Multilin 750760-5-6
Multilin 750760-5-6
The 750/760 performs accurate measurement The 750/760 features user-configurable inputs The 750/760 can be protected against
of the following: and outputs: unauthorized setpoint changes. A key switch
may be installed on the rear terminals to allow
• Actual V, A, Hz, W, Wh, var, varh, VA‑PF
Outputs setpoint changes from the front panel. An
• Watthour cost optional passcode restricts setpoint changes
The 750/760 has eight electromechanical relay
• Phasor presentation of V and I outputs. from both the front panel and ports.
• Symmetrical components of V and I
• Two are factory programmed for breaker
• Line (synchronous) voltage: RMS voltage, control EnerVista Software
frequency, and differentials
• Five can be configured to operate as either The EnerVista™ Suite is an industry-leading
• Percent of load-to-trip failsafe or non-failsafe, and either latching, set of software programs that simplifies
• Analog input self-resetting, or pulsed; these relays can be every aspect of using the 750/760 relay. The
programmed to be operated by any feature EnerVista™ suite provides all the tools to monitor
• Running and maximum demand: A, MW,
• One of the relays is factory programmed as a the status of your protected asset, maintain the
MVAR, MVA
fail safe internal failure alarm relay relay, and integrate information measured by
Setpoints allow the user to simulate three the 750 into DCS or SCADA monitoring systems.
common electrical utility demand measuring The 750/760 has one high-speed SCR solid state
Convenient COMTRADE and Sequence of Events
techniques. output.
viewers are an integral part of the 750 Setup
The 750/760 has eight analog output channels. software included with every 750 relay, to carry
Data Logging Any of 31 measured parameters can be selected out postmortem event analysis to ensure proper
A configurable memory block can record to drive these outputs. protection system operation.
eight channels of any measured or calculated
parameter. In continuous mode, this feature can IRIG-B Input EnerVista Launchpad
be programmed to capture from 136 seconds of An IRIG-B input allows time synchronization EnerVista™ Launchpad is a powerful software
data per cycle to 48 weeks of data per hour. using a satellite signal. package that provides users with all of the
setup and support tools needed for configuring
Simulation
and maintaining Multilin products. The setup
The relay provides a powerful simulation feature
Communications
software within Launchpad allows configuring
for testing the functionality of the relay in The 750/760 is equipped with three standard devices in real-time by using serial, Ethernet,
response to programmed conditions. System serial communications ports, one RS232 located or modem connections, or offline by creating
parameters are entered as setpoints. Pre-fault, in the front panel, and two RS485/RS422 in the setting files to be sent to devices at a later time.
fault, and post-fault conditions can be simulated rear of the relay. A rear Ethernet port is also
available as an optional feature. The front panel Included in Launchpad is a document archiving
to exercise relay features.
port allows easy local computer access. The and management system that ensures critical
Logic Inputs rear ports provide remote communications or documentation is up-to-date and available when
connection to a DCS, SCADA, or PLC. The baud needed. Documents made available include:
rate of all the serial ports is variable from 300 • Manuals
to 19,200 bps. The optional Ethernet port can
• Application Notes
be used to connect the 750/760 to 10 Mbps
Ethernet networks. The 750/760 supports • Guideform Specifications
ModBus® RTU, DNP3.0 Level 2, and ModBus • Brochures
Setpoints block diagram. RTU TCP/IP protocols. • Wiring Diagrams
The three serial ports support ModBus RTU • FAQ’s
protocol, while any one of the two rear ports • Service Bulletins
but not both can be configured to support
DNP 3.0 Level 2. The optional Ethernet port
supports ModBus RTU via TCP/IP protocol.
The communication system of the 750/760 is
designed to allow simultaneous communication
Level detectors block diagram.
via all ports.
GEGridSolutions.com 5
Viewpoint Monitoring
Viewpoint Monitoring is a simple-to-use and full-featured monitoring and data recording software package for small systems. Viewpoint Monitoring provides a
complete HMI package with the following functionality:
With the new 8 Series Retrofit Kit, users are able to install a new 850 Feeder Management System without modifying existing panel or switchgear cutouts,
re-wiring, or need for drawing changes and re-engineering time and cost.
With this three-step process, operators are able to upgrade existing SR relays in as fast as 21 minutes, simplifying maintenance procedures and reducing system
downtime.
1 2 3
Update Replace Plug & Play
Settings File Relay Reconnection
EnerVista 8 Series Setup Software provides Simply remove the 4 existing terminal blocks Insert the new 8 Series Retrofit chassis into the
automated setting file conversion with graphical and then remove the SR chassis from the panel. switchgear and simply plug-in the old terminal
report to quickly and easily verify settings and No need to disconnect any of the field wiring. blocks - there is need to make any cut-out
identify any specific settings that may need modifications or push and pull cables.
attention.
The 8 Series Retrofit Kit comes factory assembled and tested as a complete unit with the 8 Series protection device and includes replacement hardware (terminal
blocks and screws) if the existing hardware is significantly aged or damaged.
6 GEGridSolutions.com