Structural Requirements
Structural Requirements
Structural Requirements
and Specifications for Buildings
Structural Design and Structural Drawings
(First Editions) (Draft)
Prepared by:
The Building Permit Structural Department
May 2022.
i|Page
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Table of Content
Chapter Content Page
ii | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
iii | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
iv | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
v|Page
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
vi | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
3|Page
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
4|Page
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Article 7
Structural codes of practices adopted in the Sultanate shall apply to structural design
calculations of buildings of various heights provided that the safe bearing capacity
of soil used in calculating the foundations.
Article 8
Materials used in the construction of any new building or additions or alterations of
an existing building shall be of high quality and in conformity with local and
international standards adopted in the Sultanate of Oman.
Article 9
If the building height exceeds three floors, the documents and drawings submitted
should be supported by a report on soil test signed by a registered consultant, a
specialist firm or a recognized soil testing laboratory, if so, required by the
Municipality. The Municipality may require the submission of a report of a soil test
for buildings of less than three floors, depending on the nature of the site or building
in which case the Municipally, may only accept a report, from the designing
consultant stating the nature of the building site and condition of soil at the site. The
designing consultant shall be held responsible for the type of soil and its safe bearing
capacity.
5|Page
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Article 103
No alteration is permitted in the approved permit, drawings or any other official
document unless prior approval is obtained from the concern department. No
alterations should be endorsed unless signed and stamped by the department that
issued the permit or the document.
Article 105
Any person who demolishes, builds or lays the foundations of any building shall
take all necessary measures to secure the safety of neighbours, their property,
protection of workers, passers-by, roads, and whatever is under and above the
ground including equipment and public service facilities and shall adhere to the law
on the Conservation of National Heritage (Royal Decree No. 6/80).
Article 108
The owner, contractor or consultancy office supervising the building shall strictly
adhere to the approved drawings, legal boundaries and shall sign the prescribed
undertaking form.
Article 109
The consultant responsible for design, the soil test consultant, supervising the
building and the building contractor, each in his respected field, are fully responsible
for the safety of the building for minimum period of 10 years starting from the date
of completing building works. The responsibility shall be in accordance with laws
in force in the Sultanate.
6|Page
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Introduction
This is the structural guidelines and regulations manual which should be followed
along with all the requirements of the adopted codes. This manual is considered
mandatory starting from 1/7/2022. In preparing the structural design of buildings
and structures, the following requirements must be fulfilled:
a. The structural design of buildings and structures
• should be prepared be a qualified structural engineer licensed.
• For specialized design such as post tensioned concrete, steel works structures,
precast structures and geotechnical engineering, the engineer who is involved
in such projects should be a qualified engineer licenced to practice the
profession and approved in the relevant field.
b. The engineer or contractor in charge should use only the approved and
licensed smart technical applications and computers programs in performing
the structural design and structural detailing works.
c. The buildings and structures and the materials used on them and all the
components they include, should meet all the standards and the requirements
that ensure their safety, stability and durability against the following factors:
• The most critical forces and loads, or their combinations, in respect of impact
on structures or buildings, including the combinations of forces and loads that
may lead to progressive collapse and also:
• Any other factors that may affect the buildings or structures including but not
limited to the steel corrosion and rust, concrete deterioration or residual
stresses that the buildings or structures may be subjected to.
The latest editions of the standards on the classifications and design of building, and
the design purposes and mechanism should be all followed in order to prevent the
occurrence of progressive and disproportionate collapse in all structures. Buildings
and structures should be designed in accordance with the latest editions of the
American, European, or British codes and specifications as specified in these
regulations. The structural design and geotechnical software used should be
approved by the Municipality. The specialized engineering contactors should be
registered and approved before practicing the profession. The drawings should be
clear, organized and detailed well to provide all information needed for construction.
7|Page
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter One
Structural Requirements for Application Submission
1 Introduction
Usually, almost all applications should have structural drawings as well as structural
documents including the new projects, modifications and additions. Few types of
applications may not need structural drawings such as the technical initial study and
the applications that have proposed modifications that does not affect the existing
approved structural design. It is required to keep updated and follow the memo
announced and the regulations that are regularly published by the Department
regarding the regulations and the associated documents thar are necessary to be
submitted in every application. Furthermore, Check the following required
documents before submission:
1.1 Buildings in General
Submit the structural drawings and the structural documents for all the buildings in
the plot including the proposed new ones, the modified ones as well as the additions.
The documents can include structural drawings, structural calculations, structural
reports, soil investigation reports and undertaking letters. For submitting structural
requirements and documents for buildings and structures in general, the submitted
details should cover all the buildings and also all service buildings, other small
structures and plot protections. Design and drawings for smaller structures on the
plot should be submitted as well.
• Check (proposed, existing or as built). Follow clause below for each category
• Match with arch. Drawings such as all dimensions, grids, loadings, framing
layouts, vertical element’s locations, projections, heights and number of floors
• Check complete structural drawings (including frames, sections, schedules,
plans and details.
• Check consultant logo and specialized designer logos are there in drawings
and the calculations. Submit main consultant letter explaining the submission.
• Submit all floor plans and at different heights. If size of floor is large divided
it into zones where each zone in a separate sheet for clarity.
• Include Materials details and codes
• Show loadings, foundations specifications and general sheets
• Submit Structural calculations (see also calculations and loading chapters)
8|Page
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• Check that calculations cover whole structures and buildings and all the
structural elements
9|Page
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• Structural calculations (see also loading, calculations and pt. design chapters)
1.5 Service Steel Structure
• Match with arch. (Tower type, size, height and shape)
• Check structural drawings (both foundations, pedestal and steel superstructure
frame)
• Check documents (safety letter from designer, letters from related authorities)
• Check calculations (foundation and the steel frame of the tower). It is steel
frame usually wind affect more. Add also dynamic loads and seismic loads.
• Check company logo with consultant logo is there in drawings
1.6 Solar Panel in Building
• Check (proposed, existing or as built)
• Match with arch. (Such as location, size, steel frame shape, dimensions, layout
and heights)
• Check structural drawings (add load 0.5 KN/m2 – 1 KN/m2 max on roof and
check design)
• Check calculations (check if the existing structure can take the extra loads)
• Check company logo with consultant logo is there in drawings
1.7 Sign Board on Roof
• Check (proposed, existing or as built)
• Match with arch. Drawings (such as location, size, steel frame shape,
dimensions and heights).
• Check structural drawings sign board steel frame design and calculations as
well as the bracing system. Take exact DL (static and dynamic if exists).
• Check documents (get letter initial approval from local Municipality), fill a
form from local Municipality and fill clients, company, consultant, and civil
aviation approval details for height of building and height of sign board.
• Letter from client no objection for sign board on the building
• Letter from consultant for safety of the design
• Check existing building for framing and extra loads on building.
• The sign board should be sitting on beams and columns not on slabs.
• Check calculations (for both the extra load on roof beams, columns and
footing and the design of the sign board steel frame)
• Check company logo with consultant logo is there in drawings
10 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
11 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• Accordingly, there should be a safety and stability report for the as built part
and for the whole building and should be prepared by specialized consultant.
• Then, see as built safety report requirements in chapter 10.2.
• The as built firstly, is subjected for approval from other authorities if required
and from the architectural department for applying design regulations. From
structural perspective, If the as built was small like adding a room for example
or relatively small area, then a letter could be enough for safety from the
consultant with small safety report with few typical materials tests. If the case
is large such as adding relatively large area or full floor or complete steel
workshop or major changes in large projects, then a comprehensive complete
safety report from a third-party special consultant must be submitted first for
study. If it was proven that the as built is safe and fulfilling all the
requirements regarding architectural technical regulations and other
requirements covering all code structural specifications for safety and stability
then go to the next step. (For safety report requirements for as built see the
respected chapter 10).
• The as built drawings along with the safety report and the structural
calculations are checked fully.
• The structural as built part will be matched with the architectural drawings
and particular care will be focused on that the as built is not affecting other
buildings foundations, neighbouring plots, adjacent buildings, public services,
roads services and similar aspects and cover all safety aspects
12 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter Two
Structural Drawings Requirements.
2.1 Introduction
The structural drawings should be complete, organized and clear. They should cover
all the buildings on the plot including all the structural systems. Minor structures and
protections should also be covered. The drawings should be in Arabic or English
writing or both. Preferably no colors are shown unless in some drawings such as
loadings plans or similar drawings that need to show illustrations or logos.
Highlight the point of interest by different hatching or clouding areas such as to show
which part is proposed and which art is approved and which part is modified or a
combination of all. Match all the structural drawings with each other and match the
structural drawing with the architectural drawings in all relevant aspects including
but not limited to size, dimensions, grid’s locations, height, projections, cutouts,
column’s locations, framing, duct’s location and sizes, stairs and lifts, levels both
existing and proposed, protections and retaining walls, elevations, the structural
system used and the materials shown in architectural drawings to be used in
construction. Control the scale to be suitable not too small or not too large also and
details should be aligned with nearby details so it is illustrated in professional
manner.
2.2 Drawings Layout
The drawings should include
• the main consultant and logo
• the sub consultant and logos if exists
• the specialized contractor and their logos such as precast company, post
tension system, steel work company or new approved building system.
• The owner, plot details as per the krooki, locations
• Drawings numbering and to show structural indication
• Date, designer, checker and other similar details
• Drawing title such as which floor or which presentation (ex. foundation plan)
• Revision if applicable and any details the main consultant wants to add.
13 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
14 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
2.1 There should be space for engineer and municipality stamp of size not less
than 8 x 25 cm, see figure (2.1) as a guideline.
2.2 The drawing should include three main parts: the details, enough space for
stamp and the details of the involved parties.
MM STAMP
Engineer
stamp
DETAILS Client
Plot
Consultants
Others
Figure (2.1)
The following figure (2.2) show only suggestion of how the structural drawings
looks. However, the consultant can arrange the details and the design layout in a
more suitable way. This shows only some points to be considered in the presentation.
2.5 Plot survey drawing
The site level supporting documents details:
• For site which is not flat, survey drawings should be submitted which should
include existing levels contours
• The site plan (discussed below) when there is a level difference at site, it
should include the existing levels and the proposed levels inside the plot as
well as the proposed levels of the roads which to be obtained from the related
departments
• The photos submitted should represent the slopes and levels of the plot and
they should be complete and covers all four sides.
• Some representative cross sections for the plot levels both the natural levels
as well as the proposed ones all should be submitted as required and more
sections are better
15 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Figure (2.2) some suggestion for structural drawing layout (only optional)
16 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
17 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• Number of floors for design foundation and columns and to find if soil report
is required and if seismic loads and winds is necessary?
• The function and use, for loadings calculations in design
• Floor height to design slenderness of columns
• Excavation depth can be get from arch. drawings shown in sections, adding
basements height and liquid tank depth and matching proposed levels and
existing levels in site plan.
• Proposed and existing levels on side plan
• The protection walls inside and around the plot
• Setback are important to check foundations not outside the plot
• Type of building concrete, steel, precast, composite, new system or others
• Material used for example steel roof is it sandwich panel or steel normal sheet
• Slope for tilted roof (rare cases)
• Internal walls in building if they are normal blocks, lightweight or partitions
because they affect loading in calculations and structural design
• Sunk slabs or false ceiling is proposed because they affect loading and
structural layout.
• No beams crossing inside middle of rooms and halls unless false ceiling is
used.
• Location of roof water tanks, swimming pool, plantation, landscaping loads if
exists and others for precise loadings on roof.
18 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
purlins, decking slab, trusses, bracings roof … etc. Provide enough sections
for the steel frames across grids in typical frames. In drawings submitted:
show typical details of baseplates and end connections, trusses connections,
other connections. Show in drawing the foundations, concrete and steel
specifications fully.
20 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter Three
Documents Required for Application
3.1 Introduction
Before apply for an application, check the required documents that need to be
submitted. If major components are not submitted, the application may be
immediately rejected. If some structural documents are not ready, show in the
application status and in the main consultant letter the reasons for that and when will
be submitted and that effect in the design and calculations. Make sure all the
documents are submitted as per the requirements.
Furthermore, not all the documents are listed here and therefore check always the
engineering common approved practices and the correct procedure to submit all the
documents that are necessary to make the structural design and the structural
calculations clear, safe, stable and can be constructed and ensure it follow all the
local and the international accepted design and construction standards. Make the
submission arranged well and organized. Moreover, make the submission
professional and well documented.
3.2 Main Submission Items
For all projects, the Main submission in general to be uploaded in the application
includes:
• Complete structural drawings if the application involve structural design and
drawings,
• letter from the consultant explaining the situation and the purpose of the
submission,
• photos for the site from all four sides which should be latest, clear,
representative and have date and time.
• structural calculations if the application involve structural design and
drawings
21 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
For Additions and modifications in addition to the previously listed documents add
the followings
• (Previously approved drawings)
• and in structural calculations check existing structure for additional loads.
• Add photos for the location where the parts are proposed to add or modify
23 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter Four
Design Codes for Buildings
4. Structural Codes
4.1 Structural Loadings
For loads, design in accordance with the latest editions of the American, European,
or British codes and specifications and any updates and amendments there. For
example: use
• In general, The American Code ASCE7 latest, or The British Code BS6399-
1: loadings for buildings or The European code: Eurocode1 Actions on
structures.
• For wind loads, The American Society of Civil Engineers ASCE7-5/
ASCE7-10/ ASCE7-16 or The British Code BS6399-2 or The European code:
Eurocode 1 Actions on structures.
• For seismic loads. Oman Seismic Design Code for buildings or The American
Code ASCE7 latest or The European code: Eurocode1: Actions on structures.
For post tensioned buildings use the American Code ACI latest.
4.3 Steel Structures Codes
Steel buildings and structures should be designed in accordance with the latest
editions of the American, European, or British standard codes and specifications as
follows:
• The American Institute of Steel Construction Specifications for Structural
Steel Buildings (AISC):
a. Specification for structural steel buildings (AISC 360).
24 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
25 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
26 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
27 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter Five
Loads on Buildings
5.1 Vertical Gravity Loads (DL & LL)
For vertical gravity LL and DL loads, design in accordance with the latest editions
of the American, European, or British codes and specifications. For example: use
• The American ASCE7 or
• The European code: Eurocode 1 Actions on structures or
• The British Code BS 6399-1 loadings for Buildings.
Vertical gravity loads (LL and DL) will be calculated in accordance with the
American codes, European code, or British code, taking into account the followings:
• Include all design loads including but not limited to Loadings in details (LL,
DL, SDL, walls, finishing, collateral loads, services, AC’s, pedestals,
hydrostatic loads, earth pressures, water tanks, machines, swimming pools,
landscaping loads, thermal loads, lateral loads (seismic and wind), dynamic
machine loads, …etc.) in details for each floor and for each part of the building
if applicable.
• Live load on floors including mezzanine floor, commercial areas, shops,
showrooms, and halls should not be less than 5 KN/m2.
• Live load on stores should be at least 5 KN/m2 and should be evaluated
accurately as there are heavy stores.
• In car park buildings and car parks floors in other buildings, live load should
be not less than 3 KN/m2, taking into consideration the loads of car movement
lanes, and also using the modal load pattern in design.
• Live load on final roof should not be less than 1.5 KN/m2
• Live load in post tensioned slabs and RCC flat slab designs should not be less
than 3 KN/m2 in all buildings. The designer can use the values specified in the
code such as 2 KN/m2 for residential use but in this case should consider the
modal loads pattern in the design and take into account the installation and
services in the ceiling.
• Minimum finishing loads on roof should be 2 KN/m2 but it can be higher
depending on the type of the finishing and the composition of the finishing
sections.
28 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• The minimum values for the walls and partitions loads of the slabs should be
determined in according with the following table
Type of partitions DL min. (KN/m2)
Normal wight partitions 5.5
Light weight partitions 4.5
Dry wall partitions 4
Façade cladding loads 1.5 KN/m
30 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter Five
Loads on Buildings
5.3 Wind Loads Design of Building
5.3.1 Introduction
Wind loads affect buildings and thus the structures should be designed safely to
withstand wind loads and their effects according to the code of practices. Muscat is
located on coastal area and it is affected highly by extreme cyclones that reach
category five. One cyclone on 2007 reached category five approached the
governorate where winds can exceed 280 KM/hr. Furthermore, the calculations of
the wind load should be accurate and consider these high winds. Apply wind loads
for all steel structures, RCC buildings of 4 floors and above and important concrete
structures irrespective of size, locations, height and type.
5.3.1 Wind Loads Codes
Codes of Practice:
• British BS6399 part 2 code wind loads
• Eurocode 1: Actions on Structures
• American ASCE7 code for wind loadings
5.3.2 Basic Wind Speed
Consider the map shown below for basic wind speed. The figures are based on the
mean annual average hourly wind speed in (m/s). The map does not take into
consideration the tropical cyclones that affect the Country which can reach category
five where wind speeds can exceed 280 Km/hr. Currently the Municipality is looking
for conducting a study to prepare a map to consider these extreme values for wind
speeds. Till the study is ready, consider now the figures presented on the map and
multiply them by 1.25 to get the basic annual hourly average wind speed.
BS code utilizes annual mean average hourly wind speed. For example, for Muscat
city take 30 x 1.25 = 38 m/s. then multiply the value 38 by the following table 5.3.1
for importance factor (I). ASCE7 utilize 3 – second gust wind speed. Follow the best
practice and code conversion guidelines of basic wind speed value between annual
mean hourly to 3 second gust. Usually, a minimum of 1.5 factor is used for
conversion. For example, before Appling the values of the importance factors, in
Muscat, the 3 second gust wind speed is 38 x 1.5 = 57 m/s.
31 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Table 5.3.1 the importance factor (I) for different buildings types and functions
Type of the structure The importance factor
(I)
Villas, car park, open small sheds, small workshops,
small stores, commercial or industrial building with
1.0
height less than 10 m buildings. Industrial small
warehouse
Medium size warehouse or workshops, height of
general building larger than 10 m but less than 15 m, 1.10
tourism projects such as located at beaches and hotels
Governmental projects, public large projects, heights
greater than 15 m, large area investments, buildings
include special uses such as factories, stores where
explosives, hazardous or toxic materials are stored,
telecommunication towers and power plants including
generation or stand alone. Civil defence, transportation
1.25
essential facilities and important similar
infrastructures. Shopping malls and markets,
stadiums, museums, educational facilities such as
colleges and schools, health institutes such as
hospitals. Projects that are on the beach or on high
hills and mountains which are exposed to high winds
Note:
• If abuilding type or its specification use is not listed in the table 5.3.1 above,
the closest use type can be assumed.
• The Municipality can increase the importance factor if required depending
on the nature of the submitted project.
5.3.3 Wind Exposure and Wind Calculation Factors
For calculating the winds loads, the code uses factors for terrain, height,
probabilities, structure type and exposure. Use the code requirements and apply
applicable and suitable factors exactly for the structure. For exposure, Muscat city
is located mainly in the coastal areas. Use exposure C as minimum exposure type
for areas far from the beach and areas surrounded by many buildings (obstacles) but
preferable use exposure D as default especially for important structures. For coastal
areas or areas close to the beach use exposure D.
32 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
A basic wind speed for Oman. (Annual hourly mean speeds) (m/s).
Credit: A.S, Al Nuaimi et al. (2014). A basic Wind Speed for Oman. The Journal of Engineering
Research.11(2), 64-78
33 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter Five
Loads on Buildings
5.4 Seismic Design of Building
5.4.1 Introduction
The consultant in all cases will be responsible to take into account all the loads
including the seismic loads on buildings with sufficient margin of safety accurately
so that the design and the performance ensure full safety and stability of the building
for the whole anticipated life time of the building as per the local and the
international codes. It is recommended to design all the buildings to resist seismic
forces for all types of projects irrespective of size, type, location or height to ensure
full safety of the project. However, it is necessary to apply seismic design for all
types of the projects that are listed in clause 5.4.3 below. The municipality has the
right to ask for seismic design if needed for any project at any time.
5.4.2 Seismic Design Codes
The codes that can be used in seismic design of buildings are the followings:
• Oman Code: Oman Seismic Design Code for Building (recommended)
• American code: ASCE7
• European code: Eurocode Volume 8
It is recommended to use one code to design buildings to be consistent. Oman
seismic code is recommended to be used in seismic design for building. Figure 5.4.1
shows one of Oman Seismic Hazard Maps. If building is to be design fully by the
American code, then for seismic design, ASCE7 should be used. In all cases
irrespective of the above permitted codes used, the calculated base shear and seismic
forces and actions should not be less than that calculated by the Oman seismic design
code for buildings. Alternatively, use ASCE code for seismic design with R value as
q in Oman seismic design code for buildings table 5.4.1 as follows:
Table 5.4.1 – Behavior Factors (q) for reinforced concrete structural types
Structural type q
Moment resisting frame system 3.5
Coupled structural wall system 3.5
34 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
and the importance factor (I) should be from Oman seismic code table 5.4.2.
Table 5.4.2 – Building Importance Factors ( I )
Occupancy (I)
Purpose of Occupancy of Building
Category
35 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Note: the buildings listed in category III should be increased to category II in case
the project is important or occupied by many users or represent a large investment
or is a full complex or the building is large in terms of size, complexity or number
of floors exceeds 3 floors or need increase due the nature of the project. The
Municipality may request to design for seismic and increase the importance factor
for any building at any time if it was found that this is more suitable.
5.4.3 Buildings with Seismic Design
Since the country is located in a seismic zone, it is recommended to design all types
of buildings for seismic design irrespective of size, type, location or height. The
following represents the cases where seismic design should be added.
• All governmental projects irrespective of size, type, location or height
• All private project essential to support the community irrespective of size,
type, location or height
• City infrastructures such as Power plants, grid electrical facilities,
telecommunication towers, water building and sewage treatment
infrastructures, transportations buildings and similar important projects.
• All the public buildings projects irrespective of size, type, location or height
including but not limited to the followings: educational institutions and
facilities (universities, colleges, schools), health institutions (hospitals), All
Worship buildings, halls, stadium, sports,
• Residential complexes such as large housing areas
• Commercial and residential commercial complexes
• Toursims complexes including hotels, tourism development
• Large investments both public or private irrespective of type, location or
height
• Building that are used by large number of users overthought they are one floor
• multi story buildings (Residential, commercial or residential commercial)
with more than three floors.
• All markets, shopping malls and assembly areas
• Industrial buildings medium size and above
• Villas with more than 4 floors
36 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Figure 5.4.1 Probabilistic Seismic Hazard Maps for the Sultanate of Oman
Credit: El-Hussain Issa, et al. (2012). Probabilistic Seismic Hazard Maps for the Sultanate of
Oman. Journal of the International Society for the Prevention and Mitigation of Natural
Hazards.64(1), 173-210
37 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
38 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
company who prepares soil report can give more accurate values for soil type
such as class A, B, C, D, E, F and it is included in the soil report.
• The building should have enough stiffness and rigidity for seismic resistance
and this can be done by adding sufficient shear walls and lift cores as well as
eccentricity in the buildings is minimized as possible in both directions.
Distribute all shear walls and lift cores in proper manner in both directions.
• Add beams as possible as can be. Make floor rigid enough with thick slabs.
• Minimize ducts and duct sizes and if required try to add stiffening beams or
drop caps or other suitable methods.
• Check if the slab is rigid or semi- rigid and reflect that in the calculations.
• Check diaphragm behaviour as per the code requirements and reflect that in
the analysis.
• Avoid opening adjacent to columns or even nearby columns.
• All lateral bracing systems such as shear walls and lift cores should be
continuous starting from foundation so no lateral bracing system is permitted
to be planted or floating on above floors.
• Try to minimize planted (floating columns) in number and in number of floors
as possible. Main columns should be continuous throughout the buildings. If
required make a reasonable percentage of columns only floating (planted).
• The planted columns or walls should be on designed transfer beams or transfer
slabs as per design and code requirements. The loads on the columns which
carry the transfer beams and slabs should be multiplied by 2.9 extra factor or
as per the code specifications.
• The width of the shear wall or lift core should not be less than 250 mm and
preferable at least 300 mm or as per the specified code above. wider section
could be needed depending on the design. At lift core and shear walls corners,
more steel should be added as per code requirements.
• The building should have sufficient lateral bracing systems where one lift core
could be not enough and thus more shear walls should be distributed in the
building at different locations in both directions.
• The steel at columns head should consider gravity loads, seismic loads, and
thermal loads (if applicable) added together.
• Spacing between stirrups (links) and diameters should be detailed for seismic
requirements on the drawings.
• Seismic mass is 25% live load, 100% mechanical live load and 100% of DL.
39 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter Six
The Structural Systems
6.1 Reinforced Concrete Structures
6.1.1 Reinforced Concrete Structures Codes
Codes of Practice:
Concrete Buildings and structures in general including the conventional
reinforced concrete structures and precast structures should be designed in
accordance with the latest editions of the American, European, or British codes
and specifications. For pre-stressed refer to the relevant chapter. American codes
such as ACI Code, and ASCE7 for loadings, British Standards including BS8110
and Eurocode including Eurocode 2 design of concrete structures. Some code
does not have seismic loads components, so if seismic loads are involved it is
recommended to use one code only (mixing codes not recommended) that have
those important components such as the American Code.
6.1.2 Reinforced Concrete Drawings
• Match the structural drawings fully with architectural including floors
dimensions, loadings, heights, RCC frame, load paths, the facade structural
system, walls, opening, projections and number of floors.
• Check the lateral bracing system. Control the drifts as per the code. lateral
bracing such as shear walls and lift core are useful. They should be adequate.
Lateral bracing system should be arranged to be distributed correctly in both
directions as required so that they provide full diaphragm and lateral load bath.
The centre of the rigidity should coincide with the centre of the mass so that
no torsional effects exists or torsional effects to be kept on steel works to very
small values. Check diaphragm behaviours for slabs in buildings and add
beams as much as can be. Avoids ducts and cut outs nearby or touching the
lateral bracing systems and columns. Reduce larger spans as possible. Try to
make planted columns and transfer beams and slabs to the minimum.
• Make design safer and not complicated for constructions. Do not use extreme
design alternatives. Some times more columns can be starting from
foundations throughout the whole buildings and not affecting the architectural
design so in many cases no need to propose too many planted columns and
thus making the structure more relaxed and safer and easier for construction.
40 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• Floors and roofs must be coordinated with the vertical framing actions to resist
all the forces both gravity forces, thermal forces if calculated and lateral
seismic and wind forces. The whole structure including the steel works and
the RCC part such as columns, slabs, pedestals and foundations should be
checked for integrity and safety.
• Submit load maps in colours and make detailed loadings for all proposed loads
and code requirements loads such as live loads, finishing, DLs, suspended
loads, walls load, services, water tanks loads, ACS pedestals, swimming pools
loads, landscaping loads … etc. and show these loads are they line loads or
distributed. Expect any additional future loads to be added. Add wind loads
for all types of the steel works structures irrespective of size, type, height, use
and location.
• Check all elements, frames drifts and deflections are within allowable limits.
• For long structures without expansion joints, exceeding 55 m, add thermal
loads in the analysis and the design. Separate the structure if possible and
make expansion joints not more than every 50 m for long structures.
• Try not to make very long spans if the architectural drawings permit which
means better to add columns to make the structure relaxed and safer by
reducing the spans as possible.
• Submit reinforced concrete drawings including but not limited to, all floors’
plans, details and sections, materials and loads, the RCC thicknesses and
reinforcement details, all schedules, all typical connections such connection
between main beams and columns, RCC cores and shear walls sections, and
all possible details that makes the drawings representation clear and adequate.
• When there are large openings, it is preferable to add beams, or stiffen
columns and check how the loads are transferred because such large opening
may make slab behave as one way instead of two-way.
• Floating columns and transfer beams should be avoided as possible as can be
unless it has been proven that there are no other alternatives.
• Check the supporting elements and load path and how the floor behaves
structurally.
• Add margin of safety for the calculated forces, stresses, moments and
deflections. Do not use the code upper limits especially if the project is new
and the design is under control. Consider the likelihood of extra loads are
added, future extension, site quality conditions, workmanship skills and
construction errors.
41 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
42 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• Check the total building drift and the inter-storey drift of each floor for the
values limited by the RCC listed codes and also by the relevant listed seismic
design codes limits and wind drift design limits.
• The lateral inter-storey drift may not exceed 10 mm. If it exceeds this limit
then special details should be provided for the installation of non-structural
elements and both drift limits and façade performance specification must be
available for application by the specialist contractor.
• The minimum vertical percent in columns is (1%) and (0.4%) in walls
• The maximum reinforcement limit in reinforced columns and walls should not
exceed (4%). However, it can reach (8%) in case of utilizing couplers.
• The minimum horizontal percent of reinforcement is (0.25%)
• If the vertical reinforcement ratio of columns and walls is greater than (1%),
the diameter of the stirrups should not be less than 10 mm and the maximum
spacing between stirrups should be followed as per the code and the
regulations.
• The minimum percentage of the concrete cube compressive strength is 30
N/mm2 for reinforced concrete structures.
• See the other relevant requirements mentioned in chapter seven and chapter
eight.
43 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter Six
The Structural Systems
6.2 Steel Work Design
6.2.1 Steel Work Designers
Steel Works companies should register in the Municipality and this details and the
procedure will be given soon and starting from a specified period, steel works
engineering companies are not allowed to practice until registering In the
Municipality and fulfilling the following requirements:
Main requirements
• The local steel works company should be a branch of international
respected steel works company of long records and high standards along
with the proper certificates. Local companies are allowed to practice
temporally (period to be announced soon). However, if a local steel works
company proved professional work, having excellent staff for design,
detailing, and fabrication, material sources are guaranteed, testing are done
frequently for materials and inspections, having local and international
updated certificates, possessing good reputation, with high quality designs
and construction procedure, then, the local steel works company will be
approved.
• Steel works company should fill the form. Form should be collected from
the Building Permit Department and resubmitted. Company’s details,
certificates, data, designers, and profile will be submitted for initial study
before receiving final approval.
• The registration is valid for one year and to be renewed.
• The company should have a professional staff and should have a local
registered office with specialized steel works engineer. The company
suppliers’ details for steel, accessories and all steel works hardware should
be submitted and later testing certificates should be submitted as well.
• The company and the steel works engineers will be interviewed and
examined
• The company has to perform presentation for the Municipality
44 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• Only the same steel works company mentioned in the drawings is allowed
to construct related project. Later, if owner wants to change the steel works
company, then further submission with the new company should be
submitted for approval. For supervision, the consultant should.
• Approval is subjected to passing all the requirements
Note:
Steel works design is not allowed temporarily (starting from a specified period) for
the following cases but later after companies’ classification and registration, some
of the following cases or most of them will be accepted. For the following cases:
• Villas
• Basements
• Substructures
• Public halls and worship areas (all uses)
• The municipality has the right to reject any steel works design proposal and
ask for conventional structural systems such as RCC frames.
45 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• The steel works structural drawings match with the architectural drawings in
areas, dimensions, projections, cut outs, frames, number of floors, including
all the loads.
• Safety letter from steel works design should be submitted along with main
above consultant letter.
Both the main consultant and the steel works designer should always keep updated
and follow the memos and the regulations that are regularly published by the
Municipality regarding all aspects of steel works design and system. The
municipality can reject steel works design if it does not follow the codes and the
regulations or if the steel works as a proposed system was not accepted for the
project.
46 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
47 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• Submit steel part including but not limited to base plates, frames at all
possible grids in both directions, all floors plans, bracing systems both vertical
and horizontal, end connections details and sections, typical connection
sections, materials and loads, roof details such as purlins, sandwich or decking
slabs, sections for decking slab with the RCC reinforcement and slab
thickness, all main beams and secondary beams locations and schedules, all
typical connections such connection between main beams and columns,
connection of main beams with secondary beams, in general all types beams
to beams connections and beam to columns connections, steel beams to RCC
beams or RCC cores, anchorage bolts inside pedestals, trusses typical
connections and plates, purlins and roof sheeting connections and all possible
details that makes the drawings representation clear and adequate.
• When there are large openings, it is preferable to add beams, or stiffen
columns and check how the loads are transferred because such large opening
may make slab behave as one way instead of two-way.
• Floating columns and transfer beams should be avoided as possible as can be
unless it has been proven that there are no other alternatives.
• Check the supporting elements and load path and how the floor behaves
structurally.
• Add margin of safety for the calculated forces, stresses, moments and
deflections. Do not use the code upper limits especially if the project is new
and the design is under control. Consider the likelihood of extra loads are
added, future extension, site quality conditions, workmanship skills and
construction errors.
• Make all the drawings clear, organized, complete and representative.
• Add in the drawings that the steel company logo
• Add all general sheets for foundations, steel work specifications and typical
design and construction specifications if needed.
• Design for two hours minimum fire rating and show clearly in all the structural
drawings highlighted that all steel works should be protected for at least two
hours fire rating. Columns can have encasement for fire protection.
• All welding work teams should be qualified as per the requirements specified
in AWS D1.1 M:2015 / BS EN ISO 9606-1, BS EN ISO 14732 and must hold
certificates accredited by independent inspection bodies as well.
• Also, special welding procedures should be compliment with the requirements
of AWS D1.1/ D1.1 M:2015/ BS EN ISO 15614
48 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
49 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
50 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• Submit steel work beams detailed design and other RCC beams found in the
steel work roof
• For trusses, submit design of all the members and connections
• Match in design the used loads in calculations, height of buildings and shape
with architecture. Submit all buildings design in the project.
• If there are extra loads on the building add them. Check if presents concentrate
loads or the project is affected by others loads such as earth pressure, liquids,
floods, loads transmitted be nearby structures, traffic or similar.
• The grade of steel as code specified such as G43 275N/mm2, G50 355N/mm2
and G55 460 N/mm2. For built up sections use grade G55 minimum. For hot
rolled sections G43 can be used but preferably G50 at least.
• Use sand blasting and Protect steel for durability and rusting with best
treatment with full epoxy system (epoxy primer with undercoat with top coat)
total should be at least 250 microns or more or as per client higher than that
requirement. Or provide a better performance protection.
• Apply fire rating not less than 2 hrs for all steel elements and connections
• Primary design loads include LL, DL, seismic and wind. Secondary loads
include other design loads such as mechanical equipment and devices both
static and dynamic. Both the primary and the secondary loads need to be
specified and indicated in the drawings.
• Steel structures loads should be applied according to the design loads listed.
In additions, loads need to be calculated in accordance with the latest edition
of the Metal Building Manufacturers Association (MBMA) Manual. See wind
loads requirement and steel structures system requirement in other chapters.
The loads stated below are the minimum design loads:
a. Roof DL: 0.25 KN/m2 (excluding self-weight)
b. Pitched roof live load: 0.6 KN/m2
c. Flat roof live load: 1.5 KN/m2
d. Other roof loads to which a roof is exposed:0.25 KN/m2
e. Wind loads see wind load chapter.
f. Construction loads and initial loads
g. Crance and winches loads and their effects. Also based on factory
specifications
h. Thermal loads +_ 25 C
51 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
i. For structures with flat decking slabs and horizontal roof , the loads should be
as per the code and see the gravity vertical loads requirements in the
regulation.
• Each steel structural element should be designed according to the stress
resulting from a combination of load as per the code requirements, taking into
account the maximum ratio of actual stress to allowable stress in the element
in accordance with the applicable code.
• Steel structures ultimate allowable deflection limits should be as per the code
used for each structural element and also as follows:
a. (L/360) for deflection of the primary horizontal elements caused only by live
loads (LL).
b. (L/240) for deflection of the primary horizontal elements caused only by DL
and LL
c. (H/100) for deflection of vertical elements (for buildings with metal cladding)
d. (H/200) for deflection of vertical elements of brickwork with a height greater
than 2 m.
• Loads resulting from construction works should be considered at all
construction stages
• All types of loads and load combinations acting on a structure resulting from
construction works should be taken into consideration.
• Wind- induced oscillations and vibrations should be mitigated to avoid
causing disturbance for its users or damage to its content. Some special
structures such as buildings with large spans or roof having large sports
activities or relatively slender structures may need special checks for such
effects.
• Steel structures should be protected against corrosion. Approved of high-
quality product should be applied such as galvanisation, protective paint,
protective concrete coating or similar protection systems. The most suitable
corrosion protection system should be chosen carefully.
• Other requirements than need to be considered in the design such as vibrations
and displacements, Expansion and shrinkage, Corrosion and durability,
Upwards arching and Sliding joints
52 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
53 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
the building may be connected to the lateral force resisting system with only
one point.
• All column splices should be capable of resisting a tensile force equal to the
largest factored vertical reaction from (DL + LL), DL, or (WL + LL) and
applied on the column at a single floor level located between that column
splice and the next column splice below.
• Unless the steel frame is fully continuous, all column should be carried
through at each beam-to-column connection.
• When precast concrete or any other solid construction systems are used, they
should be connected tightly at their own level by tying them directly to the
bearings or by bonding them together at the bearings level as specified by the
applicable code.
• If the requirements listed above were not fulfilled, then, each floor should be
checked to ensure that disproportionate collapses will not occur when
hypothetical removal of any element of the lateral force resisting systems, on
at a time, and also that the area of that part at risk of collapse does not exceed
(15%) of the area of that floor or roof or does not exceed 70 m2 whichever is
smaller, whether at the immediately adjacent upper or lower levels or at the
effected level.
• If the removal of any element of the lateral resisting system or hypothetical
removal of a column increase the risk of a collapse in larger areas which are
more than the upper limit, then this element or column should be designed as
a key element as specified by the used code. This key elements and ties should
be designed to resist an accidental load of 34KN/m2 due to accidental loads
such as explosion or vehicle collision for example.
54 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter Six
The Structural Systems
6.3 Post Tension Concrete Design
6.3.1 Post Tensioning Designers
Post tension companies should register in Municipality and this details and the
procedure will be given soon and starting from a specified period, post tensioned
engineering companies are not allowed to practice until registering In the
Municipality and fulfilling the following requirements:
Main requirements
• The local pt company should be a branch of international respected pt
company of long records and high standards along with the proper
certificates. New local companies are allowed to practice temporally
(period to be announced soon). However, if a local pt company proved
professional work, having excellent staff for design, detailing, and
fabrication, material sources are guaranteed, testing are done frequently for
materials and inspections, having local and international updated
certificates, possessing good reputation, with high quality designs and
construction procedure, then, the local pt company will be approved.
• pt company should fill the form. Form should be collected from the
Building Permit Department and resubmitted. Company’s details,
certificates, data, designers, and profile will be submitted for initial study
before receiving final approval.
• The registration is valid for one year and to be renewed.
• The company should have a professional staff and should have a local
registered office with specialized pt engineer. The company suppliers’
details for strands, anchorages and all PT hardware should be submitted
and later testing certificates should be submitted as well.
• The company and the pt engineers will be interviewed and examined
• The company has to perform presentation for the Municipality
• Only the same pt company mentioned in the drawings is allowed to
construct related project. Later, If owner wants to change the pt company,
55 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
then further submission with the new company should be submitted for
approval. For supervision, the consultant should.
• Approval is subjected to passing all the requirements
Note:
Post tensioned design is not allowed temporarily (starting from a given period) for
the following cases but later after companies’ classification and registration, all the
following case or most of them will be accepted. For the following cases:
• Villas (but allowed only for villa that have most areas and rooms in them are
relatively very large spans or its structural system is very complicated which
are rare cases)
• Foundations
• Basements (except the upper basement which should be above ground)
• Substructures
• Public halls (all uses), industrial areas and all worship buildings.
• Buildings with Small to medium spans where other structural system works
• The municipality has the right to reject any pt design and ask for conventional
structural systems such as RCC frames or flat slabs.
56 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Both the main consultant and the pt designer should always keep updated and follow
the memos and the regulations that are regularly published by the Municipality
regarding all aspects of post tensioning design and system. The municipality can
reject post tension design if it does not follow the codes and the regulations or if the
post tension as a proposed system was not accepted for the project.
57 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
foundations throughout the whole buildings and not affecting the architectural
design so in many cases no need to propose too many planted columns and
thus making the structure more relaxed and safer and easier for construction.
• Pt slabs must be coordinated with the vertical framing actions to resist all the
forces both gravity forces, thermal forces if calculated and lateral seismic and
wind forces.
• Submit load maps in colours and make detailed loadings for all loads such as
live loads, finishing, walls load, services, water tanks loads, ACS pedestals,
swimming pools loads, landscaping loads … etc. and show these loads are
they line loads or distributed. Expect any additional future loads to be added.
• Try not to make very long spans if the architectural drawings permit which
means better to add columns to make the structure relaxed and safer by
reducing the spans as possible.
• Flat pt plate with columns is not preferable. Instead, better to add drop caps,
band beams, beams either RCC or PT in order to make the structure more rigid
and stable and work conveniently with vertical lateral bracing systems
• When there are large openings, it is preferable to add beams, or stiffen
columns by drop caps and check how the loads are transferred because such
large opening may make slab behave as one way instead of two-way.
• Floating columns and transfer beams should be avoided as possible as can be
unless it has been proven that there are no other alternatives.
• Check the supporting elements and load path and how the floor behaves
structurally.
• Add margin of safety for the calculated forces, stresses, and deflections. Do
not use the code upper limits especially if the project is new and the design is
under control. Consider the likelihood of extra loads are added, future
extension, site quality conditions, workmanship skills and construction errors.
• There should be a separate drawing that show the theoretical (software
generated) elongations of strands. The accepted deviation between the
theoretical elongation and site recorded elongations should be within +_ 10%
and should be inspected by the specialist engineer and the consultant.
• The maximum allowable differences between the location and the height of
the tendon are +_5 mm in the vertical direction and +_ 100 mm in the
horizontal direction. But is recommended to minimize the differences and use
exact values as specified in the drawings and follow the adopted code.
58 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
59 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• Deflections all short term, incremental and long term. Short and incremental
limits are L/480 or 20 mm max, and long-term L/240 but long term cannot be
too high for long span also and the preferable max long term is limit 30 mm.
satisfy all deflections limits. Pre-camber is only used for extreme cases as last
option to control cracks and it is subjected to municipality approval and only
for rare cases and if proposed need to be as per the code and maximum 25 mm
for very long spans. Pre-camper in the PT slabs if accepted and used, then the
designer should give a clear justification in accordance with the adopted code.
• P/A should be submitted for both directions. The lowest is 0.9 but preferable
to exceeds this low limit to 1 or more.
• Cables in both x and Y directions.
• Crack widths should be shown on calculations in both direction at different
stages.
• If the design graphics are not clear and contains overlap details due to large
size of the slab, then one full floor and enlarged parts in every floor need to
be submitted so an engineer can review clearly.
• Submit reactions for all columns for every floor and show if they are working
or ultimate.
• Submit punching shear plan and related calculations checks. Submit punching
shear plan and stress ratios and the design for that by an approved software or
spread sheets for every column Flat plate better to have drop caps with
punching shear reinforcement or at least thicker plate with punching shear
reinforcement for medium stresses.
• Submit PT beams detailed design and other RCC beams found in the PT roof
• Submit the full design status check plan
• For every floor for every check in the calculations write note. For example the
calculation shows maximum deflections in the contour 20 mm. write what is
the maximum limit as per the code and whether satisfied or not.
• Show reinforcement requirements plans for both directions for all top and
bottom areas. The steel provided on the drawings should include gravity loads,
post tensioning, lateral loads and thermal loads.
• Use only laboratory certified tensile strands tests of high approved quality
with nominal tensile strength of (1860 MPa)
• The wall thickness of metal ducts should not be less than (0.4 mm). Both
galvanized flat or corrugated metal ducts can be used.
60 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
61 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
ask for top mesh whenever the project demand that. Additional top mesh
should be provided in the spans and over the beams and columns to control
moments, shear, thermal stresses, seismic effects and to assist in resisting
punching shear at columns. The minimum diameter of the basic top mesh is
10 mm bar and maximum spacing 250 mm. The thermal load’ reinforcement
will add to the top mesh and can be separated by half in top and bottom.
• Show all cables in both directions X and Y. the spacing between the cables
should not exceeds 1.5 m. It is preferable to make alternatives stressing where
live ends stressed from both sides. For cables exceeds 30 m make stressing
from both sides. It is recommended to limit maximum length of the cables not
more than 50 m.
• Add pour strips around RCC in basement floor. Divide long buildings to many
pour strips in all directions and it is preferable to add pour strips every not
more than 30 m. design pour strips and their locations should be in the first
third or quarter of the span from the support.
• Show in drawings the PT company logo, materials (concrete strength,
stressing details, strands properties, … etc
• Show the number of the cables as wells as the cable profile shape and values.
• Additional steel in top and bottom of the pt slab must be provided as per the
calculations.
• For all the code regulations for design, sections and detailing.
• Top steel should be provided on supporting beams and as U bars around all
external beams and slabs supports. Top steel should be provided on column
heads and around shear walls and lift core as per the calculations and the code
requirements.
• Show all the possible and necessary sections for example sections for
punching shears reinforcement, anchorage reinforcements, beams profiles,
sections on pt beams both at mid span and support, sections for slab
reinforcements, section for seismic connections, some reinforcement detailing
sections and other structural important sections.
• Show all the materials properties and the posttensioning specifications for the
project.
• The use of curved tendons should be avoided as much as possible. If required,
it is subjected to the Municipality approval, and the tendons curving should
not exceed 1:12 and anchorage should be used in additions to the top and or
the bottom steel mesh.
62 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• Tendons should not be stopped inside the slab without supports at the end such
as walls or columns, drop or hidden beams or any other special details.
• Jacking force should not exceed (80%) of the breaking loads and should be
compliant with the design code.
• A minimum amount of reinforcing steel bars must be provided over the
supports to ensure many requirements such as mitigation of any cracks that
could occur in these places.
• The reinforcement bars should be placed along the edges of all slabs in all
directions. And this should include U-bars with longitudinal both bars top and
bottom as shown below
• All columns should be checked for punching shear. To meet all the
requirements of the ductility for the seismic resistance design, all the columns
should be provided with a minimum punching shear reinforcement.
• Steel bars should be used to resist stress concentration at cables ends. These
reinforcements can be achieved by using spiral steel reinforcement, or any
other approved detailing of the steel reinforcement may be used.
• The bottom steel at columns and support locations should not less than (30%)
of the top steel used at this same location. More percentage is recommended
63 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter Six
The Structural Systems
6.4 Load Bearing Buildings
6.4.1 Introduction
Load bearing structures are structures that their roof loads are transmitted to the
foundations though the walls and strip foundations. They can be used when the
buildings are relatively small, they have small spans, the architectural design wall
division is the same in all the floors and for limited number of floors. Generally, they
are weaker in the performance compared to the reinforced concrete structures. They
have low capacity to resist lateral loads such as seismic loads, wind loads, and floods.
However, for light small structures, if conventional RCC not to be used, they can be
used for small size structures provided that all the requirements for masonry
structures as per the adopted code have been considered as well as taking into
account the quality of work at site and workmanship skills.
6.4.2 Load Bearing foundations
Load bearing has to have strip foundations along all the structural walls that carry
the loads from the roofs. The walls have to be fully through all floors till foundations
where no walls can be starting from the roof. No floating walls are permitted. The
load bearing walls should be fully solid block work not hollow of good strength
usually 10 – 12 N/mm2 or more. The load bearing foundations should be designed
for the suitable soil bearing capacity. The foundations excavation depth should be
determined as per the adopted code and the soil parameters. In all cases the minimum
allowable excavation for load baring foundation is 1.2 m where deeper excavation
might be required but the recommended depth should not be less than 1.5 m.
6.4.3 Load Bearing Structural Layout
• Use load bearing system for light structures such as small to medium spans,
less no of floors, light loads, the upper floor architectural divisions is same as
the blow floor.
• Use solid block work to carry the loads
• Opening need to be small as possible and the maximum openings size in the
walls should not exceed 2 – 2.5 m such as large internal doors or arches and
these openings should be in limited locations.
64 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• Add beams at plinth location and roof along the whole walls for tying the
structure and to add more stiffness.
• Add columns at least 20 x 25 cm, 4Y16 vertical bars, stirrups Y 8@200 c/c.
at all the corners within the buildings to assist in resisting lateral loads such
as seismic loads.
• Add enough lintel around all the opening both top and bottom and should be
stiff capable of transmit the loads throughout the wall.
• The load bearing is a choice for buildings with small to medium spans say up
to 5 m and the roof is a two-way direction slab not one way.
• Projections and cantilever should be not used with loads bearing structures as
possible as can be,
• Load bearing structures is allowed up to two floors only for new structures.
For additional third pent house floor, there should be approval from the
Municipality before proposing that floor.
• Submit design calculations for the load bearing structure including foundation
design, masonry design and all other structural members.
• Specify in drawings block work type, materials, SBC, depth of foundations
and show all the plans and add sections throughout full buildings both inside
and outside the buildings. Add sections as much as can be to give enough
details.
• Loads bearing foundations should be all inside the plot. If there are neighbour
load bearing foundations then tie these foundations be tie beams every 5.5 m.
• To avoid differential settlements, it is not recommended to mix strip load
bearing foundations with other part of buildings which have different types of
buildings such as isolated and raft foundations.
65 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter Seven
Structural Calculations Requirements
7.1 Documentation of the Structural Calculations
The structural calculations book should be documented, organized, complete and
clear. The calculations should be documented very well. One example as follows:
• In the first cover sheet show clearly: the land location as per the krooki, the
project name, main consultant name and logo, sub consultants names and
logos if involved in the design and the designer name and logo (designer can
be a specialized company) if involved in the design , building type, reference
to which building in the plot, show if the whole building or part of it, if for the
whole building or a particular floor, to show if (new, modifications, additions
, or mix) , other requirements such as strengthening or particular special
design , date …etc and any particular information the consultant wants to add.
• In the later pages, the following should be included: the designers, the
checkers, date and signatures for involved designers and the main submitting
consultant.
• along with responsibility letters as separate files uploaded in the application
from the main consultant as well as the sub consultant or designer if involved
showing that the submitted calculations are matching with the drawings
completely and design was carried out as per the local and international code
considering all structural elements for safety, stability, long term effects,
structural effects as well as environmental effects, integrity with other
structural elements in the building are met, effect of the proposed structure or
loads on existing structures are considered, protection for building, protection
for neighbor or plots are all considered….etc.
66 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
67 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• The outputs of some software are not clear and difficult to review and, in this
case, submit with that other meaningful output and snapshot from the
software.
68 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
design aspects required by the code such as thermal effects, long term
deflections, vibrations, fatigue, dynamic loads, thermal, … must be submitted.
• Design of beams should include moments, shear, torsions, and also deflection.
Special cases such as for design for long beams, deep beams, spandrel beams
or two-way beams design such as waffle slab and rib beams should be
comprehensive.
• Design of columns should be clear to reflect braced or un-braced, pin or fixed,
axially loaded or with uni-axial or biaxial, short or long …etc. Some types
such as floating (planted) columns, terminated columns, change in column
orientations should be addressed carefully as per code.
• Transfer beams and slabs should be designed carefully.
• Foundations should show type, settlements, modulus of sub-grade reaction,
assumptions, pressures, moments, shear, may be punching shear, etc
• Design of retaining wall of all possible cross sections and types
• Design of shoring, Post tension slabs, precast, steel work, pile caps, composite
elements should be submitted (conditional permit can be issued if required
when a specialized design consultant is not appointed yet and these will be
submitted later for Municipality approvals).
• Design of base plates, connections, composite sections, bracings for steel
structures must be submitted.
• Add lateral loads such as seismic and wind whenever is required. See loading
chapter. Check design stability for the building.
• Design of building and protection systems such as shoring. If shoring design
is not available, later to be submitted for approval before construction.
• Design of all the structural elements should be submitted fully in details
• If the plot is affected by floods or sea waves, especially the ones close to wadis
and beaches ensure design a safe protection.
• Consider durability in design, high humidity and high temperature which can
reach over 50 C. Pay attention to these requirements as per the code such as
the cover to the main reinforcement.
• Consider fire resistance in the design with a minimum of two hrs. or check the
civil defense requirements if higher rating is required.
• Design number of floors as per the architectural requirements and consider if
future addition is required.
69 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• For additions and modifications on existing structures, check the extra loads
coming on the existing structure so check all footings, columns, beams, slabs
or other related existing members. If a new building affects nearby building
check the extra loads and ensure safety of both buildings or both structures.
• If the existing structure cannot withstand proposed additions or modifications,
find solutions to reduce loads or propose strengthening for the existing
structure if applicable.
• Model the structures as 3D with all loads (lateral and gravity loads). Show in
the calculation’s nodes and members label for emery floor in order to review
them and refer to their output. 2D modes such as portal for steel frames can
be used provided that the stability is checked correctly. For post tension design
each floor can be modeled separately.
• Check all the combinations for all loads as per the code with all possible types
and directions. If the software gives automatic combinations, show a note in
the calculations in the first page a reference for few mostly used ones such as
the service gravity loads, the ultimate gravity loads, the envelope ultimate
combinations for quick reference while checking.
• When designing and calculating sections, steel, stresses and deflections, it is
a good practice to consider enough margin of safety not taking exact results
only to account for many factors such as for errors in calculations,
underestimated loads, materials uncertainty, local labor qualifications and
experience, construction methodology, severe environmental effects, floods,
high winds and dynamic loads.
• Consider punching shear extremely, make lower one-way shear and punching
shear stresses as much as can be and make maximum shear stress ratio after
considering all loads, safety and stability factors, and load combinations to be
not more than 0.8. lower ratios is safer and better.
• Check deflections (short term minimum of L/480 or 20 mm, incremental
minimum of L/480 or 20 mm, long term minimum of L/240 or 30 mm). For
the combination of these three cases refer to the code or get from the provided
circulations. It is not accepted to design new building and reach the upper limit
of the deflections so make margin of safety.
• For flat slabs and raft foundations and flat plates when using software, submit
snapshots for moments in both directions, steel designs where this can be by
70 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
showing steel in the plans or assigning a mesh and the extra steel is shown in
the contour for both directions. Show also punching shear plans stress ratio.
Show also defections contours for short, incremental and long term. For raft,
show plan contour for soil bearing capacity, settlements and punching.
• Add stiffened modifiers to structural members as per the code requirements
• Model the buildings projections, cutouts, structural framing, dimensions, and
loadings as per the project.
71 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter Eight
Design Detailing Requirements
8.1 Introduction
The structural details in the drawings should be clear and comprehensive so that for
construction the details are clear. Sections thicknesses and reinforcements amounts
should be as per the design and within the code limits. Make design detailing
professional according the best practices. Structural plans, reinforcement schedules
and steel sections details should be well organized, coordinated and clear.
8.2 Durability Requirements
Durability requirements as per the code of practice should be met. Some
requirements include the cover to the main reinforcement. The cover to the
reinforcement should be shown in the drawings for all the structural elements
including foundations, columns, beams and slabs. The structural members should be
checked if it is fully exposed to the environment or partially to decide the cover
requirements. Muscat Governorate is affected by relatively high humidity and high
temperature and a large area is coastal area. This means a large part of the plots are
affected by severe climate conditions and thus need to be considered in the design
for the cover thickness and other design related parameters. The minimum concrete
cube crushing strength should not be less than 30 N/mm2 for villas and 40N/mm2 for
other projects. Grade 35 N/mm2 can be accepted for small size projects other than
villas but 40 N/mm2 Is recommended as a minimum value. More strength is better.
8.3 Fire Rating
Recheck the code specifications for fire rating in structural design of buildings such
as the minimum thicknesses of the structural members and similar specifications for
concrete structures and for steel work structures, all steels work should be covered
by approved high quality fire protection product. The minimum design fire rating is
two hours. If the project requires civil defense approval from the authority, then
check the required number of hours of fire rating if it exceeds the two hours then
design for that value.
Points to be considered
• All buildings should be designed to withstand fire for the periods specified in
the used code. However, fire rating should be not less than two hours.
72 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• Load bearing structures should have solid block work and large opening is not
permissible. Preferable maximum opening is 2 m.
8.5 Slab Cutout and Ducts
Large cut outs or ducts should be supported by beams on columns, small cut outs
can be on slabs but should not be in critical stress areas and steel sections should be
provided for that to show extra steel around the cut out or alternatively, the
reinforcement can be shown on the plans. No cutout or duct around columns or shear
walls so if that present, use drop caps or preferable beams to transfer the loads.
8.6 Reinforcement Detailing
For all the structural members check the code requirements for minimum and
maximum steel percentage and the reinforcement presentation. The spacing is
calculated center to center (c/c). The following are some main requirements:
• For all types of slabs, the minimum bar diameter of steel is Y10 and the
maximum spacing of reinforcement is 200 mm. If the basic mesh is at 200
mm spacing then the extra steel can be at larger spacing to resists the forces
such as the moments and the punching shear provided that the extra steel is in
the same layer as the basic mesh not another layer.
• For all types of foundations, the minimum bar diameter of steel is Y12 and
the maximum spacing of reinforcement in is 200 mm. If the basic mesh is at
200 mm spacing then the extra steel can be at larger spacing to resists the
forces such as the moments and the punching shear provided that the extra
steel is in the same layer as the basic mesh not another layer.
• For beams and columns maximum spacing of longitudinal bars depends on
the code and related to its requirements but should not be more than 150 mm.
• For structural walls, shear walls, and retaining walls, minimum main vertical
steel is Y12 but higher diameter steel can be required depending on the design.
and the reinforcement spacing for vertical and horizontal bars in both faces is
limited maximum to 200 mm.
• For piles, the vehicle steel spacing is limited to 200 mm.
• The minimum diameter of stirrups or links steel in beams and columns should
be limited to Y8 and spacing is limited to 200 mm max. but check seismic
requirements for steel confinement at joints such as beam to column
connection where links spacing can be limited to 100 mm max or less.
74 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• For wide beams and columns, there should be sufficient number of links to
bind the main bars as per the code specifications. The minimum stirrups
diameter is 8 mm.
• The minimum punching shear reinforcement diameter is 8 mm for slabs and
12 mm for foundations and higher diameters may be required depending on
the design.
• Face bars (side bars) should be provided for beams equal or greater than 700
mm in depth.
• For usual beams with 200 mm wide, provide not than two bars top in each
layer and this is for vibrator to work properly during casting. But the number
of the bottom bars can be more than two in a layer. In all cases minimum
spacing between reinforcement should be satisfied as per the code.
• For sections of (wide beams, large columns and hidden beams) show in the
schedule number of legs or stirrups to be provide and sections should be
shown for clarity.
• Minimum size of longitudinal steel bars in beams and columns is 14 mm.
• Top steel should be added as per design for columns in flat slabs, for shear
walls and lift cores, above beams for negative moments and above periphery
beams.
• Solid slabs which are equal to 200 mm or more should have top mesh also or
T/B steel.
8.7 Substructures Requirements
For foundation and substructure, the type of the cement used should be addressed to
deal with substances such as sulphate and chloride. Soil investigation report can give
guidelines on the type of the cement used such as OPC or SRC. Details such as
water/cement ratios and the minimum and maximum cement content on concrete
should be shown on drawings as guideline. Water proof protection for foundation
and substructures is required and the most suitable method and protect should be
illustrated on the drawings. Make sure no foundations are overlapping with other
existing foundations and no foundations are outside the plot. Check the requirements
of the underground water table.
75 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
76 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
77 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter Nine
Foundations, Excavations and Soil Investigation Reports
78 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
soil report which should be new or at least prepared not long before the submission.
If the plot is exposed to high fluctuation in water tables, or its soil strata or natural
topography has been changed, then the soil details and parameters could have been
changed and thus another soil investigation report might be needed. Soil report for
neighbouring plots is not permitted as well as not valid for soil report conducted on
plot and then the plot size, topography or its previous natural landscaping have been
changed. Soil investigation report need to be submitted in clause 9.1.4 below which
cover new project and even projects that have modifications or additions. If there is
a proposal for soil enhancement for the building then this enhancement should be
detailed in the soil report and should be approved by specialized soil company. The
soil improvement details and related detailed sections should be shown on the
structural drawings. Moreover, if required soil improvement, when doing
compaction of soil while enhancing the soil, compaction tests should be carried out
for all soil layers and later plate load test should be conducted. The results of these
tests should be submitted to the Municipality for approval before constructing
foundations. For the projects that do not need soil report, while excavation, if water
table encountered, or soil types and specifications found to be different than the
assumed values, then construction work should stop and there should be technical
evaluation, design change of foundations and consequently another approval is
necessary from the Municipality as structural modifications and in these cases a soil
report could be requested depending of the situation.
9.1.3 Content of Soil investigation Report
Experienced and professional geotechnical companies submit professional report
that include most of the required details and specifications. Soil investigation report
should be carried out in accordance with the latest editions of the adopted codes,
regulations and standards. The soil investigation report should be based on the
location of the structure, geological features, topography, previous plot use, the
number of floors, the floors below the grounds such as the number of the basements,
the shape of the structure and other required parameters as per the adopted codes
requirements.
In additions to that, soil investigation reports should in all cases include the
followings:
• The company details and logos
• The owner, plot, and locations details
79 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
80 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• Grading and details for soil enhancement if required and for the backfilling
soil
• If soil encountered issues, it is recommended to highlight some suggested
solutions.
• All the tests, drilling sections and laboratory results
• Materials recommendations and concrete
• The European Code (Eurocode 7) refer to the minimum number of boreholes.
Provided that there is a homogeneity between the soil samples collected from
the boreholes. more boreholes are better to reflect the site. It is recommended
for important structures, public structures or multistorey buildings which are
more than 5 floors to have a minimum of three boreholes and this number
increases when the area of the plot increases and the site features and details
demand that. The code of practice guidance recommendation should be
followed regarding these requirements and the geotechnical contractor should
provide sufficient boreholes to provide full knowledge about the site
conditions, soil strata, the challenges and the soil report recommendations.
• The minimum borehole depth should extend below the level of the pile and
the zone of the influence of proposed foundations in accordance with the
European Code (Eurocode 7) as follows:
a. The Drilling should be carried out at a greater depth at some locations to
investigate the possible groundwater issues and settlements conditions
according to the recommendations of the experienced specialists in the field.
b. For isolated and strip foundations the depth of the bore holes should exceed
the anticipated foundation level by at least 3 times the width of the foundation.
c. In all cases, the depth of the boreholes should not be less than 8 m below the
proposed level of foundations.
d. In some case, deeper boreholes need to be considered below the strata level
of the ground when the soil is not suitable for the foundations of the buildings
such as compressive soils, weak soils and expansive soils.
e. For raft foundations, the depth of the boreholes should be at least equal to or
greater than the width of the foundation, unless a bedrock is encountered
within this depth.
81 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
82 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
83 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
The soil bearing capacity is evaluated from soil report. In the absence of soil report,
the consultant is responsible in estimating the soil specifications and the soil bearing
capacity to be used in the design and in this case:
• For plots with good soil, the evaluated soil bearing capacity should not be
more than 150 KN/m2
• For plots within 1 km from the beach the maximum bearing capacity should
not exceed a value between 100 - 120 KN/m2
• and in all cases the design consultant should be responsible in estimating the
soil bearing capacity of the project.
When there is filling on foundation, depending on the soil bearing capacity whether
it is gross or net, the filling loads should be added to the design of the foundations.
84 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
The forces exerted by the building on the soil beneath should be considered on the
foundations and the retaining walls of the building itself as well as the nearby
structural elements such as other buildings foundations or protections such as
retaining walls.
85 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
86 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• There are adjacent plots with close existing buildings especially if these
buildings’ foundations are higher than the proposed foundations and as a
result leading to affecting stability of the existing nearby buildings.
• There are basements or deep structures.
• The plot has large level difference and required to propose very deep cutting
and filling works which are required by the project.
Shoring can be temporary and permanent. Usually if there are deep excavation or
proposing two basements and more, or a in case proposing deep excavation with
adjacent buildings, then, a permanent shoring may be needed. In all cases a
specialized geotechnical company can decide the type of the shoring and design it.
Shoring is very important because it protect the plot and the surrounding public and
private plots, buildings, and services. Permanent shoring consists of many types such
as secant piles and temporary shoring such as soldier sheet piles. The shoring should
be inside the plot. In all cases, no shoring is permitted outside the plot and therefore
when designing the project evaluate the situation if required shoring then allow
setback for the shoring inside the plot and this need to be reflecting in both the
architectural and the structural drawings.
Depending on the depth of excavation, soil type, and surrounding buildings, services
or roads, usually if there are three basement or more or if there are two basements or
more with adjacent multistorey buildings which have no basements, most likely a
permanent shoring is required but this also is decided by specialized geotechnical
company. Shoring design if required need to be submitted to be approved by the
Municipality before construction. To assist in facilitating and accelerate the
drawings approval, the consultant can submit the application of the project for
approval and get a conditional building permit to submit shoring design later for
approval by additional application and this has to be before construction.
87 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter Ten
Additions, As Built and Modifications
10.1 Additions on Existing Buildings
When adding structures on existing structures such as proposing additional floors or
adding a structure beside a structure and connecting with it, then, all loads need to
checked with all combinations as per the adopted code. Furthermore, the structural
safety, stability and integrity for both the structures (the existing and the proposed)
need to be checked fully. In this case, the existing structure should be checked for
the additional loads and thus its foundations, columns, slabs, beams, … etc all has
to be analysed with all loads as per the adopted code and to verify that the existing
building framing structural sections, their reinforcement is meet the requirements
and safe for all the forces and the stresses such as the moments, shear, axial loads,
torsions and deflections.
The structural calculations for the model should include all the existing and the
proposed part since they are connected. If the new structure is not connected to it its
adjacent building, then it will be analysed separately but its effect on the adjacent
existing buildings should be checked such as if the existing building has basement
and the proposed nearby building has no basement and therefore there is lateral load
form the proposed foundations transferred to the existing basement. If there is
connection between the existing and the proposed structure, then connections details
have to be shown such as using epoxy chemicals or other suitable system. The epoxy
used has to be approved. In drawings, highlight by hatching or clouding the existing
and the proposed parts separately to differentiate them. When connecting structures
either vertically or horizontal they should act as one unit and thus has to be analysed
to perform well and design check for all elements need to be verified and sufficient.
The existing structure after analysis may be not able to resist the additional loads
due to proposal and thus there could be solutions such as reducing the loads by using
light weight blocks or Appling strengthening to the structural elements of the
existing structure. If the additions involve complicated methodology to apply at site
with certain procedure to be followed and considering special care, then, these
details have to be presented in the structural drawings in plans with all necessary
structural sections and structural details and the procedure need to specified step by
step in the drawings clearly.
88 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
89 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
90 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
of the floor and the building’s parts touching such as below and around for
instance as extra loads are coming on existing roofs, columns and foundations.
• Tests details, results, location of tests, types of tests. May be core tests for
concrete is needed, ultrasonic tests, rust tests, deflections measurements or
others tests depends.
• Structural calculations as per the requirements
• Results, is the constructed part as built is safe and stable? any further tests
need to be carried out, if there is need for repairs, enhancement or demolition
should be all specified. Others important notes found can be added and will
be useful.
• Recommendations and conclusions
• Appendices
91 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• Tests can be done by more than one testing company if a specific test is
required and the appointed testing laboratory company does not have that
facility.
92 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
• If there are covered structures like as built foundations, then to tests there
might be a need to excavate or do suitable methods to reach some of these
foundations and do the required tests.
• Some tests give more components. For example, core tests for concrete
may give strength, cover, density of concrete, water content and similar
results where every component leads to some results. Tests are different
for soil capacity, concrete, steel, or any other materials.
2. As built drawings if available
for the as built structure, it could be fully as built without drawings or it could be
partially as built such as some modifications and additions have been added. The
following drawings as built need to be submitted for checking:
• as built architectural drawings need to be prepared as per site conditions
and submitted for checking as per the regulations. For as built
modifications and additions, existing drawings could be useful to prepare
such drawings.
• For structural as built drawings: there could be available as built drawings
with the consultant or the contractor which could be useful and should be
coordinated with site condition and utilized for information only during
preparing the report and should also be checked with the tests results.
Otherwise, if there are no structural details or drawings then depending on
the type of the structure, for example a steel work shed structural elements
can be known like H beams sizes and thicknesses, columns sizes and
thicknesses, bracings, base plates and bolts, end connections … etc. are
clear at site and In this case some can be shown in drawings as possible
as can be. For concrete structures, since steel is inside at least structural
concrete dimensions such as slabs thicknesses, beams, columns cab be
measured and sketches in drawings to give an idea. The few tested
structural elements by ultrasonic will give an idea about the steel.
Concrete strength grade from ready mix if available can give some ideas.
And the consultant needs to decide how to reach a conclusion on the safety
of the as built structure based on available details and specifications. More
detailed drawings will be very helpful but this subjected to available
details.
93 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
3. Structural calculations
Not only tests find out the status of the existing as built structures but calculations
also give the results. Structural calculations with code loadings are required. For
example, if there is an existing building consisting of many floors with detailed
available drawings and a floor as built constructed on top of it. This floor exerts extra
stresses on the columns and foundations. Therefore, it needs to carry out structural
analysis and design for the whole structure to determine the structural safety.
Moreover, Calculations are also carried for as built part. For example, there is a steel
work store as built, after determining the sizes of the sections of the structural
members since they are usually clear, structural analysis can be performed to check
the safety.
For concrete structures with as built structural drawings, calculations can be done to
verify the safety of the building. The only issue is for concrete as built structure
without details, where concrete sections and sizes can be determined at site but steel
is not known. In this case calculations can be done for concrete and resultant force
such as moment. Shear, axial loads and deformation calculated. The limited done
tests such as cover meter tests, ultrasonic tests on members gives steel bars details
and will be cross checked with calculations to verify the safety and stability. Then,
the consultant based on these details and as per code guidance for checking structures
should evaluate the case and decide whether the as built structure is safe.
5. Enough photos for the as part and the overall building
The report should include photos for the as built structure and if it is a part of a
structure, photos for the whole structure should be attached. The photos should be
recent with shown date and should cover different location and different structural
elements in the as built structures. If there is settlements, cracks, deflections or
collapse, some photos should highlight these locations. The photos should be
sufficient and give a clear idea about the situation. The important thing is not the
number of the photos but the details about the as built structure they provide. Some
photos during testing can be attached in the report for more details.
6. Letters for safety and stability
The consultant office who prepares the report has to submit a letter for safety and
stability of the as built and the whole structure. It should declare clearly the status of
the structure whether it is: safe and stable and structurally sound. Or it needs repairs,
strengthening and maintenance and what are the structural elements that need these
94 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
procedures and how will be constructed and what are the outcomes and will the
structure be safe after such improvements. Some of the items that the letter should
include:
• The location, plot number, square, city, … etc
• Date and time
• Description of the case briefly what is the as built part, statement of the
problem, the procedure, methodology, the level of the damages and the
solutions.
• A reference to the submitted report and as built drawings
• To whom this report is submitted (MM) and who is the consultant who did it
• The results conclusion
• Signature and stamp of the consultant
• The letter should be clear and details are enough
• Does the structure need special treatment such as immediate evacuation or
similar?
• A reference for the international code of practices used in the evaluation of
safety (the material testing, structural evaluation as well as and the structural
analysis and design).
• To show that the submitted currently as built drawings in the report are exactly
as per site conditions
• To show that the international and local standards and guidance have been
followed during preparing the report and carrying out tests and technical
evaluations.
• The most important is Declaration of the status of the as built structure current
existing structural conditions and performance, the responsibility for safety
and the stability.
95 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Chapter Eleven
Treatment of High Underground Water Tables
Underground Water Table
And its effects on foundations
Key Words: Underground water table, dewatering, uplift forces, water proof,
liquefaction, water table in soil report, water table pressures
Notes:
• If there is a soil report for the plot, it should mention the
underground water table and accordingly the design,
specifications and drawings should consider this such as the
effect on SBC, dewatering, depth of excavations, uplift
pressures, water proof methods, and any ground improvement
techniques required.
• For the type of the projects that does not have soil reports, if
during excavation it was found that there is higher underground
water table which was not expected earlier, then work should
stop, dewatering will take place through a specialized
geotechnical company and the approved drawings should be
resubmitted to Municipality for modifications, guidance and
approvals.
96 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
supervisor consultant and the contractor should follow the best international
engineering practices when dealing with site with underground water levels.
Specialized geotechnical company should be appointed to carry out the
dewatering. Contractor should choose high quality water proof and skills
workmanship.
97 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
dams
beach wadi
I am wondering if
I do excavation
for my house will
we find water
Fact:
below?!
During excavation,
A. Before water table can be
excavation from encountered at site
And how do I know If the plot is nearby a
there is a water table?
soil investigation
report. Please beach, wadi, dam,
refer to clause 9.4 water channel or the
for further area is usually
information on flooded or even
B. during excavation water will may exist
this report. exposed to water
and then precautions must be followed
since long
98 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Well, what else higher water table can cause to my building? And how can I use engineering?
What about water proof methods if I found high underground water table?
If there is a high underground water table, after stopping the dewatering process, the substructures such as
retaining walls of basement or foundations, subgrade level or plinth beams will be submerged fully or partially in
the water. Therefore, the usual applied bitumen-based paints layer for water proof may not be enough, and using
high quality water proof membrane is recommended. At least a water proof membrane of high quality of thickness
not less 4 mm or better.
99 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Some examples of the notes in soil reports regarding the status of the underground water table
water table
There is no
Some examples of the notes in soil reports regarding the status of the underground water table
100 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
Water proof guidance for substructures What about the suitable water proof methods and are
there any recommendations?
101 | P a g e
Structural Requirements and Specifications Issued May 2022 First Edition (Draft)
102 | P a g e