WP Lower Ethernet Cost With Daisy Chain
WP Lower Ethernet Cost With Daisy Chain
Many older automation fieldbus networks use a form of daisy chain topology. Daisy chain topology
consists of a cable acting as a physical bus with taps or connectors installed close to the
equipment location. The benefits are several: little to no infrastructure costs beyond the
connectors, and installation flexibility as the cable can be easily routed from one device to the next.
While Ethernet has enjoyed widespread adoption and vendor support in industry, there are
attributes of Ethernet which make it more costly to deploy as compared to this legacy fieldbus
design.
Ethernet networks require infrastructure equipment like hubs and switches. Switches introduce a
per port cost that increases the overall cost of the installation. Adding to this cost are unused ports
on Ethernet switches. While it may be prudent to order switches with extra ports, the effect is an
increase in the initial cost of the network. Difficulty planning for future port requirements adds to
the problem.
Ethernet also imposes distance constraints which require careful planning to efficiently locate
switches. End devices typically use RJ45 Category 5 cable which must be located within 100
meters of the switch port.
As shown in Figure 2, a daisy chain device has 2 embedded Ethernet ports which function as an
Ethernet switch, as well as an interface to the local device. This allows information to flow to the
device, or flow through the ports to other devices in the daisy chain.
Ethernet Daisy Chain allows devices to be cabled together in series using standard Ethernet
cable, similar to legacy fieldbus’ without the need for additional Ethernet switches. Cabling
devices in
series permits
flexibility
locating
devices, eases
installation, and
lowers
infrastructure
costs. Point-to-
point cable
routing flexibility
along with
reduced
installation costs
offer a significant advantage over the costs and design constraints of a traditional star based
Ethernet topology.
While daisy chain can be deployed in a straight line bus topology, having a redundant ring daisy
chain offers fast recovery in the event of a cable break. Simply adding a single switch with
redundant capability connects the daisy chain to the overall network and affords robust
redundancy.
Choose a switch, available from many vendors, offering redundancy with fast recovery using the
Rapid Spanning Tree Protocol (RSTP). RSTP is the IEEE 802.1w redundancy standard
interoperable with switches from many OEM’s. RSTP not only restores communications in the
event of media disconnect or failure, it protects against accidental cabling loops which can cause
non-RSTP networks to fail. Daisy chain RSTP monitors the health of the physical ring while
blocking traffic to prevent a traffic loop. Should RSTP detect a failure in the ring, RSTP will recover
and rebuild the network automatically to divert traffic around the failure.
Consider the same conveying application discussed earlier fitted with daisy chain Ethernet instead
of a switch based star topology as shown in Figure 3. Message traffic between the PLC and end
devices can be any standard 802.3 Ethernet protocol, from any automation OEM.
Once a media break or device failure in the network is detected, the Ethernet devices and the
switch work
together to
reconstruct new
message
forwarding tables
around the fault.
The standby link
will begin
forwarding traffic
around the problem
segment and
restore network
communications.
The total time from when the media fault occurs, until the time traffic begins flowing again ranges
from under 100 milliseconds to less than 1 second depending on the switch RSTP capability. The
entire fault detection and recovery effort is automatic. When the fault is repaired, the daisy chain
RSTP will detect the change and restore the original configuration.
This means that the total time it takes for a message to travel from the first device in the daisy
chain to the last device, with 32 daisy chain devices and ‘worst case’ 40 microsecond latency for
each device is less than 1.3 milliseconds.
Daisy chain Ethernet offers the best of both worlds. Simple installation and setup with the
robustness of the Ethernet protocol marries together 21st century technology with the simplicity of
earlier fieldbus’. Daisy chain Ethernet is also not restricted to any single vendor or organizational
protocol. ModbusTCP, Profinet, and ODVA EtherNet/IP all work well, even together, in a daisy
chain topology. This allows end users to mix devices, even using different protocols, in a single
daisy chain for maximum convenience.
Automatic fault detection and recovery also allows individual devices to be taken offline and
restored for service without significant interruption to other devices. Taken together, lower costs,
easier installation, design flexibility and range, daisy chain Ethernet is an attractive evolution of the
industrial fieldbus.
For further information please contact Michael B. Roche, Principal Network Application Engineer