0% found this document useful (0 votes)
34 views1 page

ELECTRICAL

The document provides general notes for electrical works including standards to follow, materials to use, wiring methods, mounting heights and other specifications. Key points include following the Philippine Electrical Code, using new approved materials, properly grounding metal frames, running power and data cables separately, and having a licensed engineer supervise electrical works.

Uploaded by

jc ramos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
34 views1 page

ELECTRICAL

The document provides general notes for electrical works including standards to follow, materials to use, wiring methods, mounting heights and other specifications. Key points include following the Philippine Electrical Code, using new approved materials, properly grounding metal frames, running power and data cables separately, and having a licensed engineer supervise electrical works.

Uploaded by

jc ramos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

GENERAL NOTES:

LEGENDS & SYMBOLS :


1. ALL GENERAL ELECTRICAL WORKS SHALL BE EXECUTED IN ACCORDANCE WITH THE PROVISIONS OF
THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, LAWS AND ORDINANCES OF THE LOCAL
ENFORCING AUTHORITIES CONCERNED, RULES AND REGULATIONS OF THE LOCAL UTILITY COMPANY.

2. POWER SUPPLY MUST BE 230V, 1 , 3-WIRES, 60Hz, OR AS SHOWN ON THE DRAWING.

3. ALL MATERIALS AND EQUIPMENT TO BE USED SHALL BE BRAND NEW AND APPROVED TYPE AS THE
LOCATION AND PURPOSE INTENDED. MATERIALS SHALL CONFORM TO THE STANDARD SPECIFICATION OF
THE STANDARD COUNCIL.

4. ALL METAL FRAMES SHALL BE PROPERLY AND ADEQUATELY GROUNDED/BONDED.


THE SITE
5. WIRING METHOD SHALL BE COLOR CODED AS FOLLOWS:
a. L1 - RED
b. L2 - YELLOW
c. L3 - BLUE
d. GROUND - GREEN / WHITE

6. MOUNTING HEIGHTS
OILINK INTERNATIONAL
7. ALL ELECTRICAL INTERMEDIATE METAL CONDUIT (IMC) OF HIGH STRENGTH GALVANIZED WITH AND VICINITY MAP
ADDITIONAL EXTERIOR PROTECTIVE COATING SHALL BE USED.

8. CONDUITS SHALL BE INTERMEDIATE METAL CONDUIT (IMC) SCHEDULE 40 OR AS INDICATED IN THE


PLANS.
a. SERVICE ENTRANCE / LATERAL-IMC

9. INTRINSICALLY SAFE CIRCUITS SHALL NEVER SHARE THE SAME CONDUIT OR TRUNKINGWITH NOT
INTRINSICALLY SAFE CIRCUITS.

10. CONDUITS SHALL GENERALLY RUN WITH MINIMAL NUMBER OF BENDS, NEATLY ARRANGED IN TRENCHES.
POWER CABLE / CONDUITS SHALL RUN SEPARATELY FROM DATA / SENSOR CABLES. PROVIDE
1000mm SEPARATION WHERE POSSIBLE.

11. ALL CONDUITS SHALL BE PROTECTED AGAINST DAMAGES BY THE ENTRANCE OF WATER AND FOREIGN
MATTER DURING CONSTRUCTION. ALL ENDS OF CONDUITS TO EXCLUDE MOISTURE AND DUST
IMMEDIATELY AFTER THE CONDUITS ARE PLACED.

12. WIRE GUTTERS, SQUARE BOXES AND PULL BOXES SHALL BE PROVIDED ON CONDUITS AND HOMERUN
IN EXCESS OF 30 METERS OR WHERE NECESSARY, ALTHOUGH SUCH BOXES ARE NOT INDICATED ON
PLANS.

13. UTILITY BOXES SHALL BE GAUGE NO.16 (MIN.) PRESSED STEEL GALVANIZED DEEP TYPE.

14. MOUNTING HEIGHTS NOT SHOWN ON PLANS AS FOLLOWS:

a. LIGHT CONTROLLED SWITCHES - 1.40 METER ABOVE FINISH FLOOR LINE NATIONAL/
PANASONIC
b. RECEPTACLE OUTLETS - 0.40 METER ABOVE FINISH FLOOR LINE NATIONAL/
PANASONIC
c. PANEL BOARDS - 1.80 METER ABOVE FINISH FLOOR LINE SCHNEIDER,
SQUARE D, SIEMENS, ABB & GE
d. EMERGENCY LIGHT OUTLET - 2.20 METER ABOVE FINISH FLOOR LINE NATIONAL/
PANASONIC

15. MINIMUM SIZE OF CONDUCTORS AND CONDUIT WHEN NOT INDICATED IN THE PLAN SHALL BE 3.5mm2
TYPE THHN AND 15mm RESPECTIVELY RSC CONDUIT SHALL BE RIGID SCH. 40 CONDUIT IMC.
PANASONIC, SMART TUBE, PVC NELTEX, EMERALD, CROWN CABLE, PHELPS DODGE, PHILFLEX,
COLUMBIA WIRES AND CABLES.

16. WHENEVER NECESSARY PULL-BOX SHALL BE PROVIDED EVEN IF NOT INDICATED IN PLANS. BOXES
GALVANIZED G.I. UTILITY, JUNCTION BOX, FUMACO, QUAPCOR, AMTECH, STEEL CITY
THE SITE

17. ALL RECEPTACLES SHALL BE OF GROUNDING TYPE IN NATIONAL / PANASONIC. TOSHIBA.

18. CIRCUIT BREAKERS SHALL BE BOLT IN TYPE AND OF THE MAGNETIC TERMINAL TYPE COMMON TRIP
WITH THE RATING AND NUMBER OF POLES AND AS INDICATED IN DRAWINGS.
SQUARE D. SIEMENS, ABB & GE

19. ALL MOLDED CASE CIRCUIT BREAKERS FOR MOTORS SHALL BE INDUSTRIAL TYPE.

20. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE SUPERVISION DULY
QUALIFIED LICENSED / REGISTERED ELECTRICAL ENGINEER.

21. THE ELECTRICAL CONTRACTOR IS REQUIRED TO CONDUCT GROUNDING TEST, INSULATION TEST PRIOR
TO COMPLETION OF PROJECT.

22. WIRE MUST BE CONTINUOUS FROM OUTLET TO OUTLET, WITHOUT SPLICE THROUGHOUT THE CONDUIT
BODY. SPLICES ARE PERMITTED ONLY AT OUTLET BOXES. JUNCTION BOXES, WHERE THE SPLICE.
OTHERWISE PERMANENTLY ACCESSIBLE.

23. ALL MATERIALS SHALL BE NEW AND APPROVED TYPE FOR THE LOCATION AND PURPOSE IN WHICH
THEY ARE INTENDED TO BE INSTALLED.

24. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF THE POWER SUPPLY.

25. ALL PERIMETER LIGHTS MUST BE POWERED BY SOLAR PANEL WITH IP65 250WATTS LED 25,000
LUMENS. AS PART OF THE OWNER SUPPLIED MATERIALS.

BAO DRIVERS QUARTERS

Cable Routing Layout

Project name: Project Location: Sheet Contents Rev. Description Date Designed By: Rev.

Bryan Carlo T. Yu CROSS SECTION


UPPI Eng
Drawn By:
Architect LONGITUDINAL SECTION
JCR 0
SCHEDULE OF DOORS & WINDOWS

PRC No. 30753 Validity 10/01/2023


PROPOSED DRIVERS QUARTERS Lucanin Pt. Mariveles Bataan Date: 04, 25, 2023
Dwg. No.:

International Corp. PTR No. 8049252 Date 01-10-2023 A-01


Place Antipolo City Tin 407-033-410

You might also like