BCGA GN 11 - Revision 4 - For Publication
BCGA GN 11 - Revision 4 - For Publication
REVISION 4: 2018
GUIDANCE NOTE 11
REVISION 4: 2018
Website:
www.bcga.co.uk
BCGA GN 11 – Revision 4
PREFACE
For the assistance of users, references are given, either in the text or
Appendices, to publications such as British, European and
International Standards and Codes of Practice, and current legislation
that may be applicable but no representation or warranty can be given
that these references are complete or current.
BCGA GN 11 – Revision 4
CONTENTS
1. INTRODUCTION 4
2. SCOPE 4
7. WORKPLACES AT RISK 16
8. WHO IS AT RISK 17
9. EVALUATION OF RISK 17
9.1 Preliminary risk assessment 18
9.2 Detailed risk assessment 20
9.3 Calculations for risk assessment 21
9.4 Risk evaluation 22
BCGA GN 11 – Revision 4
10.4 Administrative controls 25
10.5 Personal protective equipment 26
12. REFERENCES * 28
Appendixes:
Appendix 1 Example Calculations 31
Appendix 2 Workplace ventilation 35
Appendix 3 Atmospheric monitoring equipment 37
Appendix 4 Work in confined spaces 40
Appendix 5 Considerations for cryogenic or liquefied gases 42
* Throughout this publication the numbers in brackets refer to references in Section 12.
Documents referenced are the edition current at the time of publication, unless otherwise
stated.
BCGA GN 11 – Revision 4
TERMINOLOGY AND DEFINITIONS
Confined space Any place, including room, chamber, tank, vat, silo, pit, trench,
pipe, sewer, flue, well, or other similar space in which, by virtue
of its enclosed nature, there arises a reasonably foreseeable
specified risk.
Evaporation rate The rate at which the phase state change occurs.
1
BCGA GN 11 – Revision 4
Gas expansion ratio Liquid to gas volume expansion conversion – volume of gas
generated from 1 volume of liquid.
Inert gas A gas that is neither toxic nor flammable, but which does not
support human life and which reacts scarcely or not at all with other
substances.
Pyrophoric gas Pyrophoric gases can ignite and combust on contact with air (or
oxidants). Under some conditions, ignition may not occur,
resulting in the formation of a mixture of the pyrophoric gas with
air or oxidant gas, which may be unstable and potentially
explosive.
Reduced oxygen An atmosphere where the level of oxygen is reduced (or depleted)
atmosphere below the normal concentration in air, that is, nominally 20.9 %
measured by volume.
2
BCGA GN 11 – Revision 4
Risk The risk associated with any particular “hazard” is commonly
defined as the “likelihood” (or probability) of the hazard condition
arising multiplied by “a measure of the potential consequences”, for
example, injury or death.
Toxic gas Any gas that, by nature of its chemistry, has a harmful effect on
humans. This includes gases that may be harmful due to their
corrosive properties.
3
BCGA GN 11 – Revision 4
GUIDANCE NOTE 11
THE MANAGEMENT OF RISK WHEN USING GASES
IN ENCLOSED WORKPLACES
1. INTRODUCTION
The key to successful safety management is the assessment and management of risk. The
Management of Health & Safety at Work Regulations (4) require all employers to assess risk
and try to anticipate what can go wrong, then to implement control measures to reduce the risk.
As such, safety management focuses on prevention.
This document provides guidance that can be used in the assessment of risk associated with
gases in enclosed workplaces, to identify where hazardous atmospheres may occur and the
appropriate control measures.
Ambient air is primarily composed of two gases; nitrogen at approximately 78 % and oxygen
at 20.9 %. Changes to the air composition can result in a potentially hazardous atmosphere.
Human senses cannot detect different compositions in the atmosphere and are not a valid
indicator.
Changes to the composition of the air will occur from the release of gas(es) into the local
environment. Examples include evaporation, leakage and process exhaust. There is also the
potential for gases to enter the workplace from external sources. Examples include the release
of gases from neighbour sites, or concentrations of naturally occurring gases. The changes will
be more pronounced in an enclosed space and where there is inadequate ventilation.
It should also be borne in mind that even before the introduction of stored gases into certain
workplace situations, gases and low oxygen concentrations may have been generated within an
enclosed space by natural decay mechanisms such as the production of hydrogen sulphide from
stagnant water, or the corrosion (oxidation) of some metals which can deplete the available
oxygen. Atmospheric checking prior to entry to an enclosed space is therefore vital.
Incidents can occur unexpectedly, and may be serious, and sometimes fatal. All personnel
accessing an enclosed workplace should be aware of the hazard(s) associated with non-
respirable atmospheres and be given the necessary equipment, information, instruction and
training.
The British Compressed Gases Association (BCGA) provide a model risk assessment in
support of this document, refer to BCGA Technical Information Sheet (TIS) 35 (34), Model
risk assessment for the management of the atmosphere in the workplace when using gases.
This Guidance Note is intended for use in conjunction with current guidance and information
produced by the Health and Safety Executive (HSE) and other related bodies and trade
associations.
2. SCOPE
This document identifies potential hazards from the escape, leak or accumulation of gases into
the workplace and the associated risks. It also provides guidance for risk reduction measures to
4
BCGA GN 11 – Revision 4
be considered. The document scope includes all gases, whether compressed, liquefied,
refrigerated or dissolved.
Other hazards associated with the use of the gases, such as pressure, manual handling, storage
etc. are not discussed in detail in this document, but information is available in other BCGA
documents.
The scope of this document does not cover specialist activities, for example, diving, hyperbaric
conditions or deep mining, where the atmospheric pressure varies from normal ambient surface
conditions.
The Management of Health and Safety at Work Regulations (4), as well as other legislation,
such as the Confined Spaces Regulations (3), require employers to conduct risk assessments for
their activities.
When you are considering the risks associated with the use of gases in the workplace there are
several steps to be taken:
Determine how the gas(es) may enter the How may it get into the workplace?
workplace, the potential quantity of gas and in In what quantities?
what concentrations; Refer to Section 6.
5
BCGA GN 11 – Revision 4
Further information on risk assessment can be obtained from:
The Health and Safety Executive (HSE), who provide a wide range of guidance on
carrying out risk assessments on their website: www.hse.gov.uk/risk.
Further information on the storage, handling and use of gases can be found on the BCGA
website: www.bcga.co.uk
Commercially supplied gases are typically provided to the user either in bulk and stored in a
tank, or via a gas cylinder. Some gases may be present from leakage from other local sources
or appear on site naturally (for example, from the atmosphere, through human / animal
respiration, from percolation through the earth, etc.), refer to Section 6.
Commercial gas suppliers will ensure that each container they supply will correctly identify the
product it contains. The Safety Data Sheet will provide detailed information. For specific
safety information and / or advice contact your gas supplier.
On a gas cylinder the label identifies the contents and provides basic safety information on the
hazard(s) associated with the product.
Gases are classified according to their hazardous properties. There are internationally
recognised hazard pictograms used to identify each class, refer to Table 1 and Table 2.
Class 2
Division 2.2
Non-flammable
Non-toxic
Class 2
Division 2.3
Toxic
Each gas has a primary hazard and may have a number of subsidiary hazards. These will be
shown on the labels as additional pictograms.
6
BCGA GN 11 – Revision 4
Category Hazard
pictograms
Class 5.1
Oxidising substances
Class 8
Corrosive substances
There are additional hazards associated with a cryogenic gas, refer to Section 5.1.4.
5.1.1 Asphyxia
The normal concentration of oxygen in air is 20.9 %. Oxygen is the only gas that
supports life. The release of any gas will displace the existing atmosphere in an
enclosed workplace, which in turn will (other than for released air and oxygen)
reduce the volume of oxygen available to breathe. If the oxygen concentration in
the workplace atmosphere decreases there is an increased risk of asphyxiation.
Refer to Table 3.
For further information refer to the European Industrial Gases Association (EIGA)
Safety Leaflet 01 (22), Asphyxiation – The hidden killer.
7
BCGA GN 11 – Revision 4
O2 concentration Effects and symptoms
Volume %
Specific gases may have other health effects, as well as asphyxia, for example, cold
burns, toxicity, corrosive, etc. Always refer to the gas Safety Data Sheet.
5.1.3 Density
Knowing the density of the gases relative to air will suggest where the gas may
preferentially tend to accumulate. For example, a gas with a density greater than
air will tend to fall and collect in the lower areas of the workplace, such as pits,
tunnels, drains, conduits, etc.
The density of a gas varies along with its temperature such that gases superficially
regarded as being lighter or heavier than air in specific (for example, ambient)
conditions may in fact have this characteristic reversed when either warmer or
colder than those specific conditions. As an example, cold gases may initially
accumulate in low lying areas, even when at ambient conditions the gas is lighter
than air.
5.1.4 Cryogenics
Cryogenic gases may have the following additional hazards:
8
BCGA GN 11 – Revision 4
Extreme cold – hazard to materials and structures, such as
embrittlement, loss of integrity, modification of mechanical properties, etc.
Liquefaction of air - this can occur when air comes into contact with
surfaces which are at a temperature below the boiling point of an air gas, for
example, oxygen (typically at circa -183 °C). This can happen when
transferring liquid nitrogen (typically at circa -196 °C) through uninsulated
pipes which may result in the unexpected production of liquid oxygen on the
pipe outer surfaces, due to the preferential condensing of the oxygen from
atmospheric air, therefore increasing the fire risk (through oxygen
enrichment, refer to Section 5.3.4).
Acetylene, 2 to 85 %
Hydrogen, 4 to 75 %
Methane, 5 to 15 %
Hot work;
Smoking;
Welding.
NOTE: Some flammable gases, for example, hydrogen, may ignite on release for a
variety of reasons, examples include: due to the friction of the gas movement over a
surface, adiabatic compression, self-generated static electrical charge, etc. Pyrophoric
gases may ignite on contact with air (spontaneous combustion). Fusible gases may cause
9
BCGA GN 11 – Revision 4
an ignition source to be conveyed from one location to another, in some cases hundreds
of meters away.
The primary hazard from a flammable gas is the risk of fire and explosion, in addition
flammable gases have the hazard of asphyxia and some have narcotic effects.
Argon.
Helium.
Nitrogen.
The primary hazard from inert gases is asphyxia, refer to Section 5.1.1.
NOTE: Global carbon dioxide levels appear to be slowly rising. 2016 saw
average concentrations of carbon dioxide rise to 403.3 ppm, up from 400 ppm in
2015.
The effects of inhaling varying concentrations of carbon dioxide are given in Table
4, but it should be appreciated that the reactions of some individuals can be very
different from those shown.
10
BCGA GN 11 – Revision 4
CO2 concentration Typical effects and symptoms
Volume %
Nitrous oxide
Oxygen
11
BCGA GN 11 – Revision 4
The primary hazard from oxidising gases is the increased risk of combustion,
coupled with an increased intensity of combustion, refer to Section 5.3.4. Oxygen
is a reactive gas and may cause a chemical reaction.
Oxygen concentration;
Pressure;
Temperature;
Material type and quantity, as well as any local substances which could
become involved in the combustion.
NOTES:
12
BCGA GN 11 – Revision 4
2. Oil and grease should never be used to lubricate oxygen or oxygen
enriched-air equipment. Where absolutely necessary, special lubricants
which are certified as compatible with oxygen (and / or other substances
which may be present) shall be used.
Clothing, human skin and other fully or partially gas-permeable items can become
saturated with oxygen. Ensure good practice is observed in relation to clothing
ventilation (for example, when personnel move to areas where smoking is
allowed), specification, personnel awareness, proximity to sources of ignition, etc.
HSE INDG 459 (14), Oxygen use in the workplace. Fire and explosion
hazards.
Chlorine.
Hydrogen chloride.
Sulphur dioxide.
The corrosive nature of these products may have implications for and create other
(non-human) hazards, for example, mechanical considerations due to corrosion,
material deterioration, etc. These hazards may in turn result in indirect health
exposures, for example, due to loss of containment.
13
BCGA GN 11 – Revision 4
6. SOURCES OF GAS RELEASE
The workplace atmosphere may be modified through either normal use or from abnormal
release of gases. Examples include:
Process exhaust gas, for example, welding (shielding and purge gas venting),
laboratory equipment, etc.
Chilling and freezing (cryogenic liquids and dry ice) operations in open containers,
for example, shrink fitting.
Gas blanketing.
Combustion processes (for example, gas welding and cutting; localised / workplace
heating / mobile heaters, etc.) will consume atmospheric oxygen as well as using the
oxygen supply from the cylinder or pipeline and the products of combustion may include
carbon dioxide and carbon monoxide. The twin effects of gas leakage and of oxygen
consumption due to combustion may need to be considered in combination.
The use of medical gases, for example, the use of medical oxygen by patients, with
leakage from face masks etc.
Evaporation directly from open cryogenic liquid containers, for example, dewars
and bio-store freezers.
14
BCGA GN 11 – Revision 4
Poor setting up of equipment. For example, using an excess of the fuel gas,
shielding gas and / or oxygen when welding, flame cutting etc.
NOTE: Refer to EIGA Document 154 (21), Safe location of oxygen and inert gas
vents.
Cryogenic liquid spillage. The release of cryogenic liquid product will lead to the
formation of a very large volume of gas (for example, oxygen, ratio liquid to gas: 1:
860).
Liquefied gas (non-cryogenic) spillage. The release of liquefied gas will lead to
the formation of a large volume of gas (for example, propane, ratio liquid to gas: 1:400).
External sources of gas, for example, from neighbour sites, drainage systems.
15
BCGA GN 11 – Revision 4
EIGA Safety Information Leaflet 29 (24), Oxygen deficiency hazard
associated with hypoxic fire suppression systems using nitrogen injection.
NOTE: The evaporation rate will increase as the insulation efficiency deteriorates in a
cryogenic tank, for example, through wear and tear. Take this into consideration in the
risk assessment.
In addition to pressure relief valves, cryogenic tanks are normally fitted with bursting
discs. When a bursting disc operates, all the positive gas pressure in the tank, as well as
gas created from evaporation will be released. The volume of gas released and the
duration will depend upon the quantity of liquid in the tank, the pressure and the orifice
dimensions.
Consideration should also be given to the accidental release or spillage of liquid product.
For guidance on the safe storage, filling and the use of dewars and flasks refer to BCGA
CP 30 (27), The safe use of liquid nitrogen dewars up to 50 Litres. BCGA TIS 27 (32),
Model risk assessment for the safe use of liquid nitrogen dewars, provides a model risk
assessment for the safe use of liquid nitrogen dewars.
NOTE: The evaporation rate will increase as the insulation efficiency deteriorates, for
example, through wear and tear. Take this into consideration in the risk assessment.
Consideration should also be given to the accidental release or spillage of liquid product.
7. WORKPLACES AT RISK
Any area where gases are introduced, either deliberately, unintentionally or from natural
sources, may be affected by the hazards identified in this document. The following areas
typically present an increased risk:
16
BCGA GN 11 – Revision 4
Small enclosed areas – as it is a space of limited volume with potential poor
ventilation;
Below ground – due to inadequate ventilation and the collection of dense gases;
Gas product transfer areas – due to the release of a gas during transfer, coupling
and uncoupling losses, etc.;
When a change occurs to the workplace, gas usage or storage there may be a change in the risk
and possibly the hazard. The risk assessment will need to be reviewed and appropriate control
measures put in place.
8. WHO IS AT RISK
Any person who enters, or is present in, an area with an atmosphere containing gas mixtures
different from ambient air is at risk. Non-respirable atmospheres may result from gases
accumulating, whether deliberately, unintentionally or from natural sources. Examples
include:
Those in the area where the gases are being used, or where an atmosphere is being
modified, for example, through combustion or hot work;
Those who may be indirectly at risk, such as neighbours and those ‘downwind’ of a
gas release.
NOTE: Gas concentrations may have a different affect on animals than on humans.
9. EVALUATON OF RISK
As part of any assessment, the likelihood of a change in the atmosphere taking place and the
probability of harm to people shall be determined.
Carry out a preliminary assessment to establish if gases in the workplace present a hazardous
atmosphere and a risk to people. Refer to Section 9.1.
17
BCGA GN 11 – Revision 4
the largest volume of gas that can leak into the workplace;
whether the resulting foreseeable gas concentration(s) exceed threshold levels, for
some common gases refer to Table 5.
If the gas concentrations are in all foreseeable circumstances below the threshold level, and
therefore confirmed as low risk, a more thorough risk assessment is not necessary. Record the
assessment.
If the preliminary assessment indicates that the gas concentration could exceed the threshold
levels then a detailed risk assessment shall be made. Refer to Section 9.2.
NOTE: Assessing the gas concentration in a workplace is only a single assessment of one
potential hazard within the workplace and all other hazards should also be considered.
Reassessment of the risk should be carried out on a periodic basis or in the event of changes
taking place in the workplace which have the potential to create a different atmosphere.
This preliminary risk assessment considers the worst case scenario, in which the entire
content of a container(s) is released instantaneously into the workplace being assessed.
The assessment will need to be carried out for every foreseeable scenario, for example,
each type of gas present, and shall be conducted by person(s) competent to do so.
(i) Identify the gas container(s) from which gas may foreseeably be released.
Where multiple gas containers are connected together, then the combined volume
may need to be considered. You will need to understand the relationship between
container sizes and the pressure at which the gas is stored inside them. For
example, cylinders with gas at a high pressure can store a greater quantity of gas
than cylinders of a similar size with the gas stored at a lower pressure.
18
BCGA GN 11 – Revision 4
For a regularly-shaped workplace measure the height, width and length (in metres),
then multiply together to determine the volume (m3). From this volume deduct the
volumes of any objects within the workplace, such as machines, furniture, stock,
etc. (these objects reduce the volume of free air in the workplace). Allowance shall
be made for maximum stocks held during worst case conditions since these extra
stocks further reduce the free air volume in the workplace.
(iv) Calculation.
Vo
C = 100 𝑉𝑟
Where:
For some common gases the limits are referenced in Table 5. In all cases it is
recommended that reference is made to HSE EH 40 (8).
(vi) Evaluation
If the gas concentrations are within the limits in Table 5 then the workplace can be
considered low risk and a more thorough risk assessment is not necessary.
19
BCGA GN 11 – Revision 4
The preliminary assessment should be reviewed on a periodic basis and whenever
changes occur in the workplace.
If the preliminary assessment indicates that the gas concentrations exceed the limits
in Table 5, or are finely balanced, or have an unacceptable risk, a detailed risk
assessment is necessary. Refer to Section 9.2.
Potential release points, including the release rate, duration, volume and
likelihood of release:
The free air volume of the space in which the atmosphere may be present.
20
BCGA GN 11 – Revision 4
Ventilation – natural – forced – air changes per hour.
For flammable gases (and indeed all compressed gases) a DSEAR risk assessment
will be necessary. Refer to BCGA GN 13 (31), DSEAR Risk Assessment.
Other factors to consider for intoxicating, toxic and corrosive gases include:
For intoxicating, toxic and corrosive gases an assessment in accordance with the COSHH
Regulations (6) will be necessary.
Once released, a gas will be free to move and its movement will be influenced by any
ventilation conditions or systems and/or by the prevailing weather conditions. Be aware
of the hazard not only from your own gas supplies, but also from those held by your
neighbour(s).
21
BCGA GN 11 – Revision 4
This equation gives the approximate resulting oxygen percentage concentration (OCt)
after time (t) and should be used to establish the asphyxiation and oxygen enrichment
risk:
0.21 × 𝑛 −𝑡⁄
OCt = 100 (0.21 + ( [ 𝐿 ] − 0.21) (1 − 𝑒 𝑚 ))
( )+𝑛
𝑉𝑟
𝑉𝑟 × 0.21 × 𝑛
OC∞= 100 × ( 𝐿 + (𝑉𝑟 × 𝑛) ) approximately
This equation gives the approximate resulting gas percentage concentration (GCt) after
time (t) and should be used to establish the intoxicating (CO2), toxic or flammable risk:
𝑉𝑟 × 𝑛 −𝑡⁄
GCt = (100 − (100 × [𝐿 + (𝑉𝑟 × 𝑛)] )) (1 − 𝑒 𝑚)
𝑉𝑟 × 𝑛
GC∞ = 100 − (100 × [𝐿 + (𝑉𝑟 × 𝑛)] ) approximately
Where:
People
Environment
Property
22
BCGA GN 11 – Revision 4
A risk matrix can be used to help you work out the level of risk associated with a
particular issue. They do this by categorising the likelihood of harm and the potential
severity of the harm. This is then plotted in a matrix. The risk level determines which
risks should be tackled in which order. However, it does require expertise and
experience to judge the relative likelihood of harm accurately.
Any risks which are determined to be unacceptable (i.e. are not managed to a level
characterised as ‘as low as reasonably practicable’) will require risk further control
measures. Refer to Section 10.
Carry out re-assessment on a regular basis, including when a change occurs to the
workplace, gas usage or storage, and in any event, from time to time.
Risks should be reduced to the lowest reasonably practicable level by taking preventative
measures, in order of priority of effectiveness. This is what is meant by a hierarchy of control.
The list below sets out a recommended order to follow when planning to reduce risks. To
reduce the risk it may be necessary to use more than one type of control measure. Carefully
consider each of the headings in the order shown, do not simply jump to the easiest control
measure to implement.
(i) Elimination. Redesign the task or process so that the hazard is entirely removed or
eliminated. Refer to Section 10.1.
(ii) Substitution. Replace the material, substance or process with a less hazardous
one. Refer to Section 10.2.
(iii) Engineering controls. Use work equipment or other measures to control risks
from gases. Give priority to measures which protect collectively over individual
protection in line with The Management of Health and Safety at Work Regulations (4).
Refer to Section 10.3.
(iv) Administrative controls. Identify and implement robust and effective procedures
to ensure safety. Refer to Section 10.4.
(v) Personal protective equipment. Only to be considered after all the previous
measures have been applied and found not to have controlled the risks to the lowest
reasonably practicable level. Refer to Section 10.5.
Control measures are those that will reduce the probability of a hazard for example, a
hazardous atmosphere due to a gas release. The location of the gas storage, the control of gas
usage, together with adequate ventilation, are the key risk control measures. Control measures
from the recommended hierarchy set out above are discussed in further detail as follows:
23
BCGA GN 11 – Revision 4
10.1 Elimination
Remove the possibility of a hazardous atmosphere being created within an internal area.
Where possible gas should be prevented from entering the workplace unintentionally.
Examples are:
Carry out operations that use gases outside in the open air.
Carry out operations in discrete areas isolated from the general workplace
where there is adequate natural ventilation.
Store gas sources, such as cylinders and tanks, outside. Refer to the relevant
documents:
10.2 Substitution
Consider the properties of the gases in use and the environment(s) in which they will be
used or may enter. Use the most appropriate gas, with the least hazard, for any particular
situation. Examples include:
When carrying out leak testing, instead of a flammable gas (hydrogen) use a
non-flammable gas (helium).
NOTE: This will help manage flammability risks, but you will still need to
consider and appropriately manage other risks, such as asphyxiation.
Engineering controls may require specialist knowledge. Where this is the case the
controls will be required to be designed, installed and maintained by competent people.
Attention is drawn to the fact that equipment alone does not provide absolute protection,
since such equipment can malfunction, be poorly maintained, be operated by non-
competent persons, be out of calibration, be poorly located or be ignored.
24
BCGA GN 11 – Revision 4
Types of engineering control include:
Exhausts. Ensure that the exhausts from machines and pressure relief
valves, vents etc. are directed to a safe area. Refer to EIGA Document 154 (21)
and BCGA CP 4 (25).
reducing the time workers are exposed to hazards (for example, by job
rotation);
25
BCGA GN 11 – Revision 4
the use of permit to work systems to control specific tasks;
health surveillance;
Special considerations are required for access to, and work in, a confined space. Refer to
Appendix 4.
There are additional considerations where cryogenic or liquefied gases are in use, refer to
Appendix 5.
HSE L25 (15), Personal Protective Equipment at Work, provides guidance on the
Personal Protective Equipment Regulations (5). EIGA Document 136 (20), Selection of
personal protective equipment, provides guidance for selecting and using PPE at work.
Separate and / or specific PPE for different products, for example, when
handling cryogenic liquids.
Prepare for and understand how to deal with emergency situations if they arise.
26
BCGA GN 11 – Revision 4
Wherever gases are in use or in storage, alongside normal and abnormal operating procedures,
emergency procedures shall also be established and implemented. The emergency procedures
should consider:
How to prevent escalation, for example, through options for safe isolation of the
gases; use of automated or remote shutdown (or alternatively, a risk assessed decision
made to ‘walk away’ from the hazardous atmosphere and equipment whilst the gas
supply safely expends itself);
When and how to call the emergency services. Consider if pre-contact with
emergency services (especially the Fire and Rescue Service) might be suitable and
beneficial;
Recovery;
27
BCGA GN 11 – Revision 4
NOTE: Most deaths in confined spaces are of those who attempt rescue. It cannot be over-
emphasized that ill-considered rescue attempts shall be avoided.
When working in or near areas where gases are in use or in a confined space, if a person
suddenly collapses and no longer gives any sign of life, assume that the person may lack
oxygen due to the presence of an asphyxiating atmosphere. Prevent colleagues rushing to their
aid unless competent and equipped to do so, for example, with breathing apparatus.
WARNING: Do not enter a confined space without adequate preparation and risk
assessment – the biggest risk is that you will become the second victim. Get proper
assistance and support, and work according to the confined space entry procedures and
an emergency plan.
12. REFERENCES
2. SI 1996 No. 341 The Health and Safety (Safety Signs and Signals) Regulations
1996.
4. SI 1999 No. 3242 The Management of Health and Safety at Work Regulations
1999.
9. HSE Research Report Review of alarm settings for toxic gas and oxygen detectors.
RR 973
11. HSE HSG 54 Maintenance, examination and testing and testing of local
exhaust ventilation.
12. HSE HSG 250 Guidance on permit-to-work systems. A guide for the
petroleum, chemical and allied industries.
28
BCGA GN 11 – Revision 4
Document Number Title
13. HSE INDG 258 Confined spaces. A brief guide to working safely.
14. HSE INDG 459 Oxygen use in the workplace. Fire and explosion hazards.
16. HSE L101 Safe work in confined spaces. Confined Space Regulations
1997. Approved Code of Practice and guidance.
18. EIGA Document 04 Fire hazards of oxygen and oxygen enriched atmospheres.
23. EIGA Safety Carbon dioxide physiological hazards “Not just an asphyxiant”.
Information Sheet 24
24. EIGA Safety Oxygen deficiency hazard associated with hypoxic fire
Information Sheet 29 suppression systems using nitrogen injection.
25. BCGA Code of Industrial gas cylinder manifolds and distribution pipe work
Practice 4 (excluding acetylene).
26. BCGA Code of Bulk liquid carbon dioxide at users’ premises.
Practice 26
27. BCGA Code of The safe use of liquid nitrogen dewars up to 50 litres.
Practice 30
28. BCGA Code of Cryogenic liquid storage at users’ premises.
Practice 36
29
BCGA GN 11 – Revision 4
Document Number Title
32. BCGA Technical Model risk assessment for the safe use of liquid nitrogen
Information Sheet 27 dewars.
34. BCGA Technical Model risk assessment for the management of the atmosphere
Information Sheet 35 in the workplace when using gases.
UK Legislation www.legislation.gov.uk
30
BCGA GN 11 – Revision 4
APPENDIX 1
Sheet 1 of 4
EXAMPLE CALCULATIONS
One nitrogen 50 litre cylinder charged to 200 bar being used in a workplace with a free air volume of 75 m3.
Vo
C = 100 𝑉𝑟
Where:
Water capacity = 50 litre
Pressure = 200 bar
Vr = 75 m3
VO = 0.21 (Vr – Volume of gas in cylinder)
pressure capacity 200 50
Volume of gas in the cylinder = = = 10 m3
1000 1000
𝑉𝑜 = 0.21 (75 − 10) = 13.65 m3
Vo 13.65
Resulting oxygen concentration, C = 100 𝑉𝑟 = 100 = 18.2 %
75
This oxygen concentration is below the minimum workplace concentration for normal working (refer to Section 5.1.1).
However, the instantaneous release of the whole contents of a compressed gas cylinder is an almost inconceivable event, and not foreseeable as part
of normal working. Thus specific preventative measures should be assessed but are unlikely to be required in this case.
31
BCGA GN 11 – Revision 4
APPENDIX 1
Sheet 2 of 4
One 6.35 kg carbon dioxide cylinder being used in a workplace with a free air volume of 75 m3.
Vo
C = 100 𝑉𝑟
Where:
Weight = 6.35 kg
Vr = 75 m3
VO = Volume of gas in the cylinder = Weight (of product) x Specific Volume (at 1.013 bar & 15 °C) = 6.35 x 0.5344 = 3.4 m3
Vo 3.4
Resulting gas concentration, C = 100 𝑉𝑟 = 100 × 75 = 4.5 %
HSE have defined a workplace exposure limit for carbon dioxide of 0.5 % averaged over 8 hours, with a maximum exposure of 1.5 % for short
periods of 15 minutes (refer to Section 5.3.2). The volume of carbon dioxide from this 6.35 kg cylinder could produce a concentration of 4.5 % in
case of complete loss via, for example, a bursting disc failure. This would produce a dangerous atmosphere and preventive measures are necessary.
32
BCGA GN 11 – Revision 4
APPENDIX 1
Sheet 3 of 4
An inert gas is being used in a work place with a free air volume of 32 m3, the gas flow rate is 1.1 m3/h, the air changes are 0.4 per hour and the time
taken to complete the job is 2 hours.
To establish the effect of this activity on the workplace atmosphere after 2 hours the following formula is used:
0.21 × 𝑛 −𝑡⁄
OCt = 100 (0.21 + ( [ 𝐿 ] − 0.21) (1 − 𝑒 𝑚 ))
( )+𝑛
𝑉𝑟
Where:
OCt = Oxygen percentage concentration after defined time
L = 1.1 m3/h
Vr = 32 m3
n = 0.4 per hour
t = 2 hours
e = 2.72
𝑉𝑟×𝑛 32 × 0.4
m = = = 0.92
𝐿+(𝑉𝑟×𝑛) 1.1 + (32 × 0.4)
33
BCGA GN 11 – Revision 4
APPENDIX 1
Sheet 4 of 4
0.21 × 0.4 −2⁄
OCt = 100 (0.21 + ( [ 1.1 ] − 0.21) (1 − 2.72 0.92 ))
( ) + 0.4
32
0.084
OCt = 100 (0.21 + ( [0.434] − 0.21) (0.886))
OCt = 19.54 %
The oxygen concentration in the workplace has dropped to 19.54 %, which is just above the minimum recommended (19.5 %, refer to Section 5.1.1.)
and above the potentially dangerous level (18 %). However it should be noted that if the activity continues for 5 hours the oxygen concentration will
drop to 19.3 %. By increasing the ventilation air change ratio to 1 would maintain the oxygen level at approximately 20.3 %.
34
BCGA GN 11 – Revision 4
APPENDIX 2
Sheet 1 of 2
WORKPLACE VENTILATION
The HSE provide guidance on ventilation systems on their website and within HSG 37 (10), An
introduction to local exhaust ventilation, and HSG 54 (11), Maintenance, examination and
testing and testing of local exhaust ventilation.
Building size, ventilation capacity, system pressures etc. shall each be considered in specific
cases. The following guidelines generally apply:
Ventilation should be continuous or interlocked with the gas supply such that the
ventilation system operates whenever gas is being supplied or when personnel are likely
to access the hazardous area. Interlocks functionality should be checked routinely.
The ventilation system design should ensure adequate airflow around the normal
operating area to prevent a hazardous atmosphere.
The ventilation system should be compatible with all the gases that are in use. For
example, where a flammable gas is in use then the system may be within the scope of the
Dangerous Substances and Explosive Atmospheres Regulations (DSEAR) (7) and the
Equipment and Protective Systems Intended for Use in Potentially Explosive
Atmospheres Regulations (1). For additional information refer to HSE L138 (17),
DSEAR. Approved Code of Practice and guidance.
Devices indicating the effective operation of the ventilation system (air flow)
should be included in the design. Indicating devices may include:
o Warning lights.
35
BCGA GN 11 – Revision 4
APPENDIX 2
Sheet 2 of 2
Ventilation exhaust lines should be clearly identified and piped to a safe, external,
well-ventilated area. Lines should be periodically inspected to ensure they remain in a
serviceable condition, for example, there is no unacceptable damage and they are not
blocked, refer to BCGA CP 4 (25).
36
BCGA GN 11 – Revision 4
APPENDIX 3
Sheet 1 of 3
The requirement for and location of atmospheric monitoring equipment shall be determined by
risk assessment. The risk assessment should indicate the appropriate location(s) for the
detector / monitor measurement head(s).
Separate gas sensors (and where necessary, systems) shall be provided for the different
foreseeable atmospheric monitoring duties. For example, separate sensors are necessary for
carbon dioxide enrichment and for oxygen deficiency.
Atmospheric monitoring equipment shall be installed, used and maintained in line with the
manufacturer’s recommendations.
The atmospheric monitoring equipment status shall be checked for serviceability before entry
to the protected area and during occupancy. Alarm warnings, for example, flashing lights,
audible alarms, etc, shall be clearly visible and shall be duplicated / repeated both outside (i.e.
at all access points) and inside the workspace. Appropriate, clear and legible warning signs
shall be provided (for example, ‘Do not enter unless monitoring system shows no fault/safe to
enter condition’, ‘Evacuate the area in the event of gas alarm’, etc.), located appropriately and,
where of potential benefit, repeated in several locations.
Personnel competence development programmes shall include clear details of the atmospheric
monitoring equipment and the actions to take to ensure safe entry to confined spaces,
maintenance / checking of the system, verifying status, how to respond to alarms, etc.
Where forced air ventilation systems are used, they should interconnect with the atmospheric
monitoring equipment to allow automatic operation, refer to Appendix 2. What ‘automatic
operation’ precisely means will depend upon the details of the overall control system(s). An
integrated control system should be provided, in line with the Risk Assessment. Whilst it is
not possible to provide definitive advice that will apply to all installations and circumstances,
the following points should be considered in relation to system control integration:
Will the ventilation automatically trigger in the event of a gas detection alarm?
37
BCGA GN 11 – Revision 4
APPENDIX 3
Sheet 2 of 3
Should the ventilation system operate even when personnel entry is not required, or
for a specific period in advance of entry?
Will the alarm activate in the event of gas detection or ventilation fault / failure?
Can remote automatic shut-down of the dispense system be included, in the event
of alarm?
Is an uninterruptable power supply (UPS) desirable for whole or part of the system,
for example, critical control functionality or lock-outs?
Should the system(s) be linked to the premises fire alarms, taking account of the
desirability of disabling the ventilation fans in the event of fire?
How will system outages be managed (for example, for planned maintenance)?
Should you be using data-logging functions to regularly review for non-alarm gas
events in case these show trends or the need for investigation or intervention?
Should ancillary systems (for example, refrigeration fans) be incorporated into the
ventilation system (for example, where they might enhance the ventilation, rather than
just recirculate the confined space atmosphere)?
The gas detection / ventilation system(s) shall be subject to a formally planned and recorded
maintenance programme that includes calibration, periodic functional and end-to-end testing,
(often known as ‘bump testing’), alarm and interlock checks, lamp (bulb) checks for visual
alarms or annunciators and the periodic replacement of critical or wearing components, etc.
38
BCGA GN 11 – Revision 4
APPENDIX 3
Sheet 3 of 3
HSE RR 973 (9), Review of alarm settings for toxic gas and oxygen detectors.
39
BCGA GN 11 – Revision 4
APPENDIX 4
Sheet 1 of 2
Any workplace designated as a ‘confined space’ following Risk Assessment shall then be
assessed against the requirements of the Confined Spaces Regulations (3) and be subject to
specific control measures before entry. In most cases the assessment will include consideration
of:
the task(s);
Some confined spaces are fairly easy to identify, for example, enclosures with limited
openings:
Storage tanks;
Silos;
Reaction vessels;
Enclosed drains;
Sewers.
Others may be less obvious, but can be equally dangerous, for example:
Open-topped chambers;
Vats;
Ductwork;
40
BCGA GN 11 – Revision 4
APPENDIX 4
Sheet 2 of 2
It is not possible to provide a comprehensive list of confined spaces. Some places may become
confined spaces when work is carried out, or during their construction, fabrication or
subsequent modification. However, it is important to note that even a large open topped vessel
may represent a hazard, i.e. if it has contained an inert gas denser than air it may contain an
unsafe atmosphere below the level of the vessel wall that will not be removed by natural
ventilation, for example, tank bunds, dry ice containers, etc. Care should be taken not to lean
into such spaces.
Specific control measures that may be employed before entering a confined space are:
Purging of the space with air. In the specific case of flammable gases, an inert gas
purge shall be used first to prevent any explosion risk and then a subsequent purge with
air.
Information on Permit to Work systems can be obtained from HSE HSG 250 (12),
Guidance on permit-to-work systems. A guide for the petroleum, chemical and allied
industries, and EIGA Document 40 (19), Work permit systems.
The use of additional PPE, for example, breathing apparatus. Refer to Section
10.5.
Entry in to confined spaces is a legislated activity covered by the Confined Spaces Regulations
(3). HSE provide further information on working in confined spaces within:
HSE L101 (16), Safe work in confined spaces. Confined Space Regulations 1997.
Approved Code of Practice and guidance.
HSE INDG 258 (13), Confined spaces. A brief guide to working safely.
41
BCGA GN 11 – Revision 4
APPENDIX 5
Sheet 1 of 1
Ensure the location and installation of gas supply equipment is in accordance with good
engineering practice and in-line with the manufacturers’ guidance and industry best practice,
refer to Section 10.1.
NOTE: Should the storage of cryogenic or liquefied gas be in close proximity to the
workplace, there is the potential for released gases to enter. For example, the storage is located
too close to openable windows or doors in buildings, too close to breather bricks, too close to
ventilation / HVAC equipment intakes, etc.). In such cases it is advised that the location of the
storage area is reviewed against current best practice and, as necessary, adopted
retrospectively.
If multiple liquid storage tanks are installed, the potential volume of liquid unintentionally
released can be reduced by fitting simple interlock devices to prevent inadvertent use of more
than one tank or system at a time.
Storage tank fill couplings should be located in well-ventilated areas. Anti-tow away and/or
break-away protection for flexible hoses may be fitted to prevent liquid spillage due to
inadvertent movement of tank / delivery vehicle. The fitting of excess flow valves can also
prevent excessive spillage.
The risk assessment shall consider the location of pipework for liquid lines. Vent pipework,
liquid lock relief valves and equipment exhaust ports should be located in safe, freely ventilated
places. Pipe-back relief valves may be considered as an alternative to liquid lock relief valves,
as this will remove the need to pipe-away to a remote, safe area.
When moving liquid gas in ‘open’ containers such as dewars, the risk assessment shall take into
account the potential hazards which may result from, for example, spillage, venting, etc.
When transporting storage tanks that are fitted with overpressure protection such as relief
valves, bursting discs and specialist transport valves, consideration should be given to the
possibility of these devices operating and creating a hazardous atmosphere whilst being
transported. It should be appreciated that vehicle movement and vibration can increase the
evaporation rate of the liquid compared to true static conditions. Movement can also promote
premature and unintended venting due to jolting and vibration of, for example, relief device
springs.
42
BCGA GN 11 – Revision 4
British Compressed Gases Association
www.bcga.co.uk