Single Phase Transformer Test Systems
Single Phase Transformer Test Systems
Model TTS30-1
Model TTS10M
CABLE GIS CIRCUIT TRANSFORMER MOTOR GENERATOR INSULATION RECLOSER PROTECTIVE PORTABLE
G
SWITCHGEAR BREAKER MATERIALS EQUIPMENT
• Flashing red warning lamp Additional testing can be performed when the following options are
• Two copies of operation/maintenance added:
manual • Applied Potential Test with the addition of an AC Hipot
• Induced Potential Test with the addition of a Motor Generator Set
• Turns Ratio Test with the addition of a Transformer Turns Ratio Test Set
• Winding Resistance Measurement with the addition of a Winding
Resistance Meter
Unique to Models TTS5M & TTS10M Unique to Models TTS20-1, TTS30-1, TTS50-1
• Manual control of output voltage • The Human Machine Interface (HMI) allows the programming of
automation features of the test set. All output meters are displayed
• Hold function for all meters
on the LCD screen. Data acquisition and report generation of the
• Three constant kVA taps test results are performed via computer and WIN TTS testing software
• Casters for ease of mobility with all required interface cables included. The HMI eliminates a
large number of relays and meter wiring which increases reliability.
• Cable storage hooks
All calibration functions are performed and component self-
checks are achieved which aid a service technician in locating
malfunctioning components in the event of a failure.
• Zero Start interlock with auto return of regulator to zero position
• Raise and Lower pushbuttons with Off Zero indicator
• Motorized control of output voltage with adjustable rate of rise
• Control power key switch with indicator
• EMERGENCY OFF mushroom switch
• Motorized tap selector with indicators
ENVIRONMENTAL CONDITIONS • Auto-ranging wattmeter and voltmeter with direct readout
• 15 foot (4.5 meter) output leads with boots and clips (separate
• 10-40°C, indoor/outdoor in fair
power and measurement leads). Jacks for output leads are
weather recessed for operator safety; leads are removable for operator
• Humidity <95% non-condensing convenience
• Altitude <3300 ft (1000 meters) • Fork truck and overhead lifting provisions.
www.phenixtech.com
PHENIX
MODEL TTS5M TTS10M
Impedance 2% 4% 6% 2% 4% 6%
MAXIMUM TEST
CAPABILITY
APPROX.
Load Loss 375 kVA 188 kVA 125 kVA 750 kVA 375 kVA 250 kVA
Primary Voltage 30 kV 15 kV 10 kV 30 kV 15 kV 10 kV
of Transformer
Voltage/Current 208/230 VAC, 40 A, single phase 208/230 VAC, 80 A, single phase
INPUT
Current Current
TAP Voltage Voltage
Continuous 5 min ON/15 min OFF Continuous 5 min ON/15 min OFF
OUTPUT
APPROXIMATE
L 32” (813 mm)
DIMENSIONS
METERING
& WEIGHTS
Voltmeter
or Average W 29” (737 mm)
Currentmeter 0-1.999/19.99/199.9 A, True RMS
H 52” (1321 mm)
Wattmeter Auto Ranging
Temperature 0-100°, Accuracy ±1° C Wt 455 lbs (206 kgs) 510 lbs (231 kgs)
Impedance 2% 4% 6% 2% 4% 6% 2% 4% 6%
TESTCAPABILITY
Load Loss 1000 kVA 500 kVA 333 kVA 1500 kVA 750 kVA 500 kVA 2500 kVA 1250 kVA 833 kVA
Heat Run 500 kVA 250 kVA 167 kVA 750 kVA 375 kVA 250 kVA 1250 kVA 625 kVA 417 kVA
Primary Voltage
of Transformer 120 kV 60 kV 40 kV 120 kV 60 kV 40 kV 120 kV 60 kV 40 kV
Voltage/
208-600 VAC, 22 kVA 208-600 VAC, 33 kVA 208-600 VAC, 55 kVA
INPUT
Current
(voltage must be specified) (voltage must be specified) (voltage must be specified)
Frequency 50 or 60 Hz (one must be specified) 50 or 60 Hz (one must be specified) 50 or 60 Hz (one must be specified)
Current Current Current
Voltage 5 min ON/ Voltage 5 min ON/ Voltage 5 min ON/
TAP Continuous 15 min OFF Continuous 15 min OFF Continuous 15 min OFF
1 0-240 VAC 42 AAC 83 AAC 0-240 VAC 63 AAC 125 AAC 0-240 VAC 104 AAC 208 AAC
OUTPUT
2 0-300 VAC 33 AAC 67 AAC 0-300 VAC 50 AAC 100 AAC 0-300 VAC 83 AAC 167 AAC
3 0-480 VAC 21 AAC 42 AAC 0-480 VAC 31 AAC 63 AAC 0-480 VAC 52 AAC 104 AAC
4 0-600 VAC 17 AAC 33 AAC 0-600 VAC 25 AAC 50 AAC 0-600 VAC 42 AAC 83 AAC
5 0-1000 VAC 10 AAC 20 AAC 0-1000 VAC 15 AAC 30 AAC 0-1000 VAC 25 AAC 50 AAC
6 0-1600 VAC 6.3 AAC 12.5 AAC 0-1600 VAC 9.4 AAC 19 AAC 0-1600 VAC 16 AAC 32 AAC
7 0-2400 VAC 4.2 AAC 8.3 AAC 0-2400 VAC 6.3 AAC 12.5 AAC 0-2400 VAC 10.4 AAC 21 AAC
4 digit, Accuracy: ± 0.5% of reading +0.2% of range MODEL TTS20-1 / TTS30-1 / TTS50-1
Voltmeter Multi-range, Auto-ranging from 24-1600 VAC,
selectable True RMS or Average
DIMENSIONS & WEIGHTS
+1.301.746.8118
PHENIX
TESTING SOFTWARE MODEL TTS5M & TTS10M
Input Power 15’ (4.5 m)
Power
INCLUDED
Interconnect 10’ (3 m)
CABLES
Meter
Interconnect 10’ (3 m)
Ground 15’ (4.5 m)
Thermocouple 15’ (4.5 m)
INCLUDED
CABLES
Output
15’ (4.5 m)
Leads
OPTIONS
• Applied Potential Testing Capability via AC Hipot, cylinder-type
• Induced Potential Testing Capability via Motor Generator Set
includes ON/OFF controls and frequency meter built into the
control panel
• Transformer Turns Ratio Test Set,
Type ATTR-01 or Type PATTR-03A
• Transformer Winding Resistance Meter, Type WRM-10P
• Laptop Computer
• External Printer
C
High Voltage • High Current • High Power Test Systems and Components ISOER9001
TIFIED