Foxboro Evo™

Process Automation
System
Product Specifications

PSS 31H-2S247

FBM247, Current/Voltage Analog/Digital/Pulse I/O Configurable Module

In many plant situations, the signal types associated with an installation are not well known until late in the
project. The FBM247 provides the capability to accept a range of standard analog, discrete, and pulse
inputs that are user selectable and changeable at the discretion of the engineer. The HART® input signals
are electrically compatible with the standard 4 to 20 mA inputs.

OVERVIEW  Baseplate-mounted TA (RH101KA), which


The FBM247, Channel-Isolated Current/Voltage provides field I/O wiring support for one FBM247,
Analog/Digital/Pulse I/O Module contains eight as shown in Figure 1. This TA mounts directly
channels which can be individually configured for a onto the FBM247’s field I/O connector on the
range of analog, digital and pulse field I/O signals. 200 Series baseplate.

Each I/O channel is galvanically isolated from other  Baseplate-mounted TA (RH924WG), which
channels and ground. provides field I/O wiring support for two
FBM247s in paired slots (that is, in positions 1
Three types of passive termination assemblies are
and 2, 3 and 4, 5 and 6, or 7 and 8), as shown in
available for the FBM247:
Figure 2. This TA mounts directly onto the field
 DIN rail mounted TA, similar to those used with I/O connectors on the 200 Series baseplate.
the other 200 Series FBMs
PSS 31H-2S247
Page 2

Standard FBM247

Operational Status

01

02

03

04
DI/DO, Pulse HART
05

06

07

1 2 08

OFF FBM247
Baseplate I. D. Channel Isolated
No. 1 2 8 Configurable Channels
0 ON ON (AI/AO)+HART, DI/DO, Pulse
1 OFF ON P0927BN
2 ON OFF
3 OFF OFF ®

Baseplate-mounted termination assembly (RH101KA)


Figure 1. Baseplate-Mounted Termination Assembly (RH101KA) for Single FBM247

Operational Status Operational Status

01 01

02 02

03 03

04 04
DI/DO, Pulse HART DI/DO, Pulse HART
05 05

06 06

07 07

1 2 08 08

OFF FBM247 FBM247


Baseplate I. D. Channel Isolated Channel Isolated
No. 1 2 8 Configurable Channels 8 Configurable Channels
0 ON ON (AI/AO)+HART, DI/DO, Pulse (AI/AO)+HART, DI/DO, Pulse
1 OFF ON P0927BN P0927BN
2 ON OFF
3 OFF OFF ® ®

Insert here for


FBM247s in
Slots 7 and 8

Insert here for Insert here for


FBM247s in FBM247s in Baseplate Mounted
Slots 1 and 2 Slots 3 and 4 Termination Assembly
(RH924WG)

Figure 2. Baseplate-Mounted Termination Assembly (RH924WG) for FBM247 Pair


PSS 31H-2S247
Page 3

The FBM247 can serve as a HART communications FEATURES


field device host, enabling the Foxboro Evo™ system Key features of the FBM247 are:
to request and receive two digital messages per
 Eight individual isolated channels to support:
second from the field device. The message pass-
through capability can be used to support HART • HART Analog Input (AI)/Analog Output (AO)
universal, common practice, and device-specific 4-20 mA
commands, but not the burst communication mode. • 0-20 mA AI/AO, non-HART
These commands are implemented using the
• 0-10 V and 0-5 V AI, non-HART
Intelligent Field Device Configurator FoxCom™ and
HART™ Protocols (IFDC — refer to • Digital dry contact sense 24 V dc
PSS 21S-8A3 B3 for details) or PACTware (Process
• Discrete voltage monitor, configurable 0 and
Automation Configuration Tool - refer to
1 thresholds 0-10 V
PSS 2A-1Z3 G for details).
• NAMUR sensor discrete input -
The FBM247 must be used with I/A Series® system
Signal level according to DIN EN 50227
software, v8.7 to v8.8 and Foxboro Evo Control Core
(NAMUR):
Services software, v9.0 or later.
- “On” at 2.1 mA dc with short circuit
When used with the baseplate-mounted TAs, there is detection at > 6 mA
no need for a separate termination or marshalling - “Off” at 1.2 mA dc with open detection at
enclosure. When installed in G-Series or equivalent <0.25 mA
system enclosures with baseplate-mounted TAs, the
• Pulse count, frequency, acceleration and
FBM247 enables the system enclosure to support up
jerk, contact sense or voltage input
to 96 FBMs and their associated Field Control
Processors (FCP) from a single enclosure’s footprint. • Discrete Output 24 V, 20 mA current or solid
Refer to G-Series Enclosures Overview (PSS 31H- state switch output.
2GOV) or equivalent PSS for a complete list of  Rugged design suitable for enclosures in Class
modules supported in the system enclosures. G3 (harsh) environments
The FBM247 is electrically compatible with standard  Executes programs for Discrete Input, Pulse
HART signals. Count, Sequence of Events and Transient Data
Recording with support for Sustained and
Momentary Digital Outputs
 Enables higher utilization of I/O points in each
enclosure - fewer points on each FBM are likely
to be left unused due to the versatility of the
FBM247’s I/O points
 Passive Termination Assemblies (TAs) - DIN rail
mounted or 200 Series baseplate mounted - for
locally or remotely connecting field wiring to the
FBM247
PSS 31H-2S247
Page 4

 Optional baseplate-mounted Termination Their functionality varies depending on the type of I/O
Assemblies (TAs) attach directly to a 200 Series signal used on each channel:
baseplate, eliminating the need for mounting a  Red and green LEDs provide indication of the
separate TA on a DIN rail for the FBM247, and FBM operational status.
requiring space for the TA’s cable in an enclosure  Yellow LEDs indicate HART communication
 Range of I/O support and baseplate-mounted activity for each channel.
TAs reduce the amount of cabling and mounting  Yellow LEDs are provided to indicate the On or
space, eliminating the need for separate Off state of the discrete input or output channels.
marshalling enclosures and cables required for
field I/O wiring support EASY REMOVAL/REPLACEMENT
 Enables sites to reduce the number of separate The module can be removed/replaced without
types of 200 Series FBMs maintained as spares, removing field device termination cabling, or power
by replacing them with a single type of 200 Series or communications cabling.
FBM - the FBM247, which supports a wide range
of analog, digital and pulse field I/O applications.
SEQUENCE OF EVENTS
The Sequence of Events (SOE) software package (for
HIGH ACCURACY use with I/A Series software v8.x and Control Core
Services software v9.0 or later) is used for
For high input accuracy, the module incorporates a
acquisition, storage, display, and reporting of events
16-bit Sigma-Delta converter which can provide new
associated with discrete input points in a control
analog input values for each channel every 100
system. SOE, using the optional GPS based time
milliseconds. For outputs, a 13-bit D/A is used.
synchronization capability, supports data acquisition
STANDARD DESIGN across control processors at intervals of up to one
millisecond, depending on the signal source.
FBM247 has a rugged extruded aluminum exterior
for physical protection of the circuits. Refer to Sequence of Events (PSS 31S-2SOE) to
learn more about this package, and to
Enclosures specially designed for mounting the
Time Synchronization Equipment (PSS 31H-4C2), for
FBMs provide various levels of environmental
a description of the optional time synchronization
protection, up to harsh environments (Class G3), per
capability.
ISA Standard S71.04.

FIELDBUS COMMUNICATION
VISUAL INDICATORS
A Fieldbus Communications Module or a Control
Light-emitting diodes (LEDs) incorporated into the
Processor interfaces to the redundant 2 Mbps
front of the modules provide visual indication of the
module Fieldbus used by the FBMs. The FBM
module operational status, and communication
accepts communication from either path (A or B) of
activity of the input/output channels.
the 2 Mbps Fieldbus — should one path fail or be
switched at the system level, the module continues
communication over the active path.
PSS 31H-2S247
Page 5

MODULAR BASEPLATE MOUNTING


The module mounts on a Modular baseplate, which
accommodates up to eight Fieldbus Modules. The
Modular baseplate is either DIN rail mounted or rack
mounted, and includes signal connectors for a
redundant 2 Mbps HDLC module Fieldbus,
redundant independent dc power, and termination
cables or baseplate-mounted TAs.

TERMINATION ASSEMBLIES
Field I/O signals connect to the FBM subsystem via:
 DIN rail mounted TA, or

 Baseplate-mounted TA.

NOTE
A shield terminal connection (SH) is provided
for each channel. The shield terminals are
connected to the ground at the system
power supply.
The TAs used with the FBM247 are described in
“TERMINATION ASSEMBLIES AND CABLES” on
page 10.
PSS 31H-2S247
Page 6

F U N C T I O N A L S P E C I F I C AT I O N S

Supported Hart Instrument Types INPUT OVER-RANGE CAPABILITY


HART instruments compliant to Version 5, 6, or 7 of Voltage
the HART specifications may be used. 10.2 V dc or 5.1 V dc (65,535 counts), 30 V
Input/Output Channels without damage
Eight I/O channels, each individually configurable as: Current
 HART 4-20 mA analog input or analog output 20.4 mA dc (65,280 counts), 36 mA without
damage
 (non-HART) 0-20 mA analog input or analog
DIGITAL SOE OR PULSE ON LEVEL
output
Voltage
 (non-HART) 0-10 V and 0-5V analog input
6 V dc min, 30 V dc max.
 Digital dry contact sense 24 V dc Current
 NAMUR(1) sensor discrete input - 2.1 mA dc min, 10 mA dc max. NAMUR
Signal level according to DIN EN 50227 (NAMUR) compatible
- “On” at 2.1 mA dc with short circuit detection DIGITAL SOE OR PULSE OFF LEVEL
at > 6 mA Voltage
- “Off” at 1.2 mA dc with open detection at 0 V dc min, 2 V dc max.
<0.25 mA Current
0 mA dc min, 1.2 mA dc max. NAMUR
Digital voltage input, configurable 0 and 1
compatible
thresholds 0-10 V
MINIMUM PULSE ON TIME
 Pulse count, frequency, acceleration or jerk, 16 microseconds
contact sense or voltage input MINIMUM PULSE OFF TIME
 Digital output 24 V, 20 mA current or switch 16 microseconds
Discrete inputs have configurable current or voltage MINIMUM PULSE PERIOD
thresholds when not in SOE mode. 40 microseconds
Channel types are independently configurable without INPUT ACCURACY
taking the module or other channels off-line. Analog Input
Each channel is isolated and independent. 0.03% of span
Input/Output Channels Specifications Temperature Coefficient
INPUT RANGES 50 PPM/Deg C
Voltage Pulse Rate
-0.2564 to 10 V dc or -0.1282 to 5 V dc 0.05% of reading
(0.0 V = 1600 raw counts) INPUT PULSE TOTALIZING
Current No missing pulses
0 to 20 mA dc ANALOG INPUT RESOLUTION
Pulse Count 16 bits
0 to 65535 with rollover to zero PULSE COUNT RESOLUTION
Frequency Pulse Count
10 Hz to 25000 Hz. 16 bits (integer)
Frequency
32 bits (integer)

(1) For intrinsically safe installations, an external barrier is required.


PSS 31H-2S247
Page 7

F U N C T I O N A L S PE CI F I C AT I O N S ( C O N T I N U E D )

Input/Output Channels Specifications (Cont.) ANALOG OUTPUT PROCESSING DELAY


INPUT UPDATE RATE 30 milliseconds maximum
Analog FIELD DEVICE CABLING DISTANCE
25 milliseconds, 10 milliseconds in TDR For current I/O Channels, maximum distance of
mode the field device from the FBM is a function of
Pulse count and frequency compliance voltage (20 V dc @ 20.4 mA input),
10 or 25 milliseconds depending upon wire gauge, and voltage required at the field
integration time setting device.
Digital SOE update rate LOOP POWER SUPPLY PROTECTION
1 millisecond Loop power is channel-to-channel galvanically
ANALOG AND PULSE INPUT INTEGRATION isolated and current limited.
TIME HART® PROTOCOL COMPATIBILITY
100, 200, 500, and 1000 milliseconds, software The channels meet the impedance requirements
configurable on a per FBM basis for a HART high Impedance Device and can be
FASTEST ALLOWED ECB BLOCK PERIOD used in a HART loop without interfering with the
100 msec HART signals between the field device and a
INPUT SIGNAL A/D CONVERSION Hand-Held Communicator (HHC).
Each channel performs A/D signal conversion Input/Output Channel Isolation
using an independent Sigma-Delta converter Each channel is galvanically isolated from all other
INPUT CHANNEL IMPEDANCE channels and earth (ground). The module withstands,
Voltage Input without damage, a potential of 600 V ac applied for
10 M Ohm nominal one minute between any channel and ground, or
Current Input between a given channel and any other channel. See
With External Loop Supply CAUTION below.
200 Ohm nominal CAUTION
With Internal Loop Supply
250 Ohm nominal This does not imply that these channels are
INPUT CURRENT LIMIT intended for permanent connection to
30 mA nominal voltages of these levels. Exceeding the limits
MAXIMUM OUTPUT CURRENT for input voltages, as stated elsewhere in this
20.4 mA specification, violates electrical safety codes
MAXIMUM OUTPUT LOAD IN OUTPUT MODE and may expose users to electric shock.
WHEN FBM PROVIDES POWER
750 Ohms when using FBM power Communication
Communicates with its associated FCM or FCP via
ANALOG OUTPUT ACCURACY
the redundant 2 Mbps module Fieldbus.
0.05% of span (0.1 to 20 mA)
Temperature Coefficient
50 PPM/Deg C
ANALOG OUTPUT RESOLUTION
13 bits
ANALOG OUTPUT NON-LINEARITY
Non-linearity is included in the accuracy
specification.
PSS 31H-2S247
Page 8

F U N C T I O N A L S PE CI F I C AT I O N S ( C O N T I N U E D )
Power Requirements PRODUCT SAFETY
INPUT VOLTAGE RANGE (SINGLE OR Underwriters Laboratories (UL) for U.S. and
REDUNDANT) Canada
24 V dc +5%, -10% UL/UL-C listed as suitable for use in UL/UL-
CONSUMPTION (MAXIMUM) C listed Class I, Groups A-D; Division 2;
9.4 W temperature code T4 enclosure based
systems when connected to specified
HEAT DISSIPATION (MAXIMUM)
Foxboro Evo processor modules as
6.8 W
described in the Standard and Compact 200
Calibration Requirements Series Subsystem User's Guide (B0400FA).
Calibration of the module and termination Communications circuits also meet the
assembly is not required. requirements for Class 2 as defined in Article
Regulatory Compliance 725 of the National Electrical Code (NFPA
No.70) and Section 16 of the Canadian
ELECTROMAGNETIC COMPATIBILITY (EMC)
Electrical Code (CSA C22.1). Conditions for
European EMC Directive 2004/108/EC (Prior to
use are as specified in the Standard and
April 20, 2016) and 2014/30/EU (Beginning April
Compact 200 Series Subsystem User's
20, 2016)
Guide (B0400FA).
Meets: EN61326-1:2013 Class A Emissions and
European Low Voltage Directive 2006/95/EC
Industrial Immunity Levels
(Prior to April 20, 2016) and 2014/35/EU
RoHS COMPLIANCE (Beginning April 20, 2016) and Explosive
Complies with European RoHS Directive Atmospheres (ATEX) directive 94/9/EC (Prior
2011/65/EU to April 20, 2016) and 2014/34/EU
(Beginning April 20, 2016)
DEMKO certified as Ex nA IIC T4 for use in
certified Zone 2 enclosure when connected
to specified I/A Series processor modules as
described in the Standard and Compact 200
Series Subsystem User's Guide (B0400FA).
MARINE CERTIFICATION
ABS Type Approved and Bureau Veritas Marine
certified for Environmental Category EC31.
PSS 31H-2S247
Page 9

E N V I R O N M E N TA L S P E C I F I C AT I O N S

Operating Conditions Storage Conditions


TEMPERATURE TEMPERATURE
Module -40 to +70°C (-40 to +158°F)
-20 to +70°C (-4 to +158°F) RELATIVE HUMIDITY
Termination Assembly 5 to 95% (noncondensing)
Polyamide (PA) ALTITUDE
-20 to +70°C (-4 to +158°F) -300 to +12 000 m (-1000 to +40 000 ft)
Polycarbonate/Acrylonitrile Butadiene
Styrene (PC/ABS) Contamination
-20 to +70°C (-4 to +158°F) Suitable for use in Class G3 (Harsh) environments as
defined in ISA Standard S71.04, based on exposure
RELATIVE HUMIDITY
testing according to EIA Standard 364-65, Class III.
5 to 95% (noncondensing
ALTITUDE Vibration
-300 to +3000 m (-1000 to +10 000 ft) 7.5 m/s2 (5 to 500 Hz)

P H Y S I C A L S P E C I F I C AT I O N S

Mounting Dimensions - Module


MODULE HEIGHT
FBM247 mounts on a 200 Series baseplate. The 102 mm (4 in),114 mm (4.5 in) including mounting
baseplate can be mounted on a DIN rail lugs
(horizontally or vertically), or horizontally on a 19- WIDTH
inch rack using a mounting kit. Refer to 45 mm (1.75 in)
Standard 200 Series Baseplates DEPTH
(PSS 31H-2SBASPLT) for details. 104 mm (4.11 in)
TERMINATION ASSEMBLY
The DIN rail mounted TA mounts on a DIN rail
Dimensions - Termination Assemblies
and accommodates multiple DIN rail styles Refer to page 14 and page 15.
including 32 mm (1.26 in) and 35 mm 1.38 in) Part Numbers
The baseplate-mounted TA (RH101KA) mounts FBM247 MODULE
on the field I/O connector associated with its RH927BN (supersedes P0927BN)
FBM247 on a 200 Series baseplate. TERMINATION ASSEMBLIES
The baseplate-mounted TA (RH924WG) mounts See “FUNCTIONAL SPECIFICATIONS –
on the two field I/O connectors associated with TERMINATION ASSEMBLIES” on page 11.
its two FBM247s on a 200 Series baseplate.
Weight
MODULE
373 g (12 oz) approximate
TERMINATION ASSEMBLIES
DIN Rail Mounted TA
170 g (0.37 lb, approximate)
Baseplate Mounted TA
245 g (0.57 lb, approximate)
PSS 31H-2S247
Page 10

P H Y S I CA L S PE CI F I CAT I O N S ( CO N T I N U E D)

Termination Cables TERMINATION ASSEMBLIES AND CABLES


CABLE LENGTHS Field I/O signals connect to the FBM subsystem via
Up to 30 m (98 ft) DIN rail mounted or baseplate mounted termination
CABLE MATERIALS assemblies (TAs).
Polyurethane or Low Smoke Zero Halogen
(LSZH) The DIN rail mounted TAs for the FBM247 are
TERMINATION CABLE TYPE available in Polyamide (PA) material with compression
Type 1 – See Table 2 on page 13. screw terminations.
CABLE CONNECTION – TA TO BASEPLATE The baseplate mounted TA (RH101KA) for individual
FBM Baseplate End FBM247s is available in Acrylonitrile Butadiene
37-pin D-subminiature
Styrene (ABS) material with spring cage screw
Termination Assembly End
25-pin D-subminiature terminations.

Field Termination Connections The baseplate mounted TA (RH924WG) for


DIN RAIL TA COMPRESSION-TYPE ACCEPTED redundant FBM247s is available in
WIRING SIZES Polycarbonate/Acrylonitrile Butadiene Styrene
Solid/Stranded/AWG (PC/ABS) material with compression screw
0.2 to 4 mm2/0.2 to 2.5 mm2/24 to 12 AWG terminations.
Stranded with Ferrules
See the following “FUNCTIONAL SPECIFICATIONS –
0.2 to 2.5 mm2 with or without plastic collar
TERMINATION ASSEMBLIES” for the TAs used with
BASEPLATE MOUNTED TA COMPRESSION -
the FBM247.
ACCEPTED WIRING SIZES
Solid/Stranded/AWG The FBM247 provides sufficient loop resistance to
0.2 to 1.5 mm2/0.2 to 1.5 mm2/24 to 16 allow use of the HART Hand-Held Terminal, or PC20
AWG Intelligent Field Device Configurator (PSS 2A-1Z3 E).
Stranded with Ferrules
A removable termination cable connects the DIN rail
0.25 to 0.75 mm2 with plastic collar
0.25 to 1.5mm2 without plastic collar mounted TA to the FBM via a field connector on the
baseplate in which the FBM is installed. Termination
cables are available in the following materials:
 Polyurethane

 Low Smoke Zero Halogen (LSZH).


Termination cables are available in a variety of
lengths, up to 30 meters (98 feet), allowing the
Termination Assembly to be mounted in either the
enclosure or in an adjacent enclosure. See Table 2
for a list of termination cables used with the DIN rail
mounted TAs for the FBM247.
PSS 31H-2S247
Page 11

F U N C T I O N A L S P E C I F I C AT I ON S – T E R M I N AT I O N A S S E M B L I E S

TA TA
TA Part Number Termination Cable Certification
FBM
Type Input/Output Signal PA(a) PC/ABS(b) Type(c) Type(d) Type(e)

FBM247 8 configurable I/O RH924WW C 1 1, 2


channels, voltage or (supersedes
current, analog or digital. P0924WW)
Analog 4 to 20 mA I/O may
also have the HART signal
superimposed.
FBM247 8 configurable I/O RH101KA Spring Cage n/a 1, 2
channels, voltage or (SC)
current, analog or digital. (Baseplate-
Analog 4 to 20 mA I/O may mounted)
also have the HART signal
superimposed.
FBM247 Two sets of 8 configurable RH924WG C n/a 1, 2
I/O channels, voltage or supersedes (Baseplate-
current, analog or digital. P0924WG) mounted)
Analog 4 to 20 mA I/O may
also have the HART signal
superimposed.
(a) PA is Polyamide rated from -20 to +70°C (-4 to +158°F).
(b) PC/ABS is Polycarbonate/Acrylonitrile Butadiene Styrene (PC/ABS) rated from-20 to +70°C (-4 to +158°F).
(c) C = TA with compression terminals.
(d) See Table 2 for cable part numbers and specifications.
(e) See Table 1 for Termination Assembly certification definitions.
PSS 31H-2S247
Page 12

Table 1. Certification for Termination Assemblies

Type Certification(a)

Type 1 TAs are UL/UL-C listed as suitable for use in Class I; Groups A-D; Division 2 temperature code
T4 hazardous locations. They are DEMKO certified Ex nA IIC T4 Gc for use in Zone 2 potentially
explosive atmospheres.
Type 2 TAs are UL/UL-C listed for supplying field circuits Class I; Groups A-D; Division 2 hazardous
locations when connected to specified 200 Series FBMs and field circuits meeting entity
parameter constraints specified in Standard and Compact 200 Series Subsystem User’s Guide
(B0400FA). They are also DEMKO certified for supplying field circuits for Group IIC, Zone 2
potentially explosive atmospheres. Field circuits are also Class 2 limited energy (60 V dc, 30 V
ac, 100 VA or less) if customer-supplied equipment meets Class 2 limits.
Type 4 All field circuits are NEC/CEC Class 2 limited energy if customer-supplied equipment meets
Class 2 limits.
(a) All TAs are UL/UL-C listed to comply with applicable ordinary location safety standards for fire and shock hazards. Hazardous location
types comply with ATEX directive for II 3 G use. They also comply with the requirements of the European Low Voltage Directive. All
listings/certifications require installation and use within the constraints specified in Standard and Compact 200 Series Subsystem
User’s Guide (B0400FA) and the conditions stated in UL and DEMKO reports.
PSS 31H-2S247
Page 13

Table 2. Cables Types and Part Numbers

Cable Length Type 1 Type 1


m (ft) P/PVC (a) LSZH (b)

0.5 (1.6) RH916DA RH928AA


(supersedes P0916DA) (supersedes P0928AA)
1.0 (3.2) RH916DB RH928AB
(supersedes P0916DB) (supersedes P0928AB)
2.0 (6.6) RH931RM RH928AC
(supersedes P0931RM) (supersedes P0928AC)
3.0 (9.8) RH916DC RH928AD
(supersedes P0916DC) (supersedes P0928AD)
5.0 (16.4) RH916DD RH928AE
(supersedes P0916DD) (supersedes P0928AE)
10.0 (32.8) RH916DE RH928AF
(supersedes P0916DE) (supersedes P0928AF)
15.0 (49.2) RH916DF RH928AG
(supersedes P0916DF) (supersedes P0928AG)
20.0 (65.6) RH916DG RH928AH
(supersedes P0916DG) (supersedes P0928AH)
25.0 (82.0) RH916DH RH928AJ
(supersedes P0916DH) (supersedes P0928AJ)
30.0 (98.4) RH916DJ RH928AK
(supersedes P0916DJ) (supersedes P0928AK)
(a) P/PVC is polyurethane outer jacket and semi-rigid PVC primary conductor insulation.
Temperature range: -20 to +80°C (-4 to +176°F).
(b) Low smoke zero halogen or low smoke free of halogen (LSZH) is a material classification
used for cable jacketing. LSZH is composed of thermoplastic or thermoset compounds that
emit limited smoke and no halogen when exposed to high sources of heat. Temperature
range: -40 to +105°C (-40 to +221°F).
PSS 31H-2S247
Page 14

D I M EN SI ON S – N OM I N AL

DIN Rail Mounted Termination Assembly

RH924WW (supersedes P0924WW)

 
     

 
     

(a) Overall width – for determining DIN rail loading.


(b) Height above DIN rail (add to DIN rail height for total).
PSS 31H-2S247
Page 15

DIMENSIONS–NOMINAL (CONTINUED)

Baseplate Mounted Termination Assemblies

RH924WG (supersedes P0924WG)


86.1 101.1
3.39 3.98

89.5 84
3.53 3.31 (a)

RH101KA
63.1 25
2.48 .98

75
2.95

(a) Overall width – for determining DIN rail loading.


(b) Height above DIN rail (add to DIN rail height for total).
PSS 31H-2S247
Page 16

R E L AT E D P R O DU C T S P E C I F I C AT I O N S H E E T S

PSS Number Description

PSS 31H-2SOV Standard 200 Series Subsystem Overview


PSS 31H-2CERTS Standard and Compact 200 Series I/O - Agency Certifications
PSS 31H-2SBASPLT Standard 200 Series Baseplates
PSS 31H-2GOV G-Series Enclosures Overview
PSS 31H-4C2 Time Synchronization Equipment
PSS 31S-2SOE Sequence of Events
PSS 31S-2TDRA Transient Data Recorder and Analyzer
PSS 21S-3CP270IC Control Processor 270 (CP270) Integrated Control Software
PSS 31S-3FCPICS Field Control Processor 280 (CP280) Integrated Control Software

Schneider Electric Systems USA, Inc. Copyright 2015-2018 Schneider Electric.


38 Neponset Avenue All rights reserved.
Foxborough, MA 02035-2037
United States of America
www.schneider-electric.com Schneider Electric, Foxboro, Foxboro Evo,
FoxCom, and I/A Series, are trademarks owned by
Schneider Electric SE, its subsidiaries and affiliates.