DOC UMENT I D: 7 PAA0 0 25 36

RE VI SI ON: A
DATE : 2 0 24 - 03 - 26
S EC URIT Y LE VEL: P UBL IC


C Y B E R S E C U R I T Y A DV I S O RY

SECURITY – Denial of Service Vulnerability in


Control API ‘VPNI’, impact on S+ Operations, S+
Engineering and S+ Analyst
CVE ID: CVE-2024-0335

Notice
The information in this document is subject to change without notice, and should not be construed as a commit-
ment by ABB.

ABB provides no warranty, express or implied, including warranties of merchantability and fitness for a particular
purpose, for the information contained in this document, and assumes no responsibility for any errors that may
appear in this document. In no event shall ABB or any of its suppliers be liable for direct, indirect, special, incidental
or consequential damages of any nature or kind arising from the use of this document, or from the use of any hard-
ware or software described in this document, even if ABB or its suppliers have been advised of the possibility of
such damages.

This document and parts hereof must not be reproduced or copied without written permission from ABB, and the
contents hereof must not be imparted to a third party nor used for any unauthorized purpose.

All rights to registrations and trademarks reside with their respective owners.

© Copyright 2024 ABB. All rights reserved. 1/7


DOC UMENT I D: 7 PAA0 0 25 36 C YBER SE C URIT Y A DVI SO RY
RE VI SI ON: A
DATE : 2 0 24 - 03 - 26
S EC URIT Y LE VEL: P UBL IC

Purpose
ABB has a rigorous internal cyber security continuous improvement process which involves regular testing with
industry leading tools and periodic assessments to identify potential product issues. Occasionally an issue is deter-
mined to be a design or coding flaw with implications that may impact product cyber security.

When a potential product vulnerability is identified or reported, ABB immediately initiates our vulnerability han-
dling process. This entails validating if the issue is in fact a product issue, identifying root causes, determining what
related products may be impacted, developing a remediation, and notifying end users and governmental organiza-
tions (e.g. ICS-CERT).

The resulting Cyber Security Advisory intends to notify customers of the vulnerability and provide details on which
products are impacted, how to mitigate the vulnerability or explain workarounds that minimize the potential risk as
much as possible. The release of a Cyber Security Advisory should not be misconstrued as an affirmation or indica-
tion of an active threat or ongoing campaign targeting the products mentioned here. If ABB is aware of any specific
threats, it will be clearly mentioned in the communication.

The publication of this Cyber Security Advisory is an example of ABB’s commitment to the user community in sup-
port of this critical topic. Responsible disclosure is an important element in the chain of trust we work to maintain
with our many customers. The release of an Advisory provides timely information which is essential to help ensure
our customers are fully informed.

Affected products
Product / System line Products and Affected Versions

S+ Operations Versions 3.3 SP1 RU4 and earlier are affected.


Versions 2.1 SP2 RU3 and earlier are affected.
Versions 2.0 SP6 TC6 and earlier are affected.
S+ Engineering Versions 2.1 through 2.3 RU3 are affected.

S+ Analyst Versions 7.0.0.0 to 7.2.0.2 using Fast Data Logger are affected.
Note: S+ Analyst with Vibration Analysis will not be affected by the Control API VPNI
vulnerability because it does not use it.

Vulnerability IDs
CVE-2024-0335

Summary
ABB has internally identified a vulnerability in the ABB VPNI 1 feature of the S+ Control API component which may
be used by several Symphony Plus products (e.g., S+ Operations, S+ Engineering and S+ Analyst).

1 The Virtual PNI (VPNI) is a feature of the Windows-based Control API Runtime software provided with S+ Engineering product.

© Copyright 2024 ABB. All rights reserved. 2/7


DOC UMENT I D: 7 PAA0 0 25 36 C YBER SE C URIT Y A DVI SO RY
RE VI SI ON: A
DATE : 2 0 24 - 03 - 26
S EC URIT Y LE VEL: P UBL IC

If an attacker gains access to a site’s HMI network, then exploiting this vulnerability will result in a denial-of-service
(DoS) of the VPNI, which would prevent data transfer from/to the above affected S+ products that utilize the feature
to connect to the HMI network.

The unavailability of the VPNI would prevent data transactions by the connected S+ Operations, S+ Engineering and
Analyst workstations but would not affect the system configuration data, nor the Symphony Plus HMI network.

Recommended immediate actions


ABB advises all customers to review their installations to determine if they are using an impacted product as listed
above, no further analysis or tools are needed to make this determination. The recommended immediate actions for
S+ products using the VPNI feature are listed below:

– S+ Operations

Systems using S+ Operations versions 3.3 SP1 RU4 or earlier should upgrade to version 3.3 SP1 RU5 (planned
for Q3 2024) or later.

Systems using S+ Operations 2.1 SP2 RU3 or earlier should upgrade to version 3.3.1 RU5 (planned for Q3 2024)
or later.

Systems using S+ Operations 2.0 SP6 TC6 or earlier should upgrade to version 3.3 SP1 RU5 (planned for Q3
2024) or later.

– S+ Engineering

Systems using S+ Engineering 2.1 through 2.3 RU3 should upgrade to S+ Engineering 2.4 (released in January
2023) or later.

– S+ Analyst

Systems using S+ Analyst with Vibration Analysis will not be affected by the VPNI problem because it does not
use it. Systems using S+ Analyst with the Fast Data Logger versions 7.0.0.0 to 7.2.0.2 should upgrade to version
7.3 (planned for Q2 2024) or later.

End users who are unable to install one of these updates should immediately look to implement the Mitigation and
Workarounds listed below as this will restrict or prevent an attacker’s ability to compromise these systems.

ABB recommends that customers apply the update at earliest convenience.

Vulnerability severity and details


A vulnerability exists in the VPNI feature included in the product revisions listed above.

The severity assessment has been performed by using the FIRST Common Vulnerability Scoring System (CVSS)
v3.12.

2The CVSS Environmental Score, which can affect the vulnerability severity, is not provided in this advisory since it reflects the potential
impact of a vulnerability within the end-user organizations’ computing environment; end-user organizations are therefore recommended
to analyze their situation and specify the Environmental Score.

© Copyright 2024 ABB. All rights reserved. 3/7


DOC UMENT I D: 7 PAA0 0 25 36 C YBER SE C URIT Y A DVI SO RY
RE VI SI ON: A
DATE : 2 0 24 - 03 - 26
S EC URIT Y LE VEL: P UBL IC

CVE-2024-0335 - Malformed Packet Handling


An attacker could exploit the vulnerability by formatting the VPNI protocol packet with some invalid values, causing
the VPNI service to be unresponsive (crash), resulting in a denial-of-service situation.

CVSS v3.1 Base Score: 7.5 High


CVSS v3.1 Temporal Score: 7.2 High
CVSS v3.1 Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:H/RL:O/RC:C
NVD Summary Link: https://nvd.nist.gov/vuln/detail/CVE-2024-0335

Mitigating factors
Any exploit of this vulnerability would require that the attacker has access to the site’s client/server HMI network.
Following ABB’s recommended security practices, including network architecture and perimeter firewall, are miti-
gating factors in preventing external access to the HMI network.

Note that to reduce the impact on the VPNI unavailability, the VPNI can be configured to automatically restart after
a few minutes (see figure 6.4 in section 6.1 of the “S+ System Virtual PNI installation and configuration user man-
ual”, 2VAA003419).

Refer to section “General security recommendations” for the above ABB security practices and further advice on
how to keep your system secure.

Workarounds
No workarounds are available. Assess the installation specific risk based on this advisory. Use the recommendations
described under “Mitigating factors” and “Recommended immediate actions”.

Frequently asked questions


What is the scope of the vulnerability?
An attacker who successfully exploited this vulnerability could remotely cause the VPNI to stop (denial of service).
Symphony Plus applications using the VPNI functionalities (affected products are S+ Operations, S+ Engineering
and S+ Analyst) will not be able to use the service which has been stopped. This does not affect the other Symphony
Plus functionalities, nor the HMI network.

What causes the vulnerability?


The vulnerability is caused by an incorrect handling of invalid values in the VPNI protocol packet.

What is the Virtual PNI (VPNI)?


The Virtual PNI (VPNI) is a feature of the Windows-based Control API Runtime software provided with several S+
products. It is a Control API communications server configured to act as a CIU and provide PN800 connectivity to S+
Operations and Engineering servers and Analyst.

What might an attacker use the vulnerability to do?


An attacker can use the vulnerability to cause a denial-of-service situation which could affect the online activities of
the connected S+ Operations, Engineering and Analyst.

© Copyright 2024 ABB. All rights reserved. 4/7


DOC UMENT I D: 7 PAA0 0 25 36 C YBER SE C URIT Y A DVI SO RY
RE VI SI ON: A
DATE : 2 0 24 - 03 - 26
S EC URIT Y LE VEL: P UBL IC

How could an attacker exploit the vulnerability?


To exploit the vulnerability an attacker would need to get access to the site’s HMI network. With that access gained,
the attacker would need to send invalid packets to the VPNI service. Those messages could cause the VPNI compo-
nent to stop (crash) which would no longer respond to data transfer requests from client applications (which can
be described as a Denial-of-Service condition).

Could the vulnerability be exploited remotely?


Yes, an attacker who has network access to client/server HMI network could exploit this vulnerability. Recom-
mended practices include that process control systems are physically protected, have no direct connections to the
Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports
exposed.

Can functional safety be affected by an exploit of this vulnerability?


Functional safety systems are not affected by these vulnerabilities.

What does the update do?


The updates for the affected products remove the vulnerability by improving the VPNI handling of invalid packet
values.

When this security advisory was issued, had this vulnerability been publicly disclosed?
No, ABB had identified this through an internal evaluation.

When this security advisory was issued, had ABB received any reports that this vulnerability
was being exploited?
No, ABB had not received any information indicating that this vulnerability had been exploited when this security
advisory was originally issued.

General security recommendations


Control systems and the control network are exposed to cyber threats. To minimize these risks, the protective
measures and best practices listed below are available in addition to other measures. ABB strongly recommends
system integrators and asset owners to implement the measures they consider appropriate for their control system
environment:

– Place control systems in a dedicated control network containing control systems only.

– Locate control networks and systems behind firewalls and separate them from any other networks like business
networks and the Internet.

– Block any inbound Internet traffic destined for the control networks/systems. Place remote access systems used
for remote control system access outside the control network.

– Limit outbound Internet traffic originating from control systems/networks as much as possible. If control sys-
tems must talk to the Internet, tailor firewall rules to required resources - allow only source IPs, destination IPs
and services/destination ports which control systems definitely need to use for normal control operation.

– If Internet access is required on occasion only, disable relevant firewall rules and enable them during the time
window of required Internet access only. If supported by your firewall, define an expiry date and time for such
rules – after the expiry date and time, the firewall will disable the rule automatically.

© Copyright 2024 ABB. All rights reserved. 5/7


DOC UMENT I D: 7 PAA0 0 25 36 C YBER SE C URIT Y A DVI SO RY
RE VI SI ON: A
DATE : 2 0 24 - 03 - 26
S EC URIT Y LE VEL: P UBL IC

– Limit exposure of control networks/systems to internal systems. Tailor firewall rules allowing traffic from inter-
nal systems to control networks/systems to allow only source IPs, destination IPs and services/destination
ports which are definitely required for normal control operation.

– Create strict firewall rules to filter malicious network traffic targeting control system vulnerabilities ("exploit
traffic"). Exploit traffic may use network communication features like source routing, IP fragmentation and/or
IP tunneling. If such features are not required for normal control operation, block them on your firewall.

– If supported by your firewall, apply additional filters to allowed traffic which provide protection for control net-
works/systems. Such filters are provided by advanced firewall features like Application Control and Anti-Virus.

– Use Intrusion Detection Systems (IDS) or Intrusion Preventions Systems (IPS) to detect/block control system-
specific exploit traffic. Consider using IPS rules protecting against control system exploits.

– When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Please ensure
that VPN solutions are updated to the most current version available.

– In case you want to filter internal control network traffic, consider using solutions supporting Intra-LAN traffic
control like VLAN access control lists.

– Harden your control systems by enabling only the ports, services and software required for normal control op-
eration. Disable all other ports and disable/uninstall all other services and software.

– If possible, limit the permissions of user accounts, software processes and devices to the permissions required
for normal control operation.

– Use trusted, patched software and malware protection solutions. Interact with trusted web sites and trusted
email attachments only.

– Ensure all nodes are always up to date in terms of installed software, operating system and firmware patches as
well as anti-virus and firewall.

– Protect control systems from physical access by unauthorized personnel e.g. by placing them in locked switch
cabinets.

More information on recommended practices can be found in the following documents 3:

2VAA003419 S+ System Virtual PNI installation and configuration user manual

8VZZ001006 Symphony Plus Secure deployment guide for Windows 10 and Server 2016/2019 user
manual

2PAA121027 Distributed Control Systems - McAfee® ePO with VirusScan Enterprise, Endpoint Security
and Application Control

8VZZ000602 Microsoft Security Updates Validation Status for Symphony Plus

8VZZ001753 McAfee Virus Scan DAT Update Validation Status for Symphony Plus

2PAA122516 System 800xA, Symphony Plus and Freelance System Hardening - End user manual

2PAA120528 System 800xA, Symphony Plus and Freelance System Hardening: Group Policies Overview

8VZZ000368D0066 ICS Cyber Security Reference Architecture Guide

3 Access to some listed documents can be subject to the ABB Care Automation Software Maintenance specific conditions and agreements.

© Copyright 2024 ABB. All rights reserved. 6/7


DOC UMENT I D: 7 PAA0 0 25 36 C YBER SE C URIT Y A DVI SO RY
RE VI SI ON: A
DATE : 2 0 24 - 03 - 26
S EC URIT Y LE VEL: P UBL IC

Support
For additional instructions and support please contact your local ABB service organization. For contact information,
see www.abb.com/contactcenters.

Information about ABB’s cyber security program and capabilities can be found at www.abb.com/cybersecurity.

Revision history
Rev. Page (p) Change description Rev. date
Ind. Chapter (c)
A all Initial version 2024/3/26

© Copyright 2024 ABB. All rights reserved. 7/7