0% found this document useful (0 votes)
14 views

Single Phase Transformer Test Systems

These single-phase transformer test systems provide voltages and currents to test single-phase distribution transformers. They allow testing transformers for life verification, after repair or upgrade, or for preventive maintenance to ensure performance is met. Tests performed include excitation current, excitation loss, impedance voltage, copper loss, and temperature measurement in accordance with standards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
14 views

Single Phase Transformer Test Systems

These single-phase transformer test systems provide voltages and currents to test single-phase distribution transformers. They allow testing transformers for life verification, after repair or upgrade, or for preventive maintenance to ensure performance is met. Tests performed include excitation current, excitation loss, impedance voltage, copper loss, and temperature measurement in accordance with standards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Single-Phase Transformer Test Systems

➤ Verified, proven design


Testing Applications ➤ Minimal set-up time
Ensure that a transformer’s performance ➤ Quick, accurate and reliable testing
is met for life
• verifying a manufacturer’s test and
design data prior to installation
• after repair or upgrade
• when a major disruptive event
occurs, such as a lightning strike
• for preventive/predictive
maintenance

Model TTS30-1

Model TTS10M
CABLE GIS CIRCUIT TRANSFORMER MOTOR GENERATOR INSULATION RECLOSER PROTECTIVE PORTABLE

G
SWITCHGEAR BREAKER MATERIALS EQUIPMENT

Specifications are subject to change without notice. Brochure No. 20106


SAFETY and DESIGN FEATURES Phenix Technologies’ Single-phase Transformer Test Systems are designed
to provide voltages and currents to test single-phase distribution
• Circuit breaker protection transformers.
• High voltage On/Off pushbuttons with
The size of transformers which can be tested will vary with impedance.
indicator
Test systems equipped with optional high voltage taps will allow testing
• External interlock provision of transformers with higher impedances and/or higher secondary voltages.
• Slow- and fast-acting overload The precision metering system complies with DOE efficiency and
protection international transformer standards.
• Zero Start interlock Testing will ensure that a transformer meets purchase specifications
• Output overload indicator with reset and will perform adequately after installation.
switch
Perform the following tests in accordance with ANSI / IEEE C57 and
• Multi-range metering IEC60076 standards:
• Temperature meter with 15 foot • Excitation Current Measurement
(4.5 meter) thermocouple
• Excitation Loss (No-Load or Core Loss)
• Four-wire measurement system for
accurate readings • Impedance Voltage Measurement

• Surge protection devices on all meters • Copper Loss (Load Loss)


and relays • Temperature Measurement
• Recalibration provisions for all meters • Temperature Measurement (Heat Run) (via models TTS20-1,
• Foot switch for operator safety TTS30-1,TTS50-1 only)

• Flashing red warning lamp Additional testing can be performed when the following options are
• Two copies of operation/maintenance added:
manual • Applied Potential Test with the addition of an AC Hipot
• Induced Potential Test with the addition of a Motor Generator Set
• Turns Ratio Test with the addition of a Transformer Turns Ratio Test Set
• Winding Resistance Measurement with the addition of a Winding
Resistance Meter

Unique to Models TTS5M & TTS10M Unique to Models TTS20-1, TTS30-1, TTS50-1
• Manual control of output voltage • The Human Machine Interface (HMI) allows the programming of
automation features of the test set. All output meters are displayed
• Hold function for all meters
on the LCD screen. Data acquisition and report generation of the
• Three constant kVA taps test results are performed via computer and WIN TTS testing software
• Casters for ease of mobility with all required interface cables included. The HMI eliminates a
large number of relays and meter wiring which increases reliability.
• Cable storage hooks
All calibration functions are performed and component self-
checks are achieved which aid a service technician in locating
malfunctioning components in the event of a failure.
• Zero Start interlock with auto return of regulator to zero position
• Raise and Lower pushbuttons with Off Zero indicator
• Motorized control of output voltage with adjustable rate of rise
• Control power key switch with indicator
• EMERGENCY OFF mushroom switch
• Motorized tap selector with indicators
ENVIRONMENTAL CONDITIONS • Auto-ranging wattmeter and voltmeter with direct readout
• 15 foot (4.5 meter) output leads with boots and clips (separate
• 10-40°C, indoor/outdoor in fair
power and measurement leads). Jacks for output leads are
weather recessed for operator safety; leads are removable for operator
• Humidity <95% non-condensing convenience
• Altitude <3300 ft (1000 meters) • Fork truck and overhead lifting provisions.

www.phenixtech.com

PHENIX
MODEL TTS5M TTS10M
Impedance 2% 4% 6% 2% 4% 6%
MAXIMUM TEST
CAPABILITY
APPROX.
Load Loss 375 kVA 188 kVA 125 kVA 750 kVA 375 kVA 250 kVA

Primary Voltage 30 kV 15 kV 10 kV 30 kV 15 kV 10 kV
of Transformer
         
 
Voltage/Current 208/230 VAC, 40 A, single phase 208/230 VAC, 80 A, single phase
INPUT

Frequency 50 or 60 Hz (one must be specified) 50 or 60 Hz (one must be specified)


(Other input voltages are available; consult factory)

  Current Current
TAP Voltage Voltage
Continuous 5 min ON/15 min OFF Continuous 5 min ON/15 min OFF
OUTPUT

1 0-150 VAC 33 AAC 50 AAC 0-150 VAC 67 AAC 100 AAC


2 0-300 VAC 16.5 AAC 25 AAC 0-300 VAC 33.5 AAC 50 AAC
3 0-600 VAC 8.3 AAC 12.5 AAC 0-600 VAC 16.7 AAC 25 AAC

Metering/ 4 1/2 digit with LED display, MODEL TTS5M TTS10M


Accuracy ±0.5% of reading +0.2% of range

APPROXIMATE
L 32” (813 mm)

DIMENSIONS
METERING

0-150/300/600 VAC, selectable True RMS

& WEIGHTS
Voltmeter
or Average W 29” (737 mm)
Currentmeter 0-1.999/19.99/199.9 A, True RMS
H 52” (1321 mm)
Wattmeter Auto Ranging
Temperature 0-100°, Accuracy ±1° C Wt 455 lbs (206 kgs) 510 lbs (231 kgs)

MODEL TTS20-1 TTS30-1 TTS50-1


APPROX. MAXIMUM

Impedance 2% 4% 6% 2% 4% 6% 2% 4% 6%
TESTCAPABILITY

Load Loss 1000 kVA 500 kVA 333 kVA 1500 kVA 750 kVA 500 kVA 2500 kVA 1250 kVA 833 kVA

Heat Run 500 kVA 250 kVA 167 kVA 750 kVA 375 kVA 250 kVA 1250 kVA 625 kVA 417 kVA
Primary Voltage
of Transformer 120 kV 60 kV 40 kV 120 kV 60 kV 40 kV 120 kV 60 kV 40 kV

Voltage/
208-600 VAC, 22 kVA 208-600 VAC, 33 kVA 208-600 VAC, 55 kVA
INPUT

Current
(voltage must be specified) (voltage must be specified) (voltage must be specified)
Frequency 50 or 60 Hz (one must be specified) 50 or 60 Hz (one must be specified) 50 or 60 Hz (one must be specified) 
                     
Current Current Current
Voltage 5 min ON/ Voltage 5 min ON/ Voltage 5 min ON/
TAP Continuous 15 min OFF Continuous 15 min OFF Continuous 15 min OFF
1 0-240 VAC 42 AAC 83 AAC 0-240 VAC 63 AAC 125 AAC 0-240 VAC 104 AAC 208 AAC
OUTPUT

2 0-300 VAC 33 AAC 67 AAC 0-300 VAC 50 AAC 100 AAC 0-300 VAC 83 AAC 167 AAC
3 0-480 VAC 21 AAC 42 AAC 0-480 VAC 31 AAC 63 AAC 0-480 VAC 52 AAC 104 AAC
4 0-600 VAC 17 AAC 33 AAC 0-600 VAC 25 AAC 50 AAC 0-600 VAC 42 AAC 83 AAC
5 0-1000 VAC 10 AAC 20 AAC 0-1000 VAC 15 AAC 30 AAC 0-1000 VAC 25 AAC 50 AAC
6 0-1600 VAC 6.3 AAC 12.5 AAC 0-1600 VAC 9.4 AAC 19 AAC 0-1600 VAC 16 AAC 32 AAC
7 0-2400 VAC 4.2 AAC 8.3 AAC 0-2400 VAC 6.3 AAC 12.5 AAC 0-2400 VAC 10.4 AAC 21 AAC

4 digit, Accuracy: ± 0.5% of reading +0.2% of range MODEL TTS20-1 / TTS30-1 / TTS50-1
Voltmeter Multi-range, Auto-ranging from 24-1600 VAC,
selectable True RMS or Average
DIMENSIONS & WEIGHTS

L 70” (1778 mm)


Currentmeter 4 digit, Accuracy: ± 0.5% of reading +0.2% of range
APPROXIMATE

0-1.000/10.00/100.0 Amps, True RMS


METERING

W 45” (1143 mm)


4 digit, Accuracy: 1.0 pF: ± 0.5% of F.S. ± LSD,
0.3 pF: ± 1.5% of F.S. ± LSD,
Wattmeter 0.1 pF: ± 3.0% of F.S. ± LSD H 76” (1930 mm)
Auto-ranging

Temperature 4 digit, Accuray ±-3° C Wt 1500-1900 LBS (680-862 kgs)
0-199.9° C

+1.301.746.8118

PHENIX
TESTING SOFTWARE MODEL TTS5M & TTS10M
Input Power 15’ (4.5 m)

Power

INCLUDED

Interconnect 10’ (3 m)

CABLES

Meter

Interconnect 10’ (3 m)
Ground 15’ (4.5 m)
Thermocouple 15’ (4.5 m)

MODEL TTS20-1/ TTS30-1/ TTS50-1

INCLUDED
CABLES
Output
15’ (4.5 m)  
Leads

OPTIONS
• Applied Potential Testing Capability via AC Hipot, cylinder-type
• Induced Potential Testing Capability via Motor Generator Set
includes ON/OFF controls and frequency meter built into the
control panel
• Transformer Turns Ratio Test Set,
Type ATTR-01 or Type PATTR-03A
• Transformer Winding Resistance Meter, Type WRM-10P
• Laptop Computer
• External Printer

OPTIONS Available for Models TTS5M and TTS10M


• Computer Interface and Testing Software
Includes RS232 output for interfacing all metering of the test
system to a computer. The software performs all loss calculations
(including correction for temperature and sine wave basis),
records all test data, and generates reports.

OPTIONS Available for Models TTS20-1, TTS30-1, TTS50-1


• Variable Frequency / Electronic Power Supply
– Replaces variable transformer and motor generator
– Adds 50 Hz testing capability (selectable 50/60/400 Hz)
– Less than 2% Total Harmonic Distortion (THD)
– Main input requirement changes to 3 phase
• Remote Control Console with writing desk and 25 foot (7.6 m)
interconnect cables (longer cables are available upon request)

C
High Voltage • High Current • High Power Test Systems and Components ISOER9001
TIFIED

World Headquarters Branch Offices


Phenix Technologies, Inc. Phenix Systems AG
Riehenstrasse 62A, 4058 Basel, Switzerland
75 Speicher Drive Ph: +41.61.383.2770 • Fx: +41.61.383.2771
Accident, MD 21520 USA [email protected]

PHENIX Ph: +1.301.746.8118


Fx: +1.301.895.5570
Phenix Asia
Zhong Cheng Rd, Sec 1, No 177, 2F, Taipei 11148 Taiwan
Ph: +886.2.2835.9738 • Fx: +886.2.2835.9879
TECHNOLOGIES [email protected] [email protected]

www.phenixtech.com © Copyright – Phenix Technologies, Inc. 7/2016

You might also like