This document provides specifications for a standard generator set package including an engine and generator.
The generator is brushless, synchronous with a self-lubricated single bearing and direct coupled design. The engine is a water-cooled, 4-cycle V12 cylinder Mitsubishi heavy duty diesel model.
The package includes optional equipment such as automatic transfer switches, paralleling systems, and enclosures. Engineering data is provided including standby ratings, fuel consumption levels, and air flow requirements for the 60Hz and 50Hz models.
This document provides specifications for a standard generator set package including an engine and generator.
The generator is brushless, synchronous with a self-lubricated single bearing and direct coupled design. The engine is a water-cooled, 4-cycle V12 cylinder Mitsubishi heavy duty diesel model.
The package includes optional equipment such as automatic transfer switches, paralleling systems, and enclosures. Engineering data is provided including standby ratings, fuel consumption levels, and air flow requirements for the 60Hz and 50Hz models.
S SSt tta aan nnd ddb bby yy P PPo oow wwe eer rr STANDARD GENERATOR SET PACKAGE
ENGINE GENERATOR Air Cleaner (Dry Type) Cooler, Lube Oil Lube Oil Pump, gear driven Brushless, Synchronous Alternator, Battery Charging Exhaust Flange with Flex section Muffler, Residential Insulation Tropicalized Base, Structural Steel Filters, Fuel & Oil Radiator (mounted) Regulator, Adjustable Battery Charger Flex Fuel Lines Shut-off Solenoid (energized to run) Volts Per Hertz Battery Cables and Battery Flywheel (SAE) & Housing (SAE) Starter, Electric Voltage Adjust Rheostat Block Heater Electronic Governor Turbocharger Crankcase Jacket Water Pump Vibration Isolators, pad type
OPTIONAL EQUIPMENT ENGINE Air Starter Paralleling/Synchronization ELECTRICAL & SWITCHGEAR EQUIPMENT Heat Exchanger Cooling Remote Annunciator Automatic Transfer Switch Remote Radiator Remote Communication System Circuit Breaker with RS232 Ports and Modem Dual Standby Systems GENERATOR Paralleling Systems Paralleling Options/Accessories Power Control Centres Space Heater ENCLOSURE Synchronization with Utility Oversize Duty Options Aluminum ISO Container CONTROL PANEL Motorized Louvres TRAILER/VEHICULAR SYSTEM Analog Readout Sheet Metal Cogeneration with Utility Sound Attenuation CUSTOM FUEL SYSTEM Data Logging Seismic Isolators TRANSFER SYSTEMS, UL TANKS
02/04/2004 ENGINEERING DATA MODEL HERTZ VOLTAGES PHASE STANDBY RATINGS SP0880D:S12A2-PTA 60 120/208 277/480, 347/600 3 880 kW / 1100 kVA @ 0.8 pf SP0880D-S12A2-PTA 50 220/380, 230/400 240/415 3 880 kW / 1000 kVA @ 0.8 pf
STANDBY RATING - Continuous output available with varying load for the duration of the interruption of normal power service. For Prime Power or Unlimited Running Time Rating at variable load, see detailed specification sheets. Consult factory for Base Load (continuous) application with no load variation or for special voltages.
GENERATOR ENGINE Type - Brushless, Revolving Field, Solid State Exciter Type - Water-cooled Diesel, 4 Cycle, V12 Cylinder Construction - Single Bearing, Direct Coupled, and Self-Lubricated Model S12A2-PTA rugged MITSUBISHI Heavy duty Diesel Insulation - Class H with Special Coating for High Humidity Piston Displacement 33.9 litre (2070 cu.in.) and Anti-abrasion Enclosure IP-21 Compression Ratio 14:5:1 Overspeed Capability, 125 % for 5 minutes (per NEMA) Bore & Stroke - 150 mm (5.91 in.) x 160 mm (6.3 in.) Generator Mounted AVR, Vibration Isolated Lubrication Oil Capacity - 120 Litre (31.7 US gal.) Three Phase Sustained Short-circuit, 300% for 10 secs. 24 Volt Electric Start with Engine Driven Alternator Voltage Regulation, 0.5 % steady state Isochronous Governor, 0.25% Windward Proact Adjustable Volts per Hertz, for Torque Matching to Diesel CONTROL PANEL for Full Load Pickup Generator Mounted, facing rear TIF less than 50 (Telephone influence factor) Drip Visor THD less than 5%, 2/3 pitch stator windings EEMAC 2 Enclosure Vibration Isolated
HERTZ FUEL CONSUMPTION (100% Lead) EXHAUST BACK PRESSURE (Maximum Allowance) COMBUSTION AIR (Inlet Flow Rate) COOLANT FAN AIR FLOW (Maximum at Rated Speed) 60 209 L/hr (55 USG/hr) 450 mm (17.7 in) H20 83 M 3 /min (2931 CFM) 1,380 M 3 /min (48,728 CFM) 50 190 L/hr (50 USG/hr) 450 mm (17.7 in) H20 73 M 3 /min (2578 CFM) 1,140 M 3 /min (40,253 CFM)
11545 Kingston St., Maple Ridge B.C., Canada V2X 0Z5 Tel: 604.460.3611 Fax: 604.460.1974 www.simpower.com www.collicutt.com Specifications subject to change without notice and subject to engineering approval
Gas-Engines and Producer-Gas Plants
A Practice Treatise Setting Forth the Principles of Gas-Engines and Producer Design, the Selection and Installation of an Engine, Conditions of Perfect Operation, Producer-Gas Engines and Their Possibilities, the Care of Gas-Engines and Producer-Gas Plants, with a Chapter on Volatile Hydrocarbon and Oil Engines