LoRaWAN® Controller

UC50x Series
User Guide
Safety Precautions
Milesight will not shoulder responsibility for any loss or damage resulting from not following the
instructions of this operating guide.
 The device must not be remodeled in any way.
 Do not place the device close to objects with naked flames.
 Do not place the device where the temperature is below/above the operating range.
 Make sure electronic components do not drop out of the enclosure while opening.
 When installing the battery, please install it accurately, and do not install the reverse or
wrong model.
 Make sure both batteries are newest when install, or battery life will be reduced.
 The device must never be subjected to shocks or impacts.

Declaration of Conformity
UC50x series is in conformity with the essential requirements and other relevant provisions of
the CE, FCC, and RoHS.

Copyright © 2011-2022 Milesight. All rights reserved.

All information in this guide is protected by copyright law. Whereby, no organization or individual
shall copy or reproduce the whole or part of this user guide by any means without written
authorization from Xiamen Milesight IoT Co., Ltd.
For assistance, please contact
Milesight technical support:
Email: [email protected]
Support Portal: support.milesight-iot.com
Tel: 86-592-5085280
Fax: 86-592-5023065
Address: Building C09, Software Park III,
Xiamen 361024, China

2
Revision History
Date Doc Version Description
Dec. 9, 2021 V 2.0 Initial version based on hardware 2.0
June 16, 2022 V 2.1 Update 3.3V power output feature
1. Add RS485 byte order feature
Nov. 21, 2022 V 2.2 2. Add GPIO initial counting value
modification feature

3
Contents

1. Product Introduction ......................................................................................................................... 5


1.1 Overview ...................................................................................................................................5
1.2 Features ................................................................................................................................... 5
2. Hardware Introduction ...................................................................................................................... 5
2.1 Packing List ..............................................................................................................................5
2.2 Hardware Overview ................................................................................................................. 6
2.3 Internal Interfaces ................................................................................................................... 7
2.4 Dimensions .............................................................................................................................. 8
3. Hardware Switch ............................................................................................................................... 8
4. Operation Guide .................................................................................................................................8
4.1 Log in the ToolBox ...................................................................................................................8
4.1.1 NFC Configuration ........................................................................................................ 9
4.1.2 USB Configuration ........................................................................................................ 9
4.2 LoRaWAN Settings ................................................................................................................ 10
4.3 Interface Settings .................................................................................................................. 13
4.3.1 RS485 Settings ........................................................................................................... 14
4.3.2 RS232 Settings ........................................................................................................... 17
4.3.3 GPIO Settings ..............................................................................................................18
4.3.4 AI Settings ................................................................................................................... 20
4.4 Maintenance .......................................................................................................................... 22
4.4.1 Upgrade ....................................................................................................................... 22
4.4.2 Backup .........................................................................................................................23
4.4.3 Reset to Factory Default .............................................................................................24
5. Installation ....................................................................................................................................... 25
6. Milesight IoT Cloud Management ..................................................................................................26
7. Device Payload ................................................................................................................................ 27

4
1. Product Introduction

1.1 Overview
UC50x series is a LoRaWAN® controller used for data acquisition from multiple sensors. It
contains different I/O interfaces such as analog inputs, digital inputs, digital outputs, serial ports
and so on, which simplify the deployment and replacement of LoRaWAN® networks.
UC50x series can be easily and quickly configured by NFC or wired USB port. For outdoor
applications, it provides solar or built-in battery power supply and is equipped with IP67-rated
enclosure and M12 connectors to protect itself from water and dust in harsh environments.

1.2 Features
 Easy to connect with multiple wired sensors through GPIO/AI/RS232/RS485 interfaces
 Long transmission distance up to 15 km with line of sight
 Waterproof design including IP67 case and M12 connectors
 Solar powered and built-in battery optional
 Quick wireless configuration via NFC
 Compliant with standard LoRaWAN® gateways and network servers
 Quick and easy management with Milesight IoT Cloud solution

2. Hardware Introduction
2.1 Packing List

1 × UC50x 2 × Data Cables 1 × Mounting 4 × Wall 2 × Hose Clamps

Device (30 cm) Bracket Mounting Kits

1 × Fixing Screw 1 × Quick Guide 1 × Warranty Card 1 × Solar Panel Kit

(Optional)

If any of the above items is missing or damaged, please contact your sales Representative.

5
2.2 Hardware Overview

UC501 UC502

Data Interface 1:
Pin Description
1 5V/9V/12V OUT (Switchable)
2 3.3V OUT
3 GND
4 Analog Input 1
5 Analog Input 2
6 5-24V DC IN
①②

Data Interface 2:
Pin Description
1 5V/9V/12V OUT (Switchable)
2 3.3V OUT
3 GND
4 GPIO1
5 GPIO2
6
RS232/RS485 (Switchable)
7
8 Reserved
Pin RS232 RS485
6 TXD A

7 RXD B

When both DC external power and batteries are connected, external power will be the preferred power supply

option.
For UC502, the DC interface can’t be to charge battery.

6
2.3 Internal Interfaces

DIP Switch:
Interface DIP Switch
12V: 1 on 2 off 3 off
Power Output 9V: 1 off 2 on 3 off
5V: 1 off 2 off 3 on
4-20mA ADC: 1 off 2 on 3 on
Analog Input
0-10V ADC: 1 on 2 off 3 off
Add 120 Ω resistor between A and B: 1 on 2 off 3 off
RS485 Add 1k Ω pull-up resistor on A: 1 off 2 on 3 off
Add 1k Ω pull-down resistor on B: 1 of 2 off 3 on

Note:
1) Analog inputs are set to 4-20mA by default, power outputs are set to 12V by default.
2) Power output on interface 1 is used for powering analog devices, power output on interface 2
is used for powering serial port devices.

Power Button:
Function Action LED Indication
Turn On Press and hold the button for more than 3s. Off →
Turn Off Press and hold the button for more than 3s. → Off
Reset Press and hold the button for more than 10s. Blinks.
Check : Device is on.
Quickly press the power button.
On/Off Status Light Off: Device is off.

7
2.4 Dimensions (mm)

3. Hardware Switch
When using the analog input or power output of UC50x series, please follow the steps to switch
the working mode of hardware interface:
1. Remove the screw caps and take off the roof cover.
2. Change DIP switches that are related analog inputs and power outputs as shown in Section
2.3.
3. Put back the roof cover and screw the screws.
Note: turn off the device before changing DIP switches.

4. Operation Guide

4.1 Log in the ToolBox


UC50x series can be configured via NFC or Type-C port. Please select one of them to complete
configuration.

8
4.1.1 NFC Configuration
1. Download and install “Milesight ToolBox” App from Google Play or Apple App Store.
2. Enable NFC on the smart phone and launch Milesight ToolBox.
3. Attach the smart phone with NFC area to the device to read device information.
4. Basic information and settings of the device will be shown on ToolBox App if it’s recognized
successfully. You can read and configure the device by tapping the Read/Write device on the
App. In order to protect the security of the device, password validation is required when first
configuration. The default password is 123456.

Note:
1) Ensure the location of smart phone NFC area and it’s recommended to take off phone case.
2) If the smart phone fails to read/write configurations via NFC, keep the phone away and back
to try again.
3) UC50x series can also be configured by dedicated NFC reader, which can be purchased from
Milesight IoT.

4.1.2 USB Configuration


1. Download ToolBox software from Milesight IoT website.
2. Open the case of UC50x and connect the UC50x to computer via type-C port.

3. Open the ToolBox and select type as “General”, then click password to log in ToolBox.
(Default password: 123456)

9
4. After logging in the ToolBox, you can click “Power On” or “Power Off” to turn on/off device
and change other settings.

4.2 LoRaWAN Settings


LoRaWAN settings is used for configuring the transmission parameters in LoRaWAN® network.

Basic LoRaWAN Settings:


Go to “LoRaWAN -> Basic” of ToolBox software or “Setting -> LoRaWAN Settings” for ToolBox
App to configure join type, App EUI, App Key and other information. You can also keep all
settings by default.

10
Parameters Description
Device EUI Unique ID of the device which can also be found on the label.
App EUI Default App EUI is 24E124C0002A0001.
The port used for sending and receiving data, default port is 85.
Application Port
Note: RS232 data will be transmitted via another port.
UC501: Class A and Class C are available;
Working Mode
UC502: Class A.
Join Type OTAA and ABP mode are available.
Application Key Appkey for OTAA mode, default is 5572404C696E6B4C6F52613230313823.
Device Address DevAddr for ABP mode, default is the 5th to 12th digits of SN.
Network Session
Nwkskey for ABP mode, default is 5572404C696E6B4C6F52613230313823.
Key
Application
Appskey for ABP mode, default is 5572404C696E6B4C6F52613230313823.
Session Key
RX2 Data Rate RX2 data rate to receive downlinks.

11
RX2 Frequency RX2 frequency to receive downlinks. Unit: Hz
Spread Factor If ADR is disabled, the device will send data via this spread factor.
If the device does not receive ACK packet from network server, it will resend
Confirmed Mode
data once.
Reporting interval ≤ 30 mins: the device will send a specific number of
LinkCheckReq MAC packets to the network server every 30 mins to validate
connectivity; If there is no response, the device will re-join the network.
Rejoin Mode Reporting interval > 30 mins: the device will send a specific number of
LinkCheckReq MAC packets to the network server every reporting interval to
validate connectivity; If there is no response, the device will re-join the
network.
ADR Mode Allow network server to adjust datarate of the device.
Tx Power Tx power of the device.
Note:
1) Please contact sales for device EUI list if there are many units.
2) Please contact sales if you need random App keys before purchase.
3) Select OTAA mode if you use Milesight IoT cloud to manage devices.
4) Only OTAA mode supports rejoin mode.

LoRaWAN Frequency Settings:


Go to “LoRaWAN -> Channel” of ToolBox software or “Setting -> LoRaWAN Settings” for ToolBox
APP to select supported frequency and select channels to send uplinks. Make sure the channels
match the LoRaWAN® gateway.

12
If frequency is one of CN470/AU915/US915, you can enter the index of the channel that you
want to enable in the input box, making them separated by commas.
Examples:
1, 40: Enabling Channel 1 and Channel 40
1-40: Enabling Channel 1 to Channel 40
1-40, 60: Enabling Channel 1 to Channel 40 and Channel 60
All: Enabling all channels
Null: Indicates that all channels are disabled

Note:
For -868M model, default frequency is EU868;
For -915M model, default frequency is AU915.

4.3 Interface Settings


UC50x series support data collection by multiple interfaces including GPIOs, analog inputs and
serial ports. Besides, it can also power the terminal devices by power output interfaces. Basic
settings are as follows:
Go to “General -> Basic” of ToolBox software or “Setting -> General Settings” page to change the
reporting interval.

13
Parameters Description
Reporting interval of transmitting data to network server. Default: 20
Reporting Interval mins, Range: 1-1080 mins.
Note: RS232 transmission will not follow the reporting interval.
The device returns
If the device loses power and return to power supply, the device will be
to the power supply
on or off according to this parameter.
state
Change the password for ToolBox APP or software to read/write this
Change Password
device.

4.3.1 RS485 Settings


1. Connect RS485 device to RS485 port on interface 2. If you need UC50x to power the RS485
device, please connect the power cable of RS485 device to 5V/9V/12V or 3.3V power output on
interface 2.
2. Go to “General -> Serial” of ToolBox software or “Setting -> Serial Setting” to enable RS485
and configure serial port settings. Serial port settings should the same as RS485 terminal
devices.

14
Parameters Description
Enable 5V/9V/12V power output of interface 2 to supply power to RS485
Interface 2(Pin 1)
terminal devices. It’s 12V by default and you can change DIP switches to
5V/9V/12V Output
change voltage.
5V/9V/12V power output will power the RS485 terminal devices for a period
Power Output Time
of time before collecting data for terminal device initialization.
Before Collect
Range: UC501 is 0-600s, UC502 is 0-10s.
Interface 2(Pin 2) Enable 3.3V power output of interface 2 to supply power to RS485 terminal
3.3V Output devices.
Power Supply Select “Continuous power supply” or “Configurable power supply time”.
Mode When you select “Configurable power supply time”, the time range is 0-600s.

Baud Rate 1200/2400/4800/9600/19200/38400/57600/115200 are available.

Data Bit 8 bit is available.

Stop Bit 1 bit/2 bit are available.

Parity None, Odd and Oven are available.

Execution Interval The execution interval between each Modbus command.

The maximum response time that the UC50x waits for the reply to the
Max Resp Time command. If it does not get a response after the max response time, it is
determined that the command has timed out.
Set the maximum retry times after device fails to read data from RS485
Max Retry Time
terminal devices.
If this mode is enabled, UC50x will transparent Modbus RTU commands
Modbus RS485 from network server to RS485 terminal devices and send Modbus reply
bridge LoRaWAN originally back to network server.
Port: Select from 2-84, 86-223.
Note: When you use power output to power RS485 Modbus slave devices, it only supplies power
when reporting interval is coming. It’s suggested to power slave devices with external power
during the PoC test.

3. Click to add Modbus channels, then save configurations.

15
Parameters Description
Channel ID Select the channel ID you want to configure, 16 channels selectable.
Name Customize the name to identify every Modbus channel.
Slave ID Set Modbus slave ID of terminal device.
Address The starting address for reading.
Quantity Set read how many digits from starting address. It fixes to 1.
Type Select data type of Modbus channels.
Set the Modbus data reading order if you configure the type as Input
Register or Holding Register.
Byte Order
INT32/Float: ABCD, CDBA, BADC, DCBA
INT16: AB,BA
Sign The tick indicates that the value has a plus or minus sign.
After click, the device will send Modbus read command to test if it
can read correct values.
Example: as this setting, the device will send command: 01 03 00 00
00 01 84 0A
Fetch

4. For ToolBox software, click “Fetch” to check if UC50x can read correct data from terminal
devices. You can also click “Fetch” on the top of list to fetch all channel data.

Note: do not click “Fetch” frequently since response time to reply is differ for every terminal
device.

16
For ToolBox App,
a. Tap every Modbus channel, click “Collect” and attach smart phone to device to make device
collect data.
b. Click “Fetch” and attach smart phone to make App read the data. You can also tap “Collect
All” and “Fetch All” to fetch all channel data.

4.3.2 RS232 Settings


1. Connect RS232 device to RS232 port on interface 2. If you need UC501 to power the RS232
device, connect the power cable of RS232 device to power output on interface 2.
2. Go to “General -> Serial” of ToolBox software or “Setting -> Serial Setting” to enable RS232
and configure serial port settings. Serial port settings should the same as RS232 terminal
devices.

17
Parameters Description
Enable 5V/9V/12V power output of interface 2 to supply power to RS232
Interface 2(Pin 1) terminal devices continuously. Only UC501 supports this feature.
5V/9V/12V Output Note: Power output is 12V by default and you can change DIP switches to
change voltage.
Interface 2(Pin 2)
Enable 3.3V power output of interface 2 to supply power to RS232 terminal
3.3V Continuous
devices continuously.
Output

Baud Rate 300/1200/2400/4800/9600/19200/38400/57600/115200 are available.

Data Bit 8 bit is available.

Stop Bit 1 bit/2 bit are available.

Parity None, Odd and Oven are available.

Port The port used for RS232 data transmission.

4.3.3 GPIO Settings


1. Connect devices to GPIO ports on interface 2.
2. Go to “General -> GPIO” of ToolBox software or “Setting -> GPIO Setting” to enable GPIO port.

18
3. Select GPIO type according to your requirements.
Digital Input:
Digital input can be used to detect high or low status of devices.

Parameters Description
Initial status of digital input.
Digital Input Pull Down: rising edge will be triggered
Pull Up/None: falling edge will be triggered
Fetch Click to get current status of digital input.

Digital Output:
Digital output will send voltage signals to control devices.

19
Parameters Description
Fetch Click to get current status of digital output.
Click to switch the digital output status to check if UC50x can trigger
Switch
devices.

Pulse Counter:

Parameters Description
Initial status of counter.
Digital Input Pull Down: Increase 1 when detecting rising edge
Pull Up/None: Increase 1 when detecting falling edge
Digital Filter It’s recommended to enable when pulse period is greater than 250 us.
Keep last value
Keep the counted values when the device powers off.
when power off
Make the device start/stop counting.
Start/Stop Note: UC50x will send non-changable counting values if you do not click
“Start”.
Refresh Refresh to get latest counter values.
Clear Count the value from 0.
Modify the
Set the initial counting value.
count values

4.3.4 AI Settings
1. Connect analog device to analog input ports on interface 1. If you need UC50x to power the
analog device, connect the power cable of analog device to power output on interface 1.

20
2. Go to “General -> AI” of ToolBox software or “Setting -> AI Setting” to enable analog input and
select the analog type.
Note: Ensure DIP switches has changed if you need to use 0-10V mode.

3. Enable “Interface 1 (Pin 1) 5V/9V/12V Output” or “Interface 1 (Pin 2) 3.3V Output” and
configure “Power Output Time Before Collect”, UC50x will power the analog devices for a period
of time before collecting data.
Note: When you use power output to power analog devices, it only supplies power when
reporting interval is coming. It’s suggested to power slave devices with external power during
the PoC test.

4. For ToolBox software, click “Fetch” to check if UC50x can read correct data from analog
devices.

21
For ToolBox App,
a. Click “Collect” and attach smart phone to device to make device collect data.
b. Click “Fetch” and attach smart phone to make APP read the data.

4.4 Maintenance
4.4.1 Upgrade
ToolBox Software:
1. Download firmware from www.milesight-iot.com to your PC.
2. Go to “Maintenance -> Upgrade” of ToolBox software, click “Browse” to import firmware and
upgrade the device. You can also click “Up to Date” to search for the latest firmware of the
device and upgrade.

22
ToolBox App:
1. Download firmware from www.milesight-iot.com to your smart phone.
2. Open ToolBox App and click “Browse” to import firmware and upgrade the device.
Note:
1) Operation on ToolBox is not supported during the upgrade.
2) Only Android version ToolBox supports the upgrade feature.

4.4.2 Backup
UC50x devices support configuration backup for easy and quick device configuration in bulk.
Backup is allowed only for devices with the same model and LoRa frequency band. Please select
one of following methods to backup device:
ToolBox Software:
1. Go to “Maintenance -> Backup and Reset”, click “Export” to save current configuration as json
format backup file.
2. Click “Browse” to select backup file, then click “Import” to import the configurations.

23
ToolBox App:
1. Go to “Template” page on the App and save current settings as a template. You can also edit
the template file.
2. Select one template file which saved in the smart phone and click “Write”, then attach to
another device to write configuration.

4.4.3 Reset to Factory Default


Please select one of following methods to reset device:
Via Hardware: Open the case of UC50x and hold on power button more than 10s.
Via ToolBox Software: Go to “Maintenance -> Backup and Reset” to click “Reset”.

24
Via ToolBox App: Go to “Device -> Maintenance” to click “Reset”, then attach smart phone with
NFC area to UC50x to complete reset.

5. Installation
UC50x series support wall mounting or pole mounting. Before installation, make sure you have
the mounting bracket, wall or pole mounting kits and other required tools.
Wall Mounting:
1. Fix the wall plugs into the wall, then fix the mounting bracket to the wall plugs with screws.
2. Put the device on the mounting bracket, then fix the bottom of the device to the bracket with
a fixing screw. It’s necessary to fix this bracket to device, or it will affect the signal.

Pole Mounting:
1. Straighten out the hose clamp and slide it through the rectangular rings in the mounting bracket, wrap
the hose clamp around the pole. After that use a screwdriver to tighten the locking mechanism by
turning it clockwise.

25
2. Put the device on the mounting bracket, then fix the bottom of the device to the bracket with
a fixing screw. It’s necessary to fix this bracket to device, or it will affect the signal.

6. Milesight IoT Cloud Management


UC50x series can be managed by Milesight IoT Cloud platform. Milesight IoT cloud is a
comprehensive platform that provides multiple services including device remote management
and data visualization with the easiest operation procedures. Please register a Milesight IoT
Cloud account before operating following steps.

1. Ensure Milesight LoRaWAN® gateway is online in Milesight IoT Cloud. For more info about
connecting gateway to cloud please refer to gateway’s user guide.

2. Go to “My Devices” page and click “+New Devices”. Fill in the SN of UC50x and select
associated gateway.

26
3. For UC501, click and go to “Basic Settings” to change class type the same as device
settings.

4. After UC50x is online in Milesight IoT Cloud, click and go to “Interface Settings” to
select used interfaces and customize the name, sign and formulas.
Note: Modbus channel settings should be the same as the configuration in ToolBox.

7. Device Payload
UC50x Series use the standard Milesight IoT payload format based on IPSO. Please refer to the
UC50x Series Communication Protocol; for decoders of Milesight IoT products please click here.

-END-