Unit 7
Unit 7
UNIT 7 REFRIGERATION
Structure
7.1 Introduction
Objectives
7.1 INTRODUCTION
Refrigeration is the process of maintaining a body, or a zone in space, at a
temperature lower than the local surroundings temperature. Hence, refrigeration
requires the continuous transfer of heat from the body, or the zone, to be
‘refrigerated’ to the surroundings at a relatively high temperature. It has been
explained in Unit 6 that such a job can be done by a ‘Reversed Heat Engine’ (a
refrigerator). However, this is not the only method available for providing
refrigeration. There are several other methods used in practice. The most Commonly
used methods are :
(a) Vapour Compression Refrigeration System,
(b) Gas Compression Refrigeration System,
(c) Vapour Absorption Refrigeration, and
(d) Steam Jet Refrigeration System.
In this unit, while the first two systems in the above list are discussed in detail from
the view point of thermodynamics, only a brief mention of the working of the other
systems, their application advantages and disadvantages is made.
Objectives
After studying this unit, you should be able to
• understand the working of various refrigeration systems and the
principles on which they operate,
• represent the basic cycles on T – s and p – h diagrams and read the
properties at each state using the property Tables or Charts,
• analyse a cycle and evaluate the performance of the system using the
principles of thermodynamics studied earlier,
5
Engineering Applications
Condenser 2
Exp.
Device Compressor WC
4
Evaporator
1
QL
The VCRS, shown in Figure 7.1, has four major components, namely, the
EVAPORATOR, the COMPRESSOR, the CONDENSER and the EXPANSION
DEVICE. The ideal or the basic cycle on which such a system operates is shown in
Figure 7.2 on both T – s and p – h diagrams.
T P
PH
3
TH 2 PH
3 2
TH
PL
4
TL PL 1
4 1 TL
S h
6
Refrigeration
Wet refrigerant vapour at state 1 from the evaporator enters the compressor. This
vapour is compressed reversibly and adiabatically to saturated vapour at state 2. Let
the work required by the compressor be W. At state 2 the pressure is equal to the
saturation pressure of the refrigerant corresponding to the condenser temperature. The
high pressure vapour at state 2 is condensed to saturated liquid at the same pressure
as it passes through the condenser and let QH be the heat transferred from the
refrigerant to the surroundings at TH. The saturated liquid at state 3 is then throttled
through the expansion device to low quality vapour at state 4. At state 4 the pressure
of the refrigerant vapour corresponds to its saturation pressure at the evaporator
temperature. This low quality vapour, as it flows through the evaporator, picks up
heat to maintain the refrigerated space at a temperature TL, and then leaves it at state 1
as high quality vapour. Let QL be heat transferred to the refrigerant at the evaporator.
7.2.1 Refrigerants
The design of a VCRS is greatly influenced by the properties of the refrigerant used
in the system. The most widely used refrigerants are the halocarbons of the FREON
family. The chemical composition of each halocarbon in the above family is
identified by the number ascribed to it. For example, the commonly used refrigerant
in the domestic refrigerators is FREON-12 or R-12 which is nothing but ‘dichloro
difluoro methane (CCI2F2)’. Similarly, FREON-22 or R-22 which is commonly used
in window – airconditioners is ‘manochloro difluoro methane (CHCIF2)’. The other
refrigerants in the family are : R-11, R-13, R-14, R-22, R-113 and R-114. The
selection of the refrigerant depends upon the evaporator temperature needed, the type
of compressor used in the system and the capacity of the system.
It is not always the halocarbons that are used as refrigerants. Many inorganic
substances such as NH3, H2O, Air, CO2 and SO2 are also used as refrigerants in
certain specific situations.
Properties of the refrigerants are available in the form of tables or charts in hand
books on refrigeration and air-conditioning.
Given in Tables 7.1 and 7.2, at the end of this Unit, are the extracts of property
Tables for Freon-12 and Ammonia.
7.2.2 Performance of Vapour Compression Refrigeration System
The performance of a VCRS is expressed, as explained in Unit 6, by its Coefficient of
Performance (COP).
(Heat transfer to the refrigerant at the evaporator)
COP =
Work input
QL
or, COP = ...
W
(7.1)
Applying First Law to the cycle
W = QH − QL
QL
and hence, COP = ...
(QH − QL )
(7.2)
The following relations that give the magnitudes of heat and work interactions my be
obtained by the application of SFEE (based on unit mass) to the four components of
the VCRS. The state points marked on the schematic (Figure 7.1) and the cycle
diagram (Figure 7.2), are compatible.
QL = h1 − h4 ...
(7.3)
7
Engineering Applications
W = h2 − h1 ...
(7.4)
QH = h2 − h3 ...
(7.5)
h3 = h4 ...
(7.6)
Using Eqs. (7.1) to (7.6) it may be further written that :
(h1 − h4 )
COP = ...
(h2 − h1 )
(7.7)
(h1 − h4 )
= ...
[(h2 − h3 ) − (h1 − h4 )]
(7.8)
Refrigerating Effect
In refrigeration technology, the cooling produced per kg refrigerant is referred
to as the refrigerating effect. Therefore,
Ref. effect = (h1 – h4) kJ/kg
Capacity of the VCRS
The capacity of a VCRS, expressed in kW, is the rate at which cooling is
produced in the evaporator, therefore,
Capacity = (Mass flow rate of the refrigerant ) × ( Ref. effect).
i.e. Capacity = m&× ( h1 − h4 ) kW ...
(7.9)
where m is in kg/s and h is in kJ/kg.
Ton of Refrigeration
This is the unit of capacity of the refrigeration system commonly used in
British System of Units. A refrigeration system is said to have a capacity of
one ton if it can provide cooling at a rate of 200 BTU/min. This is so because a
system cooling at this rate can completely freeze one ton (2000 lbs) of water at
32oF to ice at the same temperature in a day (24 hours). This can easily be
checked assuming the enthalpy of fusion of water to be 144 BTU/lb.
(cooling produced)
capacity =
(time taken)
(2000 lb × 144 BTU/lb)
1 ton capacity =
24 × 60 min
= 200 BTU/min
Because of its long time continuous use in the refrigeration industry, this unit
of capacity has come to stay and is used widely everywhere irrespective of the
system of units used. It is advised not to use this unit of capacity in SI system
of Units. Here the capacity is best expressed in kW. However, to have a feel
for the relative magnitudes of ‘1 ton’ and ‘1 kW’ the following conversion
factor can be used.
1 ton = 200 BTU/min = 3.5 kW.
Compressor Power
This is the power to be supplied to the system from the surroundings.
Power = (mass flow rate of the refrigerant) × (work per kg)
8
Refrigeration
3 2
TH
TL 1
4* 4
1
=
QH
−1
QL
Replacing the ratio of heat transfer by the ratio of temperatures and rearranging,
TL
COPcarnot = COPmax = ...
(TH − TL )
(7.11)
No refrigeration cycle operating between given TH and TL can be thought of as a
model of perfect refrigeration cycle, it is impracticable as the work obtained by
expanding the high pressure liquid in the expander is so insignificant that it does not
9
Engineering Applications
warrant the use of the expander at an additional cost and added problems of its
operation and maintenance.
In actual practice, while a short capillary tube can do the job of expansion in small
VCRS, a simple expansion valve does the same job in large VCRS. It is for this
reason that attempts are not made to replace them by expanders.
SAQ 2
(a) What is the maximum COP of a VCRS operating between an evaporator
temperature of – 3oC and a condenser temperature of 27oC.
(b) Why is reversed Carnot cycle not considered as the ideal cycle for a
VCRS?
T PH P
2
3 3 2
TH PH
PL T2
TH
TL PL 1
4 1 4
TL
In the absence of any specific information, in the analysis of a simple VCRS, the
system is assumed to work on basic or ideal dry compression cycle shown in Figure
7.4. In such a case the vapour at entry to the compressor is saturated vapour at the
evaporator temperature and the compression of this vapour to state 2 is through
reversible and adiabatic compression in the compressor. Also, at state 2 the pressure
is the saturation pressure of the refrigerant corresponding to the condenser
temperature.
In actual practice the cycles do not strictly follow the basic cycles because of
irrversibilities. Also many modifications are made on the basic or ideal cycles to
improve the system performance. Explanation of all these improved cycles is beyond
the scope of this unit and hence the reader is advised to look into standard books on
refrigeration for further details if required.
SAQ 3
Show on T – s and p – h diagrams the effect of irreversibilities on compressor
work. Express adiabatic efficiency of the compressor in terms of enthalpies.
10
Refrigeration
Heater
Turbine
W T− W C
WC WT
Compressor Cooler
4
1
QL
Figure 7.5 : Closed Cycle Gas Turbine Power Plant
This is the Brayton or Joule Cycle. The states of air marked in the schematic and
cycle diagrams are compatible. The Brayton Cycle, as shown in Figure 7.6, consists
of the following process : 1 – 2, reversible adiabatic compression; 2 – 3, reversible
constant pressure heating; 3 – 4, reversible adiabatic expansion and 4 – 1 reversible
constant pressure cooling. The heat transfer to the system is QH and the net work
output of the system is (WT – WC).
T
3
WT
QH
4
2
WC
1
S
Figure 7.6 : Brayton Cycle
11
Engineering Applications
Turbine Compr.
WT WC WC - WT
4
1
QL
T 2
3
TH
TL
1
Air leaving the refrigerated space at state 1 is compressed to state 2 reversibly and
adiabatically. The compressed air is then cooled at constant pressure, Ph, to state 3 by
passing the air through the cooler. The air at state 3 is then expanded reversibly and
adiabatically in the turbine to state 4. The work output of the turbine, WT, aids the
compressor to the extent it can, thereby reducing the net work to be supplied from
outside from WC to (WC – WT). Low pressure, low temperature air at state 4 enters the
space to be refrigerated to pick up the heat to maintain the refrigerated space at a
temperature corresponding to state 1.
Here, per kg air, the magnitudes of heat and work are,
QL = h1 − h4 = c p (t1 − t4 ) ...
(7.12)
WC = h2 − h1 = c p (t2 − t1 ) ...
(7.13)
QH = h2 − h3 = c p (t2 − t3 ) ...
(7.14)
and WT = h3 − h4 = c p (t3 − t4 ) ...
(7.15)
12
Refrigeration
γ γ
⎛ ph ⎞ ⎛ T2 ⎞ γ − 1 ⎛ T3 ⎞ γ − 1
Also, ⎜ ⎟=⎜ ⎟ =⎜ ⎟ ...
⎝ pl ⎠ ⎝ T1 ⎠ ⎝ T4 ⎠
(7.16)
QL (T1 − T4 )
COP = = ...
(WC − WT ) [(T2 − T1 ) − (T3 − T4 )]
(7.17)
Refrigeration capacity = m&c p (T1 − T4 ) ...
(7.18)
Compressor power = m&c p (T2 − T1 ) ...
(7.19)
The above cycle is only an ideal cycle and hence the irreversibilities in the
compressor and turbine are not considered. In actual practice, because of
irreversibilities the temperatures at the end of compression and expansion increases,
leading to the decrease in COP of the system.
SAQ 4
(a) An airconditioning system operates on reversed Brayton cycle
maintaining the cold room at 20oC while the surroundings are at 40oC.
Show the cycle on T – s diagram and identify the states corresponding to
the above two temperatures.
(b) Air enters the compressor of an ideal air cycle refrigeration system at 1
bar, 20oC. The discharge pressure from the compressor is 3 bar. Find the
temperature of air at the exit of the compressor.
Air from
engine Heat
compr. exchanger
Fan
Air from
surroundings
13
Engineering Applications
Shown in Figure 7.9 is the schematic of a simple system used for cooling aircraft
cabins. Air bled from the jet engine compressor is passed through the heat exchanger
cooled by the outside air. This cooled high pressure air is then expanded in a small
turbine. The work from the turbine can be used to run the fan that sucks the air over
the heat exchanger. The air emerging out of the turbine at low temperature is passed
through the cabin. The by-pass line is used for temperature control.
QC
QG
Generator
Condenser
Expn.
Device
Liquid
pump
Reducing
QE valve WP
QA
Evaporator Absorber
14
Refrigeration
refrigerant vapour is absorbed by the weak solution and the resulting strong solution
is then pumped to the generator through the liquid to liquid heat exchanger. This heat
exchanger is an important component in the system. In the heat exchanger heat is
transferred from the hot but weak solution coming from the generator to the strong
solution going to the generator. Thus, the heat exchanger ensures that low
temperature weak solution enters the absorber to improve its performance, and high
temperature strong solution enters the generator to decrease the heat transfer in it,
both contributing to the improvement in performance of the system.
The COP of the system is given by
QE
COP =
(WP + QG )
The COP is low because although WP is very small for a given QE, the QG required is
very large.
In the simple system explained above it is assumed that pure refrigerant vapour
leaves the generator to be condensed in the condenser. This is barely a fact in
practice. The vapour leaving the generator is only rich in the refrigerant component.
It also carries a small fraction of absorbent. This absorbent also gets condensed in the
condenser and when it enters the throttle valve gives rise to several problems in the
expansion device and the evaporator. Hence in the actual system provision must be
made to rectify the vapour leaving the generator to assure that only refrigerant vapour
leaves the generator and the absorbent vapours are separated, condensed and returned
back to the generator. This is accomplished by installing a rectifying equipment
(analyzer and a rectifier) on the generator.
Among the various refrigerant-absorbent combinations used in VARS the most
important commercial combination has been the Ammonia-water combination in
which ammonia is the refrigerant. A VARS working with this combination is called
the Aqua-ammonia absorption refrigeration system.
Another popular combination from the air-conditioning point is the water-Lithium
Bromide combination in which water is the refrigerant.
7.4.1 Maximum COP of the VARS
If the absorption system were to operate under ideal conditions then its COP shall be
the maximum. To imagine such an ideal situation all processes must be assumed to be
reversible. The system operates continuously (in a cycle) with five interactions:
Heat transfer QG to the system at generator temperature TG;
Heat transfer QE to the system at evaporator temperature TE;
Heat transfer QC from the system at condenser temperature TC;
Heat transfer QA from the system at absorber temperature TA;
Work transfer WP to the system at the pump.
As the condenser and the absorber are cooled by the water from the surroundings, for
Ideal conditions, TC = TA = TO the ambient temperature, and the net heat transfer to
the surroundings = QO where
Qo = QC + Q A ..
. (i)
Applying the first law of thermodynamics to the system
Qo = QG + QE + WP ..
. (ii)
If the system were to be working reversibly the net entropy change of the system and
surroundings would be zero. There can be no change in entropy of the working
15
Engineering Applications
Flash
Chamber
Cooling
coil Make up
water Chilled
water
Pump
16
Refrigeration
Water to be chilled is sprayed in the flash chamber. This chamber is well insulated
and maintained at low pressure with the help of the steam ejector which continuously
removes the water vapour flashing in the chamber. Because the chamber is insulated,
the energy required for vapourising a part of spray water has to be supplied by the
non- vaporizing liquid part. Hence the temperature of liquid water in the flash
chamber decreases to provide the required chilled water. The chilled water is pumped
out to an external heat exchanger, through the cooling coils, where it cools the air to
be conditioned. The water from the cooing coils is again passed to the flash chamber.
As water vapour is being continuously removed from the flash chamber there is need
for supplying make up water to the system. The steam from the ejector is condensed
in a large condenser which is cooled by water from the local source. The condenser is
maintained at the required low pressure, normally sub-atmospheric, by wet and dry
pumps.
17
Engineering Applications
(a) For maximum COP the system must be operating in a reversible cycle,
i.e. on a reversed Carnot cycle. In such a case,
TL
COP = ...
TH − TL
(7.20)
273 − 10
= = 5.26
40 + 10
(b) The cycle can be assumed to be same as 1-2-3-4*-1 in Figure 7.3.
(h1 − h4* )
Also COP = 5.26 = ...
[(h2 − h1 ) − (h3 − h4* )]
(7.21)
where, h1, h2 and h3 have the same values as in Example 7.1.
Substituting these in the above relation,
(177.9 − h4* )
5.26 =
[(203.5 − 177.9) − (74.53 − h4* )]
The above table reveals that while the ref. effect and COP in Example
7.2 are greater than those in Example 7.1, the work input is smaller. The
difference between the two is because while the cycle in Example 7.2 is
reversible, the cycle in Example 7.1 is not.
Example 7.3
Re-do Example 7.1 assuming dry compression, and that the enthalpy after
compression is 209.4 kJ/kg.
Solution
The T – s diagram of Figure 7.4 may be used for the solution of this problem.
Reading the required properties from the property table :
h1 = hg at – 10oC = 183.06 kJ/kg
h2 = 209.4 kJ/kg (from data)
h3 = hf at 40oC = 74.53 kJ/kg
h4 = h3 = 74.53 kJ/kg
(a) Ref. effect = h1 – h4 = 183.06 – 74.53 = 108.53 kJ/kg
(b) Comp. work = h2 – h1 = 209.4 – 183.06 = 26.34 kJ/kg.
Ref. effect 108.37
(c) COP = = = 4.12
Comp. work 26.34
18
Refrigeration
Example 7.4
Re-do Example 7.3 assuming compressor efficiency is 0.8.
T
2 PH
2S
3
TH
PL
TL
4 1
Solution
Here the compression process is not reversible as its efficiency is not 100 %,
but is given to be 80%. Hence, more work is required by the compressor during
this irreversible adiabatic compression process. The efficiency of a compressor
is defined as the ratio of the reversible adiabatic work of compression to the
actual work, the compression occurring in both the cases from the same initial
state to the same discharge pressure.
In Figure 7.12 while 1 – 2s is the reversible adiabatic compression process, 1 –
2 is the actual compression process.
Wrev.ad. (h2 s − h1 )
Thus, =
Wactual ( h2 − h1 )
State 2s is the same as in Example 7.3.
Therefore, Wrev.ad. = h2s – h1 = WExample 7.3 = 26.34 kJ/kg, and the values of h1
(from Table or from Example 7.3) = 183.06 kJ/kg.
26.34
0.8 = , or Wact = 32.955 kJ/kg
Wact
Ref. effect = h1 – h4 = same as in Example 7.3 = 108.53 kJ/kg.
Ref. effect 108.53
COP = = = 3.3
Comp. work 32.955
(This problem illustrates that the irreversibility in compression leads to
increased work of compression, thereby decreasing the COP of the system)
Example 7.5
An R-12 refrigeration plant of capacity 17.5 kW maintains a cold store at –
20oC. The condenser cooling water is available in plenty at 30oC. The enthalpy
of refrigerant vapour at the end of isentropic compression is 206 kJ/kg. Find :
(a) COP,
(b) mass flow rate of the refrigerant,
(c) compressor power, and
(d) compressor cylinder dimensions assuming stroke = 1.2 diameter,
speed = 900 rev/min and volumetric efficiency = 0.92.
Solution
Figure 7.4 can be assumed to represent the cycle on which the system operates.
Properties at various states can be found using the Table of properties.
h1 = 178.61 kJ/kg
19
Engineering Applications
20
Refrigeration
cp 1.005
and γ= = = 1.4
cv 0.718
323
i.e. T4 = 0.4
= 236 K
(3) 1.4
= c p (T2 − T1 ) − c p (T3 − T4 )
2
T
2s
21
PL
B B
3
Engineering Applications
Hence, T1 = 278 K
T2s = 380.5 K
T3 = 323 K
and T4s = 236 K
W1 − 2 s (T2 s − T1 )
Comp. effect = =
W1 − 2 (T2 − T1 )
(380.5 − 278)
∴ 0.7 = or T2 = 424.4 K
(T2 − 278)
W3 − 4 (T3 − T4 )
Similarly, Turb. effect = =
W3 − 4 s (T3 − T4 s )
(323 − T4 )
∴ 0.75 = or T4 = 258 K
(323 − 236)
(T1 − T4 )
COP =
(T2 − T1 ) − (T3 − T4 )
(278 − 258)
= = 0.245
(424.4 − 278) − (323 − 258)
Capacity 10
Mass flow rate = =
Ref. effect c p (T1 − T4 )
10
= = 0.497 kg/s
1.005 (278 − 258)
7.7 SUMMARY
• Most commonly used refrigerating system is the VCRS.
• Dry compression is preferred to wet compression.
• Refrigerating effect is the cooling produced per kg refrigerant.
22
Refrigeration
• COP of a simple VCRS is equal to the ratio of refrigerating effect and the
compressor work per kg.
• Capacity of a refrigerating system is the rate at which cooling is produced and
is given by the product of refrigerating effect and the mass flow rate of the
refrigerant.
• A system is said to be of 1 ton capacity if it cools at a rate of 3.5 kW.
• Irreversibilities in a VCRS decrease the COP.
• Unless and otherwise mentioned an ideal vapour compression refrigeration
cycle is assumed to operate on dry compression with saturated vapour entering
the compressor.
• The COP of a VARS is low.
• VARS can be used advantageously wherever thermal energy is available in
plenty with negligible cost.
• The maximum COP of a VARS, maintaining an evaporator at TE at a place
where surroundings are at TO and having heat interaction with a high
temperature reservoir at TG is equal to the product of the Carnot efficiency of a
heat engine operating between TG and TO and the COP of a reversed Carnot
refrigerator operating between TE and TO.
• While R-12 is a very commonly used refrigerant in domestic refrigerators, R-
22 is used in window air-conditioners.
• Most VARS operate with ammonia as the refrigerant and water as the
absorbent.
• When VARS is used for air-conditioning normally water is used as the
refrigerant and lithium bromide is used as the absorbent.
23
Engineering Applications
SAQ 2
(a) 9.
(b) Reversed Carnot cycle is not used as the reference cycle as the turbine in
the system is not practical. Also the work output from it is insignificant
and does not warrant its use.
SAQ 3
In the T – s and p – h diagrams shown below, in Figure 7.12, state 1 is the state
of the refrigerant at entry to the compressor irrespective of whether the
compression is reversible or not. But, the end state after compression is 2 if the
compression is ierreversible and adiabatic and 2s if the compression is
reversible and adiabatic. The adiabatic efficiency of the compressor is given by
T P
2
2s
3 2s 2
3
4 1 4 1
S h
SAQ 4
(a) PH
2
T
o
3
40 C
o
P
20 C
1
S
Figure 7.15 : Figure for SAQ 5
(b) 128oC.
SAQ 5
2.25.
24
Refrigeration
25