3phase Power Measurement Using Two Wattmeter Method
3phase Power Measurement Using Two Wattmeter Method
The two-wattmeter method is the most commonly used method for three-phase
power measurement.
The two wattmeters must be properly connected to any two phases, as shown
in Fig.,
The current coil of each wattmeter measures
the line current, while the respective voltage
coil is connected between the line and the
third line and measures the line voltage.
The algebraic sum of the two wattmeter
readings equals the total average power
absorbed by the load, regardless of whether it
is wye- or delta-connected, balanced or
unbalanced.
The total real power is equal to the algebraic
sum of the two wattmeter readings, 43
The total power consumed by the circuit is,
𝐑𝐍 𝐑𝐍 𝐘𝐍 𝐘𝐍 𝐁𝐍 𝐁𝐍
44
Due to the inductive (RL) load
impedance, each voltage coil
leads its current coil by so that
the power factor is
We recall that each line voltage
leads the corresponding phase
voltage by
Thus, the total phase difference
between the phase current and
line voltage is
45
The average power read by wattmeter-1 (𝐖𝟏 ) is
𝐖𝟏 + 𝐖𝟐 = 𝟑 𝐕𝐋 . 𝐈𝐋 𝐜𝐨𝐬 𝛟1
P= 𝟑 𝐕𝐋 . 𝐈𝐋 𝐜𝐨𝐬 𝛟
𝐖𝟐 − 𝐖𝟏 = V . I sin ϕ2.
𝟑(𝐖 −𝐖 ) = 3 V . I sin ϕQ
Q= 𝟑 𝐕𝐋 . 𝐈𝐋 𝐬𝐢𝐧 𝛟
46
Phase angle Power factor Watt meter readings (W) Remarks
1 +ve +ve
0.5 < pf < 1 +ve +ve
0.5 +ve 0 Total power P=W1
0 < pf < 0.5 +ve -ve Total power=+ve
47