AM2832 - Instrumentation and Controls Standards
AM2832 - Instrumentation and Controls Standards
1. General Requirements
1.1 Acronyms and Abbreviations
All abbreviations and acronyms used in additional documentation, shall follow the conventions
used through this and other related project documents.
Acronym Description
ABS Acrylonitrile Butadiene Styrene
AD Active Directory
AI Analogue Input
AO Analogue Output
COTS Commercial Off The Shelf
Cu Copper
DI Digital Input
DIN German Institute for Standards (Deutsches Institut für Normung)
DNP3 Distributed Network Protocol (version 3)
DO Digital Output
ELV Extra Low Voltage
EMC Electromagnetic Compatibility
FAT Factory Acceptance Test
FDS Functional Description Specification
HMI Human Machine Interface
IEC International Electrotechnical Commission
iLO Integrated Lights Out
IO Input Output
IP Ingress Protection
ITP Inspection Test Plan
LCD Liquid Crystal Display
LED Light Emitting Diode
LV Low Voltage
mAHD Metre Australian Height Datum
NTP Network Time Protocol
OTDR Optical Time Domain Reflectometer
P&ID Process & Instrumentation Diagram
PC Personal Computer
PLC Programmable Logic Controller
PSU Power Supply Unit
1.2 Scope
This specification outlines South East Water’s minimum standards for the selection, fabrication,
delivery, installation and testing of instrumentation and controls equipment, associated items
used at new or renewed water and sewerage infrastructure sites.
Excluded from the scope of this specification are:
a. South East Water assets not containing water and sewerage infrastructure (e.g.,
WatersEdge office, depots)
b. Functional or operational requirements relating to electrical assets.
c. Monitoring, protection, control and communication system design, configuration and
programming. This is covered by other South East Water standards such as
AM2779_Treatment Plant Monitoring and Control Specification.
d. Civil, mechanical arrangements, pump selection, pump performance or hydraulic
assessment.
e. Work practices associated with the management of electrical risks during construction
and installation works.
1.3 Standards
The following standards shall apply in the given order of preference:
a) Australian Standards or its IEC/ISO equivalent
b) OH&S Regulations 2017 (Victoria)
c) Electricity Safety (Installations) Regulations (Victoria)
d) Victorian Service & Installation Rules
e) Essential Services Commission Electricity Distribution Code
f) Requirements of the Electricity Distribution Company
g) Electricity Safety Act (Victoria)
h) Manufacturer’s Guidelines
i) Water Industry Standards, including:
i. WSA04 Sewage Pumping Station Code Of Australia
ii. South East Water supplementary manual to WSA04
iii. South East Water Standard Electrical Drawings
iv. AM2779_Treatment Plant Monitoring and Control Specification (SEW)
v. AM2717_Generator Specification (SEW)
vi. AM2522_O&M Manual Specification (SEW)
vii. AM2755_Testing, Commissioning and Handover Plan (SEW)
viii. AM2739_Corrosion Mitigation Specification (SEW)
ix. AM2727_Covers for Underground Structures (SEW)
x. AM 2758_Noise Specification (SEW)
xi. AM2775_Watershed Collection Details (SEW)
xii. AM2776.3_Air Treatment Unit Specification and Commissioning (SEW)
xiii. AM2488_2D and 3D Drafting
The order of precedence of documents shall be as follows:
a) Legislated requirements
b) Project specific specifications
c) Project specific drawings
d) South East Water standards
e) South East Water standard drawings
f) Water Industry Standards (WSAA)
1.6 Labelling
Please refer to AM2775.
2. Installation Requirements
Please refer to AM2714.
All works shall be done by appropriately* qualified, competent, recognised and approved by SEW
representative instrument technician/personnel or vendor subject matter expert specific to the
task.
*Shall be determined by SEW. Minimum requirements would be to undergo the following
Swagelok trainings for instrument fitters:
Instrument Pipe Work fittings. – technician must have completed Swagelok Tube bending
essentials course & Tube Fitting Installation Course.
Calibration and setup of instruments – must be carried out by qualified Instrument or
Instrument/Electrical Technician or Vendor Representative.
3. Instrumentation
3.1 Installation
3.1.1 Arrangement
Instruments shall be arranged so that adjustments can be readily made in the field. Permanent
access shall be provided for all field indicators, transmitters, analysers, actuators and points of
calibration or challenge testing. Where applicable provide drain and 1/4 inch test points with
associated isolation valves for in situ calibration without the requirement to dismantle supports
or pipework.
3.1.5 Support
Where applicable instruments shall be mounted using brackets as supplied by the
manufacturer. No instrument shall be installed dependent only on its impulse piping, process or
electrical connection.
3.1.8 Piping
Provide pipe unions, isolation valves, test and drain points to enable removal or in situ calibration
of in line instruments with threaded connections such as pressure transmitter switches, and
gauges, rotameters etc.
All small bore fittings shall be per AM2848 Approved EIC Equipment List e.g., Swagelok
gaugeable fitting.
All threaded joints shall be BSP threads. NTP threading, BSB tapered and BSP parallel threading
may be required for connection of some components.
All cock valves shall be Swagelok quarter turn ball valves. All needle valves shall be Swagelok
screwed bonnet needle valves.
All piping and impulse tubing shall be stainless steel or flexible nylon. Flexible nylon tubing shall
be rated to 1.5 times the maximum measurement value and be fitted with Swagelok gaugeable
fittings.
Where piping or tube is exposed to the elements or installed in an area with a run greater than
1m shall be stainless steel.
3.1.10 Transmission
All instruments shall be capable of transmitting the output signal by loop powered 4-20mA
analogue current loop. The output signal shall be linear with a proportional increase in the
measured variable. Each transmitter shall be fitted with a configurable local indicator. The
indicator shall be integral to the transmitter assembly. The local indicator shall display the
measured value in engineering units.
Signal transmission shall be HART protocol compatible. A series resistor of 250 ohms shall be
connected within the signal loop located adjacent to the instrument to allow connection of a Hart
configurator/ calibrator. Consideration to minimum operating voltage (loop power instruments)
and total loop resistance shall be consider when adding series resistance.
NOTE: Burn-in/burn-out or fail-low/fail-high transmitter settings must be documented
3.2.4 Potting
All sensors must be potted with the manufacture recommended potting mix. Any unused cable
glands must be sealed with appropriate o’ring sealed, threaded plastic conduit plugs.
If the site only has a cabinet the transmitter must be mounted either in its own
tier/compartment or with station control with the flow rate programmed onto the site HMI
and to SCADA.
Direct Mounting may be allowed as advised by SEW M&E Team, with station control with
the flow rate programmed onto the site HMI and to SCADA. This will normally only be
considered if the flow meter is indoors and the display can be accessible from the ground.
Treatment Plants
If the flow meter signal converter (transducer) resides near a building then the transmitter
must be mounted on the internal side wall of the building wall between 1.5m and 1m, with
the flow rate programmed onto the site SCADA and to Remote SCADA
If the flow meter signal converter (transducer) is remote it must be installed in a vented
S/S or Aluminum River gum enclosure painted G62 Rivergum.
Direct Mounting may be allowed as advised by SEW M&E team, with station control with
the flow rate programmed onto the site SCADA and to Remote SCADA. This will normally
only be considered if the flow meter is indoors and the display can be accessible from the
ground.
3.2.11 Fasteners
All bolts/ nuts / washers shall be stainless steel 316 coated with nickel-based anti-seize.
Combination of Metal and Plastic Pipes Bonding Not including Full Bond above
Sewer Pump stations - with a PDWF (Peak Dry Weather Flow) of equal to or
greater than 25 l/s
Water Booster Pump stations - All
Treatment Plants - Critical flow paths lines
3.3 Underground
3.3.1 Location
A preference is not to bury flow sensors, pits need to be considered as per requirements in
AM2714.
Water:
Refer to Standard drawings
Sewer:
Refer to Standard drawings
3.5 Transmitter
3.5.1 Lightning Protection
If available from the manufacturer, lighting protection shall be installed in the flow meter sensor
and transmitter.
3.5.2 UV Protection
All transmitters not installed indoors shall be fitted with an aluminium or s/s cabinet refer to
AM2714.
If a transmitter is installed directly on the sensor outdoors it shall be fitted with stainless steel or
aluminium hinged cover. This cover shall cover the full transmitter height.
3.8.2 Calibration
Conduct calibration of instruments against a reference instrument, test pressure or standard.
Calibrate instrument at 0, 25, 50, 75 and 100% of nominated range.
Provide a calibration report for each function indicating instrument uncertainty, error and
adjustment.
Calibrated measurements are to be compared against the manufacturer's specification.
Provide manufactures calibration certificates stating the instrument compliance against the
instrument specification.
3.8.3 Ranges
Unless otherwise specified the instrument range shall be from zero (0) to 1.5 times the expected
maximum measurement value.
Fibre optic cables and structured copper cabling shall be terminated in a patch panel located
either in an existing 19 inch server rack or control cabinet / panel.
4. Verification / Documentation
4.1 Verification
All instruments such as flowmeter, etc shall be verified by the manufacturer or by their approved
verification device.
If the verification comes back failed it is the contractor’s responsibility to excavate (if buried) and
rectify the problem
4.2 Documentation
Sensor locations shall marked on site CAD plans.
All underground Sensors shall be GPS marked and locations, cable runs updated on CAD
drawings.
All verification certifications shall be set through to SEW.
Output signals shall be setup and recorded on SEW standard calibration sheets and submitted.
Photo evidence shall be submitted for the below
Location if reference to something in the background not likely to move
Installed before Wrapping with cable connected
Transmitter location
Transmitter Cabinet with doors closed and open showing equipment
After Sensor is wrapped
Backfilled with washed sand
Backfilled and area cleaned up.
The Flowmeter Installation Sheet in Appendix C shall be completed and submitted for all flow
meter installations.
5.1 General
PLC and RTU installations shall meet the following requirements:
PLCs and RTUs shall be located within a separate compartment of the switchboard which
shall contain the programmable devices, relevant I/O, communications interfaces and
associated terminal strips and interposing relays. This compartment shall be designed and
installed in accordance with section 3 of AM2714.
5.2 IO Termination
IO shall be terminated as follows:
Where possible and for all new PLC or RTU installations, IO terminal strips shall be used
between field wiring and PLC IO terminals.
Multicore cable with pre-numbered cores shall be used between PLC IO cards and IO
terminal strips, with numbered cable identification at the junction of each core at the IO
terminal strip.
These terminal strips shall be DIN rail mounted.
Terminal strips are to be labelled and segregated into a) input analogue, b) input digital,
c) output analogue, and d) output digital.
In each terminal strip, order terminals in alphanumerical order in accordance with the
wire’s unique identification number.
Digital inputs and outputs shall be individually fused at the IO terminal strip and a test link
for the common terminal; each common supplying a group of inputs shall also be
separately fused.
Analogue input and output IO terminal strips shall have a fuse installed on the positive (+)
and a test link installed on the negative (-). In addition to this, each analogue IO point shall
contain a terminal for the connection of outgoing shield connection.
Space shall be allocated within the PLC and RTU compartment of the switchboard to
terminate all spare slots (cards).
Wiring colours shall follow AM2714.
5.3 IO Segregation
Where plant or equipment has operational redundancy, the control system IO shall be configured
to ensure the plant redundancy is maintained if there is a failure of a control system IO card. In
such cases, all PLC IO shall be segregated between IO cards / modules for each piece of
redundant plant equipment. E.g. Dosing pumps in a duty / standby arrangement shall have all
inputs / outputs for each pump connected to different IO cards in the PLC.
Where plant equipment has further redundancy employed such as redundant paths or
redundancy of entire plant processes, the IO should be segregated into different IO racks in
separate switchboard compartments that each comprises all of the equipment associated with
each redundant plant item.
SCADA VALUES
Tag No Zero Full Scale
Office ☐ Plant Computer ☐
FLOW METER DETAILS
Flow Sensor Model: Flow Sensor Serial No:
Sensor Size: Cal Factor Insertion Depth:
Sensor Prom Code Number: Transmitter Serial No: Flow Direction Uni. Bi.
CALIBRATION EQUIPMENT
Input: Serial No: Calibration Date:
Output: Serial No: Calibration Date:
CALIBRATED BY
Technician Name: Company: Signature:
Comments: Pass ☐ Fail ☐
Action Raised ☐ Operator informed ☐