2 The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan mode
is set as low, the A/C operates at the DRY mode with a set temp. of 24℃
9.11.3 All protections of remote control cooling are available at forced cooling operation
9.11.4 Forced Auto function
Select forced auto function with the forced auto button or the switch.
In forced auto status the A/C operates at remote control mode with a set temp. of 24℃.
Manual operation is controlled by touching buttons and divided into force cooling and forced auto
mode.
It transfer between these two modes by pressing the buttons, the cycling order of the button press is as
below graph show to you.
- 28 -
Service manual
The set temperature rise 1℃ per hour. Two hours later, the set temperature will maintain as a
constant and the fan speed is kept at low speed.
9.12.3 Heating:
The set temperature decrease 1℃ per hour. Two hours later, the set temperature will maintain as a
constant and the air circulation is kept at low speed (Anti-cold function takes precedence over all).
9.12.4 Auto:
After an hour running under economic mode, the set temp will rise 1℃, if it is under cooling mode; the
set temp will decrease 1℃,if it is under heating mode; the set temp will be changeless, if it is under
fan-only mode; the condition will be the same after the air conditioner running under economic mode
after 2 hours, and during the next time the set temp do not change. The total time is 7 hours, after 7
hours the unit stops.
In case of a sudden power failure, this function automatically sets the unit to previous settings before
the power failure when power returns.
9.14.1 Ionizer (air clean) function is effected when the unit is working and controlled by the remote
controller.
9.14.2 This function is active when the unit received the signal from the remote controller first time and
inactive when received the signal again. Repeat this circle when received signal again.
9.14.3 This function is working only when the indoor fan is working.
9.14.3 This function will not stop when the working mode changed, and be inactive when the unit shut
- 29 -
Service manual
down.
9.15.1 This function starts when the indoor unit received the signal from remote controller, and the air
conditioner is operated by the temperature information included in the signal and the set temperature.
In this mode, the indoor temperature sensor in the indoor unit is inactive.
9.15.2 When the indoor unit received the signal by pressing the button of remote controller, the buzzer
in indoor unit will sound once. And the remote controller will send the corrected signal automatic per 3
minutes, the buzzer keep quiet at this time.
9.15.3 When the indoor unit have not received the corrected signal for 7 minutes, this function will be
shut down. The air conditioner is working in common way.
9.16.1 This function is available only under COOLING (including AUTO and FORCE cooling mode) or
DRY mode, no matter it’s cooling only or cooling & heating model.
9.16.2 For cooling only models, the air conditioner will operate under FAN ONLY mode at LOW fan
speed for 30 minutes, and then stop the operation and the unit turn off.
9.16.3 For cooling & heating models, the air conditioner will operate: FAN ONLY mode at Low fan
speed(13 minutes)--Heating operation with LOW fan speed (1 minute)---FAN ONLY operation(2
minutes)--Stop Operation---Turn off the unit.
9.16.4 Once the Auto Clean function is activated, all TIMER setting will be cancelled.
9.16.5 This operation will be stopped only by press the AUTO CLEAN button on remote controller again
or the OFF button, then the unit will turn off.
9.16.6 During Cleaning operation, only the on/off, auto clean, swing, air direction, clear air and LED
display buttons are available.
9.17 Turbo
9.17.1 Under cooling mode (except Force Cooling mode), the indoor fan motor will run in Turbo speed
when receive the signal from remoter controller, and will get back to the presetting speed when receive
again.
9.17.2 The turbo mode will cancel and indoor fan motor will get back to the presetting speed when one
of following condition occur:
a. mode changed;
b. get into Force Cooling mode;
c. turn off the air conditioner;
9.17.3 Sleep mode is not available in this mode.
- 30 -
Service manual
- 31 -
Service manual
TE1 28 28 34
TE2 32 32 37
TE3 30 30 33
TE4 26 26 22
TE5 4 4 4
TE6 10 10 10
TE7 60 60 63
TE8 53 53 53
TE9 50 50 52
THDEFROST 15 17 18
TMDEFROST 16 18 19
TLDEFROST 17 19 20
ANGLHEAT 22 22 22
ANGLCSL 8 8 8
ANGLCSH 40 40 40
ANGLHSL 8 8 8
ANGLHSH 40 40 40
ANGLDL 8 8 8
ANGLFL 50 50 50
- 32 -
Service manual
Model 18K
DELAY_TIME 127sec
DEFROST_TIME 7.5min
I3SEC 17
I5MIN 15
IFAN 14
IRESTORE 12
IDEFROST 8.5
TE1 37
TE2 34
TE3 30
TE4 20
TE5 3
TE6 12
TE7 60
TE8 53
TE9 52
THDEFROST 19
TMDEFROST 20
TLDEFROST 21
ANGLRANGE 190
ANGLOFF 97
ANGLCOOL 174
ANGLHEAT 15
ANGLCSL 10
ANGLCSH 40
ANGLHSL 10
ANGLHSH 40
ANGLDL 10
ANGLDH 190
ANGLFL 60
ANGLFH 150
HSPEEDH 1280
HSPEEDM 1100
HSPEEDL 1000
HSPEEDS 900
CSPEEDP 1280
CSPEEDH 1250
CSPEEDM 1100
CSPEEDL 900
CSPEEDS 800
- 33 -
Service manual
11 Troubleshooting
ON/OFF indicator
AUTO indicator
This indicator illuminates when the indoor air exchange with the outdoor air.
TIMER indicator
This indicator illuminates when the air conditioner starts defrosting automatically or when the warm air control
Turbo indicator
- 34 -
Service manual
Indoor fan indicator
This display is separated into three zones. Once the indoor fan is on, the zones illuminate gradually
Displaying the current set temperature when the air conditioner is in operation. When Self-Clean feature is
,, ,,
activated, it displays .
E1 EEPROM error
- 35 -
Service manual
After energizing, no indicator is lighted and the air conditioner can’t be operated.
- 36 -
Service manual
Yes
Yes
Indoor PCB is defective.
YES
- 37 -
Service manual
This is alarm signal when the main chip can’t detect over-zero signal. When such failure occurs, the main control board
must have fault.
- 38 -
Service manual
- 39 -