Jun 2014

WILHAMS INSULATION FAR EAST SDN BHD

FirePro®

CONLIT® 150 Systems


Fire protection solution for structural steel

The CONLIT® 150 series of fire


protection systems embodies a complete
‘tool-box’ of options to offer contractors

S
ON
simple and economical fire protection OP
TI
solutions to the very real diversity of
X
FI
Y

modern steel constructions.


DR

Proven in service over many years, these


versatile Rockwool boards have been
widely used to combat the extremes of
site, mixed trade and climatic conditions.
Configuration options
CONLIT® 150 boards can be fitted to
provide glued or dry joint solutions
offering up to 4 hours fire protection.
Dry fix solutions
• Unique friction-fit system
• Quick and simple to apply
• Up to 2 hours fire protection
• Dry process, no masked off areas
required
Glue fix solutions The unique CONLIT® 150 dry fix clip system International Patent Application
• Traditional nogging & stud welded pin No PCT/GB 00/01955
systems Fire resistances of CONLIT® 150 systems
• Up to 4 hours fire protection
System Fire resistance (mins)
• High resilience 30 60 90 120 180 240
Dry fix clips • • •
Advantages
Dry fix glued noggings • • • •
• No maintenance
Dry fix stud welded pins • • • •
• Moisture repellent
Glued nogging fix • • • • • •
• Choice of three finishes
Glued stud welded pin fix • • • • • •
• Easy to repair
Product options

CONLIT® 150 P CONLIT® 150 A/F CONLIT® 150 T


A plain product with a natural ‘green’ finish. With Class ‘O’ reinforced aluminium foil, With a white glass tissue factory-applied to
factory-applied to the outer face. the outer face.

For concealed areas. For limited view areas. For limited view areas.

Composition and manufacture Performance and properties


CONLIT® 150 is manufactured from a melt of volcanic rock. Fire performance
The molten rock is spun into a wool and immediately Up to 4 hours fire resistance for structural steelwork, assessed
impregnated with special resins for handling and shaping. at 550°C failure criteria. The base rockwool material achieves
The material is then compressed, cured and formed into Euro Class A1, foil and tissue faced materials achieve Euro
boards. Class A2.
CONLIT® 150 boards are sized 2400 × 1200mm, in a range of Moisture
thicknesses from 25mm up to 110mm. The rockwool fibres of CONLIT® 150 boards are randomly
Board density oriented, avoiding any tendency to promote capillary action or
hygroscopic moisture absorption.
Nominally 165 kg/m³.
Moisture content
Standards 0% in air-dried state.
CONLIT® 150 fire protection materials have been
assessed to BS 476 : Part 21 : 1987 for the fire protection Moisture absorption
of loadbearing steel beams and columns for up to 4 hours 0.004% by volume at 20°C and 90% relative humidity.
protection, based on tests carried out to BS 476 : Part 8 :
1972 and BS 476 : Part 21 : 1987. Water absorption
Maximum 60 grammes/m² after 24 hour water immersion
Protection stability has been examined for up to 6 hours. testing (i.e. approximately 1.5% by weight for 25mm plain
High air flow situations board).
Unfaced CONLIT® 150 systems have been evaluated for
use in return air plenums by the Institute of Occupational
Medicine to World Health Organisation test standards and
for use in subways for train speeds up to 150km per hour.

Installation options Pigtail screws (twice the insulation thickness, less 5mm) are
A comprehensive range of practical systems is available to used to secure the insulation boards to each other.
meet a variety of site requirements.
CONLIT® 150 glued fix solutions
CONLIT® 150 dry fix solutions These use an inorganic and non-toxic glue to bind
These use either purpose-made clips, glued mineral wool board-to-board joints. Standard flat head nails, twice the
noggings or stud welded pins to secure the insulation to thickness of
structural steel sections. All board-to-board joints are the insulation, are used to support the joints while the glue
straight butt joints, without the need for glue. dries.

Rockwool friction fit clip Noggings glued between steelwork flanges Fixing stud welded pins
Installation
1 Clip Fix Dry Joint Board System
A quick and user-friendly dry joint board system
featuring ROCKWOOL®’s friction-fit clip system.

The spring action of the clip creates a vice-like grip


on the steelwork flange. The CONLIT® 150 board is
impaled on the clip pins and held in place with
sprung steel non-return washers. Supplementary
pigtail screws fixed through the side boards into the
soffit boards complete this system.

The clips are located at maximum 600mm centres to 1 Clip fix dry joint board system 1 Clip and stud welded pin dry joint
(up to 2 hours fire protection) system (up to 2 hours fire protection)
top flange and maximum 900mm centres to bottom
flange, with pigtail screws for board to board joints at
150mm centres.

Combined Clip and Stud Welded Pin Dry Joint


System
Where it is not possible to clip fix, eg beneath
concrete soffits, stud welded pins (at the same fixing
centres) are used in lieu of the clip fixing.

Hp/A limit for 2 hours = 200

2 Glued Noggings Dry Joint Board System


An easy-to-apply and fast dry joint board system
where noggings are glued into position between the
steelwork flanges using CONLIT® Glue. Noggings
are fixed at 900mm nominal centres. The CONLIT®
150 boards are then retained by means of pigtail
screws, fixed at 120mm nominal centres to the
noggings and 200mm centres for board-to-board
joints.

For beam depths over 500mm a Tee-nogging is


used to provide the support for the cover boards. 2 Glued noggings dry joint board system 2 Alternative Tee-nogging arrangement
(up to 2 hours fire protection) (up to 2 hours fire protection)
3 Stud Welded Pin Dry Joint Board System
A dry joint system employing steel welded pins.

The steelwork is cleaned in the area where the


welded pin is to be positioned. The pin is then
welded to the steel flange.

The CONLIT® 150 board is then impaled on the stud


welded pins and held in place with spring steel
non-return washers.

The steel welded pins are fixed at 800mm nominal


centres. The CONLIT® 150 board-to-board joints
are then secured by means of pigtail screws fixed at
nominal 150mm centres.

4 Glued Board Systems 3 Stud welded pin dry joint board system 3 Two-sided protection with stud
(up to 2 hours fire protection) welded pins (up to 2 hours fire
Glue-fixed Noggings and Board-to-Board protection)
Glued Joints
CONLIT® 150 noggings are glued between the
steelwork flanges, and the CONLIT® 150 side
boards are glued to the noggings. The CONLIT® 150
side boards are also glued at all vertical joints and
horizontal board-to-board joints.

Round head nails (length = 2 × thickness of board)


are fixed through the side boards into the noggings
and soffit boards to consolidate the glued joints.

The noggings are fixed at 900mm nominal centres,


and the nails at 450mm nominal centres.

Stud Welded Pins and Board-to-Board Glued


Joints
Pins are stud welded at 800mm centres, and all
board-to-board joints are glued. 4 Glue-fixed noggings and board-to-board 4 Stud welded pins and board-to-board
glued joints (up to 4 hours fire protection) glued joints (up to 4 hours fire
protection)
Board jointing Health and safety
Butted corner joints All ROCKWOOL® products are subject to a Maximum
Butted corner joints are made with square edge boards using Exposure Limit of 5 mg/m³ total dust 8 hour Time Weighted
either a dry joint with pigtail screws, as below, or CONLIT® Average.
Glue and nails at 450mm centres. Current HSE ‘CHIP’ Regulations and EU Directive
97/69/EC confirm that Rockwool fibres are not classified
Pigtail screws at
as a possible carcinogen.
150 or 200mm
nominal centres
Dry joint
(see system options, Supply
page 3) CONLIT® 150 slabs are supplied on pallets,
shrink-wrapped in polyethylene, 26 pallets per 40 ft
container.
Screw length = minimum 2 ×
thickness of cover board - 5 mm References
This is one of a series of data sheets covering the
Axial joints
complete range of ROCKWOOL® products, available from
All axial joints are made with square butt edges, without Wilhams Insulation Far East Sdn Bhd.
nails. Glue is only required for glued board systems.
CONLIT® Tube is also available for circular steel sections.

CONLIT® dry fix ductwork solutions are also available for


CONLIT® glue steel duct protection.
Joints can be finished with either a tissue or Class ‘O’ foil
tape. Typical specification clauses
(to be read in conjunction with System Options on page 3)
Noggings
CONLIT® 150 boards can be fixed to noggings, cut from 1 The structural steel is to be fire protected using
CONLIT® 150 offcuts over 100mm wide. CONLIT® 150 ..........s system, with a ..........f facing, to
provide ..........h fire resistance.
The edges of the noggings are glued where they contact the
steelwork, then, once the glue has set firmly, the cover 2 The main fixing system will be:
boards are fixed in position with either pigtail screws or a) CONLIT® clip system fixed at 800mm centres, or
CONLIT® Glue and nails. The thickness of the nogging is to b) CONLIT® nogging system fixed at 900mm centres,
be the same as that of the cover board used. or
c) CONLIT® stud welded pin system fixed at 800mm
Welded steel pins centres.
Boards are secured to stud welded pins with non-return
washers. 3 Board-to-board joints should be dry fixed using pigtail
screws or glued and nailed in accordance with the data
Joints and glue sheet.
CONLIT® Glue is an inorganic, non-toxic product with a pH of
s
11. CONLIT® Glue is supplied pre-mixed in 17kg tubs. A insert system type
f
variety of joint types can be used (see page 3). insert facing option
h insert period of fire resistance

The coverage rate of CONLIT® Glue is approximately 35m²


of applied board per 17kg tub.

FirePro® is the registered trademark of Wilhams Insulation Far East Sdn Bhd

Wilhams Insulation Far East Sdn Bhd


15 & 17 Jalan Utarid U5/23
Mah Sing Integrated Industrial Park
40150 Shah Alam, Selangor, Malaysia
Tel : 603-7846 6728 Fax : 603-7846 6540
E-mail : [email protected]
Website : www.wilhams.com.my

IMPORTANT NOTICE: Any directions for use are given for guidance only and are not intended to form part of any contract. They should be varied or adapted to suit your particular materials or conditions of use.
Goods supplied by the company are made to approved standards from the highest quality raw materials but no warranty or guarantee is given as to their suitability for any particular purpose or application, and no
liability is accepted for any loss or damage arising directly or indirectly from the use of the Company’s products irrespective of any information given to us as to intended use of such products. It is therefore
recommended that prospective users should test a sample of this product under their own conditions to satisfy themselves that the product to be used is suitable for that purpose intended.

You might also like