Third Year Power Quality Unit 1 PDF
Third Year Power Quality Unit 1 PDF
POWER QUALITY
UNIT I
1.1 Introduction
✓ Power quality is any abnormal behaviour on a power system arising
in the form of voltage or current, which affects the normal operation of
electrical or electronic equipment.
✓ Power quality is any deviation of the voltage or current waveform
from its normal sinusoidal wave shape.
✓ Power quality has been defined as the parameters of the voltage that
affect the customer’s supersensitive equipment.
✓ Power quality problems are o Voltage sag o Voltage swell o Voltage
Flicker o Harmonics o Over voltage o Under voltage o Transients
✓ Voltage sags are considered the most common power quality
problem. These can be caused by the utility or by customer loads. When
ELECTRICAL POWER QUALITY
sourced from the utility, they are most commonly caused by faults on the
distribution system. These sags will be from 3 to 30 cycles and can be
single or three phase. Depending on the design of the distribution system,
a ground fault on 1 phase can cause a simultaneous swell on another
phase.
✓ Power quality problems are related to grounding, ground bonds and
neutral to ground voltages, ground loops, ground current or ground
associated issues.
Transients
✓ Transient over voltages in electrical transmission and distribution
networks result from the unavoidable effects of lightning strike and
network switching operations.\ ✓ Response of an electrical network to a
sudden change in network conditions.
o Oscillatory transient
Page | 1
ELECTRICAL POWER QUALITY
Impulsive transient:
A sudden, non power frequency change in the steady state condition of voltage or
current that is unidirectional in polarity.
Oscillatory transient:
A sudden, non power frequency change in the steady state condition of
voltage or current that is bidirectional in polarity.
Page | 2
ELECTRICAL POWER QUALITY
2. Under Voltage: An under voltage is a decrease in the rms ac voltage to less than 90 percent
at the power frequency for a duration longer than 1 min. Sources: A load switching on or
a capacitor bank switching off.
3. Sustained Interruptions: When the supply voltage becomes zero for a period of time in
excess of 1 min, the long-duration voltage variation is considered a sustained
interruption.
2. Sags(dips): A sag is a decrease in rms voltage or current between 0.1 and 0.9 pu at the
power frequency for durations from 0.5 cycle to 1 min.
Sources: Voltage sags are result of system faults and also can be caused by energization of
heavy loads or starting of large motors.
3. Swells: A swell is defined as an increase to between 1.1 and 1.8 pu in rms voltage or current
at the power frequency for durations from 0.5 cycle to 1 min.
Sources: Voltage swells occur from temporary voltage rise on the unfaulted phases during
an SLG fault. Swells can also be caused by switching off a large load or energizing large
capacitor bank
Page | 3
ELECTRICAL POWER QUALITY
Page | 4
ELECTRICAL POWER QUALITY
1. DC offset:
The presence of a dc voltage or current in an ac power system is termed dc offset.
Effects: (a) It may saturate the transformer core causing additional heating and loss of transformer
life.
(b) Direct current may also cause the electrolytic erosion of grounding electrodes and
other connectors.
2.Harmonics
Harmonics are sinusoidal voltages or currents having frequencies that are integer multiples of the
supply frequency (fundamental frequency).
Sources: Non-linear loads
Total Harmonic Distortion is used to measure the effective value of harmonic distortion. The
following figure illustrates the waveform and harmonic spectrum for a typical adjustable speed-
drive (ASD) input current.
Page | 5
ELECTRICAL POWER QUALITY
3. Interharmonics
Voltages or currents having frequency components that are not integer multiples of the frequency
at which the supply system is designed to operate (e.g., 50 or 60 Hz) are called interharmonics.
Sources: Static frequency converter, cycloconverters, induction furnaces, and arcing devices.
Power line carrier signals can also be considered as interharmonics.
4. Notching
Notching is a periodic voltage disturbance caused by the normal operation of power electronic
devices when current is commutated from one phase to another.
The following figure shows an example of voltage notching from a three-phase converter that
produces continuous dc current. The notches occur when the current commutates from one phase
Page | 6
ELECTRICAL POWER QUALITY
to another. During this period, there is a momentary short circuit between two phases, pulling the
voltage as close to zero as permitted by system impedances.
5. Noise
Noise is the unwanted electrical signals with broadband spectral content lower than 200 kHz
superimposed upon the power system voltage or current in phase conductors, or found on neutral
conductors or signal lines.
Sources: Power electronic devices, control circuits, arcing equipment, loads with solid-state
rectifiers, and switching power supplies.
The problem can be mitigated by using filters, isolation transformers, and line
conditioners.
Voltage Fluctuation:
Page | 7
ELECTRICAL POWER QUALITY
✓ Arc welders
Page | 8
ELECTRICAL POWER QUALITY
Page | 9
ELECTRICAL POWER QUALITY
✓ While many modern computers have greater tolerance than this, the
curve has become a standard design target for sensitive equipment to be
applied on the power system and a common format for reporting power
quality variation data.
✓ The axes represent magnitude and duration of the event. Points below
the envelope are presumed to cause the load to drop out due to lack of
energy. Points above the envelope are presumed to cause other
malfunctions such as insulation failure, overvoltage trip, and over
excitation.
✓ The upper curve is actually defined down to 0.001 cycle where it has
a value of about 375 percent voltage.
✓ We typically employ the curve only from 0.1 cycles and higher due
to limitations in power quality monitoring instruments and differences in
opinion over defining the magnitude values in the sub cycle time frame.
✓ The CBEMA organization has been replaced by ITI, and a modified
curve has been developed that specifically applies to common 120-V
computer equipment (see Fig. 1.6). The concept is similar to the CBEMA
curve. Although developed for 120-V computer equipment, the curve has
been applied to general power quality evaluation like its predecessor
curve.
✓ Both curves are used as a reference in this book to define the
withstand capability of various loads and devices for protection from
power quality variations.
✓ For display of large quantities of power quality monitoring data, we
frequently add a third axis to the plot to denote the number of events
within a certain predefined cell of magnitude and duration.
Page | 10
ELECTRICAL POWER QUALITY
Fig 1.5 A portion of the CBEMA curve commonly used as a design target for
equipment And a format for reporting power quality variation data.
Page | 11
ELECTRICAL POWER QUALITY
Page | 12
ELECTRICAL POWER QUALITY
Page | 13
ELECTRICAL POWER QUALITY
Page | 14
ELECTRICAL POWER QUALITY
Page | 15
ELECTRICAL POWER QUALITY
IEEE Standards:
✓ IEEE power quality standards: Institute Of Electrical and Electronics
Engineer.
✓ IEEE power quality standards: International Electro Technical
Commission.
✓ IEEE power quality standards: Semiconductor Equipment and
Material International.
✓ IEEE power quality standards: The International Union for Electricity
Applications
✓ IEEE Std 519-1992: IEEE Recommended practices and requirements
for Harmonic control in Electric power systems.
✓ IEEE Std 1159-1995: IEEE Recommended practices for monitoring
electrical power quality.
✓ IEEE std 141-1993, IEEE Recommended practice for electric power
distribution for industrial plants.
IEC Standards:
Page | 16
ELECTRICAL POWER QUALITY
are the major cause of power quality problems and cause disturbance in voltage
wave form. The power quality problems are
1. Poor load power factor
2. Non-linear loads and unbalanced loads
3. Dc offset in loads
4. Notching in load voltage
5. Disturbance in supply voltage
-1 to +1. A power factor of less than one indicates the voltage and current are
not in phase. A load with a low power factor draws more current than a load
with a high power factor. The higher current increase the energy lost in the
distribution system and require larger wires and other equipment. Because of
the cost of larger equipment and wasted energy, electrical utilities will usually
charge a higher cost to industry and customers where there is a low power
factor.
The power factor can lie in the leading and lagging sides. A lagging
power factor signifies that the load is inductive, the load will consume reactive
power and the reactive component Q is positive it is consumed by inductive
load. A leading power factor signifies that the load is capacitive, the load
supplies reactive power and the reactive component Q is negative.
Page | 17
ELECTRICAL POWER QUALITY
Page | 18
ELECTRICAL POWER QUALITY
Page | 19
ELECTRICAL POWER QUALITY
Page | 20
ELECTRICAL POWER QUALITY
Page | 21
ELECTRICAL POWER QUALITY
Page | 22