Foxboro Evo™ Process Automation System: Product Specifications
Foxboro Evo™ Process Automation System: Product Specifications
Process Automation
System
Product Specifications
PSS 31H-2S247
In many plant situations, the signal types associated with an installation are not well known until late in the
project. The FBM247 provides the capability to accept a range of standard analog, discrete, and pulse
inputs that are user selectable and changeable at the discretion of the engineer. The HART® input signals
are electrically compatible with the standard 4 to 20 mA inputs.
Each I/O channel is galvanically isolated from other Baseplate-mounted TA (RH924WG), which
channels and ground. provides field I/O wiring support for two
FBM247s in paired slots (that is, in positions 1
Three types of passive termination assemblies are
and 2, 3 and 4, 5 and 6, or 7 and 8), as shown in
available for the FBM247:
Figure 2. This TA mounts directly onto the field
DIN rail mounted TA, similar to those used with I/O connectors on the 200 Series baseplate.
the other 200 Series FBMs
PSS 31H-2S247
Page 2
Standard FBM247
Operational Status
01
02
03
04
DI/DO, Pulse HART
05
06
07
1 2 08
OFF FBM247
Baseplate I. D. Channel Isolated
No. 1 2 8 Configurable Channels
0 ON ON (AI/AO)+HART, DI/DO, Pulse
1 OFF ON P0927BN
2 ON OFF
3 OFF OFF ®
01 01
02 02
03 03
04 04
DI/DO, Pulse HART DI/DO, Pulse HART
05 05
06 06
07 07
1 2 08 08
Optional baseplate-mounted Termination Their functionality varies depending on the type of I/O
Assemblies (TAs) attach directly to a 200 Series signal used on each channel:
baseplate, eliminating the need for mounting a Red and green LEDs provide indication of the
separate TA on a DIN rail for the FBM247, and FBM operational status.
requiring space for the TA’s cable in an enclosure Yellow LEDs indicate HART communication
Range of I/O support and baseplate-mounted activity for each channel.
TAs reduce the amount of cabling and mounting Yellow LEDs are provided to indicate the On or
space, eliminating the need for separate Off state of the discrete input or output channels.
marshalling enclosures and cables required for
field I/O wiring support EASY REMOVAL/REPLACEMENT
Enables sites to reduce the number of separate The module can be removed/replaced without
types of 200 Series FBMs maintained as spares, removing field device termination cabling, or power
by replacing them with a single type of 200 Series or communications cabling.
FBM - the FBM247, which supports a wide range
of analog, digital and pulse field I/O applications.
SEQUENCE OF EVENTS
The Sequence of Events (SOE) software package (for
HIGH ACCURACY use with I/A Series software v8.x and Control Core
Services software v9.0 or later) is used for
For high input accuracy, the module incorporates a
acquisition, storage, display, and reporting of events
16-bit Sigma-Delta converter which can provide new
associated with discrete input points in a control
analog input values for each channel every 100
system. SOE, using the optional GPS based time
milliseconds. For outputs, a 13-bit D/A is used.
synchronization capability, supports data acquisition
STANDARD DESIGN across control processors at intervals of up to one
millisecond, depending on the signal source.
FBM247 has a rugged extruded aluminum exterior
for physical protection of the circuits. Refer to Sequence of Events (PSS 31S-2SOE) to
learn more about this package, and to
Enclosures specially designed for mounting the
Time Synchronization Equipment (PSS 31H-4C2), for
FBMs provide various levels of environmental
a description of the optional time synchronization
protection, up to harsh environments (Class G3), per
capability.
ISA Standard S71.04.
FIELDBUS COMMUNICATION
VISUAL INDICATORS
A Fieldbus Communications Module or a Control
Light-emitting diodes (LEDs) incorporated into the
Processor interfaces to the redundant 2 Mbps
front of the modules provide visual indication of the
module Fieldbus used by the FBMs. The FBM
module operational status, and communication
accepts communication from either path (A or B) of
activity of the input/output channels.
the 2 Mbps Fieldbus — should one path fail or be
switched at the system level, the module continues
communication over the active path.
PSS 31H-2S247
Page 5
TERMINATION ASSEMBLIES
Field I/O signals connect to the FBM subsystem via:
DIN rail mounted TA, or
Baseplate-mounted TA.
NOTE
A shield terminal connection (SH) is provided
for each channel. The shield terminals are
connected to the ground at the system
power supply.
The TAs used with the FBM247 are described in
“TERMINATION ASSEMBLIES AND CABLES” on
page 10.
PSS 31H-2S247
Page 6
F U N C T I O N A L S P E C I F I C AT I O N S
F U N C T I O N A L S PE CI F I C AT I O N S ( C O N T I N U E D )
F U N C T I O N A L S PE CI F I C AT I O N S ( C O N T I N U E D )
Power Requirements PRODUCT SAFETY
INPUT VOLTAGE RANGE (SINGLE OR Underwriters Laboratories (UL) for U.S. and
REDUNDANT) Canada
24 V dc +5%, -10% UL/UL-C listed as suitable for use in UL/UL-
CONSUMPTION (MAXIMUM) C listed Class I, Groups A-D; Division 2;
9.4 W temperature code T4 enclosure based
systems when connected to specified
HEAT DISSIPATION (MAXIMUM)
Foxboro Evo processor modules as
6.8 W
described in the Standard and Compact 200
Calibration Requirements Series Subsystem User's Guide (B0400FA).
Calibration of the module and termination Communications circuits also meet the
assembly is not required. requirements for Class 2 as defined in Article
Regulatory Compliance 725 of the National Electrical Code (NFPA
No.70) and Section 16 of the Canadian
ELECTROMAGNETIC COMPATIBILITY (EMC)
Electrical Code (CSA C22.1). Conditions for
European EMC Directive 2004/108/EC (Prior to
use are as specified in the Standard and
April 20, 2016) and 2014/30/EU (Beginning April
Compact 200 Series Subsystem User's
20, 2016)
Guide (B0400FA).
Meets: EN61326-1:2013 Class A Emissions and
European Low Voltage Directive 2006/95/EC
Industrial Immunity Levels
(Prior to April 20, 2016) and 2014/35/EU
RoHS COMPLIANCE (Beginning April 20, 2016) and Explosive
Complies with European RoHS Directive Atmospheres (ATEX) directive 94/9/EC (Prior
2011/65/EU to April 20, 2016) and 2014/34/EU
(Beginning April 20, 2016)
DEMKO certified as Ex nA IIC T4 for use in
certified Zone 2 enclosure when connected
to specified I/A Series processor modules as
described in the Standard and Compact 200
Series Subsystem User's Guide (B0400FA).
MARINE CERTIFICATION
ABS Type Approved and Bureau Veritas Marine
certified for Environmental Category EC31.
PSS 31H-2S247
Page 9
E N V I R O N M E N TA L S P E C I F I C AT I O N S
P H Y S I C A L S P E C I F I C AT I O N S
P H Y S I CA L S PE CI F I CAT I O N S ( CO N T I N U E D)
F U N C T I O N A L S P E C I F I C AT I ON S – T E R M I N AT I O N A S S E M B L I E S
TA TA
TA Part Number Termination Cable Certification
FBM
Type Input/Output Signal PA(a) PC/ABS(b) Type(c) Type(d) Type(e)
Type Certification(a)
Type 1 TAs are UL/UL-C listed as suitable for use in Class I; Groups A-D; Division 2 temperature code
T4 hazardous locations. They are DEMKO certified Ex nA IIC T4 Gc for use in Zone 2 potentially
explosive atmospheres.
Type 2 TAs are UL/UL-C listed for supplying field circuits Class I; Groups A-D; Division 2 hazardous
locations when connected to specified 200 Series FBMs and field circuits meeting entity
parameter constraints specified in Standard and Compact 200 Series Subsystem User’s Guide
(B0400FA). They are also DEMKO certified for supplying field circuits for Group IIC, Zone 2
potentially explosive atmospheres. Field circuits are also Class 2 limited energy (60 V dc, 30 V
ac, 100 VA or less) if customer-supplied equipment meets Class 2 limits.
Type 4 All field circuits are NEC/CEC Class 2 limited energy if customer-supplied equipment meets
Class 2 limits.
(a) All TAs are UL/UL-C listed to comply with applicable ordinary location safety standards for fire and shock hazards. Hazardous location
types comply with ATEX directive for II 3 G use. They also comply with the requirements of the European Low Voltage Directive. All
listings/certifications require installation and use within the constraints specified in Standard and Compact 200 Series Subsystem
User’s Guide (B0400FA) and the conditions stated in UL and DEMKO reports.
PSS 31H-2S247
Page 13
D I M EN SI ON S – N OM I N AL
DIMENSIONS–NOMINAL (CONTINUED)
89.5 84
3.53 3.31 (a)
RH101KA
63.1 25
2.48 .98
75
2.95