Short CKT Calc

The document provides technical specifications for a medium voltage power cable, including its construction details, materials used, electrical ratings, testing requirements, and packaging details. Key specifications include the cable being copper/XLPE insulated with 3 cores of 300 mm^2 conductors, rated for 15 kV, and having a maximum operating temperature of 90°C.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
54 views3 pages

Short CKT Calc

The document provides technical specifications for a medium voltage power cable, including its construction details, materials used, electrical ratings, testing requirements, and packaging details. Key specifications include the cable being copper/XLPE insulated with 3 cores of 300 mm^2 conductors, rated for 15 kV, and having a maximum operating temperature of 90°C.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

short circuit calculations

system data
Medium Voltage Level = 13.8 KV
Low Voltage Level = 400 V
Bus 1 fault level = 25 KA

SOURCE IMPEDENCE

ZSOURCE = 0.3186973 Ω

ZSOURCE REF LV = 0.0002678 Ω


Cable from Medium voltage to SSt :
No. of Runs/phase = 1
Type of insulation = CU/XLPE
No. of cores of cable = 3C
Size of selected cable = 300 Sq.mm

Unit Cable Resistance R = 0.0804 Ω/km/Run


Unit Cable Reactance X = 0.120 Ω/km/Run
Cable Length = 20 m
Cable Impedence = √(R²c2+X²c2) = 0.144444315 Ω/km/Run
Total Cable Impedence (Zc1) = 0.00289 Ω
Total Cable Impedence (Zc1) REF LV = 0.00000 Ω
13.8kV/400V Transformer Data
MVA = 1500 kVA
Z = 5.00 %
Calculations:

Transformer Impedance = 0.005333333 Ω

Cable from Station Service Transformer to Main ACDB :


No. of Runs/phase = 3
Type of insulation = CU/XLPE
No. of cores of cable = 1C
Size of selected cable = 630 Sq.mm

Unit Cable Resistance R = 0.0420 Ω/km/Run


Unit Cable Reactance X = 0.081 Ω/km/Run
Cable Length = 20 m
Cable Impedence = √(R²c2+X²c2) = 0.091063934 Ω/km/Run
Total Cable Impedence (Zc2) = 0.00061 Ω

Total Impedance on 400 V = SOURCE IMPEDENCE + Zc1+Transformer Impedance + Zc2


side
= 0.00621 Ω

Fault level,400 V side = 37184.771 KA


TECHNOLOGY DEPARTMENT

TECHNICAL DATA SHEET


MEDIUM VOLTAGE POWER CABLES
Cable Description:
Cu / XLPE / LAT / PVC-FROR 3X300/200 mm2 15kV CWS IEC 60502-2 FR-IEC 60332-1
Design and Construction Data:
Reference Manufacturing Standard IEC 60502-2, IEC 60228
Max. Permissible Continuous Conductor Temp °C 90
Maximum Conductor Short Circuit Temperature for 5 Seconds °C 250
Rated Voltage ' Uo / U (Um) ' kV 8.7 / 15 (17.5)
Number of Cores x Conductor Cross-Section mm2 3 x 300
Conductor Material & shape Cu, Compacted Round Class 2
Approx. Diameter of Conductor mm 21.7
Conductor water tight Yes
Insulation Material XLPE
Nominal Thickness of Insulation mm 4.5
Approx. Cross Section Area of Copper Wire Screen mm2 200
Approx. No. , Thickness & Width of Helically O.H. Copper mm 1 x 0.1 x 15
Tape
Core Identification tape color (Red, Yellow, Blue)
Radial Water Protection Laminated Aluminium Tape
Nominal Thickness of Radial Water Protection Tape mm 0.3
Outer Sheath Material PVC - ST2
Approx. Overall Diameter of the Cable mm 102.0
Colour of Outer Sheath RED
Approx. Weight of Conductor kg/km 7900
Approx. net weight of the cable kg/km 18031
Electrical Data:
System Frequency Hz 60
Max. Conductor DC Resistance at 20°C Ohms/km 0.0601
Conductor AC Resistance at 90°C Ohms/km 0.0800
Inductance mH/km 0.3196
Inductive Reactance Ohms/km 0.120
Conductor Impedance at 90°C Ohms/km 0.144
Capacitance µF/km 0.4203
Charging Current Amps/km 1.379
Short Circuit Rating of Cable based on Maximum Conductor Operating Temperature
- Conductor for 1 second KA 42.90
- Screen for 1 second KA 25.06
Screen Temperature before Short Circuit °C 85
Screen Temperature at the end of Short Circuit °C 200
Permissible load under Service Conditions given below (for both end bond installation)
- In Air @ 40°C Ambient Temperature Amp 572
touched to vertical surface
- Direct in Ground with the following conditions: Amp 495
Ambient Ground Temperature: 35 °C
Depth of laying in ground: 0.8 m
Soil Thermal Resistivity: 1.2 °K.m/W

Inquiry No.: PS-012095 mmhussein 29/03/2022


Product ID: 23035120 Page 1 /2
TECHNOLOGY DEPARTMENT

Additional Data:
Maximum pulling Tension kN 45.0
Maximum side wall press kN/m 29.4
Minimum Bending Radius m 1.530
The Cable shall meet all Test requirements of IEC-60502-2 Yes
Packing Data:
Drum Type Non-Returnable
Length of Cable per drum (± 5%) m 500
Drum Dimensions "Height x Width" (Approx.) m 3 x 1.66
Gross Weight (Approx.) kg 9,890
Cable Sheath Marking:
BAHRA CABLES CO. KSA ELECTRIC CABLE 3x300/200 mm² CU / XLPE-4.5 mm / LAT / PVC 13.8 KV IEC
60502-2 FR-IEC 60332-1 OIL RESIS. (UV Resis.) 'Manufacturing Year' 'Meter marked' - PROPERTY OF
SAUDI ELECTRICITY COMPANY - 'Arabic Marking is required'"
Arabic ‫خاص بالشركة السعودية للكهرباء‬
Cable Drawing:

1 2

3 4

5 6

Description Cu / XLPE / LAT / PVC-FROR 3X300/200 mm2 15kV CWS Approx. Diameter
1 Core
- Copper Conductor (Longitudinal Water Tight) 21.72
- Extruder Inner Semi-Conductor 22.98
- Extruded XLPE insulation 31.98
- Extruder Outer Semi-Conductor (Strippable) 34.54
- SemiCon Water Blocking Tape 35.66
- Copper Wire Metallic Screen 39.12
- SemiCon Water Blocking Tape 40.24
2 Extruded Filling 90.56
3 Non Conductive Water Blocking Tape 91.06
4 Laminated Aluminum Tape (LAT) 91.96
5 LLDPE Inner Covering 95.22
6 PVC Outer Sheath 101.99

Inquiry No.: PS-012095 mmhussein 29/03/2022


Product ID: 23035120 Page 2 /2