0% found this document useful (0 votes)
61 views

Line Sizing & Line List

Uploaded by

Nurdin nurdin
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
61 views

Line Sizing & Line List

Uploaded by

Nurdin nurdin
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 15

Line Connection

No Line Number P&ID


From To
DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Header SG Package
Design Condition Operating Condition
Fluid Pressure Temp Pressure Temp Material NPS Rating
(barg) ( °C ) (barg) ( °C )
Air Compress
Pipe Sch Remark
Line Connection
No Line Number P&ID
From
1 06-1"-AI-B4CS2F-0-101 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Header
2 06-1/2"-AI-B4CS2F-0-102 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Header
3 06-3"-GFW-E4CS2F-0-101 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Header
4 06-2"-GFW-E4CS2F-0-102 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Header
5 06-3"-GFW-E4CS2F-0-103 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Header
6 06-1½"-FG-E4CS2F-0-101 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Header
7 06-¾"-FG-E4CS2F-0-102 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Header
8 06-¾"-FG-E4CS2F-0-103 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Header
9 06-2"-FG-E4CS2F-0-104 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Header
10 06-10"-FG-E4CS2F-0-105 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Header
11 06-3"-SP-E4CS2F-0-101-HI1 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Steam Discharge
12 06-3"-SP-D4CS2F-0-101-HI1 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Steam Discharge
13 06-2"-SB-E4CS2F-0-101-HI1 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Blowdown
14 06-2"-SB-D4CS2F-0-101-HI1 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Blowdown
15 06-½"-SC-D4CS2F-0-101-HI1 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Drain
16 06-1"-SC-D4CS2F-0-102-HI1 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Drain
17 06-4"-SC-D4CS2F-0-103-HI1 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Drain
18 06-4"-SC-D4CS2F-0-104-HI1 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Drain
19 06-6"-SC-D4CS2F-0-105-HI1 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Drain
20 06-4"-SC-D4CS2F-0-106-HI1 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 -
21 06-6"-SC-D4CS2F-0-107-HI1 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 -
22 06-1"-WG-E4CS2F-0-101 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 -
23 06-½"-WG-E4CS2F-0-102 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 -
24 06-1"-WG-E4CS2F-0-103 DURI-STSF06GN000-PRO-DIA-PHR-2001-02 Cooling Manifold
Design Condition Operating Condition
Line Connection
Fluid Pressure Temp Pressure Temp Material NPS
To (psig) ( °F ) (psig) ( °F )
SG Package Air Compress 150.0 150.0 100.0 95.0 A-106 Gr.B 1"
SG Package Air Compress 150.0 150.0 100.0 95.0 A-106 Gr.B ½"
SG Package Water 1,700.0 200.0 1,300.0 150.0 A-106 Gr.B 3"
SG Package Water 1,700.0 200.0 1,300.0 150.0 A-106 Gr.B 2"
SG Package Water 1,700.0 200.0 1,300.0 150.0 A-106 Gr.B 3"
SG Package Gas 60.0 100.0 50.0 75.0 A-106 Gr.B 1½"
SG Package Gas 60.0 100.0 50.0 75.0 A-106 Gr.B ¾"
SG Package Gas 60.0 100.0 50.0 75.0 A-106 Gr.B ¾"
SG Package Gas 60.0 100.0 50.0 75.0 A-106 Gr.B 2"
SG Package Gas 60.0 100.0 50.0 75.0 A-106 Gr.B 10"
Steam Header Steam 1,265.0 575.5 1,150.0 563.5 A-106 Gr.B 3"
Steam Header Steam 1,160.0 568.8 1,050.0 552.3 A-106 Gr.B 3"
Header Steam 1,265.0 575.5 1,150.0 563.5 A-106 Gr.B 2"
Header Steam 1,160.0 568.8 1,050.0 552.3 A-106 Gr.B 2"
Cond. Header Condensate 1,160.0 568.8 1,050.0 552.3 A-106 Gr.B ½"
Cond. Header Condensate 1,160.0 568.8 1,050.0 552.3 A-106 Gr.B 1"
Cond. Header Condensate 1,160.0 568.8 1,050.0 552.3 A-106 Gr.B 4"
Cond. Header Condensate 1,160.0 568.8 1,050.0 552.3 A-106 Gr.B 4"
Cond. Header Condensate 1,160.0 568.8 1,050.0 552.3 A-106 Gr.B 6"
Cond. Header Condensate 1,160.0 568.8 1,050.0 552.3 A-106 Gr.B 4"
Cond. Header Condensate 1,160.0 568.8 1,050.0 552.3 A-106 Gr.B 6"
Viewport Waste Gas 60.0 100.0 50.0 75.0 A-106 Gr.B 1"
Viewport Waste Gas 60.0 100.0 50.0 75.0 A-106 Gr.B ½"
Viewport Waste Gas 60.0 100.0 50.0 75.0 A-106 Gr.B 1"
Rating Remark

150
150
900
900
900
900
900
900
900 FG Pilot Line
900 FG Main Line
900
600
900
600
600
600
600
600
600
600
600
900
900
900
14.700 0.0206

Wall Schedule Actual


O.D
No Line Number NPS Thk Cal Designations I.D Fluid
( in ) ( in ) Sch Thk ( in )
06-1"-AI-B4CS2F-0-101 1" 1.315 0.069 40 0.133 1.049 Air Compress
06-1/2"-AI-B4CS2F-0-102 ½" 0.840 0.067 40 0.109 0.622 Air Compress
06-3"-GFW-E4CS2F-0-101 3" 3.500 0.252 80 0.300 2.900 Water
06-2"-GFW-E4CS2F-0-102 2" 2.375 0.191 80 0.218 1.939 Water
06-3"-GFW-E4CS2F-0-103 3" 3.500 0.252 80 0.300 2.900 Water
06-1½"-FG-E4CS2F-0-101 1½" 1.900 0.066 80 0.200 1.500 Gas
06-¾"-FG-E4CS2F-0-102 ¾" 1.050 0.065 80 0.154 0.742 Gas
06-¾"-FG-E4CS2F-0-103 ¾" 1.050 0.065 80 0.154 0.742 Gas
06-2"-FG-E4CS2F-0-104 2" 2.375 0.067 80 0.218 1.939 Gas
06-10"-FG-E4CS2F-0-105 10" 10.750 0.084 40 0.365 10.020 Gas
06-3"-SP-E4CS2F-0-101-HI1 3" 3.500 0.205 80 0.300 2.900 Steam
06-3"-SP-D4CS2F-0-101-HI1 3" 3.500 0.194 80 0.300 2.900 Steam
06-2"-SB-E4CS2F-0-101-HI1 2" 2.375 0.159 160 0.344 1.687 Steam
06-2"-SB-D4CS2F-0-101-HI1 2" 2.375 0.152 160 0.344 1.687 Steam
06-½"-SC-D4CS2F-0-101-HI1 ½" 0.840 0.094 160 0.188 0.464 Condensate
06-1"-SC-D4CS2F-0-102-HI1 1" 1.315 0.112 160 0.250 0.815 Condensate
06-4"-SC-D4CS2F-0-103-HI1 4" 4.500 0.231 80 0.337 3.826 Condensate
06-4"-SC-D4CS2F-0-104-HI1 4" 4.500 0.231 80 0.337 3.826 Condensate
06-6"-SC-D4CS2F-0-105-HI1 6" 6.625 0.311 80 0.432 5.761 Condensate
06-4"-SC-D4CS2F-0-106-HI1 4" 4.500 0.231 80 0.337 3.826 Condensate
06-6"-SC-D4CS2F-0-107-HI1 6" 6.625 0.311 80 0.432 5.761 Condensate
06-1"-WG-E4CS2F-0-101 1" 1.315 0.065 80 0.179 0.957 Waste Gas
06-½"-WG-E4CS2F-0-102 ½" 0.840 0.064 80 0.147 0.546 Waste Gas
06-1"-WG-E4CS2F-0-103 1" 1.315 0.065 80 0.179 0.957 Waste Gas
Design Condition Operating Condition Flowrate Gas
Specific Compress Fluid
Density Volume Viscosity
Pressure Temp Pressure Temp Liquid Gas Factor
(psig) ( °F ) (psig) ( °F ) BPD lb/h lb/ft3 ft3/lb Z cP
150.0 150.0 100.0 95.0 0.87 1.15 0.0205
150.0 150.0 100.0 95.0 0.87 1.15 0.0205
1,700.0 200.0 1,300.0 150.0 3,771.4 - 62.4 0.02 0.3041
1,700.0 200.0 1,300.0 150.0 3,771.4 - 62.4 0.02 0.3041
1,700.0 200.0 1,300.0 150.0 3,771.4 - 62.4 0.02 0.3041
60.0 100.0 50.0 75.0 0.06 17.86 0.0107
60.0 100.0 50.0 75.0 0.06 17.86 0.0107
60.0 100.0 50.0 75.0 0.06 17.86 0.0107
60.0 100.0 50.0 75.0 0.06 17.86 0.0107
60.0 100.0 50.0 75.0 0.06 17.86 0.0107
1,265.0 575.5 1,150.0 563.5 40,722.0 2.98 0.34 0.94 0.0198
1,160.0 564.6 1,050.0 552.3 40,722.0 2.69 0.37 0.94 0.0194
1,265.0 575.5 1,150.0 563.5 40,722.0 2.98 0.34 0.94 0.0198
1,160.0 564.6 1,050.0 552.3 40,722.0 2.69 0.37 0.94 0.0194
1,160.0 564.6 1,050.0 552.3 2.69 0.37 0.0194
1,160.0 564.6 1,050.0 552.3 2.69 0.37 0.0194
1,160.0 564.6 1,050.0 552.3 2.69 0.37 0.0194
1,160.0 564.6 1,050.0 552.3 2.69 0.37 0.0194
1,160.0 564.6 1,050.0 552.3 2.69 0.37 0.0194
1,160.0 564.6 1,050.0 552.3 2.69 0.37 0.0194
1,160.0 564.6 1,050.0 552.3 2.69 0.37 0.0194
60.0 100.0 50.0 75.0 0.06 17.86 0.0107
60.0 100.0 50.0 75.0 0.06 17.86 0.0107
60.0 100.0 50.0 75.0 0.06 17.86 0.0107
Velocity Reynold
Liquid Gas Number
ft/s ft/s Re
- 186.4 692
- 186.4 410
53.8 - 2,670
120.4 - 3,993
53.8 - 2,670
- -
- -
- -
- -
- -
- 82.9 3,017
- 91.6 3,066
- 244.9 5,186
- 270.7 5,270
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- -
- -
- -
R 8.31446261815324
M 0.0289652
R/M 287.05006760365

rho = P/((R/M)*T) 13.9744455354848

P 1200000
T 299.15
kg/m3 0.87239613524

Pa
K

You might also like