HUe - User Manual - EN - 08
HUe - User Manual - EN - 08
Part of EasyLogic
M588AB000y / HUe
User Manual
This manual provides information for the assembly, wiring, configuration, and
maintenance of the HUe module.
SE-USR-M588
www.se.com
Public
19/04/2024 User Manual – HUe
Change Control
07 1-11-2023 • Technical Specification table section updated with the reference to railways
certification (EN 51121-5)
General Information
The Saitel platform and all its components have been developed in accordance to the requirements
for a quality management system, complying with the ISO 9001:2015 Norm.
Reference Documents
Pag 2
User Manual – HUe 19/04/2024
Module Version
Baseline 11.06.27
Pag 3
19/04/2024 User Manual – HUe
Content
1 SAFETY & HEALTH ................................................................................................5
Pag 4
1 Safety & Health
Public
19/04/2024 User Manual – HUe
Content
1 SAFETY & HEALTH ................................................................................................5
Pag 6
User Manual – HUe 19/04/2024
1.1 Introduction
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious
injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or
serious injury.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety alert symbol shall
not be used with this signal word.
To Keep in Mind
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
A qualified person is who fulfill the requirements in section 1.2 .
1.1.2 Presentation
This manual provides information for an appropriate handling, commissioning and testing. This
chapter about Safety also includes descriptions of the labels on the equipment.
Documentation for equipment ordered from Schneider Electric is dispatched separately from
manufactured goods and may not be received at the same time. Therefore, this guide is provided in
order to printed information (which may be present on the equipment) is fully understood by the
recipient.
The technical data in this safety guide is typical only, see the technical data section of the user
manual for specific details of a particular equipment.
Pag 7
19/04/2024 User Manual – HUe
Before carrying out any work on the equipment the user should be familiar with the
contents of this Safety guide, the ratings on the equipment’s rating label and the user
manual.
THE SAFETY SECTION MUST BE READ BEFORE STARTING ANY WORK ON
THE EQUIPMENT.
The information in this chapter is provided in order to the equipment is properly installed and
handled maintaining it in a safety condition. It is assumed that everyone who will be associated with
the equipment will be familiar with the contents of that Safety section.
When electrical equipment is in operation, high voltages will be present in certain parts of the
equipment. Failure to observe warning notices, an incorrect or not appropriate use may endanger
personnel and equipment and also cause personal injury or physical damage.
WARNING
Before working with the terminal of connection, the equipment must be switched off and
disconnected of the power supply.
Proper and safe operation of the equipment depends on appropriate shipping and handling, proper
storage, installation and commissioning, and on careful operation, maintenance and servicing. For
this reason, only qualified personnel may work on or operate the equipment.
Qualified personnel are individuals who:
• Have read and understood the information on the device and its user manual.
• Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected.
• Are able to safely perform switching operations in accordance with accepted safety engineering
practices and are authorized to energize and de-energize equipment and to isolate, ground,
and label it.
• Are trained in the care and use of safety apparatus in accordance with safety engineering
practices.
Pag 8
User Manual – HUe 19/04/2024
Before the equipment is installed or commissioned, the user must understand the following
symbols, which may be used on the equipment or referred to in the user documentation:
Table 1 – Symbols
Symbol Associated Text Description
There are several acquisition blocks in Saitel DR that use high voltages (> 50 V). The user is
responsible to check that the characteristics of each equipment are adapted and convenient for his
installation. The user should read the instructions of installation before proceeding to the use or
maintenance of the equipment.
Not following these instructions can be dangerous for the people and the equipment.
Pag 9
19/04/2024 User Manual – HUe
DANGER
Devices that handle dangerous tensions are marked with a sticker on the front label (size: 12,5
mm). This label must be visible all the time while the module is installed on the DIN rail.
• HU_AF: Advanced head unit with acquisition (P/N M503xx3x0x and P/N M503xx4x0x). For
other part numbers, depending on the voltage handled by the equipment connected to the
digital outputs (voltage > 50 V), this module must be marked with an electric risk label. It will not
be marked on factory.
• AB_DIDO: Input and output digital module (P/N M5722x000x, M5723x000x and M5724x000x).
For other part numbers, depending on the voltage handled by the equipment connected to the
digital outputs (voltage > 50 V), this module must be marked with an electric risk label. It will not
be marked on factory.
• AB_DO: This module does not handle high voltages. This module must be labeled with an
electric risk label when some equipment that manage voltage higher than 50 V are connected
to digital outputs.
It is recommended to install the RTU inside a cabinet with a key. This cabinet only should be
opened by a qualified person.
WARNING
If this type of cabinet is not available, a barrier must be installed in order to avoid an accidental
contact with these dangerous elements. This barrier should only be able to be uninstalled using
a special tool.
If the barrier has to be removed in order to access to equipment, personnel responsible for the
task must be sure that the barrier is installed again when the task is finished.
While the RTU is accessible for a user, all people must follow all instructions to prevent
electrical risk or discharges.
Not following these instructions can give like result that the equipment do not work
properly or even can damage to the people or equipment.
An electrical risk symbol with enough size must be included on the cabinet’s door or
on the barrier.
Pag 10
User Manual – HUe 19/04/2024
NOTICE
Terminals will not be accessible to the user directly once it has made the installation of the
equipment. The cabinet will have to remain closed with key or the screen of installed protection.
The cabinet or installation must have a general switch placed just in the cable entry of the
installation (see paragraph 1.7.1 ).
For the cleaning of the equipment, it is recommended to remove the power and to use only a dry
cloth by the surface when it detects excessive presence of dust or any element deposited on the
surface.
WARNING
Do not use liquid products of cleanliness due to the presence of active parts.
Because of the variety of uses of the product, the managers of the application and use of this
controller device will have to take the measures to the fulfillment of all the safety requirements and
provision of each application. These requirements are according to the applicable laws,
regulations, codes and standard.
1.5 Earthing
WARNING
Before energizing the equipment, it has to be earthed properly such as it indicates in the
sections 1.5.1 and 1.5.2 .
When installing the equipment, ground is the first thing that should be connected and the last
one that should be disconnected.
• Improve the behavior in Electromagnetic Compatibility (EMC) and derive perturbations to earth
(functional Earth).
The modules must be installed on a metallic DIN Rail which is fixed on a metallic
surface. This metallic surface must have an M4 screw marked with this symbol.
According to the norm IEC 61010-1, the ground of the cabinet or installation must be
connected to this screw.
Saitel DR modules have a metallic enclosure offering protection for isolation faults.
WARNING
All electronic equipment with high voltage must be disconnected before dismounting a module
from the DIN rail.
A dedicated connection with green/yellow wire should be used to have electric continuity to the
installation protective earth. Use a wire with adequate section according to IEC 61010.
Pag 11
19/04/2024 User Manual – HUe
The design and installation of the cabinet is responsible for compliance with all the existing
international and national electrical codes concerning protective grounding of any equipment.
WARNING
According to Electrical Safety:
NOTICE
The DIN rail must have terminals of earthing (of yellow and green color) necessary to connect
the terminals of PE (if it is present).
All Saitel DR modules with power or polarization connector have an exclusive terminal for earthing
EMC. These modules are HUe, HU_B, HU_A, HU_AF, XU, AB_DO, AB_DIDO and AB_SER with
external polarization.
It must be connected as follows:
Figure 4 – Example of earthing for EMC
Pag 12
User Manual – HUe 19/04/2024
Like any electronic equipment, Saitel is susceptible to receive electrostatic discharges during the
handling. It is necessary to take the usual measures to minimize this risk, since serious damage to
the equipment can be caused, which may not be detected immediately but which may affect the
reliability of the product.
WARNING
The enclosure should ONLY be removed by authorized use and ONLY when is strictly
necessary because this action has a risk for the equipment. The following precautions will be
taken:
• Before removing the enclosure, the operator be equipotential with the equipment. The
operator must have a grounding bracelet and the device must be connected to ground
as well
• Avoid touching the electronic. The board must be always manipulated for the edges.
• If the equipment has to be passed between two persons, both must be equipotential.
• Put the module always on an antistatic surface or on a surface equipotential with the
operator.
• During the storage and transport, the module will remain in the packaging.
Not following these instructions can give like result that the equipment do not work
properly or even can damage the people or equipment.
WARNING
The connection / disconnection switch must be installed in a fixed element (for example the wall
of the cabinet) and it must not break any earthing wire.
WARNING
This equipment has been designed ONLY for indoor use.
If it is necessary for his use in some external surroundings, it has to mount in a cabinet or specific
accommodation that contributes at least a degree of protection IP54, protected against the dust
and water.
Pag 13
19/04/2024 User Manual – HUe
The electronic cards of the modules will be able to be tropicalized or not according to the
manufacturing option. The tropicalized used is the AVR80, of the company ABchimie. It can consult
all the technical information of this type of finishing in http://www.abchimie.com.
Other data to consider about the environmental are:
• Operation temperature range: Between -40 ºC and 70 ºC. (IEC 60068-2-1 and IEC 60068-2-2).
WARNING
According to the standard 60950-1, all electrical safety tests have been done in an
environmental temperature range of -40 ºC to 60 ºC. For higher temperature (> 60 ºC), the
module must be handled with care since the metal surface could reach a dangerous
temperature for the user.
Each Saitel product includes a technical label with the following information:
Figure 5 – Technical label
NOTICE
The “Technical data” includes a zone with relevant information about the input and output
voltage in the module. Any voltage greater than 50 V must be considered as a high voltage.
Pag 14
User Manual – HUe 19/04/2024
All Saitel modules are packaged separately in their own carton box and shipped inside outer
packaging. Use special care when unpacking the equipment. Do not use force.
NOTICE
Our products leave our factory in closed, sealed original packaging. If at receipt of the delivery
the transport packaging is open or the seal is broken, the confidentiality and authenticity of the
information contained in the products cannot be ensured.
The design revision and manufacturing options can be determined using the P/N included in the
packaging label on packaging.
After unpacking the equipment, inspect it visually to be sure it is in proper mechanical condition.
If the product needs to be shipped, the original packaging must be used, including foams and the
carton box. If the original packaging is no longer available, make sure that the packaging used is
according to ISO 2248 specifications for a drop height of 1 m.
This symbol, means that, at the end of its life cycle, the product must not be disposed
together with habitual residues. To avoid any possible damage to the environment or
to the human health that represents the uncontrolled elimination of residues, please,
separate the battery (if there is one) of the other elements, and each one must be
recycled according to the local regulation.
Pag 15
19/04/2024 User Manual – HUe
Pag 16
User Manual – HUe 19/04/2024
Content
2 GENERAL DESCRIPTION OF HUE ......................................................................16
Pag 17
19/04/2024 User Manual – HUe
Saitel DR – part of the EasyLogic range - is a hardware platform by Schneider Electric specifically
designed for real-time control and energy automation applications. Saitel DR is a high-technology
embedded platform which serves Schneider Electric’s business areas.
On this hardware platform, the Baseline Software Platform is installed. This software is used in
Saitel families (Saitel DP and Saitel DR) and other Schneider Electric products.
Other features identifying Saitel DR are:
• The communication between the controls units integrated in a distributed system is mainly
established by Ethernet.
• The terminal blocks for field-connection are completely built into acquisition blocks.
Figure 6 – Saitel DR
Saitel DR’s design has been optimized to meet the most demanding requirements of multiple
sectors:
• Safety and reliability requirements for power, gas and water supply, as well as sewage
treatment plants, etc.
• Local monitoring and control with data sharing capabilities of plant-distributed equipment.
NOTICE
Please, note Saitel DR does not support hot-swapping, that is, module replacements during
operation.
HUe is a high-performance CPU developed by Schneider Electric within the Saitel DR family. HUe
performs the control functions for the complete system, centralizes the information acquired by
other modules, and executes the programmable logic control, communication protocols and user-
specific applications.
The communication with the acquisition modules in the ITB is established by an internal high-speed
bus that makes the system highly reliable even in noisy environments.
Pag 18
User Manual – HUe 19/04/2024
ITB Controller
This block controls the operation of both the HU and the ABs connected to the HU through the bus.
These functions include:
• Operation mode monitoring. It performs functions as hardware and software Watchdog control,
the states control of the ABs and the HU and the provision of diagnostic information about the
ITB status through the LED indicators and several log files. These files can be consulted by a
user with sufficient privileges through SFTP or webApp.
• Interface with the operator through the console, webApp (for supervision and maintenance)
and Easergy Builder (for configuration).
• Firmware upgrade by SFTP or webApp (using MNT port) or USB 2.0 port.
ITB Configuration
HUe maintains and manages the information that supports the real-time database, coreDb. In this
database, the I/O signals are related to the communication protocols signals. The configuration is
based on XML files that are generated with the Easergy Builder tool. These files are generated on
a PC and sent to the CPU via an SFTP connection through the MNT port.
ITB Synchronization
Up to two different synchronization sources can be configured. In this configuration is included the
priority level for each source, so there will be a primary and a secondary source. If both sources
are active, only the primary source will synchronize the system.
NOTICE
The primary source is used to synchronize the ITB, if available. Otherwise, the secondary
source is used.
• A GPS connected to the COM1 port. The time received from the GPS is used to set the
system’s clock and the RTC.
• An SNTP source through Ethernet. HUe can be used as SNTP server and client.
• Console: The user can set the system's time manually from the console terminal.
• IRIG-B: HUe can be used as a server and/or a client. The communication always will be made
with IRIG-B compliant devices.
Pag 19
19/04/2024 User Manual – HUe
NOTICE
If the HUe is configured as IRIG-B server an AB_SER module must be included in the ITB. The
IRIG-B signal will be send to client devices through the COM ports of this module. More
information in the AB_SER user manual.
If the synchronization source is not configured, the console device will always be created by
default. The console operates as the lowest priority when other source is configured.
ITB Communications
The HUe configuration includes information about definition and parameterization of
communications:
I/O Acquisition
HUe manages the information exchange with the ABs. Its main functions include:
• Processing I/O information, which offers an added value to the information exchanged with the
ABs.
• The HUe module has 4 digital inputs that can be used as 4 general-purpose digital inputs or as
2 specific-purpose digital inputs and 2 general-purpose digital inputs (more details below in this
manual).
Pag 20
User Manual – HUe 19/04/2024
coreDb can also have as a source of information the result of a logic, which can be implemented by
a third-party software such as ISaGRAF® or within the database itself with an internal device of the
type "Formula".
Consult more information about this functionality in the Easergy Builder user manual.
Cybersecurity
The HUe module is supplied with a standard security policy, complemented with the definition of an
RBAC model (Role-Based Access Control). This model is defined and managed through a special
tool, CAE (EcoStruxure™ Cybersecurity Admin Expert.
2.3 Interfaces
The HUe module is a high-performance CPU, which offers superior performance to other Saitel DR
CPUs. It includes the Baseline Software Platform based on Linux operating system and with an
integrated cybersecurity brick.
Figure 9 – HUe front view
• A reset button integrated allowing the user to reset the module mechanically.
• It implements a security mechanism for data in memory (NVRAM) allowing to keep the
information for some time if the power is temporarily down.
• Synchronization using: IRIG-B input, PPS signal (through a GPS), console or SNTP.
• A watchdog isolated output is available and can be used according to the requirements of the
system.
Pag 21
19/04/2024 User Manual – HUe
• Two additional Fast-Ethernet ports, which can be copper (10/100BaseT) or fiber optic
(100BASE-FX) depending on the mounting options.
• Two RS-232 non-isolated communication ports. COM1 allows modem control but COM2 does
not.
• SD slot.
The HUe module is composed by two or three electronic boards, depending on the manufacturing
options.
Figure 10 – Electronic boards in HUe
These electronic boards and the metallic enclosure makeup the HUe module.
This information is shown in the technical label on the module with the Part Number (P/N):
Figure 11 – Part Number description
If the module is manufactured without optic fiber, only two boards will be mounted.
Ordering options:
• (Bx) Power supply. The module can be powered with 24 VDC or 48 VDC, both ±20%.
Pag 22
User Manual – HUe 19/04/2024
Pag 23
19/04/2024 User Manual – HUe
Content
3 PHYSICAL MOUNTING & INSTALLING ...............................................................23
Pag 24
User Manual – HUe 19/04/2024
WARNING
Electrostatic discharges may damage semi-conducive devices within the module.
NOTICE
In order to minimize the adverse effects of noise and heat, it is recommended to install the ITB’s
head unit as far as possible from other modules handling alternating current and high voltages.
Saitel DR modules have a DIN-rail bracket at the rear side that allows mounting on a DIN rail.
Figure 12 – Mount bracket on DIN rail
• Press the lower front panel gently until a click confirms that the bracket is fit on the rail.
• Verify the module is anchored firmly to the rail, although lateral movement is possible.
Figure 13 – Saitel DR module on a DIN rail
• If necessary, disconnect the bridge(s) connecting the module to the system bus.
• Holding the module by the front panel, push the upper metal tab downward. The user can also
pull the tab down using for example a screwdriver as shown:
• Pressing the tab, remove the module from the lower DIN rail.
Type
1.5-2.5 mm²
Power 7 mm 0.5 Nm Copper
15-13 AWG
1.5 mm²
Digital Inputs 7 mm 0.5 Nm Copper
15 AWG
1.5 mm² Copper,
RS-485 7 mm 0.5 Nm
15 AWG shielded
1.5 mm²
IRIG-B 7 mm 0.5 Nm Copper
15 AWG
1.5 mm²
Watchdog 7 mm 0.5 Nm Copper
15 AWG
The following section describes each HUe interface, including functionality and wiring when it is
required.
Pag 26
User Manual – HUe 19/04/2024
NOTICE
Follow all wiring recommendation for EMC included in Saitel DR Platfom user manual.
The power supply input terminal is located in the upper left area. There is a DC/DC converter, next
to the filtering electronic components, which is used to power both the HUe module itself and all the
AB modules assembled on the same row.
NOTICE
The maximum power to be supplied to the rest of modules in the same row by the HUe module
is 10 W. If the modules to be assembled on the ITB require a higher power, then, the ITB must
be divided into several rows, always observing the above-mentioned maximum power allowed
for each row.
A Reset button is included in this block allowing the user to reset all the ITB.
Power Wiring
The POWER connector must be used as power input. The input voltage range is 24 to 48 VDC, with
a tolerance of ±20%.
WARNING
For safety reasons, the use of ferrules on power input cables is recommended to avoid possible
short-circuits.
From left to right, the connecting order must be functional Earth, negative and positive terminal.
WARNING
For safety reasons, before connecting the aerial terminal to the module, it is recommended:
• To check that the voltage between the positive and negative poles does not exceed the
maximum operating voltage (see the technical table in chapter 6).
• To check that the polarity has not been inverted according to the label on the terminal.
Pag 27
19/04/2024 User Manual – HUe
HUe has 4 digital inputs located in the lower left, only configurable as single inputs. These signals
are useful to inform the operator about some controlled malfunction in the system. For example,
the cabinet door is open (the appropriated wired must be done).
The digital inpus 1 and 2 can be used for the following purposes:
• Digital input 1: This signal provides the HUe module with information about the digital inputs’
polarization status of the ABs installed in the ITB. When the signal is active, the polarization of
all digital signals is correct. If the signal is disabled, the HU will understand that there is a
polarization fault.
• Digital input 2: If this signal is enabled, the HUe module will interpret that the ITB is working in
LOCAL mode, whereas if it is disabled, the ITB is operating in REMOTE mode. When the ITB
is in LOCAL mode the commands are disabled.
To use these two signals with the purpose described above, they must be defined in the database
following the instructions included in paragraph 4.5.1 of this manual.
WARNING
Before doing any local operation, for safety reasons, the operator MUST:
These digital inputs are designed for internal use within the cabinet where the HUe module is
installed.
WARNING
These signals must not be connected to equipment that are outside the cabinet. Failing this
instruction could modify EMC behavior of the equipment.
The following figure illustrates how each input receives the polarization through the common:
WARNING
These digital inputs are internally polarized. Please, DO NOT CONNECT to other power supply.
Failure to observe this instruction can result in equipment damage.
Pag 28
User Manual – HUe 19/04/2024
• COM1 and COM2: non-isolated RS-232 communication ports for general-purpose. Both ports
use male DB-9 connector.
1 Not connected -
2 Rx – Data Reception I
3 Tx – Data transmission O
4 Not connected -
5 GND – Ground -
6 Not connected -
7 RTS – Request to Send O
8 CTS – Clear to Send I
9 Not connected -
Pag 29
19/04/2024 User Manual – HUe
NOTICE
COM1 can receive a pulse per second signal (PPS) through pin 8, so it must be used as the
GPS input, if required. The input PPS signal must be valid for RS-232 levels.
The validated GPS devices to be connected to the COM1 port are GPS35 (Garmin) and GPS16
(Garmin).
Some GPS devices don’t allow to use PPS signal.This operation mode implies that the
synchronization accuracy will be lower. It can produce a desviation of up to 10 ms in the generation
of the signal.
NOTICE
When using a GPS synchronization device, it is always advisable to wire the PPS signal to
achieve the highest accuracy in the synchronization.
WARNING
The installer should check that the cable connected to each COMx port is correct. It is also
recommended to use identification tags on the cables to avoid errors.
1 - Not connected
2 Data - White O
3 Data + Green I
4 Mode detection - Not connected
5 Ground Black Ground
Pag 30
User Manual – HUe 19/04/2024
WARNING
The connector RS-485 of HUe includes a termination resistor that cannot be disabled, so HUe
only can be installed as first and last device on the RS-485 bus. In this case, the termination
resistor included in any other element in the bus must be disabled.
VERY IMPORTANT: Three HUe device cannot be installed as part of the same RS-485 bus.
The relationship between this 3-poles terminal and the SM_SER’s DB9 connector is the following:
Table 5 – 2-wire RS-485 to DB9
A Pin 9 (Y)
B Pin 8 (Z)
Ground Pin 5
• MNT: Fast-Ethernet port (10/100BaseT) for maintenance purpose. It uses a RJ-45 connector.
• LAN1 and LAN2: Fast-Ethernet communication ports using copper or fiber optic depending on
the manufacturing options.
o Copper ports allow 10/100 BaseT IEEE 1588, with a RJ-45 connector.
o Fiber optic ports allow 100Base-FX with SFP connectors.
WARNING
The installer should check that the cable connected to each Ethernet port is correct. It is also
recommended to use identification tags on the cables to avoid errors.
Pag 31
19/04/2024 User Manual – HUe
TIA/EIA 568A and TIA/EIA 568B are two color codes used for wiring eight-position RJ45 modular
plugs. Both are allowed under the ANSI/TIA/EIA wiring standards. The only difference between
both codes is that the orange and green pairs are interchanged.
WARNING
Each network segment cable length may be up to 100 m.
Pag 32
User Manual – HUe 19/04/2024
IRIG-B Wiring
This terminal block is used to receive an IRIG-B claqsignal (non modulated TTL - 5V) which can be
used by the CPU to synchronize the ITB. The input impedance is 600 Ohm.
The connector for IRIG-B has the following pinout:
HUe can be set as an IRIG-B client and/or server, according the standards IRIG-B002, 003, 006
and 007.
WARNING
The watchdog output is not designed to be wired as a field output. This output was designed to
be connected to a local device inside the same cabinet. The connection wire must be shorter
than 3 meters.
The slot for the SD card is located on the left side of the module. This card can be used for mass
storage of data, for example, the event log or configuration files.
The slot for the Compact-Flash card is located on the left side of the module. This card can be
used for mass storage of data, for example, the event log.
The following Compact Flash card have been validated (both with capacity of 512 MB):
NOTICE
For P/N E7 and later, this ejector is not mounted. To extract the compact flash card, use an
appropiate tool, for example a tweezers for electronic.
Pag 33
19/04/2024 User Manual – HUe
If the CF ejector is not available for the module and there is some problem to access the card, the
enclosure can be removed allowing access to the card:
WARNING
Turn off all power supplying this equipment before working on or inside it. Consider all sources
of power, including the possibility of back feeding.
3.4 Expansion
Through a flat ribbon connector, the CPU starts the data and power bus, expanding it to the other
modules.
Figure 21 – Expansion bus connector
NOTICE
Before disconnecting the secondary devices from the bus (disconnecting the flat ribbon) the ITB
must be unpowered.
There are 4 configuration switches on the front of the module. They are numbered 1 to 4 from the
left to the right.
Figure 22 – Configuration switches
Pag 34
User Manual – HUe 19/04/2024
• Switch 4: It restores the factory IP configuration. If switch 4 is ON when HUe starts, the
network configuration will be restored for all Ethernet ports. If the network configuration file
(netConfig.xml) exists, it will be renamed to old_netConfig.xml. The default IP addresses are
indicated in paragraph 4.1 .
• Transmission/Reception in COM1, COM2, CON and RS-485 ports (Tx and Rx).
NOTICE
There is not a LED associated to the MNT port.
Pag 35
19/04/2024 User Manual – HUe
→ Blink → On → Off
On Powered. -
Unpowered. Connect the module to a power supply
according to the input voltage of the
module.
Bat The supercapacitor is discharged. While this Switch 1 must be turned OFF. The led will
led is on, the system cannot keep the data in turn off when the supercapacitor is
memory if a power down occurs. loaded.
Normal state. If the supercapacitor is fully
charged, data in memory can be kept for 8
hours (at 25 ºC) if a power down occurs.
DIO There is at least one module in Fail status in Identify the module with problems and
the ITB. perform the recommended actions. More
information in the user manual of the
module in fail status.
All modules in the ITB are OK.
RED. Redundant system. This CPU is in HOT
status.
Pag 37
4 Configuration & Maintenance
Public
User Manual – HUe 19/04/2024
Content
4 CONFIGURATION & MAINTENANCE ...................................................................38
Pag 39
19/04/2024 User Manual – HUe
HUe is supplied with a basic configuration, which will help us have a first contact with the system.
To get started, the following data should be known:
Default IP Addresses
Table 8 – Default IP addresses
User
In accordance to the policy provided with the CAE tool, the default users which can log into the
system are:
Table 9 – Default users
NOTICE
It is recommended to use Engineer user to perform configuration tasks with Easergy Builder
and Installer user to use the console.
Pag 40
User Manual – HUe 19/04/2024
When working with the HUe module, the user will need to prepare the working environment, in
terms of installing the adequate tools, making the software files available, in case the CPU needs
to be upgraded, and so on.
There are certain tasks that the user must be familiar with before using Saitel DR, such as:
• Installing and using Easergy Builder: This manual describes specific operations to be
performed with this tool (see Chapter 5 in this manual). For detailed information about the use
of Easergy Builder, please refer to “Easergy Builder User Manual”.
• Using webApp: For detailed information about the use of the web server, please refer to
“webApp User Manual”.
• Operating Saitel DR modules: For further information about the wiring, configuration, and use
of the modules which be included in an ITB, please refer to their respective user manual.
• A console cable if a USB cable is used. For connecting to the HUe, the cable must have a
miniUSB connector (for further information about the CON port and its pinout, please refer to
section 3.2.4 in this manual).
• Software for serial channel connection. In the examples of this user manual, PuTTY is used,
which is a free-license software that can be used in most PC’s running on Microsoft®
Windows® and several UNIX® platforms.
Connection
Connect the cable between the CON port (miniUSB connector) in the HUe to a PC serial port (one
of the USB ports can be used).
Switch on the HUe module and execute PuTTY (or another commercial software).
Pag 41
19/04/2024 User Manual – HUe
The commands that can be executed in the console will depend on the logged-in user permissions.
In order to execute the usual actions with this tool, it is recommend using Installer user with
Installer1! password.
Figure 26 - Login session
For a complete list of all BLMon commands and its actions, please refer to section 5.9.1 in this
manual.
• /mnt/bf: Flash memory. This is a general-purpose memory. It stores ISaGRAF®, web server,
and other application's files.
• /mnt/flash: Main memory. It stores user applications of Baseline Platform, for example, the
software for the Device Drivers and their configuration files.
• /nvRam: Non-volatile SRAM memory. Memory used for data storage (i.e. Event log).This
memory has a power fail protection by means of a supercapacitor, which is capable of retaining
data for 8 hours.
• /mnt/sd1: Memory for mass data storage in a SD memory card. The board needs to be
inserted in the slot on the module’s side panel. The /mnt/sd1 folder is listed in the file system
when the card is inserted in this slot. If the card is not inserted, then the folder will not be
displayed in the file system.
• /mnt/usb1: Memory for mass data storage in a pen drive. When the device is connected to a
USB port, the /mnt/usb1 folder is listed in the file system, and its content will be available. If
there is no pen drive connected to this port, the folder is not displayed in the file system.
Pag 42
User Manual – HUe 19/04/2024
NOTICE
The host USB port can be used to update Baseline. Connect a pen drive containing new
Baseline file to be installed (for example, “Baseline_11.06.02.tar.gz”) and, then, click Reset on
the equipment.
IMPORTANT: For the update to be successful, there should only be one file
Baseline_XX.XX.XX.tar.gz on the pen drive.
Network Interfaces
Figure 27 – Network interface settings
The network settings in the CPU can be read by clicking . Then, they can be modified and sent
to the RTU by clicking ). All changes will be effective in the next reboot.
To add new network interfaces, remove one of the existing interfaces or change their respective
parameters, use the , , and buttons respectively.
All the network interfaces integrated in the HUe can be set as DHCP client, so “IP Address” and
“Subnet Mask” fields are ignored. These data are automatically assigned by a DHCP server
through the network.
NOTICE
HUe cannot be set as a DHCP server.
It is possible to configure a Parallel Redundancy Protocol (PRP) logical interface. This interface
allows two physical ports to be used as a single port, that is, both ports will have the same MAC
address and the same IP address.
NOTICE
When a PRP interface is defined, LAN ports are not available to be defined.
Routers
To define interfaces in different networks, a device that gives us access to different networks must
be configured. Each device is configured in the “Routers” tab, in which each respective IP address
is indicated. The figure below illustrates an example with two external subnets.
Pag 43
19/04/2024 User Manual – HUe
The Destination IP and Destination Mask fields are related to the IP addresses to be reached from
the router. The Router IP is the device's IP address in the main network.
A default IP address and mask can be defined (i.e., 0.0.0.0 and 0.0.0.0) in order to access external
networks. With these settings, any device connected to the router from the CPU could be reach.
As with network interfaces, use the buttons on the right to add, remove or edit a router.
Firewall
The network ports (MNT, LAN1, and LAN2) have the Firewall tab with the following parameters:
• Defining an allowlist: A pool of IP addresses which will access the CPU through this port.
Subnet mask must be 255.255.255.255.
• Defining a blocklist: A pool of IP addresses which CANNOT access the CPU through this
port.
• Blocking a TCP or UDP port in the interface. In this case, no device can connect to this
network interface using the specified port.
Pag 44
User Manual – HUe 19/04/2024
To manage the firewall rules for each port, select it from the list and click .
Figure 30 - Edit firewall rules
The configuration of Firewalls in the system is not required. If the network interface does not have
Firewall settings, then no restrictions or capabilities are associated to use this feature.
To define an allowlist or blocklist, select the Type ("White list" or "Black list") and indicate the pool
of addresses to be included (IP Address / Subnet Mask).
To block a port, select “Blocked port” in Type field and then, indicate the port number and type
(TCP or UDP).
The firewall rules are defined in the order below:
Pag 45
19/04/2024 User Manual – HUe
• SLOT: In a redundant system, it is necessary to define the type of CPU. It will have the value A
in the main CPU, the one that is initialized HOT by default, and B for the secondary CPU.
In this tab, the values can be changed and sent to the CPU by clicking ; new values will be
applied in the next CPU initialization. Using button , the current values for these parameters in
the RTU are read.
4.2 Cybersecurity
The HUe module implements a standard security policy and a default RBAC model (Role-based
access control). This model is defined and managed by a special tool, i.e. CAE (EcoStruxure™
Cybersecurity Admin Expert). Based on this model, authorized users can create and manage other
system's users. Moreover, the CPU includes a firewall.
The RBAC model implemented in the HUe module complies with the IEC 62351-8 standard.
• Secure connections for local and remote maintenance: HTTPS and SSH.
• Firewall capability.
Default RBAC model is detailed in further sections in this manual, including:
• List of objects.
Pag 46
User Manual – HUe 19/04/2024
4.2.2 Users
During the engineering phase, CAE must be used to redefine or change the access restrictions for
the system, including the access rights and responsibilities.
In the basic model supplied with HUe, the SecurityAdmin user is the only user with sufficient
privileges to administer Saitel cybersecurity (please, see table below).It means that it is the only
user which is able to administer and/or modify the passwords and roles being assigned to the
users.
Table 10 – Default users
Once access levels are defined in the RBAC model, the HUe web server (webApp) can be used to
add or remove users, modify passwords and assign one or several predefined functions to the
users or modify them.
WARNING
When users are modified, if new RBAC configuration is uploaded from CAE, all changes here
will be overwritten.
Pag 47
19/04/2024 User Manual – HUe
NOTICE
For security reasons, these users’ password must be changed when the system is initialized.
4.2.3 Roles
Role-based-access-control (RBAC) is a control mechanism that defines the roles and privileges
assigned to each role. These privileges are defined in accordance to some objects and actions that
the user can act upon:
The table below illustrates the actions allowed for each object. Depending on the roles assigned to
the logged-in user in the system, a specific action is allowed or not for an object:
Table 11 – Default roles
Reading CONFDB_READ
CONF_DB Configuration files in coreDb.
Writing CONFDB_WRITE
Reading CONFSYS_READ
CONF_SYS Configuration files in the system.
Writing CONFSYS_WRITE
Reading FIRMWARE_READ
Directory in which Baseline executables and
FIRMWARE libraries are contained (excluding the Writing FIRMWARE_WRITE
smAutoLoad file).
Viewing FIRMWARE_VIEW
WEBSERVICE Web server. Access WEBSERVICES_ACCESS
SSH and SFTP connection to the operating SSH_ACCESS
SSH Access
system.
OSSHELL Operating system's console. Access OSSHELL_ACCESS
BLMON Baseline Console. Access BLSHELL_ACCESS
System's Log File (Baseline).It includes the Reading SYSLOG_READ
log file both for the system and SOE
SYSLOG
(sequence of events), but it does not include Writing SYSLOG_WRITE
the cybersecurity log.
The table below illustrates the privileges associated each role defined in the RBAC model for the
HUe module. For users and roles management the SecurityAdmin user must be used to login in
webApp.
Pag 48
User Manual – HUe 19/04/2024
Roles
OPERATOR
INSTALLER
ENGINEER
RBACMNT
Privilege
SECADM
SECAUD
VIEWER
CONF_DB √ √ √ √
CONFDB_WRITE √ √
CONFSYS_READ √ √ √
CONFSYS_WRITE √ √
FIRMWARE_VIEW √ √ √
FIRMWARE_READ √ √
FIRMWARE_WRITE √ √
WEBSERVICES_ACCESS √ √ √ √ √
SSH_ACCESS √ √
OSSHELL_ACCESS √
BLSHELL_ACCESS √
SYSLOG_READ √ √ √
SYSLOG_WRITE √ √ √ √
RBAC_READ √ √
RBAC_WRITE √ √
RBACLOG_READ √ √ √
RESET_ACCESS √ √ √ √
DATA_READ √ √ √
DATA_WRITE √ √
Pag 49
19/04/2024 User Manual – HUe
Inside the ITB, each acquisition block or communication block must be identified with a number.
This number is assigned with Easergy Builder when configuring the local acquisition (please see
section 5.1 ).
Once the local acquisition is defined with the configuration tool and it is transferred to the RTU, it is
necessary to define these modules’ runtime addressing. To do so, execute a so-called Automatic
Addressing Procedure (AAP) that creates a table in the memory in which the acquisition blocks
assembled physically on the ITB are associated to an address and a type. The physical
components on the system must match the configuration in Easergy Builder.
NOTICE
For AAP execution, at least one configuration needs to be loaded in the RTU; it must match the
configuration loaded in the modules that are physically installed on the ITB. For further
information about how to define and load a configuration to the RTU by using Easergy Builder,
please refer to section 5.1 .
The Automatic Addressing Procedure (AAP) must be performed every time the ITB morphology
changes, that is, every time a module is added, deleted or replaced.
The AAP procedure can be executed both automatically and manually.
Automatic Execution
For a forced execution of the AAP when the ITB is reset, switches 2 and 3 in the HUe must be set
to ON (please, see section 0).After resetting the HUe module, an AAP procedure is executed,
displaying the information about the modules that are installed and configured.
The figure shown below illustrates an example of the messages generated by the console when
AAP procedure is completed:
Pag 50
User Manual – HUe 19/04/2024
In this case, there is an AB_AI module with the address 1 and an AB_DI module with the address
2.
If any of these acquisition blocks which was configured previously with Easergy Builder is not
properly addressed (the “SUCCESSFUL!” message is not shown in the console), the module's
RUN led DOES NOT flash and the DIO led on HUe module remains lit.
Manual Execution
The user can force the module addressing at any time.
Log into the console with the Installer user and in BLMon prompt, execute the “claqStartAAP”
command to route the acquisition AB and the “MUX_startAAP” command for the communication
AB.
NOTICE
To execute the AAP procedure, the switch 2 must be set to ON.
If switch 3 is also set to ON, the entire procedure is performed automatically. Otherwise, follow
these steps:
• The user will need to verify that all necessary modules are displayed with the text
“SUCCESSFUL!” next to them.
• To complete the procedure, the user will need to execute the claqTableAck command to
confirm that the information is correct. In this case, the addressing information is stored
permanently. If the information is not correct, execute the claqTableNack command in order to
indicate that there was an addressing problem and that the information being displayed must
be ignored
NOTICE
Only after executing the claqTableAck command, the information will be recorded permanently.
Local acquisition means how the system treats the HUe information received from field devices
through acquisition blocks (AB).
This manual describes the configuration of the local acquisition signals in general terms, with no
comprehensive information about the configuration of each AB. This chapter explains how
information is processed by the CPU once it is received from each module.
For more detailed information about each AB, please refer to the corresponding user manual.
Pag 51
19/04/2024 User Manual – HUe
• Centralized Local Acquisition: All modules are installed in the same ITB, in which only one
HUe module is installed (or two if the configuration is redundant).The ITB may have more than
one row of modules, but only the first row may have a CPU.
• Distributed Local Acquisition: There are several acquisition ITB's reporting information to a
single ITB. In this case, the system is configured as if all AB modules are installed in the same
physical ITB.
More information in the Saitel DR Platform user manual.
The claq Device is responsible for the treatment and configuration of the local acquisition signals in
Easergy Builder. This Device is created by default in any configuration of Saitel DR.
For further information about how configuring ITB and how signals are added automatically in
coreDb, please refer to Easergy Builder User Manual.
• Digital 1: It informs the HUe module about the polarization of the digital signals of the AB's
installed in the ITB. When the signal is active, the polarization of all digital input is correct. If
there are inactive, the HUe module will understand that a problem with the polarization has
occurred. To use this signal for this purpose, the supervision signal POL_OK_ABDI must be
defined.
• Digital 2:Depending on its on/off state, the HUe module will understand that the ITB is
operating in LOCAL or REMOTE respectively. In LOCAL mode, the command execution will be
disabled. To use this signal, the supervision signal LOCALREMOTE must be defined in
coreDb.
Clicking the graph on the HUe figure, it lights up in green and the 4 general-purpose digital Inputs
available in the module are displayed.
For each signal, the following parameters should be defined:
• Type: Type of digital input. Only DI_ISIM (simple digital input) is available for these digital
signals in the HUe module.
• TF (ms):Filtering time to be used for the digital filtering. Expressed in milliseconds, it can range
between 0 and 255.
• NChat and TChat: They have no effect on these signals and cannot be configured.
For this type of signals, “Digital Filtering” and “Change Memory” should be considered. Both
concepts are explained in Saitel DR Platform user manual.
Pag 52
User Manual – HUe 19/04/2024
• Digital inputs
o Digital filtering
o Change memory
o Settling Time
o Anti-Chattering
o Inversion
o Edge Configuration for Counters
• Digital outputs
o Pulse time
o SBO Command Lock
• Analog Inputs
o Input Range
o Out-of-Range Detection
o Digital Filtering
o Scaling to Engineering Units
o Cancellation of Values Close to Zero
o Range Checking
o Change Threshold
• Analog Outputs
o Reset Value
o Maintenance
o Scaling to Field Values
o Output range Configuration
Consult Saitel DR user manual for all information about how HUe executes these functions.
NOTICE
To perform the operations described in this chapter, the user must be familiar with the Easergy
Builder tool. Otherwise, please, refer to the tool's user manual.
Pag 53
19/04/2024 User Manual – HUe
• Name: RTU's name. The name cannot be longer than 64 characters and it cannot contain the
following symbols:\, /, :, *, ?, “, <, > o |.The tree hierarchy will display a RTU identified with that
name.
• Description: RTU's description. This field is optional and can be 128 characters long.
• AB_SER: Number of the communication modules installed in the RTU. These modules are not
shown in Easergy Builder, even though its communication channels are available for use.
• Redundancy: This field must be checked when the RTU is controlled by two redundant CPU’s.
• Define default acquisition: If this box is checked, every time a configuration is created for this
RTU, a set of default acquisition modules will be associated. These selectable modules are
specified below.
The previous parameters are assigned as default values in each Configuration created for this
RTU.
For example, if “Define default acquisition” box is checked, all the acquisition modules included in
this RTU will also be included in its corresponding Configurations.
Figure 36 – Configuring the ITB
This default configuration can be hanged by clicking the button next to the ITB figure.
Build the ITB using the buttons on the upper part of the screen, having in account:
• The Addr field is the number associated to an acquisition block inside the ITB. This number
must be unique for each AB and will be used to identify both the AB and its points. The user
can change the associated address by selecting the module and using the buttons.
Selecting “Auto Address” box, when reordering the modules physically or when modifying the
ITB, all addresses are reassigned automatically. The address 1 is assigned to the closest AB to
the HUe module. If the “Automatic Address” is unchecked, the modules retain the assigned
address ignoring the changes made to the ITB.
• The Automatic Addressing Procedure (AAP) must be performed every time the ITB structure
changes, that is, every time a module is added, deleted or replaced from the ITB. These
procedure can be launched both manually, using the Console or Easergy Builder, or
automatically by using the switch 3 in the HUe module (more information in section 0in this
manual).
The RTU is ready for creating the different configurations. For more information about SOE,
please, consult the SOE user manual.
Pag 54
User Manual – HUe 19/04/2024
• IP CPU A and IP CPU B must be indicated. These IP addresses are used for communications
with Easergy Builder.
• In tab Network – CPU A and Network – CPU B, IP addresses for ETH1 and ETH2 for CPU A
and CPU B should be indicated.
NOTICE
It is recommend backing up the original configuration in the RTU in order to restore the CPU to
its original state at any time. To back up the security configuration, select the RTU from the tree
and generate an EBR file by clicking the button. This file will include all the settings for that
RTU. To save a copy of the configuration, select the specific configuration from the tree and click
the same button. In this case, an EBC file is generated, which only includes the selected
configuration.
To load the existing configuration in the HU, it’s necessary to follow next steps from the Easergy
Builder Workspace.
• In the RTU tree, the RTU to which the new configuration will be associated has to be selected.
If there is no configuration, a new one has to be loaded. The HU needs to have configured an
IP address so it’s possible to communicate with it.
• Once the “Read Configuration” button ( ) is pressed, the user would need to introduce a user
and password.
the button.
Figure 37 – New configuration
If “Create defined RTU acquisition points” box is checked, all local acquisition points will be
included in coreDb for each acquisition blocks included in the default configuration associated to
the RTU.
For example, if a HUe has an associated ITB that includes an AB_DI module, an AB_AI module,
and another AB_DO module, after selecting the “Create acquisition points defined in the RTU” field
when creating a new configuration, the following points will be created in coreDb:
• Change the name or description of the Device (description field allows 128 characters
maximum).
Pag 56
User Manual – HUe 19/04/2024
The user needs to be familiar with the use of Easergy Builder, since this user manual only refers to
certain aspects directly affecting the configuration of the HUe module.
4.6.6 Communications
The default configuration does not include any communication Device, since this functionality
depends on how the RTU will be used in the system. Communication Devices available for the
HUe module are:
Pag 57
19/04/2024 User Manual – HUe
NOTICE
The CON port cannot be used for communications, and that is why it is not necessary to
include it in the channel list.
• Ethernet Ports. Each port use for communications must be defined as a TCP or UDP channel.
NOTICE
It RTS control is AUTO for a specific channel:
• In COM1 and COM2, the hardware will control RTS and CTS signals. CAUTION! If the CTS
signal is not received, then there is no transmission.
• For RS-485, the control for the RTS signal and the changes between the transmission and
reception modes would be controlled by the hardware IT IS HIGHLY RECOMMENDED!!
Please refer to the Easergy Builder manual to obtain further details about how to create and define
parameters for communication channels.
4.6.9 Synchronization
The factory configuration does not include a defined Synchronization Device. The configuration
source is defined in Easergy Builder. webApp only allows changing the configuration once it has
been previously defined with Easergy Builder.
For HUe, two synchronization channels can be defined: a primary channel and a secondary
channel, which will be used when the primary channel is not available.
Figure 44 - Synchronization configuration
• SNTP: The remote unit will operate as a SNTP client; therefore, two parameters should be
indicated: the SNTP server's IP address and the synchronization period through that server.
• IRIG: The time received from the IRIG device is used to set the system’s clock and RTC. The
configurable formats are: IRIG-B002, IRIG-B003, IRIG-B006, and IRIG-B007.
NOTICE
If the HUe is configured as IRIG-B server, an AB_SER module witn external polarization
(M56720000yZZ) must be included in the firt row of the ITB. The IRIG-B signal is sent to the
client devices through COM ports of this AB_SER.
• PTP: As indicated in the IEEE-1588 standard, a primary device PTP will synchronize the
accessible secondary PTP devices through one or multiple Ethernet interfaces. This
functionality for Hue is available in version 11.06.08 and later.
Pag 59
19/04/2024 User Manual – HUe
Moreover, the HUe module can be configured as a Simple Network Time Protocol (SNTP) server,
as a primary PTP device or as an IRIG-B server.
The synchronization module allows the time zone and summer/winter (day light saving) calendars
to be configured.
Figure 45 - Time configuration
For further details about synchronization configuration, please refer to the Easergy Builder user
manual.
NOTICE
UDP port is unavailable when PTP port is configured.
NOTICE
The RTU can be configured a PTP client or a PTP server, but not both at the same time.
• Port: Select the physical port for synchronization with the PTP device.
• domainNumber: Value of the "domain" attribute of the local clock. The default value is 0.
• Announce messages period: Average time interval between "Announce messages". Value in
seconds, as a base two logarithm. The default value is 1, that is, 2 seconds.
Pag 60
User Manual – HUe 19/04/2024
• Max. Announce messages lost: Maximum number of lost messages before considering a
time-out in the reception. The default value is 3.
• Delay req period: Minimum allowed time interval between "Delay_Req" messages. It is
specified, in seconds, as a base two logarithm. The default value is 0, that is, 1 second.
• Sync period: Average time interval between synchronization messages. A shorter interval can
improve the accuracy of the local clock. It is specified, in seconds, as a base two logarithm.
The default value is 0, that is, 1 second.
• Pdelay req period: Minimum allowed time interval between "Pdelay_Req" messages. It is
specified, in seconds, as a base two logarithm. The default value is 0, that is, 1 second.
• vlan tagging: It selects whether the PTP frames should include their VLAN tagging (IEEE
802.1Q). Only can be select when “Net transport” is IEEE 802.3.
PTP Server
Select tabs Synchronization server - PTP and configure the following parameters:
Figure 47 – Configuring the RTU as PTP server
The information for each field is detailed in the previous paragraph. Other fields are available for
PTP Servers:
• Clock Class: Denotes the traceability of the time or frequency distributed by the grandmaster
clock. Default value is 127.
• Priority 1: A configurable designation that a clock belongs to an ordered set of clocks from
which a primary device is selected, through the “Best Master Clock algorithm”. Values can
range from 0 to 255 (lower values take preference). Default value is 128.
• Priority 2: A user configurable designation that provides finer grained ordering among
otherwise equivalent clocks. Values can range from 0 to 255 (lower values take preference).
Default value is 128.
NOTICE
An RTU cannot be OC (Ordinary clock) and BC at the same time. If it is synchronized by a PTP
device, it can't be configured as PTP server.
Pag 61
19/04/2024 User Manual – HUe
• Runtime: Control and execution environment for logic programs. The license is included as part
of the Baseline Software Platform installed in the HUe module.
4.6.12 Supervision
The Supervision Device is a default Device in Easergy Builder. The Device is used to monitor the
status of CPU's components and generates information about other components in the RTU.
Double click the “Supervision” Device in the tree to see a complete list of all the concepts available
for monitorization in this type of CPU:
Figure 48 – Supervision signals
Pag 62
User Manual – HUe 19/04/2024
In this window, check or uncheck the available supervision points to be used for that RTU.
NOTICE
It is highly recommend configuring the Supervision; besides, it is essential in redundant
configurations. The CPU itself cannot be arbitrated autonomously with the other CPU in
redundant systems, so there must be some supervision in charge of this Device.
For redundant configurations, most of the supervision points are also available with “_A” and “_B”
suffixes in order to provide CPU-related information. For example, the points PS1_V, PS1_V_A,
and PS1_V_B are available for power supply voltage. Regardless which CPU is in online mode, the
information about both CPUs is shown.
If points are not available with _A and _B suffixes in a redundant configuration, it means that only
values for the online CPU are available, for example, DOING_WELL.
The information generated by the supervision is complemented with control and diagnostic
information that is generated by each Device.
The table below shows the supervision points available for HUe:
Table 13 – Supervision points
Pag 64
User Manual – HUe 19/04/2024
WARNING
(*) Please do not define LOCALREMOTE and LOCALREMOTE:I simultaneously in coreDb.
Otherwise, the behavior would be unpredictable.
4.6.13 Redundancy
As it was explained previously, the system has two redundant CPU’s, there are certain differences
in the configuration of, for example, environment variables and supervision points. Moreover, the
configuration also must indicate how redundancy will be implemented both in physical terms
(control mechanism) and functional terms (data redundancy mode).
The environment variables A and environment variables B table must be correctly configured in
dbRED tab (coreDb) to indicate which CPU will act as primary and which as redundancy
NOTICE
The dbRED section is only available in Easergy Builder for redundant CPUs.
Control Mechanism
For HUe there is redundancy only through the RCAP protocol (Redundancy Control Asynchronous
Protocol). It consists of a redundant channel between the two HUe modules that is switched when
required by means of a Schneider Electric proprietary protocol.
To implement this control mechanism, up to two different channels can be used, which are used
redundantly to obtain a fault-tolerant redundancy control:
Pag 65
19/04/2024 User Manual – HUe
• Through network ports, IP addresses for CPU A and CPU B should be defined.
• Through a serial channel. The serial port to be used in both CPUs should be defined.
Mode
There are two different modes to implement redundancy:
• Cold redundancy: The databases in both CPU's are NOT synchronized. When switching, the
other CPU will initialize with its own database using default values.
NOTICE
When using the “Hot redundancy” mode, the names of the points in both databases must be
identical, that is, it is very important to use the SAME Easergy Builder configuration in both
CPU’s.
The backup CPU's database is updated when exceptions are thrown (i.e. only the modified points
are updated), except for the initialization after which the entire database is updated. The
DB_UPDATE supervision point allows us to monitor the process.
Additional IP’s
A list of IP addresses can be defined related to the HOT CPU. These addresses are dynamically
associated, so that in redundant systems they can always communicate with the online CPU at the
time.
NOTICE
When a static IP address and a virtual address is defined for the same device in the same
subnet, a warning console message will be displayed to inform about an anomalous situation
(sup_redAddIPs: dev xxx ip x.x.x.x subnetMask xxxxxxxx).
The message is an operating system warning, even though it will not cause a malfunction.
NOTICE
If PRP, HSR, BOND or RSTP interfaces are defined, the associated LAN ports will be not
available to define.
HUe can use PRP, HSR, BOND and RSTP protocols as detailed in the following sections.
Pag 66
User Manual – HUe 19/04/2024
Pag 67
19/04/2024 User Manual – HUe
Pag 68
User Manual – HUe 19/04/2024
• button, to create in coreDb acquisition and diagnostics points for all included modules.
More information in section claq in the manual of the different acquisition modules.
• Digital 1: This signal provides the HU module with information about the digital inputs’
polarization status of the ABs installed in the ITB. When the signal is active (1), the polarization
of all digital signals is correct. If the signal is disabled (0), the HU will understand that there is a
problem with polarization.
In order for the CPU to interpret the value of Digital 1 in this way, the supervision signal
POL_OK_ABDI must be included in coreDb.
• Digital 2: Depending on this signal is active or not, the CPU will understand that the ITB is in
LOCAL mode (signal is 1) or in REMOTE mode (signal is 0). In order for the CPU to interpret
the value of Digital 2 in this way, the supervision signal LOCALREMOTE or LOCALREMOTE:I
must be included in coreDb.
WARNING
(*) Please do not define LOCALREMOTE and LOCALREMOTE:I simultaneously in coreDb.
Otherwise, the behavior would be unpredictable.
• Type: Type of digital input. Only DI_ISIM (simple digital input) is available for the four digital
inputs of the HUe module.
• TF (ms): Filtering time to be used for the digital filtering. Expressed in milliseconds, it can
range between 0 and 255.
• TM (ms*10): Memory time to be considered for change memory. The indicated value is
expressed with 10-ms intervals, and it can range between 0 and 255.
• NChat and TChat: They have no effect on these signals and cannot be configured.
For this type of signals, “Digital Filtering” and “Change Memory” must be configured. Both concepts
are explained in further details below.
Pag 70
5 Advanced Operations
Public
19/04/2024 User Manual – HUe
Content
5 ADVANCED OPERATIONS ...................................................................................71
Pag 72
User Manual – HUe 19/04/2024
There are several ways to update the baseline installed in the HUe; using a SFTP client (for
example, Filezilla), using webApp (HUe web-based tool), or using a USB pen drive connected to
the USB Host port.
• An Ethernet cable connecting the PC with the MNT port in HUe. This wired connection is only
necessary when transferring the update file through SFTP or webApp. If using a pen drive, it
would not be necessary.
• A file with the new Baseline to be installed. It will be a compressed file with a name like
“Baseline_11.06.02.tar.gz”.
The file's name containing the image must have a specific syntax:
Once the connection is verified, open the FTP client software and establish connection with the
CPU using the SFTP protocol and Installer (user) and Installer1! (password).
When connection is established, move to the folder /mnt/flash and transfer the Baseline file from
the PC.
Pag 73
19/04/2024 User Manual – HUe
When loading is completed, press the Reset button on the CPU. If the console is available, the
message on it will show how the installation is in progress.
Once installed, the compressed file including the Baseline image is deleted.
Finally, reboot the system and Baseline is updated.
• To allow using the same USB device to deploy a baseline in different CPUs, the target image is
not deleted from the /mnt/usb1 device.
• Since the /mnt/usb1 image is not deleted, the system does not reboot. Thus, any "auto-
installation" of the same image is prevented. After the file is automatic copied from the
/mnt/usb1 device, it is recommended to remove the USB device and reboot the system
manually.
The priority order for the update procedure is:
• File in /mnt/bf
• File in /mnt/flash
Pag 74
User Manual – HUe 19/04/2024
NOTICE
Considering that the connection must be secure, the protocol HTTPS must be indicated in the
address bar, i.e. "https://192.168.0.254".
Log in with the “Installer” user and the webApp main screen appears:
Figure 58 - webApp main screen
In the lower area, identified with factory information, there is information about the current Baseline
version.
To install a new baseline, in the main menu, click: Maintenance → Software. Press button “Install
new software”. The following information is shown:
Figure 59 – Firmware upgrade using webApp
Pag 75
19/04/2024 User Manual – HUe
• Drag and drop the file in the designated area or search for it using the “Select file” button (Step
1).
• Click the “Install new firmware”, and the software file will be sent to the CPU to install the new
firmware (Step 4).
• Finally, the user will need to log in again and the CPU will be ready with the new software
version.
Apart from the software installed in the HUe, both the acquisition blocks and the communication
blocks have a software to be updated.
To update the software on the ITB modules, the required elements are:
• Information about the correct addressing in all ITB modules (please, see section 4.3 ).
NOTICE
Only Installer can be used to execute update commands in the console.
The table below shows the file to be used for each type of module and the command to be
executed by the operator in the console.
Table 14 – Software update file for ITB modules
Pag 76
User Manual – HUe 19/04/2024
AB_AC abaca.t00 claqDSPUpgrade all It updates the DSP in all the AB_AC
modules installed in the ITB.
AB_AC_A.bin claqUpgrade all AB_AC_A It updates the firmware in all the
AB_AC modules installed in the ITB.
AB_AC/LPVT abaca2.t00 claqDSPUpgrade all It updates the DSP in all the
AB_AC/LPVT modules installed in
the ITB.
AB_AC2.bin claqUpgrade all AB_AC2 It updates the firmware in all the
AB_AC/LPVT modules installed in
the ITB.
AB_MIO AB_MIO.bin claqUpgrade all AB_MIO It updates all the AB_MIO modules
installed in the ITB.
AB_SER AB_SER.bin MUX_upgrade “all” It updates the firmware in all the
AB_SER modules installed in the
ITB.
AB_SER AB_SER.bin MUX_upgrade “<position>” It updates the AB_SER module with
the <position> address in the ITB.
NOTICE
Only users with advanced knowledge about the equipment should perform the tasks described
in this section.
The operating system update is executed, if required, during Baseline installation, but only if the
currently installed version is older than the version to be uploaded.
Finally, reboot the system and the baseline is updated.
NOTICE
To downgrade the system (install a previous version of the baseline, including the operating
system), the name of the file used must content the suffix “_KFD.tar.gz”.
The HUe operating system offers a high-priority command console to help with certain monitoring
and diagnostic tasks.
The connection to this console from the PC is established through the CON port. The section 4.1.1
in this manual describes how access the command console.
Have into account:
• The use of the command console must be restricted only to expert operators in the system.
• The command execution in the console must return a “0” character when outputted. If it returns
other values, then there has been a problem in the execution. It is usually caused by
parameters with the wrong format.
Pag 77
19/04/2024 User Manual – HUe
• When executing a command for any controller, it must be saved into the memory to solve this
problem, that is, the controller must be included in the configuration loaded in the CPU from
Easergy Builder.
NOTICE
Only the Device controllers included in the current configuration will be loaded into the memory.
Then, the commands available in the console for the Installer user are displayed below, using the
following convention:
• <XX>:Required parameter. It must be replaced with the XX value. The symbols <>MUST NOT
be included.
• [YY]:Optional argument. If using the argument, it must be replaced with the YY value. The
characters [] MUST NOT be included.
5.4.1 BLMon
When accessing the console with the Installer user (recommended), the BLMon menu is directly
shown. The commands in this menu are executed on the operating system's prompt. Most
commands shown below are NOT available for the rest of the users.
Command Use
a It displays the list of the commands available to obtain information about the local acquisition. This
chapter includes more information about these commands.
Pag 78
User Manual – HUe 19/04/2024
Command Use
It displays the channels configured selectable by the user. If “Enter” is pressed instead of a
channel number, the command is aborted.
This command is similar to “chanSniffOn”.
h Using this command, detailed information about the system's commands is shown.
Apart from BLMon commands, the user has other commands to be executed in the prompt.
Type the desired “FUNCTION_HELP:” command to view the following information.
Use “a” to see a list of the available commands .
Pag 79
19/04/2024 User Manual – HUe
Command Use
t It displays the information about the configuration and the current synchronization status.
Pag 80
User Manual – HUe 19/04/2024
Command Use
5.4.3 Communications
Table 17 - List of communication commands
Pag 82
User Manual – HUe 19/04/2024
chanSniffOn <Channel_Name>
It activates the transparent mode for the specified channel. Use c command of BLMon
to execute this command more easily.
Example → chanSniffOn Channel1
This transparent mode can be activated for more than one channel at the same time.
Each message will indicate the related channel.
For this example, messages from channel1 and Channel485HUe are shown.
Pag 83
19/04/2024 User Manual – HUe
Pag 84
User Manual – HUe 19/04/2024
Pag 86
User Manual – HUe 19/04/2024
claqFileVersion <File>
It shows information about the software version of a file (.bin). The name of the file
must include the full path. For example:
Pag 87
19/04/2024 User Manual – HUe
If a module is included in the addressing table, but it is not installed in the ITB, the
following message will be displayed: “Module not available”.
claqJtag <File>
Be careful using this command, it can block the AB modules in the ITB!! On this
situation, each blocked AB need to be sent to the repair service!!
It restores the software of a module when it is not addressed in the ITB. This
command must be used when the claqUpdate command does not work and only for
users with great knowledge of the system.
<File>: File’s name, including the path. For example:
claqJtag /mnt/flash/AB_MIO.bin.
When this command is executed, the user must BE SURE of:
• The module has a bootLoader.
• Only the AB module to be restored must be connected in the ITB.
• The File must be the same time of the AB to be restored. For example, for an
AB_MIO module, the file must be AB_MIO.bin
Pag 88
6 Technical Specifications Table
Public
19/04/2024 User Manual – HUe
Hardware Specifications
Processing unit Sitara™ AM3356BZCZD60
Technology: ARM® Cortex™-A8
Data bus: 32-bits
Clock frequency: Up to 720 MHz
WARNING
According to the standard 60950-1, all electrical safety tests have been done in an
environmental temperature range of -40 ºC to 60 ºC. For higher temperature (> 60 ºC), the
module must be handled with care since the metal surface could reach a dangerous
temperature for the user.
Interfaces
Power supply (POWER) Voltage range 24 – 48 VDC (±20%)
3-pole terminal block
Wire: 2.5 mm² (13 AWG)
Console port (CON) Mini-USB connector
SD card Up to 32 GB
Pag 90
User Manual – HUe 19/04/2024
Interfaces
Auxiliary digital inputs (AUX DI) 5-pole terminal block with isolation
4 digital inputs for general purpose
Software
Operating System RTLinux
External synchronization GPS
IRIG-B
Protocol
Console
PTP
IRIG-B TTL input signal
Protocols: IRIG-B002, IRIG-B003, IRIG-B006 and IRIG-B007
Discrimination time for events 1 ms
Watchdog software Internal
Security control Cybersecurity brick included
Embedded firewall
Secured interfaces
User management based on a RBAC model
Ordering Options
Pag 91
19/04/2024 User Manual – HUe
Cybersecurity
Based on IEC62351
IEC62443
Security Engine SEC 3.3.2 (XOR acceleration)
Supported cryptographic algorithms 3DES, AES, MD5/SHA, RSA/ECC, & FIPS (determinist generator)
Processing Single pass encryption and authentication
Security protocols SSL 3.0, SSL 3.1 / TLS 1.0
CE Mark
Standards, Directives, and LVD – Low Voltage Directive Directive 2014/35/EU
harmonized norms.
EMC – Electromagnetic Compatibility Directive 2014/30/EU
RoHS Directive 2015/863/EU
EMC Directive
Tests according to IEC-EN 60870-2-1 (1996)
IEC/TS 61000-6-5 (2015)
EN 50121-5:2017 /A1:2019
Emission Radiated emissions
EN 55022:2006 + A1:2007 From 30 to 6000 MHz (Class A)
Conducted emissions
EN 55022:2006 + A1:2007 From 0.15 to 30 MHz (Class A)
Immunity Electrostatic discharges (ESD)
IEC-EN 61000-4-2:2009 By air ±8 kV and by contact ±4 and ±6 kV (Level 3)
Radiated, radiofrequency, electromagnetic field
IEC-EN 61000-4-3:2006 + A2:2010 From 80 to 6000 MHz (Level 3).
Fast transients, common mode
Power port: ±4 kV, 5kHz.
IEC-EN 61000-4-4:2012 Communications ports: ±2 kV 5kHz and
±4 kV 2.5kHz.
I/O ports: ±2 kV 5kHz and ±4 kV 5kHz (Level 4).
Power port: ±4 kV common and differential mode
Surges, line to line and line to ground
Other ports: ±2 kV differential mode, ±4 kV common
IEC-EN 61000-4-5:2006 mode
RF common mode
IEC-EN 61000-4-6:2014 10 VRMS 0.15-80MHz 80% AM (Level 3).
Power frequency magnetic field 100 A/m, 1000 A/m 3s (Level 4).
IEC-EN 61000-4-8:2010. 300 A/m, > 10s
Power frequency common mode disturbances
IEC-EN 61000-4-16:1998 30V 50Hz, 300V 50Hz 1s (Level 4).
Damped oscillatory wave
Power, communications, and I/O:
IEC-EN 61000-4-18:2007 + A1:2010 1kV DM, 2.5kV CM (Level 4), (f=1MHz)
Pag 92
User Manual – HUe 19/04/2024
Index of Figures
Figure 1 - Barrier of protection for elements with high voltages. ..............................................................................10
Pag 94
User Manual – HUe 19/04/2024
Index of Tables
Table 1 – Symbols ........................................................................................................................................................9
Pag 95
19/04/2024 User Manual – HUe
Glossary
A
A: Ampere.
AAP: Automatic Addressing Procedure.
AB: Saitel DR Acquisition Block.
AB_AC: Direct measurements Acquisition Block.
AB_AI: Analog Inputs Acquisition Block.
AB_AO: Analog Outputs Acquisition Block.
AB_DI: Digital Inputs Acquisition Block.
AB_DIDO: Digital Inputs and Outputs Acquisition Blocks.
AB_DO: Digital Outputs Acquisition Blocks.
AB_MIO: Multiple Inputs and Outputs Acquisition Block.
AB_SER: Communication module for expansion.
AC: Alternate Current.
AI: Analog Input.
AO: Analog Output.
B
Bps: Bits per second.
C
ºC: Celsius degree.
COM: Communication port.
CPU: Central Processing Unit.
CTS: Clear to Send.
D
DC: Direct Current.
DI: Digital Input.
DIN: Deutsches Institut für Normung.
DO: Digital Output.
DRAM: Dynamic Random Access Memory.
E
EMC: ElectroMagnetic Compatibility.
EPROM: Erasable Programmable Read Only Memory
Pag 96
User Manual – HUe 19/04/2024
F
FTP: File Transfer Protocol.
G
g: Gram.
GPS: Global Positioning System.
H
HMI: Human-Machine Interface.
HU: Head Unit. Saitel DR CPU.
HU_A: Saitel DR Advanced Head Unit.
HU_AF: Saitel DR Advanced Head Unit with acquisition.
HU_B: Saitel DR Basic Head Unit.
HUe: Saitel DR High-Performance Head Unit.
Hz: Hertz.
I
IED: Intelligent Electronic Device.
I/O: Input / Output.
IRIG: Inter Range Instrumentation Group.
IRIG-B: Mode B of the standard IRIG.
ISO 9001: International standard for Quality Systems.
ITB: Intelligent Terminal Block.
K
KB: Kilobyte.
kHz: Kilohertz.
L
LAN: Local Area Network.
LED: Light Emitting Diode.
M
mA: Milliampere.
MHz: Megahertz.
MB: Megabyte.
Mbps: Megabits per second.
m: Meter.
mm: Millimeter.
ms: Millisecond.
Pag 97
19/04/2024 User Manual – HUe
N
N/A: Non-Application.
P
PC: Personal Computer.
PPS: Pulses per Second.
PS: Power Supply.
PWR: Power.
R
RAM: Random Access Memory.
RS-232: Communication standard.
RS-485: Multipoint differential Bus.
RTDB: Real Time DataBase.
RTS: Request To Send.
RTU: Remote Terminal Unit.
Rx: Reception
S
s: Second.
SCADA: Supervisory Control And Data Acquisition.
SFTP: Secure File Transfer Protocol.
SNTP: Simple Network Time Protocol.
SRAM: Static Random Access Memory.
SSH: Secure SHell.
T
TCP/IP: Transmission Control Protocol/Internet Protocol.
TU: Terminal Unit.
Tx: Transmission.
V
VAC: Volt of Alternate Current.
VDC: Volt of Direct Current.
W
W: Watt.
X
XU: Expansion Unit.
Pag 98
Printed in:
Schneider Electric
C/ Charles Darwin s/n
Parque Científico y Tecnológico de la Cartuja
Seville, Spain
SE-USR-M588-06 11/2023
Pag 99