EVOIC3 Manual

The document provides installation and operating instructions for an energy metering device. It describes the components included, provides an overview of the device and its capabilities, and gives instructions for mounting the display unit and base module as well as connecting wiring. Technical specifications and programming information are also included.

Uploaded by

TS
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
33 views17 pages

EVOIC3 Manual

The document provides installation and operating instructions for an energy metering device. It describes the components included, provides an overview of the device and its capabilities, and gives instructions for mounting the display unit and base module as well as connecting wiring. Technical specifications and programming information are also included.

Uploaded by

TS
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 17

FREQUENCY = 49.

99
R V B TOTAL a new dimension
in energy information
VOLTS - 230.88 230.94 230.96
AMPS - 1 199.3 1 193.9 1 198.2 3591.4
KW - 276.84 275.72 276.73 829.31
KVA - 276.89 275.73 276.73 829.37
KVAR - 0.0000 0.0000 0.0000 0.0000
PF - 0.99 0.99 0.99 0.99
IMP KWH = 71.9570 EXP KWH = 0.0000
IMP KVARH = 0.1400 EXP KVARH = 0.0043
KVAH = 71.9626 AH = 310.131
AMPS VOLT POWER H-THD SETUP

installation and
operating manual

an evolution for metering a revolution for information


contents
page

description 3

installation 4-5

information 6

wiring information 7

protocol set up 8-9

communication connections 10

technical specifications 11

on screen programming of the meter 12-13

operating instructions 14-15

Please read these instructions carefully before installation


and retain them for future reference.
description

check your contents


FREQUENCY = 49.99
R V B TOTAL a new dimension
in energy information
VOLTS - 230.88 230.94 230.96
It should contain the following: AMPS
KW
KVA
-
-
-
1 199.3
276.84
276.89
1 193.9
275.72
275.73
1 198.2
276.73
276.73
3591.4
829.31
829.37
KVAR - 0.0000 0.0000 0.0000 0.0000
PF - 0.99 0.99 0.99 0.99
IMP KWH = 71.9570 EXP KWH = 0.0000
IMP KVARH = 0.1400 EXP KVARH = 0.0043
KVAH = 71.9626 AH = 310.131
AMPS VOLT POWER H-THD SETUP

• 1 installation and operating manual

• 1 graphical display unit


graphical display
• 1 base module

• 1 interconnecting lead

• 2 fixing clamps

1 2 3 4 5 6 7 8 9 10 11 12 13 14

fixing clamps interconnecting lead base module


(2 metres in length)

overview of the unit

The evo ic 3 is designed to satisfy the most demanding This enables high resolution RMS calculations,
metering requirements of engineers worldwide. and high level Harmonic Analysis – which is limited
Autometers has used the latest graphical display to the 63rd Harmonic.
and microprocessor technology to build a precision
The evo ic 3 offers accurate and reliable measurement.
multifunction meter which combines many desirable
It can also transmit information to energy monitoring
features with cost-effectiveness.
systems in a number of different formats, without
The evo ic 3 delivers exceptional functionality. diminishing the accuracy of the metered data.
The meter displays many electrical parameters on one
The evo ic 3 has a unique 1Mb memory facility
screen. It also has the capability of setting and displaying
for logging data.
multiple alarm points, which trigger relays to close.
The evo ic 3 is built on a very stable platform, enabling high
sampling – in excess of 1000 samples per cycle at 50Hz.
installation
mounting the display and base unit

installation of the display unit

Mount the meter so that the front panel is vertical. FREQUENCY = 49.99
A typical panel would be a switchgear cabinet R V B TOTAL a new dimension
in energy information
VOLTS - 230.88 230.94 230.96
door. The meter requires depth behind the panel AMPS
KW
-
-
1 199.3
276.84
1 193.9
275.72
1 198.2
276.73
3591.4
829.31
KVA - 276.89 275.73 276.73 829.37
of 60 mm excluding wiring. Prepare a single KVAR - 0.0000 0.0000 0.0000 0.0000
PF - 0.99 0.99 0.99 0.99
square hole 92mm wide and 92mm high. IMP KWH = 71.9570 EXP KWH = 0.0000
IMP KVARH = 0.1400 EXP KVARH = 0.0043
KVAH = 71.9626 AH = 310.131
AMPS VOLT POWER H-THD SETUP
location

The evo ic 3 series should be mounted in dry dirt


free environments away from heat sources and
very high electric fields. Temperatures should not
exceed 70°C or fall below -20°C.

enclosure
front panel

front fascia

fixing clamp 12mm


aperture(s) adjustment
aperture
92mm x 92mm

1 2 3
1. Cut aperture in enclosure front panel
92mm wide x 92mm high.
2. Slide unit through aperture.
3. Insert fixing clamps and screws, one either side.
Tighten carefully.
installation
mounting the display and base unit

9.33mm

19.25mm
33.75mm

91.5mm

130mm
24mm
33.75mm

19.25mm
61.75mm 91.5mm 61.75mm
40mm 60mm
215mm

installation of the base unit

Before fixing the base unit ensure the interconnecting cable will reach the display unit.
Length of cable is 2 metres. (Longer lengths are available on request.)

fixing bracket can be reversed


for concealed fixing
(with fixing bracket reversed down)

195mm
187mm
174mm

154mm

1 2 3 4 5 6 7 8 9 10 11 12 13 14

237mm

252mm
information
about the display and base unit

display
240 x 128 backlit graphical display. To activate display
FREQUENCY = 49.99
light, press any key. Light remains on for 5 minutes 1 2 3
R V B TOTAL
after last key press. VOLTS - 230.88 230.94 230.96 4 5 6
AMPS - 1 199.3 1 193.9 1 198.2 3591.4
KW - 276.84 275.72 276.73 829.31
KVA - 276.89 275.73 276.73 829.37 7 8 9
information access keys (arrow keys) KVAR - 0.0000 0.0000 0.0000 0.0000
PF - 0.99 0.99 0.99 0.99
0 .
Used to access more indepth information. IMP KWH
IMP KVARH
= 71.9570 EXP KWH = 0.0000
= 0.1400 EXP KVARH = 0.0043
KVAH = 71.9626 AH = 310.131 S1
programming keys AMPS VOLT POWER H-THD SETUP
S2
Visible only when door is opened. 11 keys in total. N Network exit

1-0 and decimal point. Used to programme the meter.

special allocation keys S1, S2, N


These three keys are special function keys
and can only be programmed by Autometers.
S1 shows Autometers contact information.
N is network exit key (used for remote display only).

A. display socket
D type 9 pin socket (male) display output.

B. programming socket
D type 9 pin socket (female) used by Autometers
for internal programming of micro processors. E1 E2 E3

C. protocol setup
7 way dip switch used as binary switches numbered 1-7.
See page 9 for protocol set up. A B C D E F
D. RS 485 modbus address
Two hexidecimal switches for individual numbering
of the meter. See page 8 for setting. 1 2 3 4 5 6 7 8 9 10 11 12 13 14

E. RS 485 connection
5 way terminal connector (plug and socket).
See page 10 for connections.
terminals
1, 2
F. pulse outputs Auxiliary voltage supply.
3 energy outputs, KVArh, KVAh, KWh.
3
See page 7 for connection details. Neutral supply.

4, 5, 6
optional Phase voltage.
E1, E2, E3
3 expansion sockets for optional plug-in cards. 7, 8, 9, 10, 11, 12, 13, 14
Available: 3 x 4 channel 4.20mA output (total 12), 3 x 4 alarm Terminals for external current transformers.

output relays (total 12), 1 memory card 1 Mb. Expansion cards fuse
can be mixed. eg. 1 4.20mA, 1 relay, 1 memory. Protects auxiliary voltage.
wiring information

power supply wiring

The standard evo ic 3 Series meters are powered Electrical and communications connections are made directly
by 230 volts AC (47 to 66 Hz) at 0.2 amps. from the front of the base unit. Electrical connections are
The units can be powered from a dedicated fused made to terminals 1-14, pulse output relays and the RS485
supply or may be powered by the voltage source which terminals are located on a higher level and numbered
they are monitoring, as long as it is a 230 volt system. accordingly. See diagrams below.
As an option the meter can be supplied with a 110 volt
power supply. A removable protection fuse for the electrical connections
auxiliary power supply is fitted in the meter.
2.5mm2 wire is recommended for all electrical connections.
Phasing and polarity of the AC current and voltage inputs
and their relationship are critical to the correct operation
of the unit.

evo ic 3 3 phase 3 wire wiring diagram

RS485 connections
1 2 3 4 5

TX+
TX-
1 2 3 4 5 6 7 8 9 10 11 12 13 14 RX+
RX-
Shield
110 volt
AUX supply S1 S2
pulse outputs
R R
MAINS

LOAD

P1 P2
1 2 3 4 5 6
Y Y
KWh

S1 S2
KVAh

B P1 P2 B
KVArh

protection fuse

evo ic 3 3 phase 4 wire wiring diagram

RS485 connections
1 2 3 4 5

TX+
TX-
1 2 3 4 5 6 7 8 9 10 11 12 13 14 RX+
RX-
Shield
230 volt
AUX supply S1 S2

R P1 P2
S1 S2
R pulse outputs
MAINS

LOAD

Y P1 P2
S1 S2
Y 1 2 3 4 5 6
KWh

B P1 P2 B
KVAh

S1 S2

N N
KVArh

P1 P2

protection fuse
protocol set up

removing the cover to alter protocol settings

Remove screw. Lift from the


bottom of the cover and slide
upward to remove cover.

RS485 modbus address

The position for the modbus


address switches are shown below.
These switches allow the meter
to have a unique number up to 128.

3456 3456
1 2 3 4 5 6 7 8 9 10 11 12 13 14
EF012

EF012
789A

789A

BCD BCD

Using the key below adjust the two rotary hexi-decimal


switches. eg. a meter which requires a number setting
of 94 will require the left switch to be set to 5 and the
right switch to E (5E)

left switch key right switch key


1 = 16 4 = 64 7 = 112 A = n/a D = n/a 1 = 1 4 = 4 7 = 7 A = 10 D = 13
2 = 32 5 = 80 8 = n/a B = n/a E = n/a 2 = 2 5 = 5 8 = 8 B = 11 E = 14
3 = 48 6 = 96 9 = n/a C = n/a F = n/a 3 = 3 6 = 6 9 = 9 C = 12 F = 15
protocol set up

binary switch
ON When using the 485 communication connection
it is essential that the protocol binary switch and
the modbus address switches are set correctly.
OFF This is done by first removing the clear cover
1 2 3 4 5 6 7 and then setting the switches. See diagram.

The position of the binary switch is indicated


on page 6 section C (protocol set up).
example of setting above
switch no on/off

1&2 baud rate (1) on / (2) off 19200


3 wire mode off 2 wire
4 modbus type on RTU
5 4 wire parity off even
6 format mode on floating point
7 floating point off FP low
word first

switch settings (options available)


For all switch setting options available
switch no on/off
please refer to the table on the left.
1&2 baud rate (1) off / (2) off 9600
(1) on / (2) off 19200
(1) off / (2) on 38400
(1) on / (2) on –

3 wire mode off 2 wire


on 4 wire

4 modbus type off ASCII


on RTU

5 4 wire parity off even


on odd

6 format mode off ASCII string


on floating point

7 floating point off FP low


word format word first

on FP high
word first
communication
connections
RS485 connection

This connection should be made using the appropriate screened twisted pair cable (22 gauge Beldon 8761 or equivalent).
It is imperative that the terminals are wired as per the diagrams below.

evo ic 3 2 wire modbus wiring evo ic 3 4 wire modbus wiring

In 2 wire mode all node transmitters are connected In 4 wire mode all node receivers are connected together
together and linked to the host transmitter port and linked to the host transmitter port and all node
and all node receivers are connected together transmitters are connected together and linked to the
and linked to the host receiver port. host receiver port.

evo ic 3 2 wire modbus wiring diagram


shield

shield
RX+

RX+
TX+

TX+
RX-

RX-
TX-

TX-
1 2 3 4 5 1 2 3 4 5

TX+/RX+
120Ω
TX-/RX-
termination
HOST resistor

evo ic 3 4 wire modbus wiring diagram


shield

shield
RX+

RX+
TX+

TX+
RX-

RX-
TX-

TX-

1 2 3 4 5 1 2 3 4 5

TX+
120Ω
TX-

RX+
120Ω
RX-
termination
HOST resistor

• 22 SWG shielded BELDEN 8761 or equivalent


caution
• Maximum 128 nodes per network
It is important that the shield must be earthed
• Total length of connecting cable not
at one end only.
to exceed 1000 metres
technical specifications

certificate no. 0275

display operating frequency


graphical display 240 x 128 dot matrix 45-65 Hz
FSTN black on white LCD
temperatures
transmissive, wide temperature type
operating temperature -20°C to +70°C
storage temperature -30°C to +80°C
membrane switches (typical characteristics)
humidity 20-90% RH non condensing
electrical properties min typ max units
contact resistance – 100 – Ohms volt free relays
switch capacitance – <25 – pF The type of relay used in the evo ic 3 is the solid state optically coupled
per switch with MOSFET technology incorporated. This device offers the superior
operating voltage 0.5 – 50 volts reliability associated with semiconductor devices, ensures enhanced
operating current 0.05 – 100 mA input to output isolation and faster bounce free contacts.
switching power (rating) – – 1.0 watts
energy relays fitted
insulating resistance
(at 100 volts) 10 – – M.Ohms 3 as standard KWh, KVAh, KVARh
dielectric strength – 500V RMS – – pulse length
@ 50 Hz default value 100ms (programmable)
contact bounce
polyester domes <20ms pulse value
low voltage 230/400V default 1 KWh, 1 KVArh, 1 KVAh
mechanical properties high voltage 110V default 10 KWh, 10 KVArh, 10 KVAh
life expectancy polyester domes 3 million operations
operating force polyester domes 75-700 gram relay contacts
max switching voltage 600VDC or PEAK AC
environmental properties max switching current 100mA
operating temp polyester domes -20°C to +70°C on resistance 50 Ohms
storage temp -40°C to +70°C
communication output 485
accuracy type Raicon 5 way plug and socket
(KWh) all energy measurements comply to BSEN61036 class 1.0 material polymide 66, flame resistant & self-extinguishing

burden protocol and baud rate settings


less than 1Va surface mount dip switch (7 position binary switch)
series 90HB SPST low profile
aux. burden
less than 10 Va standards – EMC testing for emissions and immunity
BSEN 61000-4-2 BSEN 61000-4-3 BSEN 61000-4-4
accuracy drift BSEN 61000-4-5 BSEN 61000-4-6
negligible, self compensating circuit built in
evo ic 3 material
aux. supply display housing front/back cover
230V AC +/- 10% 110V AC +/- 10% & opening door abs flame retardant
maximum measuring voltage
base unit housing top/middle &
300V AC phase to neutral 520V AC phase to phase
terminal cover clear polycarbonate
rated current black base &
5-6 amps (fully isolated) fixing bracket abs flame retardant

graph showing evo ic 3 accuracy load curve

0.5
0.4
0.3
0.2
0.1
% 0
-0.1
-0.2
-0.3
-0.4
-0.5
0 0.25 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

key unity power factor +0.8 -0.5


on screen programming
of the meter
When the meter has been installed and power
FREQUENCY = 49.99
has been applied to the meter the display
R V B TOTAL a new dimension
will run through a set up routine and default

1
in energy information
VOLTS - 230.88 230.94 230.96
AMPS - 1 199.3 1 193.9 1 198.2 3591.4
KW - 276.84 275.72 276.73 829.31
step 1 KVA
KVAR
-
-
276.89
0.0000
275.73
0.0000
276.73
0.0000
829.37
0.0000 to the main screen. You can now start
PF - 0.99 0.99 0.99 0.99
IMP KWH
IMP KVARH
KVAH
= 71.9570 EXP KWH = 0.0000
= 0.1400 EXP KVARH = 0.0043
= 71.9626 AH = 310.131
to programme the meter.
AMPS VOLT POWER H-THD SETUP

Ensure the screen is showing main


as shown in diagram

2 3
FREQUENCY = 49.99 SYSTEM DETAILS
step 2 R V B TOTAL a new dimension
in energy information
step 3 METER No
COMMS EEPROM STATUS
: 0
: EEPROM OK a new dimension
in energy information
VOLTS - 230.88 230.94 230.96 ENGINE SW VERSION No : 1
AMPS - 1 199.3 1 193.9 1 198.2 3591.4 COMMS SW VERSION No : 1
KW - 276.84 275.72 276.73 829.31 DISPLAY SW VERSION No : 1
KVA - 276.89 275.73 276.73 829.37 ENGINE MODE : 4 WIRE 230V 5A
KVAR - 0.0000 0.0000 0.0000 0.0000
PF - 0.99 0.99 0.99 0.99 RELAYS AVAILABLE : 8
RELAYS ENABLED : 10
IMP KWH = 71.9570 EXP KWH = 0.0000 4-20mA AVAILABLE : 4
IMP KVARH = 0.1400 EXP KVARH = 0.0043 4-20mA ENABLED : 3
KVAH = 71.9626 AH = 310.131 LOGGING : NOT AVAILABLE
AMPS VOLT POWER H-THD SETUP ALARMS RATIOS 4-20mA MORE MAIN

Press SET UP (bottom right of screen) Press RATIOS (bottom)

4 5
SYSTEM SET-UP PARAMETERS
step 4 RATIO DATA - PRIMARY
CT
VT
:
:
0.0000
0.0000
SECONDARY
5.0000
230.000 a new dimension
in energy information
step 5 LIFT FLAP HERE
1 2 3
NT : 0.0000 5.0000 TO ENTER NUMERICAL DATA 4 5 6
PULSE DATA - VALVE (KW) PULSE TIME (10ms)
KW : 0.0000 0
KVA : 0.0000 0 7 8 9
KVAR : 10.0000 1000 ENTER PASSWORD : XXXXXX
MD DATA
KW :
- PERIOD (MINS)
30 0 .
KVA : 30
KVAR : 30
AMP : 30 LOG INTERVAL : 0 S1
EDIT BACK MAIN ENTER
S2
N Network exit

Press EDIT (bottom first left) Enter password (password is the serial
number on the front of the base unit)
See example below.

123456

6
123456
step 6

Press ENTER

ENTER
now you are ready to edit
and enter your required values

please read screen carefully


YOU ARE ABOUT TO ENTER A MULTIPLE FIELD
You are about to enter a multiple field editing screen. EDITING SCREEN. TO HELP YOU MOVE AROUND
THIS SCREEN THERE ARE A SET OF EDITING 1 2 3
KEYS WHICH HAVE THE FOLLOWING OPERATION
To help you move around this screen there are a set EXIT :- LEAVES THE EDITING MODE 4 5 6
LAST :- MOVE CURSOR TO PREVIOUS FIELD
of editing keys which have the following operation. (DOES NOT ERASE PRESENT FIELD)
NEXT :- MOVE CURSOR TO NEXT FIELD
7 8 9
(DOES NOT ERASE PRESENT FIELD) .
BACK :- MOVE CURSOR BACK ONE SPACE 0
EXIT Leaves the editing mode ENTER :- TERMINATE FIELD AND ERASE
ALL OTHER CHARACTERS IN FIELD
S1
LAST Move cursor to previous field IF YOU EDIT A FIELD ALWAYS USE ENTER KEY
****** PRESS ANY KEY TO CONTINUE *******
S2
(does not erase present field)
N Network exit
NEXT Move cursor to next field
(does not erase present field)
BACK Move cursor back one space
ENTER Terminate field and erase
all other characters in field
If you edit a field always use ENTER key.
Press any key to continue.

1 1a
The cursor will default To alter this value,enter the
to C.T primary and number you require by opening
will be flashing on the door on the right and pressing
the first digit of the the numbers you require.
primary value. Press ENTER

The cursor will now move to V.T primary. If the meter is to be The cursor will be flashing at

2 3
used in connection with voltage transformers, then you will be N.T primary. If a neutral current
required to enter a primary voltage into the meter. Refer to 1a. transformer has been fitted, you
The secondary voltage is not adjustable. It is therefore essential will be required to enter the value
when programming the V.T setting that you carefully check in this position. Refer to 1a.
the primary and secondary parameters are correct. If no further programming
e.g. 11,000 – 110 volt or standard 3 phase 4 wire 230-230 volt is required press EXIT

pulse data log interval


The evo ic allows you to change the pulse value and the
3
The log interval is also adjustable, this can only be altered
time the contacts are closed. To alter these values follow if the meter has been fitted with a memory card.
steps 1-6 (see page 12), press NEXT until the cursor moves (See separate instructions for installing expansion cards.)
down and is flashing on the position you want to alter.
When all the data has been entered press EXIT.
Refer to 1a.
The screen will show DATA SAVED IN MEMORY
and return to system set up for you to check.
maximum demand data
The evo ic 3 allows you to change the time of the reset If all the details are correct press MAIN.
period of the maximum demand registers. To alter these This will return you to the main menu.
times follow steps 1-6 (see page 12), press NEXT until
the cursor moves down and is flashing over the position
you want to alter. Refer to 1a.
operating
FREQUENCY = 49.99
R V
VOLTS - 230.88 230.94
AMPS - 1 199.3 1 193.9

instructions
KW - 276.84 275.72
KVA - 276.89 275.73
KVAR - 0.0000 0.0000
PF - 0.99 0.99
IMP KWH = 71.9570 EXP
IMP KVARH = 0.1400 EXP
KVAH = 71.9626
AMPS VOLT POWER
The evo ic 3 has been designed to display the main electrical parameters
on one screen thus enabling at a glance to monitor power fluctuations.

The evo ic 3 has many other electrical parameters such as Maximum Demand,
Under and Over Alarm points settings and Current and Voltage Harmonic analysis.
This information is displayed on other screens available by pressing the arrow keys
located below the screen.

PHASE CURRENT (AMPS) PH-N VOLTAGE (VOLTS)


R 0 % 100 a new dimension
R 0 % 100 a new dimension
0.0000 MIN=0.0000 in energy information 0.0000 MIN=0.0000 in energy information
MAX=0.0000 MAX=0.0000
Y 0 % 100 Y 0 % 100
0.0000 MIN=0.0000 0.0000 MIN=0.0000
MAX=0.0000 MAX=0.0000
B 0 % 100 B 0 % 100
0.0000 MIN=0.0000 0.0000 MIN=0.0000
MAX=0.0000 MAX=0.0000

TOTAL MD NEUT H-THD MAIN PH-PH H-THD MAIN

PHASE CURRENT (AMPS) PHASE CURRENT (AMPS) PH-PH VOLTAGE (VOLTS) R VOLTAGE HARMONICS (CF = 1.56)
100%
TOTAL 0 % 100 TOTAL 0 % 100 R-Y 0 % 100 TO
0.0000 MIN=0.0000 0.0000 MIN=0.0000 0.0000 MIN=0.0000 ZOOM
MAX=0.0000 MAX=0.0000 MAX=0.0000 IN
PRESS
NEUTRAL 0 % 100 NEUTRAL 0 % 100 Y-B 0 % 100 1
0.0000 MIN=0.0000 0.0000 MIN=0.0000 0.0000 MIN=0.0000 THD(%)
MAX=0.0000 MAX=0.0000 MAX=0.0000 0.00 TO
MAX MAX ZOOM
DEMAND 0 % 100 DEMAND 0 % 100 B-R 0 % 100 OUT
0.0000 MIN=0.0000 0.0000 MIN=0.0000 0.0000 MIN=0.0000 PRESS
TIP=13:50 TIP=16:30 MAX=0.0000 0
0%
H-THD BACK MAIN H-THD BACK MAIN PH-N H-THD MAIN Y B N % MAIN

R CURRENT HARMONICS (CF = 1.91) R CURRENT HARMONICS (CF = 1.65) R VOLTAGE HARMONICS (CF = 1.56) R VOLTAGE HARMONICS (CF = 1.64)
100% 100% 100%
TO TO TO THD : 0.00 25th : 0.00 49th : 0.00
ZOOM ZOOM ZOOM 3rd : 0.00 27th : 0.00 51st : 0.00
IN IN IN 5th : 0.00 29th : 0.00 53rd : 0.00
PRESS PRESS PRESS 7th : 0.00 31st : 0.00 55th : 0.00
1 1 1 9th : 0.00 33rd : 0.00 57th : 0.00
THD(%) THD(%) THD(%) 1 1th : 0.00 35th : 0.00 59th : 0.00
0.00 TO 0.00 TO 0.00 TO 13th : 0.00 37th : 0.00 61st : 0.00
ZOOM ZOOM ZOOM 15th : 0.00 39th : 0.00 63rd : 0.00
OUT OUT OUT 17th : 0.00 41st : 0.00
PRESS PRESS PRESS 19th : 0.00 43rd : 0.00
0 0 0 21st : 0.00 45th : 0.00
0% 0% 0% 23rd : 0.00 47th : 0.00
Y B N % MAIN Y B N % MAIN Y B N % MAIN Y B N GRAPH MAIN

R CURRENT HARMONICS (CF = 1.64) R CURRENT HARMONICS (CF = 1.64) R VOLTAGE HARMONICS (CF = 1.64)
THD : 0.00 25th : 0.00 49th : 0.00 THD : 0.00 25th : 0.00 49th : 0.00 THD : 0.00 25th : 0.00 49th : 0.00
3rd : 0.00 27th : 0.00 51st : 0.00 3rd : 0.00 27th : 0.00 51st : 0.00 3rd : 0.00 27th : 0.00 51st : 0.00
5th : 0.00 29th : 0.00 53rd : 0.00 5th : 0.00 29th : 0.00 53rd : 0.00 5th : 0.00 29th : 0.00 53rd : 0.00
7th : 0.00 31st : 0.00 55th : 0.00 7th : 0.00 31st : 0.00 55th : 0.00 7th : 0.00 31st : 0.00 55th : 0.00
9th : 0.00 33rd : 0.00 57th : 0.00 9th : 0.00 33rd : 0.00 57th : 0.00 9th : 0.00 33rd : 0.00 57th : 0.00
1 1th : 0.00 35th : 0.00 59th : 0.00 1 1th : 0.00 35th : 0.00 59th : 0.00 1 1th : 0.00 35th : 0.00 59th : 0.00
13th : 0.00 37th : 0.00 61st : 0.00 13th : 0.00 37th : 0.00 61st : 0.00 13th : 0.00 37th : 0.00 61st : 0.00
15th : 0.00 39th : 0.00 63rd : 0.00 15th : 0.00 39th : 0.00 63rd : 0.00 15th : 0.00 39th : 0.00 63rd : 0.00
17th : 0.00 41st : 0.00 17th : 0.00 41st : 0.00 17th : 0.00 41st : 0.00
19th : 0.00 43rd : 0.00 19th : 0.00 43rd : 0.00 19th : 0.00 43rd : 0.00
21st : 0.00 45th : 0.00 21st : 0.00 45th : 0.00 21st : 0.00 45th : 0.00
23rd : 0.00 47th : 0.00 23rd : 0.00 47th : 0.00 23rd : 0.00 47th : 0.00
Y B N GRAPH MAIN Y B N GRAPH MAIN Y B N GRAPH MAIN

PHASE CURRENT (AMPS) R CURRENT HARMONICS (CF = 1.56)


100%
TOTAL 0 % 100 TO
0.0000 MIN=0.0000 ZOOM
MAX=0.0000 IN
PRESS
NEUTRAL 0 % 100 1
0.0000 MIN=0.0000 THD(%)
MAX=0.0000 0.00 TO
MAX ZOOM
DEMAND 0 % 100 OUT
0.0000 MIN=0.0000 PRESS
TIP=12:08 0
0%
H-THD BACK MAIN Y B N % MAIN

R CURRENT HARMONICS (CF = 1.65) R CURRENT HARMONICS (CF = 1.64)


100%
TO THD : 0.00 25th : 0.00 49th : 0.00
ZOOM 3rd : 0.00 27th : 0.00 51st : 0.00
IN 5th : 0.00 29th : 0.00 53rd : 0.00
PRESS 7th : 0.00 31st : 0.00 55th : 0.00
1 9th : 0.00 33rd : 0.00 57th : 0.00
THD(%) 1 1th : 0.00 35th : 0.00 59th : 0.00
0.00 TO 13th : 0.00 37th : 0.00 61st : 0.00
ZOOM 15th : 0.00 39th : 0.00 63rd : 0.00
OUT 17th : 0.00 41st : 0.00
PRESS 19th : 0.00 43rd : 0.00
0 21st : 0.00 45th : 0.00
0% 23rd : 0.00 47th : 0.00
Y B N % MAIN Y B N GRAPH MAIN

R CURRENT HARMONICS (CF = 1.64)


THD : 0.00 25th : 0.00 49th : 0.00
3rd : 0.00 27th : 0.00 51st : 0.00
5th : 0.00 29th : 0.00 53rd : 0.00
7th : 0.00 31st : 0.00 55th : 0.00
9th : 0.00 33rd : 0.00 57th : 0.00
1 1th : 0.00 35th : 0.00 59th : 0.00
13th : 0.00 37th : 0.00 61st : 0.00
15th : 0.00 39th : 0.00 63rd : 0.00
17th : 0.00 41st : 0.00
19th : 0.00 43rd : 0.00
21st : 0.00 45th : 0.00
23rd : 0.00 47th : 0.00
Y B N GRAPH MAIN
B TOTAL a new dimension
in energy information
230.96
1 198.2 3591.4
276.73 829.31
276.73 829.37
0.0000 0.0000
0.99 0.99
KWH = 0.0000
KVARH = 0.0043
AH = 310.131
H-THD SETUP
main display screen
SET UP see page 12-13
The picture to the left is showing all the electrical parameters
available on the main screen. The diagram below indicates
the route which will guide you to the various other fields
of electrical information.

REAL POWER (KW) HARMONIC ANALYSIS


R 0 % 100 a new dimension
WAVEFORMS ARE MADE FRPM PURE SINE AND a new dimension
0.0000 MIN=0.0000 in energy information COSINE COMPONENTS (HARMONICS) WHICH HAVE in energy information
MAX=0.0000 RELATIVE MAGNITUDE/PHASE RELATIONSHIPS.
Y 0 % 100 BY PERFORMING FOURIER ANALYSIS ON A
0.0000 MIN=0.0000 SIGNAL THE RELATIVE MAGNITUDE AND PHASE
MAX=0.0000 COMPONENTS MAY BE CALCULATED.
B 0 % 100 THE IC3000 CALCULATES THE ODD HARMONICS
-0.0000 MIN=0.0000 UP TO THE 63rd AND DISPLAYS THE RESULTS
MAX=0.0000 AS A PERCENTAGE OF THE FUNDAMENTAL IN
EITHER A BAR GRAPH OR TABLE FORM
KVA KVAR TOTAL MD MAIN AMPS VOLTS MAIN

REACTIVE POWER (KVAR) REAL POWER (KW) R CURRENT HARMONICS (CF = 1.46) R VOLTAGE HARMONICS (CF = 1.37)
100% 100%
R 0 % 100 TOTAL 0 % 100 TO TO
-0.0000 MIN=0.0000 0.0000 MIN=0.0000 ZOOM ZOOM
MAX=0.0000 MAX=0.0000 IN IN
PRESS PRESS
Y 0 % 100 MAX 1 1
-0.0000 MIN=0.0000 DEMAND 0 % 100 THD(%) THD(%)
MAX=0.0000 0.0000 MIN=0.0000 0.00 TO 0.00 TO
TIP=26:42 ZOOM ZOOM
B 0 % 100 OUT OUT
-0.0000 MIN=0.0000 PRESS PRESS
MAX=0.0000 0 0
0% 0%
KW KVA TOTAL MD MAIN KVA KVAR BACK MAIN Y B N % MAIN Y B % MAIN

REAL POWER (KW) APPARENT POWER (KVA) R CURRENT HARMONICS (CF = 1.64) R VOLTAGE HARMONICS (CF = 1.37)
R 0 % 100 TOTAL 0 % 100 THD : 0.00 25th : 0.00 49th : 0.00 THD : 0.00 25th : 0.00 49th : 0.00
-0.0000 MIN=0.0000 0.0000 MIN=0.0000 3rd : 0.00 27th : 0.00 51st : 0.00 3rd : 0.00 27th : 0.00 51st : 0.00
MAX=0.0000 MAX=0.0000 5th : 0.00 29th : 0.00 53rd : 0.00 5th : 0.00 29th : 0.00 53rd : 0.00
7th : 0.00 31st : 0.00 55th : 0.00 7th : 0.00 31st : 0.00 55th : 0.00
Y 0 % 100 MAX 9th : 0.00 33rd : 0.00 57th : 0.00 9th : 0.00 33rd : 0.00 57th : 0.00
-0.0000 MIN=0.0000 DEMAND 0 % 100 1 1th : 0.00 35th : 0.00 59th : 0.00 1 1th : 0.00 35th : 0.00 59th : 0.00
MAX=0.0000 0.0000 MIN=0.0000 13th : 0.00 37th : 0.00 61st : 0.00 13th : 0.00 37th : 0.00 61st : 0.00
TIP=26:42 15th : 0.00 39th : 0.00 63rd : 0.00 15th : 0.00 39th : 0.00 63rd : 0.00
B 0 % 100 17th : 0.00 41st : 0.00 17th : 0.00 41st : 0.00
-0.0000 MIN=0.0000 19th : 0.00 43rd : 0.00 19th : 0.00 43rd : 0.00
MAX=0.0000 21st : 0.00 45th : 0.00 21st : 0.00 45th : 0.00
23rd : 0.00 47th : 0.00 23rd : 0.00 47th : 0.00
KVA KVAR TOTAL MD MAIN KVAR KW BACK MAIN Y B N GRAPH MAIN Y B GRAPH MAIN

APPARENT POWER (KVA) REACTIVE POWER (KVAR)


R 0 % 100 TOTAL 0 % 100
-0.0000 MIN=0.0000 0.0000 MIN=0.0000
MAX=0.0000 MAX=0.0000
Y 0 % 100 MAX
-0.0000 MIN=0.0000 DEMAND 0 % 100
MAX=0.0000 0.0000 MIN=0.0000
TIP=26:42
B 0 % 100
-0.0000 MIN=0.0000
MAX=0.0000

KVAR KW TOTAL MD MAIN KW KVA BACK MAIN The graph will appear at a scale of 20%
APPARENT POWER (KVA) REAL POWER (KW) To zoom in press 1 key
R 0 % 100 TOTAL 0 % 100
0.0000 MIN=0.0000
MAX=0.0000
0.0000 MIN=0.0000
MAX=0.0000 To zoom out press 0 key
Y 0 % 100 MAX
0.0000 MIN=0.0000 DEMAND 0 % 100
MAX=0.0000 0.0000 MIN=0.0000
TIP=27:36
B 0 % 100
0.0000 MIN=0.0000
MAX=0.0000 R CURRENT HARMONICS (CF = 1.35)
KVA KVAR BACK MAIN
5.0%
KVAR KW TOTAL MD MAIN
TO
ZOOM
REACTIVE POWER (KVAR) APPARENT POWER (KVA)
IN
R
0.0000
0 % 100
MIN=0.0000
MAX=0.0000
TOTAL
0.0000
0 % 100
MIN=0.0000
MAX=0.0000
PRESS
Y 0 % 100 MAX
1
0.0000 MIN=0.0000
MAX=0.0000
DEMAND
0.0000
0 % 100
MIN=0.0000 THD(%)
B
0.0000
0 % 100
MIN=0.0000
TIP=27:36
5.76 TO
MAX=0.0000 ZOOM
KW KVA TOTAL MD MAIN KVAR KW BACK MAIN OUT
PRESS
APPARENT POWER (KVA) REACTIVE POWER (KVAR) 0
R
0.0000
0 % 100 TOTAL
0.0000
0 % 100
MIN=0.0000
0%
MIN=0.0000
MAX=0.0000 MAX=0.0000
Y
0.0000
0 % 100
MIN=0.0000
MAX
DEMAND 0 % 100
Y B % MAIN
MAX=0.0000 0.0000 MIN=0.0000
TIP=27:36
B 0 % 100
0.0000 MIN=0.0000
MAX=0.0000

KVAR KW TOTAL MD MAIN KW KVA BACK MAIN


4b Albany Road, Chorlton-cum-Hardy, Manchester M21 0AW Tel: +44 (0) 161 861 9056 Fax: +44 (0) 161 881 3745
email: [email protected] www.autometers.co.uk

Try our virtual meter on the product website www.evo-ic3.co.uk

an evolution for metering a revolution for information