DB - All
DB - All
POOL DISTRIBUTION BOARD:12 WAYS TPN DISTRIBUTION BOARD -REF DB-4th FLOOR
LOCATION : 4th FLOOR LOBBY
LOCATION : S. POOL PUMP ROOM FED FROM : SMSB-4th FLOOR
FED FROM : SMSB-ROOF DISTRIBUTION BOARD:12 WAYS TPN DISTRIBUTION BOARD -REF DB-G FLOOR
INCOMING CABLE : 4cx16mm² PVC/SWA/PVC+ 1cx16mm² PVC/ECC
LOCATION : GROUND FLOOR INCOMING ISOLATING SWITCH : 40 A TP. MCB
INCOMING CABLE : 2cx16mm² PVC/SWA+ 1cx16mm² PVC/ECC
FED FROM : MSB WAYS CKT LOADS (W) M.C.B. (A) PVC WIRE (mm²)
INCOMING ISOLATING SWITCH : 40 A . MCB INCOMING CABLE : 4cx25mm² PVC/SWA/PVC+ 1cx16mm² PVC/ECC DESCRIPTION SINGLE CORE
R Y B
WAYS LOADS (W) M.C.B. (A) PVC WIRE (mm²) INCOMING ISOLATING SWITCH : 63 A TP. MCB
DESCRIPTION 800 10 8. NO. LIGHTING @ 5th FLOOR LOBBY 3*2.5
CKT SINGLE CORE WAYS CKT LOADS (W) M.C.B. (A) PVC WIRE (mm²)
DESCRIPTION 1 800 10 8. NO. LIGHTING @ 6th FLOOR LOBBY 3*2.5
2 LIGHTING @ PUMP ROOM 3*2.5 R Y B SINGLE CORE
1 200 10* 800 10 8. NO. LIGHTING @ 4th FLOOR LOBBY 3*2.5
2 LIGHTING @ S. POOL 3*2.5 1000 10* 8. NO. LIGHTING + 2EX. FAN TOILET 1,2 3*2.5
2 300 10* 600 10 6. NO. LIGHTING @ 4th FLOOR LOBBY 3*2.5
1 600 10* 6. NO. LIGHTING @ KITCHEN 3*2.5
3 1500 32* CIRCULAR PUMP 3*6 2 600 10 6. NO. LIGHTING @ 5th FLOOR LOBBY 3*2.5
400 10 4. NO. LIGHTING @ SECURITY 3*2.5
4 100 16* 1No SOCKET @ PUMP ROOM 3*4 600 10 6. NO. LIGHTING @ 6th FLOOR LOBBY 3*2.5
1400 10 14. NO. LIGHTING @ STAIR-2 3*2.5
7. NO. EMERGENCY LIGHTING @ 5th FLOOR 3*2.5
5 SPARE 2 700 10 7. NO. EMERGENCY LIGHTING @ STAIR-2 3*2.5 700 10
LOBBY
6 SPARE 1000 10 10. NO. EMERGENCY LIGHTING @ G. FLOOR 3*2.5 7. NO. EMERGENCY LIGHTING @ 5th FLOOR 3*2.5
3 700 10
1000 10 10. NO. LIGHTING @ MAIN ENTRANCE 3*2.5 LOBBY
7 SPARE 7. NO. EMERGENCY LIGHTING @ 5th FLOOR 3*2.5
PHASE 2100 * Denotes MCB/ELCB Combined Unit 30 mA Sensitivity 3 1400 10 14. NO. LIGHTING @ STAIR-1 3*2.5 700 10
LOBBY
LOAD Θ Denotes PVC/SWA/PVC CABLE 1000 10 10. NO. WALL LIGHTING @ G. FLOOR 3*2.5 600 10 6. NO. WALL LIGHTING @ 7th FLOOR LOBBY 3*2.5
700 10 7. NO. EMERGENCY LIGHTING @ STAIR-1 3*2.5 4 8. NO. EMERGENCY LIGHTING @ 4,5,6,7th FLOOR 3*2.5
TOTAL 800 10
2.10 LOBBY
LOAD (KW) 4 800 10 8. NO. LIGHTING @ LOBBY 3*2.5
800 10 8. NO. LIGHTING @ 7th FLOOR LOBBY 3*2.5
800 10 8. NO. LIGHTING @ COFFEE SHOP LOBBY 3*2.5 700 7. NO. EMERGENCY LIGHTING @ 7th FLOOR 3*2.5
800 8. NO. LIGHTING @ ENTRANCE 3*2.5 10
10 LOBBY
5 800 8NO. R/M SSO @ 4,5,6,7th FLOOR LOBBY 4*4+2*2.5
5 800 10 8. NO. LIGHTING @ ENTRANCE 3*2.5 32*
DISTRIBUTION BOARD : 13 WAYS SPN DISTRIBUTION BOARD - REF DB-BASEMENT 200 10 2. NO. LIGHTING @ FIRE FCC ROOM 3*2.5 0 - SPARE -
3000 32 COOKER CONTROL UNIT 3*6 0 - SPARE -
LOCATION : BASEMENT FLOOR 0 SPARE -
6 100 10 FIRE ALARM PANEL 3*2.5 6 -
FED FROM : MSB 500 10* MAIN ENTRANCE AUTO GATE 3*2.5 0 - SPARE -
INCOMING CABLE : 2cx16mm² PVC/SWA+ 1cx16mm² PVC/ECC 200 16 A/C INDOOR UNIT @ ENTRANCE 3*4 200 16 A/C INDOOR UNIT @ 4th FLOOR LOBBY 3*4
INCOMING ISOLATING SWITCH : 40 A . MCB 7 200 16 A/C INDOOR UNIT @ LOBBY 3*4 7 200 16 A/C INDOOR UNIT @ 4th FLOOR LOBBY 3*4
A/C INDOOR UNIT @ OFFICE 3*4 200 16 A/C INDOOR UNIT @ 4th FLOOR LOBBY 3*4
WAYS CKT LOADS M.C.B. (A) PVC WIRE (mm²) 200 16
3*2.5 200 16 A/C INDOOR UNIT @ 5th FLOOR LOBBY 3*4
(W) DESCRIPTION SINGLE CORE 200 16 A/C INDOOR UNIT @ ENTRANCE
8 200 16 A/C INDOOR UNIT @ 5th FLOOR LOBBY 3*4
8 600 32* 6NO. R/M SSO @ KITCHEN 4*4+2*2.5
200 16 A/C INDOOR UNIT @ 5th FLOOR LOBBY 3*4
400 32* 4NO. R/M SSO @ FIRE FCC ROOM 4*4+2*2.5
1 800 10* 8 LIGHTING @ PARKING 3*2.5 200 16 A/C INDOOR UNIT @ 6th FLOOR LOBBY 3*4
200 16 A/C INDOOR UNIT @ LIFT LOBBY 3*4
2 800 10* 8 LIGHTING @ PARKING 3*2.5 9 200 16 A/C INDOOR UNIT @ 6th FLOOR LOBBY 3*4
9 3000 32 COOKER CONTROL UNIT 3*6
3*2.5 200 16 A/C INDOOR UNIT @ 6th FLOOR LOBBY 3*4
3 400 10* 4 LIGHTING @ RAMP 600 32* 6 NO. R/M SSO @ COFFEE SHOP 4*4+2*2.5
200 16 A/C INDOOR UNIT @ 7th FLOOR LOBBY 3*4
4 400 10 4 LIGHTING @ LOBBI 3*2.5 800 32* 8 NO. R/M SSO @ COFFEE SHOP 4*4+2*2.5
10 200 16 A/C INDOOR UNIT @ 7th FLOOR LOBBY 3*4
10 200 16 A/C INDOOR UNIT @ FIRE FCC ROOM 3*4
5 500 10* AUTOMATIC GATE 3*2.5 200 16 A/C INDOOR UNIT @ 7th FLOOR LOBBY 3*4
200 16 A/C INDOOR UNIT @ SECURITY ROOM 3*4 0 - SPARE -
6 200 10 8 LIGHTING @ OOREDOO ROOM 3*2.5
800 32* 8 NO. R/M SSO @ ENTRANCE&SECURITY ROOM 4*4+2*2.5 11 0 - SPARE -
7 900 10* 9 LIGHTING @ BOUNDARY WALL 3*2.5 11 1000 15* 1 No. EXHAUST FAN @ KITCHEN 3*4 0 - SPARE -
8 700 10 7 EMERGENCY LIGHTING @ BASEMENT 3*2.5 2000 32* POWER OUTLET FOR CCTV 3*6 0 - SPARE -
3*2.5 0 - SPARE - 12 0 - SPARE -
9 100 10* POWER SUPPLY FOR WATER CABINET
12 0 - SPARE - 0 - SPARE -
10 700 32* 7NO. R/M SSO @ LOBBY 4*4+2*2.5
0 - SPARE - PHASE LOAD 4200 4500 3700 * Denotes MCB/ELCB Combined Unit 30 mA Sensitivity
11 2000 32 A/C SPLIT UNIT @ OOREDOO ROOM 3*6 PHASE 10100 9400 7300 * Denotes MCB/ELCB Combined Unit 30 mA Sensitivity Θ Denotes PVC/SWA/PVC CABLE
LOAD Θ Denotes PVC/SWA/PVC CABLE TOTAL LOAD (KW) 12.40
12 500 32* WATER SUMP PUMP 3*6
TOTAL
- 26.80
13 SPARE LOAD (KW)
DISTRIBUTION BOARD:12 WAYS TPN DISTRIBUTION BOARD -REF DB-M FLOOR
PHASE 8000 * Denotes MCB/ELCB Combined Unit 30 mA Sensitivity
LOAD Θ Denotes PVC/SWA/PVC CABLE LOCATION : MEZZANINE FLOOR LOBBY
FED FROM : MSB-G
TOTAL LOAD
8.00 INCOMING CABLE : 4cx16mm² PVC/SWA/PVC+ 1cx16mm² PVC/ECC
(KW)
DISTRIBUTION BOARD:4 WAYS TPN DISTRIBUTION BOARD -REF DB-ELEVATION INCOMING ISOLATING SWITCH : 40 A TP. MCB
LIGHT WAYS CKT LOADS (W) M.C.B. (A) PVC WIRE (mm²)
LOCATION : MEZZANINE FLOOR DESCRIPTION
DISTRIBUTION BOARD:8 WAYS TPN DISTRIBUTION BOARD -REF DB-P. HOUSE FED FROM : MSB R Y B SINGLE CORE
LOCATION : P. HOUSE INCOMING CABLE : 4cx16mm² PVC/SWA/PVC+ 1cx16mm² PVC/ECC 600 10 6. NO. LIGHTING @ PASSENGER AND LOBBY 3*2.5
FED FROM : SMSB-ROOF INCOMING ISOLATING SWITCH : 40 A TP. MCB 8. NO. LIGHTING @ LIFT LOBBY 3*2.5
1 800 10
INCOMING CABLE : 4cx16mm² PVC/SWA/PVC+ 1cx16mm² PVC/ECC WAYS CKT LOADS (W) M.C.B. (A) PVC WIRE (mm²)
DESCRIPTION 1000 10* 8. NO. LIGHTING + 2 EX. FAN @ BATH-01 3*2.5
INCOMING ISOLATING SWITCH : 40 A TP. MCB R Y B SINGLE CORE
WAYS CKT LOADS (W) M.C.B. (A) PVC WIRE (mm²) 7. NO. LIGHTING @ G. FLOOR OUT SIDE 3*2.5 500 10 5. NO. LIGHTING @ LOBBY 3*2.5
DESCRIPTION 700 10*
R Y B SINGLE CORE 3*2.5
1 1000 10* 10. NO. ELEVATION LIGHTING @ MEZZANINE 3*2.5 2 1000 10 10. NO. EMERGENCY LIGHTING @ MEZZANINE
1000 10* 8. NO. LIGHTING + 2 EX. FAN @ BATH-01,02 3*2.5 10. NO. ELEVATION LIGHTING @ 1st FLOOR A 3*2.5 3*2.5
1000 10* 700 10* 5. NO. LIGHTING + 2 EX. FAN @ BATH-02
1 300 10* 3. NO. LIGHTING @ FIRE PUMP ROOM 3*2.5 3*2.5
1000 10* 10. NO. ELEVATION LIGHTING @ 1st FLOOR B 3*2.5
3. NO. LIGHTING @ FIRE WATER TANK ROOM 3*2.5 1000 10 10. NO. LIGHTING @ OPEN TO BELOW-1
300 10* 2 1000 10* 10. NO. ELEVATION LIGHTING @ 6th FLOOR 3*2.5
500 10 5. NO. LIGHTING @ LIFT LOBBY 3*2.5 3*2.5 3 1000 10 10. NO. LIGHTING @ OPEN TO BELOW-2 3*2.5
1000 10* 10. NO. ELEVATION LIGHTING @ 7th FLOOR A
2 1000 10* 10. NO. LIGHTING @ WALL S. POOL 3*2.5 3*2.5
1000 10* 10. NO. ELEVATION LIGHTING @ 7th FLOOR B 1000 10 10. NO. LIGHTING @ OPEN TO BELOW-3 3*2.5
500 10 5. NO. EMERGENCY LIGHTING @ P. HOUSE 3*2.5
3 1000 10* 10. NO. ELEVATION LIGHTING @ P. HOUSE A 3*2.5 3*4
0 - SPARE - 200 16 A/C INDOOR UNIT @ OPEN TO BELOW-2
1000 10* 10. NO. ELEVATION LIGHTING @ P. HOUSE B 3*2.5
3 0 - SPARE - 4 1000 10 10. NO. LIGHTING @ MULTI PURPOSE HALL-1 3*2.5
0 - SPARE -
0 - SPARE - 1000 10 10. NO. LIGHTING @ MULTI PURPOSE HALL-2 3*2.5
4 0 - SPARE -
0 - SPARE - 200 16 A/C INDOOR UNIT @ LOBBY 2 3*4
0 - SPARE -
4 0 - SPARE - PHASE 2700 3000 3000 * Denotes MCB/ELCB Combined Unit 30 mA Sensitivity 5 200 16 A/C INDOOR UNIT @ OPEN TO BELOW-1 3*4
0 - SPARE - LOAD Θ Denotes PVC/SWA/PVC CABLE 200 16 A/C INDOOR UNIT @ LOBBY 1 3*4
700 32* 7 NO. R/M SSO @ LIFT LOBBY 4*4+2*2.5 TOTAL 0 - SPARE -
8.70
5 600 32* 6 NO. R/M SSO @ STORE 4*4+2*2.5 LOAD (KW)
6 0 - SPARE -
500 10* 5. NO. WALL LIGHTING @ P. HOUSE 3*2.5
0 - SPARE -
200 16 A/C INDOOR UNIT @ P. HOUSE -1 3*4 DISTRIBUTION BOARD:12 WAYS TPN DISTRIBUTION BOARD -REF DB-1st FLOOR 800 32* 8 NO. R/M SSO @ MULTI PURPOSE HALL 4*4+2*2.5
6 200 16 A/C INDOOR UNIT @ P. HOUSE -2 3*4
LOCATION : 1st FLOOR LOBBY
200 16 A/C INDOOR UNIT @ P. HOUSE -2 3*4 7 200 16 A/C INDOOR UNIT @ MULTI PURPOSE HALL 3*4
FED FROM : SMSB-1st FLOOR
0 - SPARE -
INCOMING CABLE : 4cx16mm² PVC/SWA/PVC+ 1cx16mm² PVC/ECC 700 32* 7 NO. R/M SSO @ LOBBY 4*4+2*2.5
7 0 - SPARE - 200 16 A/C INDOOR UNIT @ STORE 3*4
INCOMING ISOLATING SWITCH : 40 A TP. MCB
0 - SPARE - WAYS CKT LOADS (W) M.C.B. (A) PVC WIRE (mm²) 8 200 16 A/C INDOOR UNIT @ LIFT LOBBY 3*4
0 - SPARE - DESCRIPTION SINGLE CORE
R Y B 8 NO. R/M SSO @ OPEN TO BELOW-1 4*4+2*2.5
0 SPARE -
800 32*
8 - 800 10 8. NO. LIGHTING @ 1st FLOOR LOBBY 3*2.5
0 - SPARE - 0 - SPARE -
1 800 10 8. NO. LIGHTING @ 2nd FLOOR LOBBY 3*2.5
PHASE 2400 2100 1500 * Denotes MCB/ELCB Combined Unit 30 mA Sensitivity 3*2.5 9 0 - SPARE -
800 10 8. NO. LIGHTING @ 3rd FLOOR LOBBY
LOAD Θ Denotes PVC/SWA/PVC CABLE 0 - SPARE -
600 10 6. NO. WALL LIGHTING @ 3rd FLOOR LOBBY 3*2.5
TOTAL 0 -
6.00 2 600 10 6. NO. WALL LIGHTING @ 2nd FLOOR LOBBY 3*2.5 - SPARE
LOAD (KW)
600 10 6. NO. WALL LIGHTING @ 1st FLOOR LOBBY 3*2.5 10 0 - SPARE -
700 10 7. NO. EMERGENCY LIGHTING @ 1st FLOOR 3*2.5 0 - SPARE -
3 700 10 7. NO. EMERGENCY LIGHTING @ 2nd FLOOR 3*2.5 0 - SPARE -
700 10 7. NO. EMERGENCY LIGHTING @ 3rd FLOOR 3*2.5 11 0 - SPARE -
DISTRIBUTION BOARD:6 WAYS TPN DISTRIBUTION BOARD -REF DB-MACHINE ROOM A/C INDOOR UNIT @ 1st FLOOR LOBBY 3*4 0 - SPARE -
200 16
LOCATION : ROOF FLOOR 0 - SPARE -
4 200 16 A/C INDOOR UNIT @ 2nd FLOOR LOBBY 3*4
FED FROM : SMSB-ROOF 12 0 - SPARE -
200 16 A/C INDOOR UNIT @ 3rd FLOOR LOBBY 3*4
INCOMING CABLE : 4cx25mm² PVC/SWA/PVC+ 1cx16mm² PVC/ECC 0 - SPARE -
0 - SPARE -
INCOMING ISOLATING SWITCH : 63 A TP. MCB
5 0 - SPARE - PHASE LOAD 3500 4400 5400 * Denotes MCB/ELCB Combined Unit 30 mA Sensitivity
WAYS CKT LOADS (W) M.C.B. (A) PVC WIRE (mm²)
DESCRIPTION SINGLE CORE 0 - SPARE - Θ Denotes PVC/SWA/PVC CABLE
R Y B TOTAL LOAD (KW) 13.30
0 - SPARE -
300 10 3. NO. LIGHTING @ MACHINE ROOM 3*2.5
6 0 - SPARE -
1 200 16* 2. NO. SOCKET @ FILTER 3*4
200 16* 2. NO. SOCKET @ MACHINE ROOM 3*4
0 - SPARE - DISTRIBUTION BOARD : 10 WAYS SPN DISTRIBUTION BOARD - REF TYPICAL ROOM
200 16 A/C INDOOR UNIT @ 2nd FLOOR LOBBY 3*4
300 10 3. NO. EMERGENCY LIGHTING @ MACHINE ROOM
3*2.5
7 200 16 A/C INDOOR UNIT @ 2nd FLOOR LOBBY 3*4 LOCATION : TYPICAL ROOMS
2 200 16 A/C INDOOR UNIT @ 2nd FLOOR LOBBY 3*4 FED FROM : SMSB
3000 32* PRESSURE PUMP 3*6
200 16 A/C INDOOR UNIT @ 3rd FLOOR LOBBY 3*4 INCOMING CABLE : 2cx16mm² PVC/SWA+ 1cx16mm² PVC/ECC
2000 32 A/C SPLIT UNIT @ MACHINE ROOM 3*6
8 200 16 A/C INDOOR UNIT @ 3rd FLOOR LOBBY 3*4 INCOMING ISOLATING SWITCH : 40 A . MCB
0 - SPARE -
200 16 A/C INDOOR UNIT @ 3rd FLOOR LOBBY 3*4
0 SPARE -
WAYS CKT LOADS M.C.B. (A) PVC WIRE (mm²)
3 - 0 - SPARE - (W) DESCRIPTION SINGLE CORE
0 - SPARE - 9 600 32* 6NO. R/M SSO @ 1,2,3 FLOOR LOBBY 4*4+2*2.5
1 600 10 6 LIGHTING @ ROOM 3*2.5
4500 CENTRAL HEATER-1 3*6 0 - SPARE -
32*
0 - SPARE - 2 300 10* 2 LIGHTING + EX FAN @ BATH 3*2.5
4 4500 32* CENTRAL HEATER-2 3*6
9. NO. EMERGENCY LIGHTING @ 1,2,3 FLOOR 3*4 3 400 32* 4NO. R/M SSO @ ROOM 4*4+2*2.5
4500 32* CENTRAL HEATER-3 3*6 10 900 10
LOBBY
4500 32* CENTRAL HEATER-4 3*6 4 400 32* 4NO. R/M SSO @ ROOM 4*4+2*2.5
0 - SPARE -
5 0 - SPARE - 0 - SPARE - 5 100 10* SHAVER SOCKET 3*2.5
0 - SPARE - 11 0 - SPARE - 3*2.5
6 100 10 BELL
0 - SPARE - 0 - SPARE -
7 200 16 A/C INDOOR UNIT 3*4
6 0 - SPARE - 0 - SPARE -
0 - SPARE - 12 0 - SPARE - 8 SPARE -
PHASE 9600 7700 6700 * Denotes MCB/ELCB Combined Unit 30 mA Sensitivity 0 - SPARE - 9 SPARE -
LOAD Θ Denotes PVC/SWA/PVC CABLE PHASE LOAD 2700 4200 2700 * Denotes MCB/ELCB Combined Unit 30 mA Sensitivity
10 SPARE -
TOTAL Θ Denotes PVC/SWA/PVC CABLE
24.00 TOTAL LOAD
LOAD (KW) 9.60 PHASE LOAD 2100 * Denotes MCB/ELCB Combined Unit 30 mA Sensitivity
(KW)
Θ Denotes PVC/SWA/PVC CABLE
TOTAL LOAD (KW) 2.10