VC0-Report
VC0-Report
PVsyst TRIAL
PVsyst - Simulation report
Grid-Connected System
PVsyst TRIAL
Prey Popel - Cambodia
PVsyst TRIAL
PVsyst TRIAL
Author
PVsyst TRIAL
Project: NPIC new building
Variant: New simulation variant
PVsyst V7.4.5
VC0, Simulation date:
02/04/24 16:10
PVsyst TRIAL
with v7.4.5
Project summary
Geographical Site Situation Project settings
Prey Popel Latitude 11.59 °N Albedo 0.20
Cambodia Longitude 104.80 °E
Altitude 13 m
Time zone UTC+7
Meteo data
Prey Popel
Meteonorm 8.1 (1996-2015), Sat=100% - Synthetic
System summary
PVsyst TRIAL
Grid-Connected System No 3D scene defined, no shadings
System information
PV Array Inverters
Nb. of modules 11 units Nb. of units 1 unit
Pnom total 1650 Wp Pnom total 1200 W
Pnom ratio 1.375
Results summary
Produced Energy 2199.25 kWh/year Specific production 1333 kWh/kWp/year Perf. Ratio PR 76.27 %
PVsyst TRIAL
Project and results summary
Main results
Loss diagram
Predef. graphs
Table of contents
PVsyst TRIAL
PVsyst TRIAL
02/04/24 PVsyst Evaluation mode Page 2/7
Project: NPIC new building
Variant: New simulation variant
PVsyst V7.4.5
VC0, Simulation date:
02/04/24 16:10
PVsyst TRIAL
with v7.4.5
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 21.4 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate
PVsyst TRIAL
PV Array Characteristics
PV module Inverter
Manufacturer Generic Manufacturer Generic
Model 36P, 150 Wp Model UNO-DM-1.2-TL-PLUS
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 150 Wp Unit Nom. Power 1.20 kWac
Number of PV modules 11 units Number of inverters 1 unit
Nominal (STC) 1650 Wp Total power 1.2 kWac
Modules 1 strings x 11 In series Operating voltage 90-580 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.38
Pmpp 1480 Wp
U mpp 182 V
I mpp 8.2 A
PVsyst TRIAL
Total PV power Total inverter power
Nominal (STC) 1.65 kWp Total power 1.2 kWac
Total 11 modules Number of inverters 1 unit
Module area 11.2 m² Pnom ratio 1.38
Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 373 mΩ Loss Fraction -0.8 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s
PVsyst TRIAL
PVsyst TRIAL
02/04/24 PVsyst Evaluation mode Page 3/7
Project: NPIC new building
Variant: New simulation variant
PVsyst V7.4.5
VC0, Simulation date:
02/04/24 16:10
PVsyst TRIAL
with v7.4.5
Main results
System Production
Produced Energy 2199.25 kWh/year Specific production 1333 kWh/kWp/year
Perf. Ratio PR 76.27 %
PVsyst TRIAL
Balances and main results
PVsyst TRIAL
February 125.6 71.39 28.75 136.4 133.1 185.0 171.9 0.764
March 157.4 86.68 30.32 159.9 155.9 214.6 199.5 0.756
April 170.3 79.47 30.55 162.3 157.6 216.2 200.6 0.749
May 169.7 86.40 30.47 151.4 145.9 203.6 189.0 0.757
June 166.5 80.44 29.29 144.0 138.4 194.9 181.0 0.762
July 161.6 78.34 29.14 141.4 136.0 191.4 177.4 0.760
August 157.1 76.89 29.04 144.8 140.0 195.8 181.2 0.758
September 145.4 74.92 28.07 143.8 139.8 195.4 181.0 0.763
October 156.1 80.90 28.45 165.9 162.0 225.5 209.9 0.767
November 115.9 71.49 27.87 127.3 124.1 175.0 162.5 0.773
December 110.9 68.26 27.56 125.1 122.0 172.5 160.1 0.776
Year 1764.3 924.63 28.92 1747.7 1697.1 2368.8 2199.3 0.763
PVsyst TRIAL
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst TRIAL
02/04/24 PVsyst Evaluation mode Page 4/7
Project: NPIC new building
Variant: New simulation variant
PVsyst V7.4.5
VC0, Simulation date:
02/04/24 16:10
PVsyst TRIAL
with v7.4.5
Loss diagram
1764 kWh/m² Global horizontal irradiation
-2.00%
-1.03%
-12.45% PV loss due to temperature
PVsyst TRIAL
-0.01% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
2199 kWh Available Energy at Inverter Output
2199 kWh Energy injected into grid
PVsyst TRIAL
PVsyst TRIAL
02/04/24 PVsyst Evaluation mode Page 5/7
Project: NPIC new building
Variant: New simulation variant
PVsyst V7.4.5
VC0, Simulation date:
02/04/24 16:10
PVsyst TRIAL
with v7.4.5
Predef. graphs
Daily Input/Output diagram
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
02/04/24 PVsyst Evaluation mode Page 6/7
PVsyst V7.4.5
VC0, Simulation date:
02/04/24 16:10
PVsyst TRIAL
with v7.4.5
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL