Chapter 5 Three-Phase Transformer v2
Chapter 5 Three-Phase Transformer v2
net/publication/337932307
CITATIONS READS
0 14,853
1 author:
Francisco Gonzalez-Longatt
Loughborough University
506 PUBLICATIONS 4,527 CITATIONS
SEE PROFILE
All content following this page was uploaded by Francisco Gonzalez-Longatt on 14 December 2019.
5
Three-Phase Transformers
F. Gonzalez-Longatt
5.1 Objective
This chapter presents a general summary of three-phase transformers and its practical aspects related to the
operation in AC steady-state systems.
5.2 Introduction
A power transformer is defined as1:
"A power transformer a static piece of apparatus with two or more windings which, by electromagnetic induction,
transforms a system of alternating voltage and current into another system of voltage and current usually of
different values and at the same frequency for the purpose of transmitting electrical power."
In the UK high-voltage, long-distance transmission systems operate at 275 kV and 400 kV; distribution systems
operate most commonly at 132 kV, 66 kV and 33 kV, with local systems operating at 11 kV down to 415 V. All of these
systems have three-phases. Transmission and distribution systems operate at high voltages in order to reduce loses
and improve efficiency. However, it is clear that for such systems to work three-phase transformers are required to
link sections operating at different voltages.
5.3 Three-phase transformer basics
The primary windings of three identical single-phase transformers are connected to a 3-phase supply, and each
winding is connected between a pair of lines. That situation is depicted in Fig. 5.1(a).
a1 c1
a2 b1
b2 c2
1 2 3
a1
a2
1 2 3
a1 b1 c1
a2 b2 c2
Under normal balanced conditions, the three voltages, and consequently the three fluxes, are mutually displaced by
120, so that 1 + 2 + 3 = 0 . If the three transformers are placed side-by-side, with a common yoke top and bottom,
there is no need to provide a return path for the flux. This arrangement, shown in Fig. 5.1(b), is the very common 3-
limb construction.
In Fig. 5.2(b), the lengths of the magnetic paths for the three phases are not quite equal, and the magnetising currents
are consequently not balanced, with the centre phase being lower.
Very large transformers use the five-limb construction of Fig. 5.2., which has windings only on the centre three limbs.
Five limb transformers have balanced phases, but because the yokes and outer limbs carry only half the flux of the
centre limbs their size can be reduced. The reduction in height can ease transportation difficulties.
1 1 1 1 1 1
1 1 2 2 3 3
2 2 2 2 2 2
1 BS EN 60076-1:2011, Power transformers, Part 1: General. Sub-section 3.1.1 of Terms and definitions General.
Chapter 5
Fig. 5.2. Illustrative example of a 3-phase 5-limb transformer core. Magnetic flux directions are shown.
A 3-phase transformer bank costs less, weighs less, requires less floor space and has a slightly higher efficiency than
three single-phase transformers of the same total rating.
The VA rating of each phase (or each transformer of a group of three single-phase transformers) is one-third of the
total VA rating of the bank, regardless of the connection or core type used. However, the voltage and current ratings
of the individual phases or transformers depend on the connection used.
5.4 Three-phase connections
The number of possible of 3-phase transformer winding connections is considerable. However, straightforward
combinations of the standard star and delta arrangements are generally preferred. Common 3-phase transformer
connections are listed in Table 5.1, where the relationships are valid for balanced conditions only.
• The star-delta connection is common in stepping down from a high to a medium or low voltage, since an earthed
neutral may then be provided on the HV side.
• Similarly, a delta-star connection is common when a voltage is stepped up to a high voltage. Delta-star is also
used in distribution systems where a neutral point is required for single-phase loads.
• In a delta-delta connection, one transformer may be removed for repair or maintenance, and the supply may be
maintained. The arrangement of the two remaining transformers is called an open-delta connection.
• The star-star connection is seldom used, because of the problems involved in harmonic reduction.
• In rectifier circuit applications secondary phase windings are sometimes inter-connected to produce a 6-phase
output or to improve load distribution between phases.
The groups are derived from BS EN 60076-1:2011, Power transformers, Part 1: General. Annex D.
2
A2 a2 A2 b1 c1
Yy0 Yy6 n
N n N
C2 B2 c2 b2 C2 B2 a1
A2 a2 A2 b c1
b1
Dd0 C A c a Dd6 C A
a c
C2 B B2 c2 b b2 C2 B B2 a1
A2 a4 A2 c3
b3
a b a b c
Dz0 C A Dz6 C A c n
b c
c n a b a
C2 B B2 c4 b4 C2 a3
B B2
Dy1 A B C A n b2
c2 n
C2 B2
C2 C B2 b2 B c2
A2 a2 A2 a2
c b
Yd1 Yd11 a
N c2 a N b2
C2 B2 b C2 B2 c
b2 c2
A2 a4 A2 a4
a
Yz1 c b
a Yz11 b b
N c N c b4
c4 n n
a a
C2 B2 b C2 B2
b4 c4 c
A1 A2 a3 a1 a2
a4
B1 B2 b3 b1 b2
b4
C1 C2
c3 c1 c2
c4
Fig. 5.4. Group 2 Dz6 winding connections
3 In conventional power applications, the terms primary and secondary are used only in reference to the direction of power flow, the windings being
identified by their rated voltage, i.e. high or low voltage. Here the terms primary and secondary are retained in the description of the equivalent
circuit to maintain continuity with previous material, however, they may not be used in practice.
4 In most cases when considering industrial 3-phase loads the connection is unknown. For example, 3-phase motors, generators transformers,
capacitors, and so on, often have only three external terminals with no way to tell the internal connection. Under these circumstances, it is normal
to assume that the connection is a star (because a star connection is slightly easier to deal with than a delta connection).
In a star connection, the impedance per phase is taken to be the line-to-neutral impedance, the voltage per phase is simply the line voltage divided
by and the current per phase is equal to the line current.
Dr. F. Gonzalez-Longatt Chapter_5_three-phase_Transformer_v2.docx Page 4 of 8
Three-Phase Transformers
• The nominal power rating of the hypothetical single-phase transformer is one-third of the rating of the 3-phase
transformer bank.
• The load on the hypothetical single-phase transformer is one-third of the load on the 3-phase transformer bank.
VP 1 Ip1 jX1
Ip1 R1 X1 I P2 IP 2 Ip1 R1
+ IP0 + V
+ P2
+ Z1 Ip1
VP 1 rm xm V P2 VP 2
EP1 f2 I P2
- IP 0a - IP 0r - - f1
N1:N2
Ideal IP0
Transformer
Fig. 5.5. Approximate phase equivalent circuit (left) and phasor diagram (right).
• IP1 is the total primary phase current and the phasor sum of IP0 and I P 2 .
• I P 2 R1 is the voltage drop associated with the total phase winding resistance and is in phase with I P 2 .
• I P 2 X1 is the voltage drop associated with the total phase leakage reactance and is in phase quadrature
with I P 2 .
• cos f1 and cos f2 are the primary and secondary power factors respectively.
• VP 2 = VP 2 ( N2 N1 )
I P 2 N 2
• N1 I P 2 = N2 I P 2 or =
I P 2 N1
Because the no-load current is relatively small rm and xm are often neglected when considering the behaviour near
full-load.
5.9 Rating and performance
The basic electrical components of a definition of rating for a 3-phase transformer are:
• Rated power
• Rated line voltages
• Rated line currents
• Rated frequency
• Group
Note: These are only some of the elements which a manufacturer is required to include on the rating plate
fixed to every transformer produced.
The two most important performance criteria by which transformers are judged - voltage regulation and efficiency -
can be predicted quite accurately using the equivalent circuits.
5.9.1 Rated power
The nominal rated power of a transformer is a conventional value of apparent power (in VA, kVA or MVA) which the
transformer can safely supply under the manufacturer's specified conditions, i.e. the rating specifies the output. It
establishes the rated secondary winding current and implies the rated primary winding current. The rated power has
an almost exclusively thermal basis, the limitation being the maximum working temperature for which the insulation
will have a reasonable economic life.
Because transformer losses are small in comparison to their operating power it is common to neglect them for the
purposes of VA calculation and to assume that:
S1 = 3VP1 I P1 S2 = 3VP 2 I P 2 (5.1)
Or:
S1 = 3VL1 I L1 S2 = 3VL2 I L2 (5.2)
and
P1 = 3VP1 I P1 cosf1 P2 = 3VP 2 I P 2 cos f2 (5.3)
or
P1 = 3VL1 I L1 cos (f1 ) P2 = 3VL2 I L2 cos (f2 ) (5.4)
where:
S1, S2 = the primary and secondary apparent powers respectively (VA)
P1, P2 = the primary and secondary powers respectively (Watt)
f1, f2 = primary and secondary power factors respectively
Note: The practice of neglecting the losses when making VA calculations is only permissible when
considering large transformers where losses are a small proportion of overall power transfer and the
efficiency is very high. In small transformers, it is usually necessary to take account of the losses.
5.9.2 Voltage regulation (VR)
Voltage regulation (VR) is the change in the secondary voltage between no-load and full-load with the primary voltage
assumed constant. It can be expressed directly as a voltage:
Voltage regulation (VR) = no-load voltage – full-load voltage (5.5)
but is usually expressed as a fraction of the no-load voltage, either per-unit or per-cent.
no-load voltage − full-load voltage
Voltage regulation (VR ) % = 100% (5.6)
no-load voltage
which can be calculated with the line or phase voltages, or
I
Voltage regulation (VR ) % P 2 ( R1 cos 2 X1 sin 2 ) 100% (5.7)
V P1
which is calculated with phase current and voltage, with the reactive component added for lagging power factors and
subtracted for leading power factors.
5.9.3 Efficiency ()
Efficiency () is the ratio of output power and input power. It can be expressed either in per-unit or percentage terms.
output power output power
efficiency, % = = 100% (5.8)
input power output power + losses
or
3VL 2 I L 2 cos (f2 )
= 100% (5.10)
3VL 2 I L 2 cos (f2 ) + Pi + Pc
Iron losses (Pi) are represented in the equivalent circuit by the power dissipated in the shunt phase resistances rm, so
that
Pi = 3
(VP1 )2 [watts] (5.11)
rm
Copper losses (Pc) are represented in the equivalent circuit by the power dissipated in the series phase resistances R1,
so that
Pc = 3 ( I P 2 ) R1 [watts]
2
(5.12)
The full-load output power = S cos (f2), where S is the product of the rated secondary voltage and current, i.e. the
apparent power, so that at n times full-load:
n S cos f2
fl = 100%
n S cos f2 + Pi + n2 Pc (5.13)
• Maximum efficiency ( = 1.0 = 100%) occurs when the iron loss and copper loss are equal:
Pi Pc (maximum efficiency) (5.14)
Maximum efficiency occurs therefore at the fraction n of full load where:
Pi = n2 Pc (5.15)
and
n = Pi Pc (5.16)
Note: All of the equations in this section are valid for balanced conditions only, under other conditions
individual phase components of voltage, current and losses must be considered.
5.10 All-day (or energy) efficiency
The efficiency () as defined in Section 5.9.3 is sometimes called the ordinary or commercial efficiency, but there is a
second definition which is a measure of the efficiency of energy transfer in any 24-hour period.
output in kilowatt-hours
all-day efficiency = 100% (5.17)
input in kilowatt-hours
Transformers are usually designed to have their maximum efficiency at a load that will maximise their all-day
efficiency. For example, generator transformers usually operate continuously at or near their full-load consequently
their maximum ordinary efficiency should be at full-load, but distribution transformers often operate well below their
full-load for long periods, consequently their maximum ordinary efficiency should occur at a lower load. Distribution
transformers have their primary windings connected to the supply 24 hours a day. The core losses are dissipated
continuously whereas the copper losses are dissipated only while the transformer is on load. If a transformer is not
operating on load continuously its all-day efficiency is less than its ordinary efficiency.
5.11 End notes
In most cases when considering industrial 3-phase loads the connection is unknown. For example, 3-phase motors,
generators transformers, capacitors, and so on, often have only three external terminals with no way to tell the
internal connection. Under these circumstances it is normal to assume that the connection is star (because a star
connection is slightly easier to deal with than a delta connection).
In a star connection the impedance per phase is taken to be the line-to-neutral impedance, the voltage per phase is
simply the line voltage divided by 3 and the current per phase is equal to the line current.
The assumption of star connection is not limited to individual loads but can be made for entire load centres such as a
factory containing motors, heaters furnaces, lights etc.