Ba sqrv2 05 14 Acv2 Nonin Profinet en
Ba sqrv2 05 14 Acv2 Nonin Profinet en
Control
Parallel
Profibus DP
→ Profinet
Modbus RTU
Modbus TCP/IP
EtherNet/IP
Foundation Fieldbus
HART
Target group:
This document contains information for assembly, commissioning and maintenance staff.
Reference documents:
●
Manual (Operation and setting) of actuator controls ACV 01.2 Profinet
●
Manual (Fieldbus device integration) of actuator controls ACV 01.2 Profinet
Reference documents are available on the Internet at: http://www.auma.com.
2
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Table of contents
3
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Table of contents ACV 01.2 Non-Intrusive Profinet
4
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Safety instructions
1. Safety instructions
1.1. Prerequisites for the safe handling of the product
Standards/directives The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
Safety instructions/ All personnel working with this device must be familiar with the safety and warning
warnings instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out by suitably qualified personnel authorised by the end user or contractor
of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Commissioning Prior to commissioning, imperatively check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation. The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Protective measures The end user or the contractor are responsible for implementing required protective
measures on site, such as enclosures, barriers, or personal protective equipment
for the staff.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior written consent of the manufacturer.
1.2. Range of application
AUMA part-turn actuators SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 are
designed for the operation of industrial valves, e.g. butterfly valves and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
5
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Safety instructions ACV 01.2 Non-Intrusive Profinet
● Buried service
● Continuous underwater use (observe enclosure protection)
● Potentially explosive areas
● Radiation exposed areas in nuclear power plants
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Information These operation instructions are only valid for the "clockwise closing" standard
version, i.e. driven shaft turns clockwise to close the valve.
1.3. Warnings and notes
Information The term Information preceding the text indicates important notes and information.
6
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Safety instructions
Hot surface
Warning of hot surfaces, e.g. possibly caused by high ambient temperatures or strong
direct sunlight.
Electrical voltage
Hazardous voltage! Warning of electric shock. At some devices, the warning sign
additionally includes a time interval, e.g. 30 s. Once power supply is switched off,
you will have to wait for the indicated period. Only then may the device be opened.
7
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Short description ACV 01.2 Non-Intrusive Profinet
2. Short description
Part-turn actuator Definition in compliance with EN 15714-2/EN ISO 5211:
A part-turn actuator is an actuator which transmits a torque to the valve for less than
one full revolution. It need not be capable of withstanding thrust.
AUMA part-turn actuator Figure 1: AUMA SQV 10.2 part-turn actuator
For non-intrusive version (control unit: electromechanical version), limit and torque
setting is made via switches within the actuator.
For non-intrusive version (control unit: electronic version), limit and torque setting is
made via the actuator controls, neither actuator nor the actuator controls housing
have o be opened. For this purpose, the actuator is equipped with an MWG (magnetic
limit and torque transmitter), also capable of supplying analogue torque feedback
signals/torque indication and analogue position feedback signals/position indication
at the actuator controls output.
For variable speed actuators SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2, the
actuator speed is modified by means of a frequency converter in the actuator controls.
Actuator controls The actuator controls ACV 01.2 may be mounted directly to the actuator or separately
on a wall bracket.
The actuator can be operated via the push buttons on the local controls of the actuator
controls or settings can be made in the actuator controls menu. The display shows
information on the actuator as well as the menu settings.
The functions of the actuator controls include standard valve control in OPEN-CLOSE
duty, positioning, process control, logging of operating data, diagnostic functions
right through control via various interfaces (e.g. fieldbus, Ethernet and HART).
App and software
Using the AUMA CDT software for Windows-based computers (notebooks or tablets)
and the AUMA Assistant App, actuator data can be uploaded and read, settings
can be modified and stored. The connection between computer and AUMA actuator
is established wireless via Bluetooth interface. With the AUMA Cloud, we provide
an interactive platform to collect and assess e.g. detailed device data of all actuators
within a plant.
8
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Short description
AUMA CDT AUMA CDT is a user-friendly setting and operation program for AUMA actuators.
AUMA CDT software can be downloaded free of charge from our website
www.auma.com.
The AUMA Cloud is the driving element of the digital AUMA world, acting as
interactive platform for efficient maintenance of AUMA actuators at moderate cost.
The AUMA Cloud collects all device data of all actuators within one site and provides
a clear overview at a glance. Detailed analysis provides valuable information on
AUMA Cloud potential maintenance requirements. Additional functions foster smooth asset
management.
The AUMA Assistant App enables remote setting and remote diagnostics of AUMA
actuators via Bluetooth using either smartphone or tablet.
The AUMA Assistant App can be downloaded free of charge from the Play Store
AUMA Assistant App (Android) or App Store (iOS).
Figure 3: Link to AUMA Assistant App
9
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Name plate ACV 01.2 Non-Intrusive Profinet
3. Name plate
Figure 4: Arrangement of name plates
10
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Name plate
(= manufacturer logo)
[1] Type designation
[2] Order number
[3] Serial number
[4] Actuator terminal plan
[5] Actuator controls wiring diagram
[6] Mains/voltage range/frequency range
[7] Rated power of the ACV
[8] Permissible ambient temperature
[9] Enclosure protection
[10] Control
[11] Data Matrix code
11
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Name plate ACV 01.2 Non-Intrusive Profinet
Table 2:
Description of actuator controls type designation (with the example of ACV 01.2)
ACV 01.2
ACVExC Type AC = Actuator controls
V = Variable speed
01.2 Size 01.2
Order number The product can be identified using this number and the technical data as well as
order-related data pertaining to the device can be requested.
Please always state this number for any product inquiries.
On the Internet at http://www.auma.com > Service & Support >myAUMA, we offer
a service allowing authorised users to download order-related documents such as
wiring diagrams and technical data (both in German and English), inspection certificate
and the operation instructions when entering the order number.
Control Table 4:
Control examples (indications on actuator controls name plate)
Input signal Description
Profinet Control via Profinet interface
Profinet/24 V DC Control via Profinet interface and control voltage for OPEN-CLOSE control
via digital inputs (OPEN, STOP, CLOSE)
Data Matrix code When registered as authorised user, you may use our AUMA Assistant App to scan
the Data Matrix code and directly access the order-related product documents without
having to enter order number or serial number.
Figure 8: Link to AUMA Assistant App:
12
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Transport, storage and packaging
Suspended load!
Death or serious injury.
→ Do NOT stand below suspended load.
→ Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→ Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→ Actuators mounted to gearboxes: Attach ropes or hooks for the purpose of lifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→ Actuators mounted to controls: Attach ropes or hooks for the purpose of lifting
by hoist only to the actuator and NOT to the controls.
→ Respect total weight of combination (actuator, actuator controls, gearbox, valve)
→ Secure load against falling down, sliding or tilting.
→ Perform lift trial at low height to eliminate any potential danger e.g. by tilting.
13
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Transport, storage and packaging ACV 01.2 Non-Intrusive Profinet
Table 5:
Weights for part-turn actuators SQV 05.2 – SQV 14.2 / SQRV 05.2 – SQRV 14.2
with 3-phase AC motors
Type designation Weight1)
Actuator approx. [kg]
SQV 05.2/ 21
SQRV 05.2
SQV 07.2/ 21
SQRV 07.2
SQV 10.2/ 26
SQRV 10.2
SQV 12.2/ 35
SQRV 12.2
SQV 14.2/ 44
SQRV 14.2
1) Indicated weight includes AUMA NORM part-turn actuator with 3-phase AC motor, electrical con-
nection in standard version, unbored coupling and handwheel. For other output drive types, consider
additional weights.
4.2. Storage
Long-term storage For long-term storage (more than 6 months), observe the following points:
1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion. If first signs of corrosion show, apply new corrosion protec-
tion.
14
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Assembly
5. Assembly
When using grease as lubricant, the product described herein can be operated in
any mounting position.
When using oil instead of grease within the actuator gear housing, perpendicular
mounting position is specified whereby the flange is pointing downward. The type of
lubricant used is indicated on the actuator name plate (short designation F...= grease;
O...= oil).
5.2. Handwheel fitting
Figure 10: Handwheel
[1] Spacer
[2] Input shaft
[3] Handwheel
[4] Retaining ring
The actuator is mounted to the valve using a coupling (standard) or via lever. Separate
instructions are available for actuator mounting to the valve when equipped with
base and lever.
15
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Assembly ACV 01.2 Non-Intrusive Profinet
Assemble valve and actuator in the same end position. As standard, the actu-
ator is supplied in end position CLOSED.
→ Recommended mounting position for butterfly valves: End position CLOSED.
→ Recommended mounting position for ball valves: End position OPEN.
Assembly steps 1. If required, move actuator in same end position as valve using the handwheel.
2. Clean mounting faces, thoroughly degrease uncoated mounting surfaces.
3. Apply a small quantity of grease to the valve shaft [2].
16
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Assembly
4. Place coupling [1] onto valve shaft [2] and secure against axial slipping by using
a grub screw [3] or a clamping washer and a screw with curved spring lock
washer [4]. Thereby, ensure that dimensions X, Y or L are observed (refer to
figure and table <Mounting positions for coupling>).
Figure 12: Examples: Fit coupling
[1] Coupling
[2] Valve shaft
[3] Grub screw
[4] Clamping washer and screw with curved spring lock washer
Figure 13: Mounting positions for coupling
Table 6:
Mounting position of the coupling within fitting dimensions according to AUMA definition
Dimensions [mm] SQ 05.2 SQ 07.2 SQ 10.2 SQ 12.2 SQ 14.2
EN ISO 5211 F05 F07 F05 F07 F10 F10 F12 F12 F14 F14 F16
X max. 3 3 3 3 3 4 4 5 5 8 8
Y max. 2 2 2 2 2 5 5 10 10 10 10
L max. 40 40 40 40 66 50 82 61 101 75 125
17
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Assembly ACV 01.2 Non-Intrusive Profinet
6. Fit actuator. If required, slightly turn actuator until splines of coupling engage.
Figure 14:
Information Ensure that the spigot (if provided) fits uniformly in the recess and that the flanges
are in complete contact.
7. If flange bores do not match thread:
7.1 Slightly rotate handwheel until bores line up.
7.2 If required, shift actuator by one tooth on the coupling.
8. Fasten actuator with screws.
Information: We recommend applying liquid thread sealing material to the
screws to avoid contact corrosion.
9. Fasten screws crosswise to a torque according to table.
Table 7:
Tightening torques for screws
Threads Tightening torque [Nm]
Strength class A2-80/A4–80
M6 10
M8 24
M10 48
M12 82
M16 200
M20 392
18
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Assembly
The mounting position of the local controls is implemented according to the order.
If, after mounting the actuator to the valve or the gearbox on site, the local controls
are in an unfavourable position, the mounting position can be changed at a later
date. Four mounting positions shifted by respectively 90° are possible (by maximum
180° into one direction).
19
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Electrical connection ACV 01.2 Non-Intrusive Profinet
6. Electrical connection
6.1. Basic information
Wiring diagram/terminal The pertaining wiring diagram/terminal plan (in German or English) is attached to
plan the device in a weather-proof bag, together with these operation instructions. It can
also be requested from AUMA (state order number, refer to name plate) or
downloaded directly from the Internet (http://www.auma.com).
Permissible networks The actuators are suitable for use in TN and TT networks with directly grounded star
(supply networks) point for nominal voltages up to maximum 480 V AC. Use in IT network is permissible
for nominal voltages up to maximum 480 V AC. For IT network, a suitable, approved
insulation monitor measuring the pulse code is required.
Current type, mains Type of current, mains voltage and mains frequency must match the data on the
voltage, mains fre- actuator controls and motor name plates. Also refer to chapter <Identification>/<Name
quency plate>.
Figure 17: Actuator controls name plate (example)
Protection and sizing on For short-circuit protection and for disconnecting the actuator from the mains, fuses
site and disconnect switches have to be provided by the customer.
20
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Electrical connection
Table 8:
Protection on site
Part-turn actu- 3-phase AC motor 380 V – 480 V/50 Hz – 60 Hz1) Fuse2)
ator
Consumed rated Blow characteristics:
power Rated current Max. current Time-delay (gG)
Type PIN [kW] IN [A] Imax [A] [A]
SQV 05.2 0.21 0.8 1.3 6.0
SQRV 05.2 0.17 0.7 1.1 6.0
SQV 07.2 0.39 1.3 1.9 6.0
SQRV 07.2 0.18 0.8 1.0 6.0
SQV 10.2 0.21 1.0 1.5 6.0
SQRV 10.2
SQV 12.2 0.21 1.0 1.5 6.0
SQRV 12.2
SQV 14.2 0.27 1.0 7 6.0
SQRV 14.2
1) For motor with different current type/mains voltage/mains frequency (refer to motor name plate),
select fuse in accordance with electrical data sheet.
2) The actuators are suitable for use in current circuits with a maximum short-circuit AC current value
of 5,000 A root-mean-square (R.M.S). The output data of the fuses to be provided on site must not
exceed the following values: 32 A/600 V at a maximum mains mains short circuit current of
5,000 A AC.
Consider the max. current (Imax) (refer to motor name plate or electrical data sheet)
when selecting the circuit breaker.
We recommend refraining from using residual current devices (RCD). However, if
an RCD is used within the mains, the residual current device must be of type B. DC
current may be present within the PE conductor.
For actuator controls equipped with a heating system and external electronics power
supply, the fuses for the heating system have to be provided by the customer (refer
to wiring diagram F4 ext.)
Table 9:
Fuse for heating system
Designation in wiring diagram = F4 ext.
External power supply 115 V AC 230 V AC
Fuse 2AT 1AT
If actuator controls are mounted separately from actuator ( actuator controls on wall
bracket): Consider length and cross section of connecting cable when defining the
protection required.
Connecting cables, ● We recommend using connecting cables and connecting terminals according
cable glands, reducers, to rated current (IN) (refer to motor name plate or electrical data sheet).
blanking plugs ● For device insulation, appropriate (voltage-proof) cables must be used. Specify
cables for the highest occurring rated voltage.
● To avoid contact corrosion, we recommend the use of sealing agents for cable
glands and blanking plugs made of metal.
21
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Electrical connection ACV 01.2 Non-Intrusive Profinet
Cable installation in ac- Signal and fieldbus cables are susceptible to interference. Motor cables are
cordance with EMC interference sources.
Profinet cables The following minimum requirements with regard to LAN cables apply for Profinet
networks: Category 5 according to ISO/IEC 11801 Edition 2.0 Class D.
Connector is suitable for wiring dual pair Profinet cables.
The following tables list the available cable types Profinet types A through C with
regard to the respective application:
Table 10:
Cable types for dual pair Profinet cables
Cable types Application type A Application type B Application type C
Version Dual pair data cable Dual pair data cable Dual pair data cable
Type of installation fixed installation, immobile after flexible installation (e.g. for contin- special applications (e.g. for contin-
installation ous movement, vibration or twist- ous movement, vibration or twist-
ing after installation) ing)
Cable parameter
Designation (minimum) “Profinet type A” “Profinet type B” “Profinet type C”
Cross section AWG 22/1 ≥ 0.610 mm² AWG 22/7 ≥ 0.318 mm² AWG 22/.. ≥ 0.318 mm²
Outer cable diameter 5.5 – 8.0 mm depending on application
Wire diameter 1.4 ± 0.2 mm depending on application
Colour of shield Green RAL6018 depending on application
Colour of wire insulation Pair 1: white, blue
Pair 2: yellow, orange
Number of wires 4
Cable design Dual pair or star quad
Shield Alumium foil + copper braid depending on application
Communication requirements
22
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Electrical connection
Minimum cable spacing The minimum spacing (according to IEC 61918) required between laying Profinet
cables and other cables must be respected. They are shown in the table below.
Table 11:
Minimum spacing for Profinet cables
Spacing to Profinet cable
Without or with non-metal Aluminium cutoff bridge Steel cutoff bridge
cutoff bridge
Signal transmission cables
E.g. other Profinet cables, Profibus cables, data cables 0 mm 0 mm 0 mm
for PCs, programming devices, shielded analogue inputs
Power supply cables
Unshielded power supply cables 200 mm 100 mm 50 mm
Shielded power cables 0 mm 0 mm 0 mm
Further references Ensure absence of equipotential earth bonding differences between the individual
devices at Profinet (perform an equipotential earth bonding).
Available Profinet recommendations, particularly planning, assembly and
commissioning guidelines of the Profibus User Organisation (PNO)
(www.profibus.com) must be met.
6.2. SF electrical connection (AUMA plug/socket connector)
23
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Electrical connection ACV 01.2 Non-Intrusive Profinet
SF version. For power and control cable connection, remove the AUMA plug/socket
connector and the socket carrier from terminal compartment. Removing the cover
is sufficient for connecting the fieldbus cables.
Technical data Table 12:
Electrical connection via AUMA plug/socket connector
Power contacts Control contacts
No. of contacts max. 6 (3 equipped) + protective 50 pins/sockets
earth conductor (PE)
Designation U1, V1, W1, U2, V2, W2, PE 1 to 50
Connection voltage max. 750 V 250 V
Rated current max. 25 A 16 A
Type of customer connection Screw connection Screw connection, crimp-type (option)
2 2
Connection diameter max. 6 mm (flexible) 2.5 mm
2
10 mm (solid) (flexible or solid)
24
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Electrical connection
4. Seal unused cable entries [6] with suitable blanking plugs [7].
Information Fieldbus connection can be accessed separately from the mains connection (refer
to <Fieldbus terminal compartment: open>.
Table 13:
Terminal cross sections and terminal tightening torques
Designation Terminal cross sections Tightening torques
2
Power contacts 1.0 – 6 mm (flexible) 1.2 – 1.5 Nm
2
(U1, V1, W1, U2, V2, W2) 1.5 – 10 mm (solid)
2
Protective earth connection (PE) 1.0 – 6 mm (flexible) with ring lugs 1.2 – 2.2 Nm
2
1.5 – 10 mm (solid) with loops
2
Control contacts 0.25 – 2.5 mm (flexible) 0.5 – 0.7 Nm
2
(1 to 50) 0.34 – 2.5 mm (solid)
25
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Electrical connection ACV 01.2 Non-Intrusive Profinet
26
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Electrical connection
1. Insert the socket carrier [5] into the connection housing [1] and fasten with
screws [4].
2. Clean sealing faces of connection housing [1] and housing.
3. Check whether O-ring [3] is in good condition, replace if damaged.
4. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5. Fit connection housing [1] and fasten screws [2] evenly crosswise.
6. Fasten cable glands and blanking plugs applying the specified torque to ensure
the required enclosure protection.
27
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Electrical connection ACV 01.2 Non-Intrusive Profinet
28
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Electrical connection
Option:
29
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Electrical connection ACV 01.2 Non-Intrusive Profinet
Table 17:
MODS (Module Status) Status Explanation
Red LED: off + Not Initialised No voltage or module in “SETUP” or “NW_INIT”
Green LED: off status
Green LED: illuminated Normal Operation The module has aborted “NW_INIT” status
Green LED: 1 brief pulse Diagnostic Events Diagnostic events available
Red LED: illuminated + Exception Error Device in “EXCEPTION” status
Red NETS LED: off
Red LED: illuminated + Fatal Event Internal device error
Red NETS LED: illuminated
Green/Red LEDs: Firmware update Do not cut power supply!
Alternately blinking
30
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Electrical connection
Table 18:
NETS (Network Status) Status Explanation
Red LED: off + Offline Absence of power supply or no connection to IO
Green LED: off controller
Green LED: illuminated RUN Connection to IO controller available
Green LED: 1 brief pulse STOP Connection to IO controller available. However, IO
controller is in STOP status or IO data is incorrect.
Green LED: blinking Blink Is used by engineering tools to identify the device
within the Profinet network
Red LED: illuminated Fatal Event Internal error, combined with “MODS” LED.
Red LED: 1 brief pulse Station Name Er- Device name (station name) not yet set
ror
Red LED: 2 brief pulses IP address Error IP address not yet set
Red LED: 3 brief pulses Configuration Er- Identification incorrect
ror
Table 19:
LINK/ACT1, LINK/ACT2 Explanation
(Link/Activity Port 1 / 2)
Red LED: off + No communication at port 1 or 2
Green LED: off
Green LED: illuminated Port 1 or 2 are in “Link Established” status
Green LED: blinking Data communication via port 1 or port 2
Red LED No function
Table 20:
LED Explanation
RESET LED: illuminated No Reset active, power supply available
DEBUG LED: illuminated Sub-assembly in Reset status
DEBUG LED: 1 brief pulse Sub-assembly in initialisation status
DEBUG LED: briefly blinking (1 Debug mode active
Hz) Normal status (Profinet application active)
DEBUG LED: slowly blinking (5
Hz)
CAN LED: illuminated Error of internal CAN communication
BA1 LED or BA2 LED: illumin- Bus active ("Link Established" at port 1 or port 2)
ated
DX LED: illuminated “Data Exchange” via Profinet
31
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Electrical connection ACV 01.2 Non-Intrusive Profinet
32
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Electrical connection
Information on installa- ● The permissible cable length of LSW between separate local controls and the
tion with wall bracket actuator amounts to 16 m maximum.
Longer cables require an external filter (available on request)
33
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Electrical connection ACV 01.2 Non-Intrusive Profinet
34
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Electrical connection
Table 21:
Terminal cross sections and earth connection tightening torques
Conductor type Terminal cross sections Tightening torques
Solid wire and stranded 2.5 mm² to 6 mm² 3 – 4 Nm
Fine stranded 1.5 mm² to 4 mm² 3 – 4 Nm
For fine stranded (flexible) wires, connection is made via cable lugs/ring terminals. When connecting
two individual wires with a U-bracket, cross sections have to be identical.
35
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Operation ACV 01.2 Non-Intrusive Profinet
7. Operation
36
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Operation
➥ The actuator can now be operated using the push buttons [1 – 3]:
- Run actuator in direction OPEN: Press push button [1] .
- Stop actuator: Press push button STOP [2].
- Run actuator in direction CLOSE: Press push button [3] .
Information The OPEN and CLOSE operation commands can be given either in push-to-run or
in self-retaining operation mode. In self-retaining mode, the actuator runs to the
defined end position after pressing the button, unless another command has been
received beforehand. For further information, please refer to the Manual (Operation
and setting).
37
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Operation ACV 01.2 Non-Intrusive Profinet
Information For actuators equipped with a positioner, it is possible to change over between OPEN
- CLOSE control (Remote OPEN-CLOSE) and setpoint control (Remote SET-
POINT). For further information, please refer to the Manual (Operation and setting).
7.3. Menu navigation via push buttons (for settings and indications)
Menu navigation for display and setting is made via the push buttons [1 – 4] of the
local controls.
Set the selector switch [5] to position 0 (OFF) when navigating through the menu.
The bottom row of the display [6] serves as navigation support and explains which
push buttons [1 – 4] are used for menu navigation.
Figure 33:
38
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Operation
Direct display via ID When entering the ID within the main menu, screens can be displayed directly (without
clicking through).
Figure 37: Direct display (example)
39
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Operation ACV 01.2 Non-Intrusive Profinet
Password A password must be entered to allow parameter modification. The display indicates:
Password 0***
A specific password is assigned to each user level and permits different actions.
Table 24:
User levels and authorisations
Designation (user level) Authorisation/password
Observer (1) Verify settings
No password required
Operator (2) Change settings
Default factory password: 0000
Maintenance (3) Reserved for future extensions
Specialist (4) Change device configuration
e.g. type of seating, assignment of output contacts
Default factory password: 0000
Service (5) Service staff
Change configuration settings
AUMA (6) AUMA administrator
1. Select desired menu and hold down push button for approx. 3 seconds.
➥ Display indicates the set user level, e.g Observer (1)
2. Select higher user level via Up ▲ and confirm with Ok.
➥ Display indicates: Password 0***
3. Use push buttons Up ▲ Down ▼ to select figures 0 to 9.
4. Confirm first digit of password via push button Ok.
5. Repeat steps 1 and 2 for all further digits.
➥ Having confirmed the last digit with Ok, access to all parameters within one
user level is possible if the password entry is correct.
40
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Operation
Menu item Service functions M0222 is only visible, if user level Specialist (4) or higher
is selected.
2. Press push button C Setup and hold it down for approx. 3 seconds.
➥ Display goes to main menu and indicates: ▶ Display
Change passwords 3. Select parameter Change passwords either:
→ click via the menu to parameter, or
→ via direct display: press and enter ID M0229
- Display indicates: ▶ Change passwords
- The user level is indicated in the top row (1 – 6), e.g.:
- For user level 1 (view only), passwords cannot be changed. To change pass-
words, you must change to a higher user level. For this, enter a password via
a parameter.
4. For a user level between 2 and 6: Press push button Ok.
➥ The display indicates the highest user level, e.g.: For user 4
5. Select user level via push buttons Up ▲ Down ▼ and confirm with Ok.
➥ Display indicates: ▶ Change passwords Password 0***
6. Enter current password (→ enter password).
➥ Display indicates: ▶ Change passwords Password (new) 0***
7. Enter new password (→ enter password).
➥ Display indicates: ▶ Change passwords For user 4 (example)
8. Select next user level via push buttons Up ▲ Down ▼ or cancel the process
via Esc.
7.4.3. Timeout for incorrect password entry
A timeout for incorrect password entry is provided with actuator controls.This prevents
unauthorised access by systematic trials. The timeout is active for incorrect entries
via the local controls as well as incorrect entries via our software tools (AUMA CDT,
AUMA Assistant App). After five subsequent incorrect trials, further entry is inhibited
for one minute. Each further incorrect entry doubles the timeout period. An active
timeout is displayed on the screen. An individual timeout is available for each user
level. This means that you may still log on with user level 3 if user level 4 is inhibited.
The incorrect entry counter can be reset in two ways:
1. Correct password entry with successful access authorisation.
2. 8 hours after the last incorrect entry.
7.5. Language in the display
The display language can be selected.
7.5.1. Language change
Display M0009
Language M0049
41
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Operation ACV 01.2 Non-Intrusive Profinet
2. Press push button C Setup and hold it down for approx. 3 seconds.
➥ Display goes to main menu and indicates: ▶ Display
Change language 3. Press Ok.
➥ Display indicates: ▶ Language
4. Press Ok.
➥ Display indicates the selected language, e.g.: ▶ Deutsch
5. The bottom row of the display indicates:
→ Save → continue with step 10
→ Edit → continue with step 6
6. Press Edit.
➥ Display indicates: ▶ Observer (1)
7. Select user level via Up ▲ Down ▼ resulting in the following significations:
→ black triangle: ▶ = current setting
→ white triangle: ▷ = selection (not saved yet)
8. Press Ok.
➥ Display indicates: Password 0***
9. Enter password (→ enter password).
➥ Display indicates: ▶ Language and Save (bottom row)
Language selection 10. Select new language via Up ▲ Down ▼ resulting in the following significations:
→ black triangle: ▶ = current setting
→ white triangle: ▷ = selection (not saved yet)
11. Confirm selection via Save.
➥ The display changes to the new language.The new language selection is saved.
42
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Indications
8. Indications
8.1. Indications during commissioning
LED test When switching on the power supply, all LEDs on the local controls illuminate for
approx. 1 second. This optical feedback indicates that the voltage supply is connected
to the controls and all LEDs are operable.
Figure 39: LED test
Language selection During the self-test, the language selection can be activated so that the selected
language is immediately indicated in the display. For this, set selector switch to
position 0 (OFF).
Activate language selection:
1. Display indicates in the bottom line: Language selection menu? 'Reset'
2. Hold down push button RESET until display of the following text in the bottom
line: Language menu loading, please wait.
Figure 40: Self-test
If the language selection feature has been activated during the self-test, the menu
for selecting the display language will now be indicated. For further information on
language setting, please refer to chapter <Language in the display>.
Figure 42: Language selection
If no entry is made over a longer period of time (approx. 1 minute), the display
automatically returns to the first status indication.
8.2. Indications in the display
43
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Indications ACV 01.2 Non-Intrusive Profinet
Status bar The status bar (first row in the display) indicates the operation mode [1], the presence
of an error [2] and the ID number [3] of the current display indication.
Figure 43: Information in the status bar (top)
Reaching the preset end positions is additionally indicated via (CLOSED) and
(OPEN) symbols.
Figure 46: End position CLOSED/OPEN reached
Torque (S0002)
● S0002 on the display indicates the torque applied at the actuator output.
44
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Indications
Select unit The push button allows to select the unit displayed (percent %, Newton metre Nm
or "foot-pound" ft-lb
Figure 48: Units of torque
Display in percent 100 % indication equals the max. torque indicated on the name plate of the actuator.
Example: Torque range on name plate = 20 – 60 Nm.
● 100 % corresponds to 60 Nm of nominal torque.
● 50 % corresponds to 30 Nm of nominal torque.
Operation commands (S0003)
The display S0003 indicates:
● active operation commands, like e.g.: Operation in direction CLOSE or in direc-
tion OPEN
● the actual value E2 as bar graph indication and as value between 0 and 100
%.
● for setpoint control (positioner): setpoint E1
● for stepping mode or for intermediate positions with operation profile: pivot
points and operation behaviour of pivot points
The navigation support (bottom row) is faded out after approx. 3 seconds and the
axis/axes for pivot point display are shown.
OPEN - CLOSE control Active operation commands (OPEN, CLOSE, ...) are shown above the bar graph
display. The figure below shows the operation command in direction CLOSE.
Figure 49: Display for OPEN - CLOSE control
Setpoint control If the positioner is enabled and activated, the bar graph indication for E1 (position
setpoint) is displayed.
The direction of the operation command is displayed by an arrow above the bar
graph indication.The figure below shows the operation command in direction CLOSE.
45
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Indications ACV 01.2 Non-Intrusive Profinet
E1 Position setpoint
E2 Actual position value
Pivot point axis The pivot points and their operation behaviour (operation profile) are shown on the
pivot point axis by means of symbols.
The symbols are only displayed if at least one of the following functions is activated:
Operation profile M0294
Timer CLOSE M0156
Timer OPEN M0206
Figure 51: Examples: on the left pivot points (intermediate positions); on the right
stepping mode
These indications are available if the parameter Diagnostic classific. M0539 is set
to AUMA.
Warnings (S0005)
If a warning has occurred, the display shows S0005:
● the number of warnings occurred
● a blinking question mark after approx. 3 seconds
Figure 52: Warnings
46
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Indications
These indications are available, if the parameter Diagnostic classific. M0539 is set
to NAMUR.
Out of Specification (S0008)
The S0008 indication shows out of specification indications according to NAMUR
recommendation NE 107.
If such an indication has occurred, the display shows S0008:
● the number of indications occurred
● a blinking triangle with question mark after approx. 3 seconds
Figure 55: Out of specification
47
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Indications ACV 01.2 Non-Intrusive Profinet
48
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Indications
49
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Indications ACV 01.2 Non-Intrusive Profinet
50
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Signals (output signals)
Feedback signals via Profinet can be configured using the engineering tool of the
DCS/PLC and the GSD file of actuator controls with Profinet (available for download
at www.auma.com).
Refer to Manual Device integration Profinet for information on control commands
and feedback signals via Profinet.
9.2. Status signals via output contacts (digital outputs)
Conditions Output contacts are only available if a parallel interface is provided in addition to the
fieldbus interface.
Characteristics Output contacts are used to send status signals (e.g. reaching the end positions,
selector switch position, faults...) as binary signals to the control room.
Status signals only have two states: active or inactive. Active means that the
conditions for the signal are fulfilled.
9.2.1. Assignment of outputs
The output signals Coding DOUT 1 – Coding DOUT 6 can be set either to high active
or low active.
● High active = output contact closed = signal active
● Low active = output contact open = signal active
Signal active means that the conditions for the signal are fulfilled.
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Coding DOUT 1 M0102
Default values:
Coding DOUT 1 = Low active
Coding DOUT 2–Coding DOUT 6 = High active
9.3. Analogue signals (analogue outputs)
Requirements Analogue signals are only available if additional input signals are provided.
Valve position Signal: E2 = 0/4 – 20 mA (galvanically isolated)
Designation in the wiring diagram: AOUT1 (position)
Torque feedback Signal: E6 = 0/4 – 20 mA (galvanically isolated)
Designation in the wiring diagram: AOUT2 (torque)
51
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Signals (output signals) ACV 01.2 Non-Intrusive Profinet
For further information on this topic, please refer to Manual (Operation and setting).
52
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Commissioning (basic settings)
The internal end stops limit the swing angle. They protect the valve in case of limit
switching failure during motor operation and serve the purpose as limitation for
manual operation via handwheel. They may not be used for torque tripping in end
positions during standard operation.
End stop setting is generally performed by the valve manufacturer prior to installing
the valve into the pipework.
Information ● The swing angle set in the factory is indicated on the name plate:
Figure 62: Example: Swing angle on name plate
53
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Commissioning (basic settings) ACV 01.2 Non-Intrusive Profinet
Information In general, the end stop OPEN does not have to be set.
1. Remove screw plug [1].
2. Move valve to end position OPEN with handwheel.
54
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Commissioning (basic settings)
2. Press push button C Setup and hold it down for approx. 3 seconds.
➥ Display goes to main menu and indicates: ▶ Display
Select parameter 3. Select parameter either:
→ click via the menu to parameter, or
→ via direct display: Press and enter ID M0086 or M0087
➥ Display indicates: End position CLOSED
CLOSE or OPEN 4. Use Up ▲ Down ▼ to select:
→ ▶ End position CLOSED
→ ▶ End position OPEN
➥ The black triangle ▶ indicates the current selection.
55
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Commissioning (basic settings) ACV 01.2 Non-Intrusive Profinet
5. Press Ok.
➥ Display indicates the current setting: Limit or Torque
➥ The bottom row of the display indicates either:
- Edit → continue with step 6
- Save → continue with step 10
6. Press Edit.
➥ Display indicates: ▶ Specialist (4)
User login 7. Use Up ▲ Down ▼ to select user:
Information: Required user level: Specialist (4) or higher
➥ The symbols have the following meaning:
- black triangle: ▶ = current setting
- white triangle: ▷ = selection (not saved yet)
8. Press Ok.
➥ Display indicates: Password 0***
9. Enter password (→ enter password).
➥ The screen indicates the pre-set type of seating (▶Limit or ▶Torque) by means
of a black triangle ▶.
Change settings 10. Use Up ▲ Down ▼ to select new setting.
➥ The symbols have the following meaning:
- black triangle: ▶ = current setting
- white triangle: ▷ = selection (not saved yet)
11. Confirm selection via Save.
➥ The setting for the type of seating is complete.
12. Back to step 4 (CLOSED or OPEN): Press Esc.
10.3. Torque switching: set
Once the set torque is reached, the torque switches will be tripped (overload protection
of the valve).
Information The torque switches may also trip during manual operation.
2. Press push button C Setup and hold it down for approx. 3 seconds.
➥ Display goes to main menu and indicates: ▶ Display
56
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Commissioning (basic settings)
The fault has to be acknowledged before the operation can be resumed. The
acknowledgement is made:
57
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Commissioning (basic settings) ACV 01.2 Non-Intrusive Profinet
58
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Commissioning (basic settings)
59
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Commissioning (basic settings) ACV 01.2 Non-Intrusive Profinet
Table 26:
Speed sources
Parameters Value Adjustable internal operating
time
Sp. source LOC OP M1700 Internal 1 Yes
Sp. source LOCAL CL M2039 Internal 2 Yes
Sp. source REM OP M1701
Internal 3 Yes
Sp. source REM CL M2040
2 DigIn: "Internal (1-4)" Yes
Internal 4 Yes
Analogue input No (external speed source)
Fieldbus No (external speed source)
For further information on setting the speed sources, refer to Manual (Operation and
Setting):
2. Press push button C Setup and hold it down for approx. 3 seconds.
➥ Display goes to main menu and indicates: ▶ Display
Select parameter for op- 3. Either click via the menu to the parameter or via direct display
erating time
Via the menu :
→
Customer settings M0041
Speed functions M1699
Operat. time internal1 M1940
Operat. time internal2 M1941
Operat. time internal3 M1942
Operat.time internal4 M1943
Oper. time rem. max. M1946
Oper. time rem. max. M1947
→ Via direct display For this, press and enter ID, e.g.: M1940.
➥ Display indicates: Operat. time internal1
Selection 4. Select via Up ▲ Down ▼:
→ ▶ Operat. time internal1 M1940
→ ▶ Operat. time internal2 M1941
→ ▶ Operat. time internal3 M1942
→ ▶ Operat.time internal4 M1943
→ ▶ Oper. time rem. max. M1946
→ ▶ Oper. time rem. max. M1947
➥ The black triangle ▶ indicates the current selection.
5. Press Ok .
➥ Display shows the set value.
➥ The bottom row indicates: Edit Esc
6. Press Edit .
➥ Display indicates:
- Specialist (4) → continue with step 7
- in the bottom row Up ▲ Down ▼ Esc → continue with step 11
60
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Commissioning (basic settings)
61
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Commissioning (basic settings) ACV 01.2 Non-Intrusive Profinet
62
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Commissioning (settings in the actuator)
The actuator is supplied with the swing angle set in the factory in compliance with
the order. The mechanical position indication is set to this swing angle.
If the factory swing angle is changed at a later date, the position indicator must be
adapted to the new swing angle:
● Increasing the swing angle: The mechanical position indication automatically
adjusts with the subsequent operation.
● Decreasing the swing angle: The mechanical position indication must be newly
set (refer to the subsequent chapters).
Figure 67: Mechanical position indication via indicator mark (not self-adjusting)
In case the mechanical position indication integrated within the actuator is NOT
self-adjusting, the switch compartment must be opened for mechanical position
indication adjustment when commissioning.
63
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Commissioning (settings in the actuator) ACV 01.2 Non-Intrusive Profinet
Open 1. Loosen screws [2] and remove cover [1] from the switch compartment.
Close 2. Clean sealing faces of housing and cover.
3. Check whether O-ring [3] is in good condition, replace if damaged.
4. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5. Place cover [1] on switch compartment.
6. Fasten screws [2] evenly crosswise.
11.2. Mechanical position indicator (self-adjusting)
The self-adjusting mechanical position indicator shows the valve position by means
of an arrow . When correctly set, the arrow points to symbol (OPEN) or
(CLOSED) in the end positions.
Information The position indications is housed in the actuator switch compartment. Opening the
switch compartment for manual setting is only necessary if the gear stage setting
must be modified of if the factory settings of predefined end position CLOSED (or
OPEN) must be adapted when commissioning.
64
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Commissioning (settings in the actuator)
2. Push both lower discs with the symbols (OPEN) and (CLOSED) towards
each other. The disc with the arrow is thereby is driven:
Figure 70: Setting position in CLOSED
4. Check settings:
➥ The setting of the mechanical position indicator is correct if the angle between
the symbols (OPEN) and (CLOSED) ranges between approx. 120° and
280°.
➥ If all three discs are turned at the same time, the indicator can be shifted in
steps of 15°. Individual shifts of 5° are possible.
➥ If the indicator is rotated too far (more than 280°) or if the angle is too small
(below 120°), adapt the gear stage setting to the actuator swing angle. Refer
to <Gear stage of the reduction gearing: test/set>.
The test/setting is only required if the mechanical position indicator cannot be correctly
set or if another swing angle range is ordered subsequently, for example, 120° ±15°
instead of 90° ±15° (replacement by the AUMA Service only).
65
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Commissioning (settings in the actuator) ACV 01.2 Non-Intrusive Profinet
1. Refer to table and check if swing angle corresponds to the setting of the reduc-
tion gearing (stages 1– 9).
Table 27:
Actuator swing angle and suitable reduction gearing setting
SQV 05.2 / SQV 07.2 SQV 10.2 SQV 12.2 SQV 14.2
30° +/–15° 2 2 3 4
60° +/–15° 3 3 4 5
90° +/–15° 3 3 4 6
120° +/–15° 3 4 5 6
150° +/–15° 4 4 5 6
180° +/–15° 4 4 5 7
210° +/–15° 4 5 6 7
290° +/–70° 5 5 6 7
2. To modify settings, lift the lever at the reduction gearing and engage at the se-
lected stage.
Figure 72: Set reduction gearing
The mechanical position indicator shows the valve position via two indicator discs
with symbols (OPEN) and (CLOSED). When correctly set, the symbols
OPEN/CLOSED point to the indicator mark at the cover in the end positions.
Setting elements The position indications is housed in the actuator switch compartment. The switch
compartment must be opened to perform any settings. Refer to <Switch compartment:
open/close>.
66
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Commissioning (settings in the actuator)
✔ If options (e.g. potentiometer, position transmitter) are available: Only set mech-
anical position indication once all optional equipment have been successfully set.
67
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Commissioning (settings in the actuator) ACV 01.2 Non-Intrusive Profinet
2. Refer to table and check if swing angle of the actuator corresponds to the setting
of the reduction gearing (stages 1– 9).
If the setting is not correct: continue with step 4.
If the setting is correct: continue with step 7.
Table 28:
Actuator swing angle and suitable reduction gearing setting
SQV 05.2 / SQV 07.2 SQV 10.2 SQV 12.2 SQV 14.2
30° +/–15° 2 2 3 4
60° +/–15° 3 3 4 5
90° +/–15° 3 3 4 6
120° +/–15° 3 4 5 6
150° +/–15° 4 4 5 6
180° +/–15° 4 4 5 7
210° +/–15° 4 5 6 7
290° +/–70° 5 5 6 7
[1] Screw
[2] Crown wheel
68
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Corrective action
Table 29:
Faults during operation/commissioning
Fault Description/cause Remedy
Mechanical position indicator cannot Reduction gearing is not suitable for actuator swing Set gear stage of the reduction gearing.
be set. angle. The control unit might have to be exchanged.
In spite of correct setting of mechan- The overrun was not considered when setting the ● Determine overrun: Overrun = travel covered
ical limit switching, actuator operates limit switching. from switching off until complete standstill.
into the valve or actuator end position. The overrun is generated by the inertia of both the ● Set limit switching again considering the over-
actuator and the valve and the delay time of the run. (Turn handwheel back by the amount of
actuator controls. the overrun)
Actuator operation is too fast or too Operating time setting is incorrect. Modify operating time.
slow.
Actuator suddenly stops in end posi- Velocity reduction switched off or incorrectly set Modify velocity.
tions. before reaching end positions.
Faults interrupt or prevent the electrical actuator operation. In the event of a fault,
the display backlight is red.
Warnings have no influence on the electrical actuator operation. They only serve
for information purposes. The display remains white.
Collective signals include further indications. They can be displayed via the
Details push button. The display remains white.
Table 30:
Faults and warnings via status indications in the display
Indication on display Description/cause Remedy
S0001 Instead of the valve position, a status text is dis- For a description of the status texts, refer to Manual
played. (Operation and setting).
S0005 Collective signal 02: For indicated value > 0: Press push button De-
Warnings Indicates the number of active warnings. tails.
For details, refer to <Warnings and Out of specific-
ation> table.
S0006 Collective signal 04: For indicated value > 0: Press push button De-
Not ready REMOTE Indicates the number of active signals. tails.
For details, refer to <Not ready REMOTE and
Function check> table.
S0007 Collective signal 03: For indicated value > 0: Press push button Details
Fault Indicates the number of active faults. to display a list of detailed indications.
The actuator cannot be operated. For details, refer to <Faults and Failure> table.
S0008 Collective signal 07: For indicated value > 0: Press push button De-
Out of specification Indication according to NAMUR recommendation tails.
NE 107 For details, refer to <Warnings and Out of specific-
Actuator is operated outside the normal operation ation> table.
conditions.
69
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Corrective action ACV 01.2 Non-Intrusive Profinet
Table 31:
Warnings and Out of specification
Indication on display Description/cause Remedy
Config. warning Collective signal 06: Press push button Details to display a list of indi-
Possible cause: vidual indications.
Configuration setting is incorrect. For a description of the individual signals, refer to
The device can still be operated with restrictions. Manual (Operation and setting).
Internal warning Collective signal 15: Press push button Details to display a list of indi-
Device warnings vidual indications.
The device can still be operated with restrictions. For a description of the individual signals, refer to
Manual (Operation and setting).
24 V DC external The external 24 V DC voltage supply of the controls Check 24 V DC voltage supply.
has exceeded the power supply limits.
Wrn op.mode run time Warning on time max. running time/h exceeded ● Check modulating behaviour of actuator.
● Check parameter Perm. run time M0356, re-set
if required.
Wrn op.mode starts Warning on time max. number of motor starts ● Check modulating behaviour of actuator.
(starts) exceeded ● Check parameter Permissible starts M0357, re-
set if required.
Failure behav. active The failure behaviour is active since all required Verify signals:
setpoints and actual values are incorrect. ● Setpoint E1
● Actual value E2
● Actual process value E4
● Check connection to master.
● Check (clear) status of master.
Wrn input AIN 1 Warning: Loss of signal analogue input 1 Check wiring.
Wrn input AIN 2 Warning: Loss of signal analogue input 2 Check wiring.
Wrn setpoint position Warning: Loss of signal setpoint position Check setpoint signal.
Possible causes:
For an adjusted setpoint range of e.g. 4 – 20 mA,
the input signal is 0 (signal loss).
For a setpoint range of 0 – 20 mA , monitoring is
not possible.
Op. time warning The set time (parameter Perm.op. time, manual The warning indications are automatically cleared
M0570) has been exceeded. The preset operating once a new operation command is executed.
time is exceeded for a complete travel from end ● Check valve.
position OPEN to end position CLOSED. ● Check parameter Perm.op. time, manual
M0570.
Wrn controls temp. Temperature within controls housing too high. Measure/reduce ambient temperature.
Time not set Real time clock has not yet been set. Set time.
RTC voltage Voltage of the RTC button cell is too low. Replace button cell.
PVST fault Partial Valve Stroke Test (PVST) could not be suc- Check actuator (PVST settings).
cessfully completed.
70
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Corrective action
Table 32:
Faults and Failure
Indication on display Description/cause Remedy
Configuration error Collective signal 11: Press push button Details to display a list of indi-
Configuration error has occurred. vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Config. error REMOTE Collective signal 22: Press push button Details to display a list of indi-
Configuration error has occurred. vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Internal error Collective signal 14: AUMA service
Internal error has occurred. Press push button Details to display a list of indi-
vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Torque fault CLOSE Torque fault in direction CLOSE Perform one of the following measures:
● Issue operation command in direction OPEN.
● Set selector switch to position Local control
(LOCAL) and reset fault indication via push
button RESET.
● Execute reset command via fieldbus.
Torque fault OPEN Torque fault in direction OPEN Perform one of the following measures:
● Issue operation command in direction CLOSE.
● Set selector switch to position Local control
(LOCAL) and reset fault indication via push
button RESET.
● Execute reset command via fieldbus.
Phase fault ● When connecting to a 3-ph AC system and with Test/connect phases.
internal 24 V DC supply of the electronics:
Phase 2 is missing.
● When connecting to a 3-ph AC system: One of
the phases L1, L2 or L3 is missing.
Thermal fault Motor protection tripped ● Cool down, wait.
● If the fault indication display persists after cool-
ing down:
- Set selector switch to position Local con-
trol (LOCAL) and reset fault indication via
push button RESET.
- Execute reset command via fieldbus.
● Check fuses.
Fault no reaction No actuator reaction to operation commands within Check movement at actuator.
the set reaction time.
Poti Out of Range Potentiometer is outside the permissible range. Check device configuration:
Parameter Low limit Uspan M0832 must be less
than parameter Volt.level diff. potent. M0833.
71
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Corrective action ACV 01.2 Non-Intrusive Profinet
Table 33:
Not ready REMOTE and Function check (collective signal 04)
Indication on display Description/cause Remedy
Wrong oper. cmd Collective signal 13: ● Check operation commands (reset/clear all op-
Possible causes: eration commands and send one operation
● Several operation commands (e.g. OPEN and command only).
CLOSE simultaneously, or OPEN and SET- ● Set parameter Positioner to Function active.
POINT operation simultaneously) ● Check setpoint.
● A setpoint is present and the positioner is not Press push button Details to display a list of indi-
active vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Sel. sw. not REMOTE Selector switch is not in position REMOTE. Set selector switch to position REMOTE.
Service active Operation via service interface (Bluetooth) and Exit service software.
AUMA CDT service software.
Disabled Actuator is in operation mode Disabled. Check setting and status of function <Local controls
enable>.
EMCY stop active The EMERGENCY stop switch has been operated. ● Enable EMERGENCY stop switch.
The motor control power supply (contactors or ● Reset EMERGENCY stop state by means of
thyristors) is disconnected. Reset command.
EMCY behav. active Operation mode EMERGENCY is active (EMER- ● Detect cause for EMERGENCY signal.
GENCY signal was sent). ● Verify failure source.
0 V are applied at the EMERGENCY input. ● Apply +24 V DC at EMERGENCY input.
I/O interface The actuator is controlled via the I/O interface (par- Check I/O interface.
allel).
Handwheel active Manual operation is activated. Start motor operation.
FailState fieldbus Fieldbus connection available, however no process Verify master configuration
data transmission by the master.
Local STOP A local STOP is active. Release push button STOP.
Push button STOP of local controls is operated.
Interlock An interlock is active. Check interlock signal.
Interlock by-pass By-pass function is interlocked. Check states of main and by-pass valve.
PVST active Partial Valve Stroke Test (PVST) is active. Wait until PVST function is complete.
12.3. Fuses
12.3.1. Fuses within the actuator controls
72
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Corrective action
The actuator is switched off and the following signals are given:
● LED 3 (motor protection trippped) on the local controls is illuminated.
● The status indications S0007 or S0011 Failure display a fault.
The fault Details is displayed when selecting Thermal fault.
The motor has to cool down before operation can be resumed.
Depending on the parameter setting (motor protection behaviour), the fault signal is
either automatically reset or the fault signal has to be acknowledged.
The acknowledgement is made:
● in selector switch position Local control (LOCAL) via push button RESET.
● In selector switch position Remote control (REMOTE) with Reset command
via fieldbus.
73
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Servicing and maintenance ACV 01.2 Non-Intrusive Profinet
AUMA
AUMA offers extensive service such as servicing and maintenance as well as
Service & Support customer product training. For the contact addresses, refer to our website
(www.auma.com).
74
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Servicing and maintenance
● Arrange for controlled waste disposal of the disassembled material or for sep-
arate recycling according to materials.
● Observe the national regulations for waste disposal.
75
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Technical data ACV 01.2 Non-Intrusive Profinet
3-phase AC
Voltages/frequencies
Volt 220 – 240 380 – 480
Hz 50 – 60 50 – 60
1–phase AC
Voltages/frequencies
Volt 110 – 120 220 – 240
Hz 50 – 60 50 – 60
76
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Technical data
Service conditions
Use Indoor and outdoor use permissible
Mounting position Any position
Installation altitude ≤ 2,000 m above sea level
> 2,000 m above sea level on request
Ambient temperature Refer to actuator name plate
Humidity Up to 100 % relative humidity across the entire permissible temperature range
Enclosure protection according to Standard: IP68
EN 60529 Refer to name plates at motor and actuator for exact version
Option: DS terminal compartment additionally sealed against interior of actuator (double sealed)
According to AUMA definition, enclosure protection IP68 meets the following requirements:
● Depth of water: maximum 8 m head of water
● Duration of continuous immersion in water: Max. 96 hours
● Up to 10 operations during immersion
● Modulating duty is not possible during immersion
Pollution degree according to Pollution degree 4 (when closed), pollution degree 2 (internal)
IEC 60664-1
Corrosion protection Standard: KS: Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Option: KX: Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
Coating Double layer powder coating
Two-component iron-mica combination
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Available colours on request
Lifetime AUMA part-turn actuators meet or exceed the lifetime requirements of EN ISO 22153. Detailed inform-
ation can be provided on request.
Sound pressure level < 72 dB (A)
77
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Technical data ACV 01.2 Non-Intrusive Profinet
Further information
EU Directives Machinery Directive 2006/42/EC
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
RED Directive 2014/53/EU
3-phase AC 1-phase AC
Voltages/frequencies Voltages/frequencies
Volt 220 – 240 380 – 480 Volt 110 – 120 220 – 240
Hz 50 60 50 60 Hz 50 60 50 60
Bluetooth Bluetooth class II chip, version 2.1: With a range up to 10 m in industrial environments; supports the
Communication interface SSP Bluetooth profile (Serial Port Profile).
Required accessories:
● AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC)
● AUMA Assistant App (Commissioning and Diagnostic Tool)
78
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Technical data
79
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Technical data ACV 01.2 Non-Intrusive Profinet
80
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Technical data
Service conditions
Use Indoor and outdoor use permissible
Mounting position Any position
Installation altitude ≤ 2 000 m above sea level
> 2,000 m above sea level on request
Ambient temperature Refer to name plate of actuator controls
Humidity Up to 100 % relative humidity across the entire permissible temperature range
Enclosure protection in accordance Standard: IP68
with IEC 60529
Option: DS terminal compartment additionally sealed against interior of actuator controls (double
sealed)
According to AUMA definition, enclosure protection IP68 meets the following requirements:
● Depth of water: maximum 8 m head of water
● Continuous immersion in water: maximal 96 hours
● Up to 10 operations during immersion
● Modulating duty is not possible during immersion.
For exact version, refer to actuator controls name plate.
Pollution degree according to Pollution degree 4 (when closed), pollution degree 2 (internal)
IEC 60664-1
Vibration resistance according to 1 g, from 10 Hz to 200 Hz
IEC 60068-2-6 Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Not valid in combination with gearboxes.
Corrosion protection Standard: KS: Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Option: KX: Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
81
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Technical data ACV 01.2 Non-Intrusive Profinet
Service conditions
Coating Double layer powder coating
Two-component iron-mica combination
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Available colours on request
Accessories
Wall bracket For actuator controls mounted separately from the actuator, including plug/socket connector. Connecting
cable on request.
Recommended for high ambient temperatures, difficult access, or in case of heavy vibration during
service.
Cable length between actuator and actuator controls is max. 16 m. Longer cables require an external
filter (filter available on request).
Programming software AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC)
AUMA Assistant App (Commissioning and Diagnostic Tool)
Further information
Weight Approx. 7 kg (with AUMA plug/socket connector)
EU Directives Machinery Directive 2006/42/EC
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
RED Directive 2014/53/EU
Reference documents Electrical data SAV 07.2 – SAV 16.2/SARV 07.2 – SARV 16.2
Electrical data SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2
Table 34:
Tightening torques for screws
Threads Tightening torque [Nm]
Strength class
A2-70/A4-70 A2-80/A4-80
M6 7.4 10
M8 18 24
M10 36 48
M12 61 82
M16 150 200
M20 294 392
M30 1,015 1,057
M36 1,769 2,121
82
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Spare parts
83
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Spare parts ACV 01.2 Non-Intrusive Profinet
Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used.
Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Representation of spare parts may slightly vary
from actual delivery.
84
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Spare parts
85
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Spare parts ACV 01.2 Non-Intrusive Profinet
Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used.
Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Representation of spare parts may slightly vary
from actual delivery.
86
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Index
E
Index Earth connection 35
Electrical connection 20, 76
A EMC 22
Accessories (electrical con- 33 Enclosure protection 10, 11, 77, 81
nection) End stops 53
Actual value - indication on 45 Error - indication on display 44
display
Actuator controls terminal 11 F
plan Failure - indication on display 48
Actuator operation from re- 37 Fault 69
mote Fault - indication on display 47
Actuator terminal plan 11, 12 Features and functions 79
Ambient temperature 10, 11, 77, 81 Flange size 12
Analogue signals 51 Frequency range 20
Applications 5 Function check - indication on 47
Assembly 15 display
Assistant App 12 Fuse 21
AUMA Assistant App 9, 12 Fuses 72
AUMA Cloud 9
H
B Handwheel 15
Blanking plug 21 Heating system 21
Bluetooth 9 Humidity 77, 81
C I
Cable entries 76 Incorrect entry 41
Cable glands 21 Indication lights 49
Cables 21 Indications 43
Cable set 33 Indications on display 43
CDT 9 Indicator disc 49, 64, 67
Coating 82 Indicator mark 50
Colour 82 Input current 12
Commissioning 5 Input signal 12
Commissioning (indications 43 Input signals Potential 21
on display) Inspection certificate 12
Connecting cable 33 Installation altitude 81
Connecting cables 21 Insulation class 11, 76
Control 11, 12 Intermediate frame 34
Control inputs Potential 21 Intermediate position indica- 49
Control voltage 12 tion via LEDs
Corrective action 69 Intrusive 8
Corrosion protection 14, 77, 81
Coupling 16, 16, 77 L
Current consumption 21 Language in the display 41
Current type 20 LEDs (indication lights) 49
Lifetime 77
D Local actuator operation 36
Data Matrix code 12 Local control 36
Digital outputs 51 Local controls 36
Direct display via ID 39 Local setting 38
Direction of rotation 61 Lubrication 74
Directives 5
Display (indications) 43
Disposal 74
Double sealed 34
87
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Index ACV 01.2 Non-Intrusive Profinet
M Q
Main menu 39 Qualification of staff 5
Mains/voltage range/fre- 11
quency range R
Mains frequency 76 Range of application 5
Mains voltage 20, 76 Rated current 11, 21
Maintenance 5, 74, 74 Rated power 11, 21
Maintenance required - indic- 48 Rated power of ACV 11
ation on display Rated voltage 11
Manual operation 36, 76 Recycling 74
Maximum current 11 Reduction gearing 67
Mechanical position indicator 49, 50, 64, 67 reductions 21
Mechanical position indicator 64 Remote actuator operation 37
(self-adjusting) Residual current device 21
Menu navigation 38 (RCD)
Motor heater 76 Running indication 49, 50
Motor operation 36
S
Motor protection 11, 76
Safety instructions 5
Motors 76
Safety instructions/warnings 5
Motor type 11
Safety measures 21
Mounting position 81
Safety standards 21
N Screw plugs 21
Name plate 10 Self-locking 76
Non-Intrusive 8 Self-retaining 37
Not ready REMOTE - indica- 47 Serial number 10, 11, 12
tion on display Service 74
Number of starts 11 Servicing 74
Setpoint - indication on dis- 45
O play
Operating the actuator from 36 Short-circuit protection 20
local controls Signals 51
Operating time 10 Signals (analogue) 51
Operating time setting 59 Size 12
Operation 5, 36 Spare parts 83
Operation commands - indic- 45 Standards 5
ations on display Status menu 39
Order number 10, 11, 12 Status signals 51
Out of specification - indica- 47 Status signals Potential 21
tion on display Storage 14
Output contacts 51 Supply networks 20
Output signals 51 Support 74
Output signals Potential 21
Overvoltage category 76 T
Technical data 76
P Temperature protection 11
Parking frame 34 Terminal plan 20, 76
Password 40 Test run 61
Password change 40 Timeout 41
Password entry 40 Torque - indication on display 44
Pollution degree 81 Torque range 10
Positioner - indication on dis- 45 Torque switching 56
play Transport 13
Position indicator 49, 50, 64, 67 Type 12
Position transmitter 12 Type designation 10, 11
Protection on site 20, 21 Type of duty 76
Protective measures 5 Type of lubricant 10
Push-to-run operation 37 Type of networks 20
88
SQV 05.2 – SQV 14.2/SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Index
U
User level 40
V
Valve attachment 77
Valve position - indication on 44
display
Vibration resistance 81
Voltage range 20
W
Wall bracket 33
Warnings - indication on dis- 46
play
Wiring diagram 12, 20
Y
Year of manufacture 12
Year of production 12
89
AUMA Riester GmbH & Co. KG
P.O. Box 1362
DE 79373 Muellheim
Tel +49 7631 809 - 0
Fax +49 7631 809 - 1250
[email protected]
www.auma.com
Y009.130/003/en/1.21