Elec Installation Design Seminar
Elec Installation Design Seminar
Seminar
Prepared By:-
Eng Elmamoun Ibrahim Mustafa
LOGO
Introduction
Distribution Transformer
Description Symbol
Cooling Medium
Oil O
Non-flammable Liquid L
Gas G
Water W
Air A
Method Of heat Dissipation
Natural N
Forced (not directed oil) F
ONAN
Cooling type
Power
Transformer
Transformers Cooling
ONAF Cooling type
Power Transformer
Transformers Cooling
Distribution Transformers Selection
Criteria
Types of load
• Motor load
• Resistive-type heating appliances&
lamps.
How to calculate installed power
Notice:-
For vertical rising mains fed at ground level, the cross-sectional
area of the conductors can evidently be progressively reduced
from the lower floors towards the upper floors.
These changes of conductor size are conventionally spaced by
at least 3-floor intervals. In the example.
2- Factor of simultaneity for distribution board
Solution
1. In this example, the total installed apparent
power is the total of all KVA in the Installation if
we assume that the power factor is constant.
Total(KVA)max=4x5+2x2+18+3+1x15+10.6+1+2x2.5+
2x15+18+1=126.6 KVA
2. Estimation of actual maximum kVA demands at all
levels of an installation ,by aid of the following
diagram.
Application of factors ku and ks
Enclosed & bunched 0.80 0.70 0.65 0.60 0.57 0.54 0.52
Single layer clipped T 0.85 0.79 0.75 0.73 0.72 0.72 0.71
to non-metal surface S 0.94 0.90 0.90 0.90 0.90 0.90 0.90
Single layer T 0.86 0.81 0.77 0.75 0.74 0.73 0.73
multicore on metal cable S 0.91 0.89 0.88 0.87 0.87 0.87 0.87
tray
Grouping
Correction factors for cables’ current
ratings (air & ground installation)
3- Thermal Insulation Derating Factor; Ci
[Regulation Table 52A].
CABLE LENGTH UNDER Ci
INSULATION (mm)
50 0.89
100 0.81
200 0.68
400 0.55
>400 0.50
Example for Ca &Cg values How affect the
Currant currying capacity
A 3-phase circuit with a load current of 35 A is
to be wired in multicore,PVC insulated and
sheathed cable which is rated at 80 A .
For approximately 2/3 of its length it is run in
trucking with 4 other circuits where the
ambient temperature is 25oC.
For the remainder of its route it is run singly
but in an ambient temperature of 45C.
By applying appropriate de-rating factors,
determine the cable rating for each section of
the run.
Example for Ca &Cg values How affect the
Currant currying capacity
SOLUTION
For a 3 Ø system:
For a 1 Ø system:
Where
A=is the minimum cross-sectional area of the cable
(mm2)
I=is the prospective short circuit current (A)
t= is the duration of the short circuit (s)
K=is a short circuit temperature rise constant
K factor values for LV conductors, commonly used in
national standards and complying with IEC 60724
k values Nature of insulation
Cross-linked-
Polyvinylchlor polyethylene (XLPE)
ide (PVC) Ethylene-propylene-
rubber(EPR)
Final temperature (°C) 160 250
Initial temperature (°C) 30 30
Insulated Copper 143 176
conductors not
incoporated Aluminium 95 116
in cables or bare
conductors in Steel 52
contact 64
with cable jackets
Conductors of Copper 115 143
a multi-core-
cable Aluminium 76 94
Example (Case Study)
11/ 0.415 KV
500 KVA, Z=5%
ONAN,Dyn11
OFF Load TAP Changer
MCCB
250 A
4 C X 120 mm2
PVC/SWA/PVC
Cable
Production Line Motor AC feeder
Example (Case Study)
Given:-
Design Isc= 15 KA , t= 3 sec
K factor from the table =115
Max Isc from the power Transformer
Isec 722
Isc= = =14440 Amp=14.4 KA
Z% .05
PVC cable >> K factor = 115
𝐼 𝑡 14440 3
A= = = = 217 mm2
𝐾 115
The minimum cable size to withstand the short circuit
is 217 mm2 so the adequate size required in this case
the nearest standard size above the actually installed
cable will be 240 mm2
Thank You
LOGO