The document provides specifications for PETRA fan coil units, including their intended applications, nomenclature breakdown, unit types, features, quality assurance measures, specifications, options, and performance data tables. It contains detailed technical information about the units covering areas such as coils, motors, casing, filters, fans, insulation, and drain pans.

Uploaded by

ahmemustafa997
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
35 views

RAC

The document provides specifications for PETRA fan coil units, including their intended applications, nomenclature breakdown, unit types, features, quality assurance measures, specifications, options, and performance data tables. It contains detailed technical information about the units covering areas such as coils, motors, casing, filters, fans, insulation, and drain pans.

Uploaded by

ahmemustafa997
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 43

TABLE OF CONTENTS

INTRODUCTION 1
NOMENCLATURE 1
UNIT TYPES 1
OUTSTANDING FEATURES 2
QUALITY ASSURANCE 2
SPECIFICATIONS 2
OPTIONS 2
GENERAL DATA TABLES 3
PERFORMANCE DATA TABLES 5
FAN PERFORMANCE DATA TABLE 30
MODEL LAYOUTS 31
PETRA HIGH WALL CHILLED WATER (PWC) 34
ELECTRICAL DATA TABLES 37
SOUND POWER LEVEL dB 38
ELECTRIC HEATER CAPACITY 38
WIRING DIAGRAMS 39
INTRODUCTION
PETRA’s fan coil units (RAC Series) are The units cover an air flow range from 200 They provide flexible operation and
ideally designed for air conditioning to 1200 nominal CFM. The standard unit control of indoor conditions in individual
residential, commercial and institutional consists of a coil section, suitable for both spaces.
buildings with low static pressure chilled / hot water, a fan section with a
application. direct drive centrifugal fan and a flat filter.

NOMENCLATURE

RAC 4 GFC H/C 3

Room Air No. of Rows


Conditioner 3 : 3 Rows
[Low static] 4 : 4 Rows

Nominal Air Flow Rate


2 : 200 CFM Heating/Cooling Coil
3 : 300 CFM
4 : 400 CFM
5 : 500 CFM
6 : 600 CFM
8 : 800 CFM GFC : (G. Steel) Floor Cabinet Model
10 : 1000 CFM GCC: (G. Steel) Ceiling Cabinet Model
12 : 1200 CFM PFC : Plastic Floor Cabinet Model (Deluxe)
PCC : Plastic Ceiling Cabinet Model (Deluxe)
FB : Floor Basic Model
CB : Ceiling Basic Model
CBP : Ceiling Basic with Plenum

UNIT TYPES
CB GFC PFC
Ceiling Basic model (Galvanized Steel) Floor Cabinet Model (Galvanized Steel) Floor Cabinet Model (Deluxe)
Designed for concealed ceiling installation Is designed for floor mounted exposed Designed for floor mounted exposed
above false ceiling with ducted supply air applications. The unit has a decorative applications, the unit has a decorative
distribution and free return of air above painted galvanized steel cabinet that painted plastic and galvanized steel
false ceiling. Units of this type consist of a Encloses all the unit’s components. Units cabinet. Units of this type consist of a fan
coil and fan without a return plenum or of this type consist of a fan, coil and flat coil and flat filter, and are supplied
filter. filter, and are supplied with fixed (steel manually operated double deflection grills
panel) lancing grill for the supply air. for the supply air and fixed deflection
plastic grills for the return air.
CBP
Ceiling Basic with Plenum (Galvanized
Steel) GCC
Ceiling Cabinet Model (Galvanized Steel) PCC
is designed for concealed ceiling
installation above the false ceiling with These units have same specifications as Ceiling Cabinet Model (Deluxe)
ducted supply and return air distribution. the GFC model, but are used for ceiling These units have the same specifications
The plenum encloses the fan section of suspended exposed applications. as the PFC plastic cover model, but are
the basic unit. Units of this type consist of used for ceiling suspended exposed
a coil, fan and a flat filter. applications.

FB
Floor Basic Model (Galvanized Steel)
Units have the same specifications as the
GFC model but without a cabinet. Units
are provided with galvanized steel
plenum without paint, consist of a fan,
coil and filter and are used for concealed
floor applications.

1
RAC
OUTSTANDING FEATURES
— Low sound level units, NC as — Coil can be on the left or right without — Coil is supplied with 2-air vents piped to
low as NC 30. affecting coil performance. (Except PFC the drain pan.
— Low height and small footprint & PCC coil that can only be on the right) — Heavy gauge sheet metal casing with
G90 - galvanized steel.

QUALITY ASSURANCE
— Units are manufactured in an ISO — Units are manufactured in an ISO — Units are rated in accordance with the
9001-2000 certified facility. 14001-2004 certified facility. ARI 440 standard.

SPECIFICATIONS
Coils Motors Casing
All coils are constructed of 3/8 inch Motors are driven by permanent split All units are constructed of heavy gauge
diameter copper tubes mechanically capacitor electric motors and are of the galvanized steel without paint except for
expanded into aluminum fins. The coil fins three speed type (with internal thermal cabinet models which are coated with
are spaced at 12 fins per inch for 3 protection). weatherproof, polyester powder,
rows,10 fins per inch for 4 rows or 12 fins electrostatic paint, oven-baked to ensure
per inch for 1 row. All coils are leak tested maximum gloss and hardness.
at 450 Psig air pressure and are suitable Filters
for up to 350 Psig working pressure with a All models are provided with 1” thick
manual air vent, piped to the drain pan. (nominal) and 7/8” thick actual frame size Insulation
with 5/8” thick aluminum media flat filter for All units are internally lined with 0.5 inch
(CBP+GCC), 1/2’’ thick filter for (GFC+FB) fiber-glass insulation for the coil and fan
Fans and a washable filter for (PFC+PCC). section.
All units are provided with forward curved
centrifugal fans of the double inlet type
that are designed for maximum efficiency Drain Pan
and uniform air distribution. The fans are All units are provided with a drain pan
statically and dynamically balanced to connection from one side. The drain pan is
ensure quiet operation and optimal insulated on its underside to prevent
performance. All fans are of the direct condensation.
drive type.

OPTIONS
The following options can be
provided:
— Manual 3-speed switch - (Wall — 3-way valve - Loose or built in unit. — Double skin construction with 1.0” fiber
Mounted), can be built-in PFC & GFC — Built-in electric heaters with the glass isolation for CBP models only.
models following standard features: Inner skin can be either solid or
— Thermostat (including 3-speed switch) - 1. Finned tube electric heating elements. perforated.
(Wall Mounted), Can be built in PFC & 2. Automatic thermal safety cutout. — Stainless steel drain pan.
GFC models — Optional components for built-in electric
— Shut-off valve - Loose item OR built in heaters are available:
unit. 1. Manual thermal safety cutout. (Not
— Auxiliary drain pan under 3-way valves. applicable for GCC & GFC models)
— 4-Pipe system units - double coil 2. Contactor (one normally open
— Synthetic media filter. contactor).
— Unit’s casing for none decorative units — All heaters are single stage.
are coated with weatherproof, polyester — All heaters are available in either 220-
powder, electrostatic paint, oven-baked 240V 1-phase 50/60Hz power supply.
to ensure maximum gloss and — Electric heater capacities are provided
hardness. in this manual.

2
RAC
GENERAL DATA TABLES
CB+CBP
MODEL RAC 2 3 4 5 6 8 10 12
Power supply Volt/Phase/Hz 220-240 / 1/ 50 or 60Hz and 110 / 1/ 50 Hz
Control voltage Volt/Hz 220-240 / 50or 60Hz and 110/ 60 Hz
Unit Casing Heavy gauge, galvanized steel,

Insulation 0.5 thick fiber glass or equivalent


Coil Copper tubes, Aluminum fins
Fins per inch 10 or 12
No.of rows For cooling 3 or 4
For heating 1,3 or 4
2
Total face area Ft 1.39 1.39 1.39 1.94 1.94 2.26 3.43 3.43
Tube diameter Inch 3/8
Fan Forward curved DWDI centrifu
No. 1 1 2 2 2 2 4 4
Type of drive Direct driven
Total air flow (Nominal) CFM 200 300 400 500 600 800 1000 1200
Fan motor Split capacitor (Three speed)
No. 1 1 1 1 1 1 2 2
Nominal motor raying HP 1/20 1/20 1/15 1/15 1/15 1/15 1/15 1/15
Coil Connection Inch 3/4 Female
Drain connection size Copper 7/8 sweat
Air filter For CBP models only
Type Aluminum mesh flat filter
Nominal thickness Inch 1
Operating weight Lb
Ceiling Basic CB 50 50 55 65 65 65 110 110
Ceiling Basic with Plenum CBP 55 55 62 73 73 110 119 119

GCC + GFC
MODEL RAC 2 3 4 5 6 8 10 12
Power supply Volt/Phase/Hz 220-240 / 1/ 50 or 60Hz and 110 / 1/ 50 Hz
Control voltage Volt/Hz 220-240 / 50or 60Hz and 110/ 60 Hz
Unit Casing Heavy gauge, galvanized steel, with oven-baked weatherproof, powder electrostatic paint
Insulation 0.5 thick fiber glass or equivalent
Coil Copper tubes, Aluminum fins
Fins per inch 10 or 12
No. of rows For cooling 3 or 4
For heating 1,3 or 4
2
Total face area Ft 1.39 1.39 1.39 1.94 1.94 2.26 3.17 3.17
Tube diameter Inch 3/8
Fan Forward curved DWDI centrifugal
No. 1 1 2 2 2 2 4 4
Type of drive Direct driven
Total air flow (Nominal) CFM 200 300 400 500 600 800 1000 1200
Fan motor Split capacitor (Three speed)
No. 1 1 1 1 1 1 2 2
Nominal motor rating HP 1/20 1/20 1/15 1/15 1/15 1/15 1/15 1/15
Coil Connection Inch 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4
Drain connection size Inch Copper 7/8 sweat
Air filter For CBP models only
Type Aluminum mesh flat filter
Thickness Inch 1
Operating weight Lb
Ceiling cabinet with Plenum GCC 104 104 106 126 126 141 194 194
Floor cabinet with Plenum GFC 82 52 93 110 110 128 172 172
*12 Fins per inch for 1-row coils.
*12 Fins per inch for 3-row coils.
*10 Fins per inch for 4-row coils.

3
RAC
GENERAL DATA TABLES
PCC + PFC
MODEL RAC 2 3 4 5 6 8 10 12
Power supply Volt/Phase/Hz 220-240 / 1/ 50 or 60Hz and 110 / 1/ 50 Hz
Control voltage Volt/Hz 220-240 / 50or 60Hz and 110/ 60 Hz
Unit Casing Decorative painted plastic and galvanized steel cabinet
Insulation 3.2mm thick fiber glass or equivalent
Coil Copper tubes, Aluminum fins
Fins per inch 10 or 12
No. Of rows For cooling 3 or 4
For heating 1,3 or 4
2
Total face area Ft 1.11 1.11 1.33 1.33 1.89 2.11 2.89 2.89
Tube diameter Inch 3/8
Fan Forward curved DWDI centrifugal fans
No. 1 1 2 2 2 2 4 4
Type of drive Direct driven
Total air flow (Nominal) 200 300 400 500 600 800 1000 1200
Fan motor Split capacitor (Three speed)
No. 1 1 1 1 1 1 2 2
Nominal motor rating HP 1/20 1/15 1/15 1/15 1/15 1/15 1/15
Coil Connection Inch 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4
Drain connection size Inch Copper 5/8 sweat
Air filter
Type Washable
Operating weight Lb
Floor cabinet PFC 88 88 95 95 117 117 157 157
Ceiling cabinet PCC 88 88 95 95 117 117 157 157

FB
MODEL RAC 2 3 4 5 6 8 10 12
Power supply Volt/Phase/Hz 220-240 / 1/ 50 or 60Hz and 110 / 1/ 50 Hz
Control voltage Volt/Hz 220-240 / 50or 60Hz and 110/ 60 Hz
Unit Casing Heavy gauge, galvanized steel, with oven-baked weatherproof, powder electrostatic paint
Insulation 0.5 thick fiber glass or equivalent
Coil Copper tubes, Aluminum fins
Fins per inch 10 or 12
No. of rows For cooling 3 or 4
For heating 1,3 or 4
2
Total face area Ft 1.39 1.39 1.39 1.85 1.85 2.26 3.17 3.17
Tube diameter Inch 3/8
Fan Forward curved DWDI centrifugal fans
No. 1 1 2 2 2 2 4 4
Type of drive Direct driven
Total air flow (Nominal) CFM 200 300 400 500 600 800 1000 1200
Fan motor Split capacitor (Three speed)
No. 1 1 1 1 1 1 2 2
Nominal motor rating HP 1/20 1/20 1/15 1/15 1/15 1/15 1/15 1/15
Coil Connection Inch 1/2 1/2 1/2 1/2 3/4 3/4 3/4
Drain connection size Inch Copper 5/8 sweat
Air filter
Type Aluminum mesh flat filter
Thickness Inch 1/2
Operating weight Lb
Floor Basic FB 63.9 63.9 75.0 75.0 88.2 108.0 156.5 183.0
*12 Fins per inch for 1-row coils.
*12 Fins per inch for 3-row coils.
*10 Fins per inch for 4-row coils.

4
RAC
PERFORMANCE DATA TABLES
CB/CBP (3-Rows cooling)
Entering Wet Bulb Temperature
Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 8789 6779 1.76 1.78 10365 6719 2.07 2.42 12086 6690 2.42 3.23
78 8840 7337 1.77 1.80 10420 7282 2.08 2.45 12207 7283 2.44 3.29
H 283
80 9021 7953 1.80 1.87 10578 7885 2.12 2.52 12296 7858 2.46 3.33
85 9346 9346 1.87 2.00 10814 9337 2.16 2.62 12447 9266 2.49 3.41
76 7328 5578 1.47 1.27 8651 5554 1.73 1.73 9966 5503 1.99 2.25
78 7381 6037 1.48 1.29 8665 6000 1.73 1.73 9928 5923 1.99 2.23
CB\CBP 2 M 221
80 7428 6491 1.49 1.30 8684 6440 1.74 1.74 10086 6425 2.02 2.30
85 7688 7687 1.54 1.39 8854 7602 1.77 1.80 10334 7619 2.07 2.41
76 5588 4203 1.12 0.77 6633 4220 1.33 1.05 7630 4192 1.53 1.37
78 5782 4608 1.16 0.82 6679 4561 1.34 1.07 7716 4551 1.54 1.40
L 158
80 5799 4942 1.16 0.82 6680 4882 1.34 1.07 7690 4865 1.54 1.39
85 5905 5793 1.18 0.85 6910 5791 1.38 1.14 7867 5746 1.57 1.45
76 10055 7806 2.01 2.29 11876 7732 2.38 3.12 13872 7685 2.77 4.18
78 10196 8491 2.04 2.35 12064 8436 2.41 3.22 14018 8376 2.80 4.26
H 340
80 10238 9134 2.05 2.37 12160 9104 2.43 3.27 14102 9038 2.82 4.31
85 10685 10685 2.14 2.56 12420 10772 2.48 3.40 14445 10744 2.89 4.51
76 8789 6779 1.76 1.78 10365 6719 2.07 2.42 12086 6690 2.42 3.23
78 8840 7337 1.77 1.80 10420 7282 2.08 2.45 12207 7283 2.44 3.29
CB\CBP 3 M 283
80 9021 7953 1.80 1.87 10578 7885 2.12 2.52 12296 7858 2.46 3.33
85 9346 9346 1.87 2.00 10814 9337 2.16 2.62 12447 9266 2.49 3.41
76 7328 5578 1.47 1.27 8651 5554 1.73 1.73 9966 5503 1.99 2.25
78 7381 6037 1.48 1.29 8665 6000 1.73 1.73 9928 5923 1.99 2.23
L 221
80 7428 6491 1.49 1.30 8684 6440 1.74 1.74 10086 6425 2.02 2.30
85 7688 7687 1.54 1.39 8854 7602 1.77 1.80 10334 7619 2.07 2.41
76 11852 9206 2.37 3.11 14026 9125 2.81 4.27 16361 9046 3.27 5.70
78 11971 10006 2.39 3.17 14187 9930 2.84 4.36 16543 9867 3.31 5.82
H 422
80 12140 10815 2.43 3.26 14373 10746 2.88 4.47 16725 10682 3.35 5.94
85 12764 12764 2.55 3.58 14769 12764 2.95 4.70 17045 12674 3.41 6.16
76 10454 8124 2.09 2.46 12353 8039 2.47 3.36 14435 7999 2.89 4.50
78 10546 8810 2.11 2.50 12490 8751 2.50 3.43 14589 8711 2.92 4.59
CB\CBP 4 M 358
80 10717 9536 2.14 2.58 12587 9448 2.52 3.48 14747 9432 2.95 4.69
85 11206 11206 2.24 2.80 12961 11229 2.59 3.68 14993 11163 3.00 4.84
76 8631 6658 1.73 1.72 10145 6586 2.03 2.33 11830 6556 2.37 3.10
L 277 78 8770 7240 1.75 1.77 10287 7177 2.06 2.39 11954 7138 2.39 3.16
80 8856 7810 1.77 1.80 10336 7728 2.07 2.41 12072 7714 2.41 3.22
85 9172 9172 1.83 1.93 10614 9167 2.12 2.53 12217 9101 2.44 3.29
76 16712 12500 3.34 6.82 19577 12393 3.92 9.16 22700 12347 4.54 12.07
78 16807 13492 3.36 6.89 19727 13420 3.95 9.29 22877 13387 4.58 12.25
H 533
80 17052 14562 3.41 7.08 19949 14474 3.99 9.48 23018 14406 4.60 12.39
85 17389 17096 3.48 7.34 20327 17044 4.07 9.82 23446 16988 4.69 12.82
76 14307 10725 2.86 5.11 16902 10715 3.38 6.96 19518 10650 3.90 9.11
78 14481 11626 2.90 5.22 17001 11580 3.40 7.04 19699 11550 3.94 9.26
CB\CBP 5 M 441
80 14628 12516 2.93 5.32 17086 12442 3.42 7.10 19887 12452 3.98 9.43
85 14914 14706 2.98 5.52 17420 14645 3.48 7.37 20067 14600 4.01 9.59
76 12744 9506 2.55 4.12 14923 9451 2.99 5.52 17222 9402 3.44 7.21
L 377 78 12848 10271 2.57 4.18 15100 10250 3.02 5.64 17367 10188 3.47 7.32
80 12904 11019 2.58 4.21 15146 10998 3.03 5.68 17494 10968 3.50 7.42
85 13140 12935 2.63 4.36 15406 12922 3.08 5.86 17700 12872 3.54 7.59

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• 0.1 inch of water external static pressure DBT : Entering Dry Bulb Temperature (OF)
• (For lower water pressure drop, special coil T.cap. : Total Cooling Capacity in (Btu/hr)
circuiting please consult PETRA factory). S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

5
RAC
PERFORMANCE DATA TABLES
CB/CBP (3-Rows cooling)
Entering Wet Bulb Temperature
Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 18180 13645 3.64 7.98 21502 13597 4.30 10.91 24879 13508 4.98 14.33
78 18485 14826 3.70 8.23 21763 14772 4.35 11.16 25136 14673 5.03 14.61
H 601
80 18618 15940 3.72 8.34 21890 15876 4.38 11.28 25408 15845 5.08 14.90
85 19168 18812 3.83 8.80 22371 18724 4.47 11.75 25818 18659 5.16 15.36
76 16712 12500 3.34 6.82 19577 12393 3.92 9.16 22700 12347 4.54 12.07
78 16807 13492 3.36 6.89 19727 13420 3.95 9.29 22877 13387 4.58 12.25
CB\CBP 6 M 533
80 17052 14562 3.41 7.08 19949 14474 3.99 9.48 23018 14406 4.60 12.39
85 17389 17096 3.48 7.34 20327 17044 4.07 9.82 23446 16988 4.69 12.82
76 14307 10725 2.86 5.11 16902 10715 3.38 6.96 19518 10650 3.90 9.11
78 14481 11626 2.90 5.22 17001 11580 3.40 7.04 19699 11550 3.94 9.26
L 441
80 14628 12516 2.93 5.32 17086 12442 3.42 7.10 19887 12452 3.98 9.43
85 14914 14706 2.98 5.52 17420 14645 3.48 7.37 20067 14600 4.01 9.59
76 21698 16046 4.34 11.88 25447 15956 5.09 15.98 29514 15922 5.90 21.07
78 21923 17369 4.39 12.11 25722 17302 5.14 16.31 29796 17260 5.96 21.45
H 693
80 22168 18677 4.43 12.36 25984 18630 5.20 16.62 29940 18550 5.99 21.65
85 22695 21958 4.54 12.92 26503 21901 5.30 17.24 30519 21844 6.10 22.43
76 19372 14346 3.87 9.62 22711 14279 4.54 12.93 26269 14220 5.25 16.96
78 19647 15560 3.93 9.88 22904 15452 4.58 13.14 26441 15388 5.29 17.17
CB\CBP 8 M 600
80 19737 16685 3.95 9.96 23130 16637 4.63 13.38 26630 16557 5.33 17.40
85 20162 19581 4.03 10.36 23515 19528 4.70 13.80 27155 19507 5.43 18.04
76 16918 12510 3.38 7.48 19738 12431 3.95 9.96 22890 12422 4.58 13.12
78 17091 13529 3.42 7.63 20017 13496 4.00 10.23 22992 13407 4.60 13.23
L 503
80 17239 14539 3.45 7.75 20094 14473 4.02 10.30 23146 14423 4.63 13.40
85 17430 16980 3.49 7.91 20430 16986 4.09 10.62 23493 16930 4.70 13.77
76 32691 23933 6.54 15.43 38259 23834 7.65 20.67 44236 23766 8.85 27.10
78 33040 25875 6.61 15.74 38617 25771 7.72 21.04 44541 25709 8.91 27.45
H 1009
80 33380 27814 6.68 16.04 38963 27734 7.79 21.39 44828 27618 8.97 27.78
85 34132 32620 6.83 16.72 39720 32538 7.94 22.17 45591 32440 9.12 28.66
76 29012 21287 5.80 12.36 33881 21185 6.78 16.49 39220 21157 7.84 21.65
78 29247 22992 5.85 12.55 34268 22945 6.85 16.84 39522 22880 7.90 21.96
CB\CBP 10 M 869
80 29575 24736 5.92 12.81 34478 24634 6.90 17.03 39737 24580 7.95 22.19
85 30060 28919 6.01 13.20 35063 28882 7.01 17.58 40315 28821 8.06 22.79
76 25382 18607 5.08 9.65 29634 18540 5.93 12.86 34228 18498 6.85 16.81
78 25597 20092 5.12 9.80 29863 20024 5.97 13.04 34348 19953 6.87 16.92
L 733
80 25720 21534 5.14 9.89 30084 21505 6.02 13.22 34607 21452 6.92 17.15
85 26194 25222 5.24 10.23 30557 25188 6.11 13.61 35094 25136 7.02 17.61
76 36370 26709 7.27 18.81 42726 26634 8.55 25.40 49477 26551 9.90 33.39
78 36858 28939 7.37 19.29 43120 28811 8.62 25.84 49824 28722 9.97 33.83
H 1165
80 37145 31078 7.43 19.57 43532 31016 8.71 26.30 50160 30903 10.03 34.26
85 38012 36483 7.60 20.43 44372 36405 8.87 27.25 51078 36327 10.22 35.44
76 32691 23933 6.54 15.43 38259 23834 7.65 20.67 44236 23766 8.85 27.10
78 33040 25875 6.61 15.74 38617 25771 7.72 21.04 44541 25709 8.91 27.45
CB\CBP 12 M 1009
80 33380 27814 6.68 16.04 38963 27734 7.79 21.39 44828 27618 8.97 27.78
85 34132 32620 6.83 16.72 39720 32538 7.94 22.17 45591 32440 9.12 28.66
76 29012 21287 5.80 12.36 33881 21185 6.78 16.49 39220 21157 7.84 21.65
78 29247 22992 5.85 12.55 34268 22945 6.85 16.84 39522 22880 7.90 21.96
L 869
80 29575 24736 5.92 12.81 34478 24634 6.90 17.03 39737 24580 7.95 22.19
85 30060 28919 6.01 13.20 35063 28882 7.01 17.58 40315 28821 8.06 22.79

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• 0.1 inch of water external static pressure DBT : Entering Dry Bulb Temperature (OF)
• (For lower water pressure drop, special coil T.cap. : Total Cooling Capacity in (Btu/hr)
circuiting please consult PETRA factory). S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

6
RAC
PERFORMANCE DATA TABLES
CB/CBP (4-Rows cooling)
Entering Wet Bulb Temperature
Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 9493 7177 1.90 2.51 11245 7179 2.25 3.43 12930 7113 2.59 4.45
78 9537 7751 1.91 2.53 11186 7708 2.24 3.40 13105 7743 2.62 4.56
H 280
80 9718 8384 1.94 2.62 11357 8337 2.27 3.50 13141 8313 2.63 4.58
85 9781 9781 1.96 2.65 11483 9776 2.30 3.57 13232 9743 2.65 4.64
76 7811 5844 1.56 1.75 9197 5839 1.84 2.37 10580 5805 2.12 3.07
78 7938 6343 1.59 1.81 9308 6331 1.86 2.42 10679 6293 2.14 3.12
CB\CBP 2 M 218
80 7948 6792 1.59 1.81 9284 6769 1.86 2.41 10767 6779 2.15 3.17
85 8098 7968 1.62 1.87 9494 7974 1.90 2.51 10878 7937 2.18 3.23
76 5998 4412 1.20 1.08 6950 4385 1.39 1.41 8033 4390 1.61 1.85
78 6138 4804 1.23 1.12 7094 4775 1.42 1.47 8129 4762 1.63 1.89
L 156
80 6131 5126 1.23 1.12 7073 5094 1.42 1.46 8085 5069 1.62 1.87
85 6326 6033 1.27 1.19 7218 5975 1.44 1.52 8223 5950 1.65 1.93
76 10937 8314 2.19 3.26 12886 8269 2.58 4.42 14991 8248 3.00 5.85
78 11007 8992 2.20 3.30 13025 8977 2.61 4.51 15049 8918 3.01 5.89
H 336
80 11030 9655 2.21 3.31 13038 9634 2.61 4.52 15141 9611 3.03 5.96
85 11330 11330 2.27 3.48 13301 11364 2.66 4.69 15373 11334 3.08 6.13
76 9493 7177 1.90 2.51 11245 7179 2.25 3.43 12930 7113 2.59 4.45
78 9537 7751 1.91 2.53 11186 7708 2.24 3.40 13105 7743 2.62 4.56
CB\CBP 3 M 280
80 9718 8384 1.94 2.62 11357 8337 2.27 3.50 13141 8313 2.63 4.58
85 9781 9781 1.96 2.65 11483 9776 2.30 3.57 13232 9743 2.65 4.64
76 7811 5844 1.56 1.75 9197 5839 1.84 2.37 10580 5805 2.12 3.07
78 7938 6343 1.59 1.81 9308 6331 1.86 2.42 10679 6293 2.14 3.12
L 218
80 7948 6792 1.59 1.81 9284 6769 1.86 2.41 10767 6779 2.15 3.17
85 8098 7968 1.62 1.87 9494 7974 1.90 2.51 10878 7937 2.18 3.23
76 12871 9836 2.57 4.41 15235 9791 3.05 6.03 17766 9758 3.55 8.02
78 13017 10669 2.60 4.50 15376 10624 3.08 6.13 17944 10612 3.59 8.17
H 416
80 13138 11495 2.63 4.58 15432 11424 3.09 6.17 17890 11362 3.58 8.12
85 13353 13353 2.67 4.72 15699 13464 3.14 6.37 18176 13419 3.64 8.37
76 11440 8687 2.29 3.55 13475 8640 2.70 4.80 15625 8599 3.13 6.32
78 11518 9404 2.30 3.59 13561 9351 2.71 4.86 15741 9323 3.15 6.40
CB\CBP 4 M 354
80 11544 10089 2.31 3.61 13645 10073 2.73 4.91 15844 10050 3.17 6.48
85 11875 11875 2.38 3.80 13744 11807 2.75 4.98 15983 11800 3.20 6.59
76 9320 7044 1.86 2.43 11039 7044 2.21 3.32 12693 6983 2.54 4.30
78 9518 7675 1.90 2.52 11169 7649 2.23 3.39 12862 7601 2.57 4.40
L 274
80 9538 8228 1.91 2.53 11147 8186 2.23 3.38 12896 8160 2.58 4.43
85 9599 9599 1.92 2.56 11268 9598 2.25 3.45 12984 9558 2.60 4.48
76 17784 13200 3.56 9.35 20862 13151 4.17 12.55 24062 13087 4.81 16.34
78 17898 14249 3.58 9.46 21029 14221 4.21 12.74 24231 14166 4.85 16.55
H 527
80 18009 15296 3.60 9.57 21062 15243 4.21 12.78 24327 15203 4.87 16.67
85 18191 17878 3.64 9.75 21282 17839 4.26 13.02 24548 17802 4.91 16.95
76 15334 11339 3.07 7.12 17971 11314 3.59 9.53 20581 11218 4.12 12.24
78 15396 12222 3.08 7.17 17964 12160 3.59 9.53 20844 12180 4.17 12.53
CB\CBP 5 M 436
80 15454 13095 3.09 7.22 18092 13073 3.62 9.65 20905 13066 4.18 12.60
85 15702 15343 3.14 7.43 18288 15288 3.66 9.85 20991 15236 4.20 12.70
76 13506 9965 2.70 5.64 15828 9952 3.17 7.54 18290 9951 3.66 9.85
78 13590 10741 2.72 5.70 15917 10736 3.18 7.62 18329 10710 3.67 9.89
L 373
80 13700 11557 2.74 5.78 15988 11508 3.20 7.69 18359 11468 3.67 9.92
85 13832 13456 2.77 5.89 16150 13442 3.23 7.83 18542 13417 3.71 10.10

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• 0.1 inch of water external static pressure DBT : Entering Dry Bulb Temperature (OF)
• (For lower water pressure drop, special coil T.cap. : Total Cooling Capacity in (Btu/hr)
circuiting please consult PETRA factory). S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

7
RAC
PERFORMANCE DATA TABLES
CB/CBP (4-Rows cooling)
Entering Wet Bulb Temperature
Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 19552 14517 3.91 11.14 22907 14444 4.58 14.92 26502 14388 5.30 19.54
78 19555 15621 3.91 11.14 22997 15587 4.60 15.03 26634 15555 5.33 19.71
H 594
80 19716 16797 3.94 11.31 23214 16784 4.64 15.29 26730 16697 5.35 19.85
85 20006 19676 4.00 11.62 23380 19616 4.68 15.49 26940 19552 5.39 20.14
76 17784 13200 3.56 9.35 20862 13151 4.17 12.55 24062 13087 4.81 16.34
78 17898 14249 3.58 9.46 21029 14221 4.21 12.74 24231 14166 4.85 16.55
CB\CBP 6 M 527
80 18009 15296 3.60 9.57 21062 15243 4.21 12.78 24327 15203 4.87 16.67
85 18191 17878 3.64 9.75 21282 17839 4.26 13.02 24548 17802 4.91 16.95
76 15334 11339 3.07 7.12 17971 11314 3.59 9.53 20581 11218 4.12 12.24
78 15396 12222 3.08 7.17 17964 12160 3.59 9.53 20844 12180 4.17 12.53
L 436
80 15454 13095 3.09 7.22 18092 13073 3.62 9.65 20905 13066 4.18 12.60
85 15702 15343 3.14 7.43 18288 15288 3.66 9.85 20991 15236 4.20 12.70
76 22916 16903 4.58 16.08 26850 16831 5.37 21.53 31050 16797 6.21 28.15
78 23164 18279 4.63 16.40 27069 18207 5.41 21.85 31295 18182 6.26 28.56
H 684
80 23239 19588 4.65 16.50 27193 19535 5.44 22.04 31389 19496 6.28 28.72
85 23548 22892 4.71 16.90 27550 22875 5.51 22.57 31650 22791 6.33 29.16
76 20449 15074 4.09 13.04 24047 15071 4.81 17.57 27701 15018 5.54 22.80
78 20648 16322 4.13 13.27 24116 16233 4.82 17.66 27806 16194 5.56 22.96
CB\CBP 8 M 593
80 20688 17444 4.14 13.32 24324 17460 4.87 17.94 28006 17409 5.60 23.27
85 20996 20408 4.20 13.69 24523 20384 4.91 18.22 28249 20349 5.65 23.64
76 17810 13085 3.56 10.12 20830 13052 4.17 13.49 23878 12970 4.78 17.34
78 17941 14121 3.59 10.25 20974 14096 4.20 13.66 24113 14050 4.82 17.66
L 497
80 18055 15148 3.61 10.37 21098 15120 4.22 13.81 24178 15062 4.84 17.75
85 18213 17653 3.64 10.54 21285 17647 4.26 14.04 24404 17593 4.88 18.05
76 34405 25163 6.88 20.67 40177 25062 8.04 27.51 46361 25009 9.27 35.82
78 34519 27085 6.90 20.80 40365 27024 8.07 27.75 46611 27004 9.32 36.18
H 997
80 34733 29042 6.95 21.04 40590 29004 8.12 28.03 46717 28927 9.34 36.33
85 35077 33506 7.02 21.42 40977 33850 8.20 28.53 47173 33806 9.44 36.99
76 30513 22312 6.10 16.58 35610 22230 7.12 22.03 40985 22172 8.20 28.54
78 30644 24023 6.13 16.71 35750 23946 7.15 22.19 41181 23905 8.24 28.79
CB\CBP 10 M 858
80 30730 25701 6.15 16.80 35951 25700 7.19 22.42 41352 25648 8.27 29.01
85 31175 30036 6.24 17.25 36289 29968 7.26 22.81 41688 29928 8.34 29.44
76 26638 19421 5.33 12.92 31054 19381 6.21 17.12 35781 19357 7.16 22.22
78 26714 20889 5.34 12.99 31232 20889 6.25 17.30 35872 20836 7.17 22.33
L 724
80 26928 22411 5.39 13.18 31249 22322 6.25 17.32 35942 22300 7.19 22.41
85 27194 26105 5.44 13.42 31508 26011 6.30 17.59 36261 26018 7.25 22.77
76 38367 28131 7.67 25.27 44917 28047 8.98 33.79 51988 28020 10.40 44.26
78 38573 30344 7.72 25.52 45268 30303 9.05 34.28 52215 30226 10.44 44.61
H 1151
80 38837 32574 7.77 25.84 45442 32482 9.09 34.52 52396 32431 10.48 44.90
85 39365 38053 7.87 26.49 45970 37989 9.19 35.26 52876 37907 10.58 45.66
76 34405 25163 6.88 20.67 40177 25062 8.04 27.51 46361 25009 9.27 35.82
78 34519 27085 6.90 20.80 40365 27024 8.07 27.75 46611 27004 9.32 36.18
CB\CBP 12 M 997
80 34733 29042 6.95 21.04 40590 29004 8.12 28.03 46717 28927 9.34 36.33
85 35077 33506 7.02 21.42 40977 33850 8.20 28.53 47173 33806 9.44 36.99
76 30513 22312 6.10 16.58 35610 22230 7.12 22.03 40985 22172 8.20 28.54
78 30644 24023 6.13 16.71 35750 23946 7.15 22.19 41181 23905 8.24 28.79
L 858
80 30730 25701 6.15 16.80 35951 25700 7.19 22.42 41352 25648 8.27 29.01
85 31175 30036 6.24 17.25 36289 29968 7.26 22.81 41688 29928 8.34 29.44

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• 0.1 inch of water external static pressure DBT : Entering Dry Bulb Temperature (OF)
• (For lower water pressure drop, special coil T.cap. : Total Cooling Capacity in (Btu/hr)
circuiting please consult PETRA factory). S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

8
RAC
PERFORMANCE DATA TABLES (CB/CBP)
(3-Rows heating)
Temperature Drop (F)
Model Fan Speed AFR 10 20 30 40
T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD
H 283 16512 3.30 4.87 14812 1.48 1.09 13012 0.87 0.40 11048 0.55 0.18
CB\CBP 2 M 221 12965 2.59 3.09 12014 1.20 0.74 10672 0.71 0.28 9139 0.46 0.12
L 158 9698 1.94 1.80 9198 0.92 0.45 8133 0.54 0.17 7036 0.35 0.08
H 340 18975 3.80 6.33 17206 1.72 1.44 15043 1.00 0.53 12504 0.63 0.22
CB\CBP 3 M 283 16512 3.30 4.87 14812 1.48 1.09 13012 0.87 0.40 11048 0.55 0.18
L 221 12965 2.59 3.09 12014 1.20 0.74 10672 0.71 0.28 9139 0.46 0.12
H 422 22759 4.55 8.92 20440 2.04 1.98 17755 1.18 0.72 14733 0.74 0.30
CB\CBP 4 M 358 19928 3.99 6.94 17858 1.79 1.54 15684 1.05 0.57 13037 0.65 0.24
L 277 16242 3.25 4.72 14498 1.45 1.04 12736 0.85 0.39 10814 0.54 0.17
H 554 30839 6.17 18.01 28275 2.83 4.20 25071 1.67 1.58 21547 1.08 0.70
CB\CBP 5 M 470 26820 5.36 13.86 24532 2.45 3.22 22085 1.47 1.25 19095 0.96 0.56
L 377 22064 4.41 9.62 20441 2.04 2.30 18478 1.23 0.90 16080 0.80 0.41
H 601 33455 6.69 20.98 29979 3.00 4.68 26851 1.79 1.80 22854 1.14 0.79
CB\CBP 6 M 533 29670 5.93 16.75 27204 2.72 3.91 24429 1.63 1.51 20884 1.04 0.67
L 441 25617 5.12 12.72 23273 2.33 2.92 20978 1.40 1.14 18172 0.91 0.52
H 693 38526 7.71 29.15 35119 3.51 6.74 31612 2.11 2.62 27404 1.37 1.18
CB\CBP 8 M 600 33831 6.77 22.86 31144 3.11 5.39 28194 1.88 2.12 24551 1.23 0.97
L 503 29557 5.91 17.76 26981 2.70 4.13 24509 1.63 1.64 21454 1.07 0.76
H 1036 57594 11.52 37.28 53250 5.33 8.86 47858 3.19 3.43 42166 2.11 1.60
CB\CBP 10 M 907 51297 10.26 30.02 47734 4.77 7.23 43341 2.89 2.86 38161 1.91 1.33
L 733 42764 8.55 21.38 39902 3.99 5.19 36510 2.43 2.09 32377 1.62 0.99
H 1165 63418 12.68 44.64 58533 5.85 10.56 52806 3.52 4.12 46069 2.30 1.88
CB\CBP 12 M 1009 56239 11.25 35.66 52081 5.21 8.50 47194 3.15 3.35 41359 2.07 1.55
L 869 49703 9.94 28.31 46049 4.61 6.77 41902 2.79 2.69 36939 1.85 1.26

(4-Rows heating)
Temperature Drop (F)
Model Fan Speed AFR 10 20 30 40
T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD
H 280 16604 3.32 5.94 15627 1.56 1.47 14007 0.93 0.57 12226 0.61 0.26
CB\CBP 2 M 218 13220 2.64 3.89 12602 1.26 0.99 11410 0.76 0.39 10023 0.50 0.18
L 156 9784 1.96 2.23 9235 0.92 0.56 8751 0.58 0.24 7669 0.38 0.11
H 336 19892 3.98 8.32 17975 1.80 1.91 16226 1.08 0.75 14088 0.70 0.34
CB\CBP 3 M 280 16604 3.32 5.94 15627 1.56 1.47 14007 0.93 0.57 12226 0.61 0.26
L 218 13220 2.64 3.89 12602 1.26 0.99 11410 0.76 0.39 10023 0.50 0.18
H 416 23378 4.68 11.23 21473 2.15 2.65 19187 1.28 1.02 16541 0.83 0.46
CB\CBP 4 M 354 20707 4.14 8.96 18887 1.89 2.09 16942 1.13 0.81 14690 0.73 0.37
L 274 16232 3.25 5.70 15292 1.53 1.42 13707 0.91 0.55 12123 0.61 0.26
H 548 31749 6.35 22.94 29237 2.92 5.48 26701 1.78 2.20 23691 1.19 1.05
CB\CBP 5 M 464 27168 5.43 17.19 25829 2.58 4.36 23414 1.56 1.73 20730 1.04 0.82
L 373 22541 4.51 12.17 21183 2.12 3.03 19469 1.30 1.24 17419 0.87 0.60
H 594 33714 6.74 25.65 31347 3.14 6.23 28599 1.91 2.50 25164 1.26 1.17
CB\CBP 6 M 527 30826 6.17 21.72 28345 2.84 5.17 25983 1.73 2.10 22935 1.15 0.99
L 436 25803 5.16 15.63 24270 2.43 3.89 22253 1.48 1.58 19731 0.99 0.75
H 684 39141 7.83 36.30 36493 3.65 8.89 33328 2.22 3.58 29768 1.49 1.72
CB\CBP 8 M 593 35146 7.03 29.74 32324 3.23 7.11 29751 1.98 2.91 26579 1.33 1.40
L 497 29544 5.91 21.58 27809 2.78 5.40 25797 1.72 2.24 22923 1.15 1.07
H 1023 59081 11.82 47.12 55097 5.51 11.55 50807 3.39 4.74 45482 2.27 2.29
CB\CBP 10 M 896 52249 10.45 37.54 49811 4.98 9.60 45666 3.04 3.90 41002 2.05 1.90
L 724 43325 8.67 26.57 41102 4.11 6.75 38156 2.54 2.81 34492 1.73 1.39
H 1151 64911 12.98 56.08 60742 6.07 13.82 55833 3.72 5.63 49759 2.49 2.70
CB\CBP 12 M 997 57955 11.59 45.47 53913 5.39 11.10 49660 3.31 4.54 44471 2.22 2.20
L 858 50272 10.05 34.96 47699 4.77 8.87 43977 2.93 3.64 39511 1.98 1.77

(1-Row heating)
Temperature Drop (F)
Model Fan Speed AFR 10 20 30 40
T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD
H 295 8479 1.696 0.773 6375 0.637 0.114 4360 0.291 0.025 2587 0.129 0.005
CB\CBP 2 M 230 7200 1.440 0.561 5349 0.535 0.081 3806 0.254 0.019 2346 0.117 0.004
L 165 5688 1.138 0.353 4433 0.443 0.056 3154 0.210 0.013 2024 0.101 0.003
H 354 9606 1.921 0.987 7191 0.719 0.144 4814 0.321 0.030 2763 0.138 0.006
CB\CBP 3 M 295 8479 1.696 0.773 6375 0.637 0.114 4360 0.291 0.025 2587 0.129 0.005
L 230 7200 1.440 0.561 5349 0.535 0.081 3806 0.254 0.019 2346 0.117 0.004
H 439 10992 2.198 1.286 8063 0.806 0.181 5396 0.360 0.038 3003 0.150 0.007
CB\CBP 4 M 373 9947 1.989 1.057 7278 0.728 0.148 4978 0.332 0.032 2893 0.145 0.007
L 289 8374 1.675 0.754 6253 0.625 0.110 4310 0.287 0.024 2582 0.129 0.005
H 577 15812 3.162 2.856 12323 1.232 0.457 9147 0.610 0.117 6167 0.308 0.032
CB\CBP 5 M 488 14064 2.813 2.272 11108 1.111 0.373 8299 0.553 0.097 5613 0.281 0.027
L 392 12142 2.428 1.706 9701 0.970 0.287 7238 0.483 0.075 5037 0.252 0.022
H 625 16537 3.307 3.118 12953 1.295 0.503 9571 0.638 0.128 6376 0.319 0.034
CB\CBP 6 M 555 15306 3.061 2.680 11991 1.199 0.433 8945 0.596 0.113 5956 0.298 0.030
L 459 13595 2.719 2.127 10651 1.065 0.344 8003 0.534 0.091 5432 0.272 0.025
H 721 19601 3.920 4.531 15642 1.564 0.762 11929 0.795 0.207 8379 0.419 0.061
CB\CBP 8 M 624 17802 3.560 3.756 14374 1.437 0.647 10955 0.730 0.176 7679 0.384 0.052
L 524 15913 3.183 3.019 12817 1.282 0.519 9925 0.662 0.146 7035 0.352 0.044
H 1079 30088 6.018 6.188 24451 2.445 1.083 19074 1.272 0.308 13822 0.691 0.096
CB\CBP 10 M 945 27547 5.509 5.213 22651 2.265 0.934 17626 1.175 0.265 12819 0.641 0.084
L 763 23846 4.769 3.940 19615 1.961 0.708 15497 1.033 0.207 11410 0.571 0.067
H 1212 32410 6.482 7.151 26276 2.628 1.244 20444 1.363 0.352 14755 0.738 0.109
CB\CBP 12 M 1050 29470 5.894 5.943 24032 2.403 1.047 18834 1.256 0.301 13667 0.683 0.094
L 904 26751 5.350 4.924 21884 2.188 0.874 17188 1.146 0.253 12534 0.627 0.080

AFR: Air Flow Rate (CFM) All capacities are based on


Fan Speed: (L: Low, M: Medium, H: High) • Air temperature 70 °F DB and 60 °F WB
DBT: Entering Dry Bulb Temperature (°F) • 0.1 inch of water external static pressure
T.CAP: Total Cooling Capacity in (Btu/hr) • 180 °F entering water temperature
GPM: Water Flow Rate in Gallon per Minute
WPD: Water Pressure Drop in (ft of water)

9
RAC
PERFORMANCE DATA TABLES
FB (3-Rows cooling)
Entering Wet Bulb Temperature
Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 8816 6795 1.76 1.80 10365 6723 2.07 2.43 12086 6693 2.42 3.24
78 8959 7391 1.79 1.85 10450 7302 2.09 2.47 12207 7286 2.44 3.30
H 283
80 9047 7970 1.81 1.88 10607 7907 2.12 2.54 12327 7873 2.47 3.36
85 9371 9371 1.87 2.01 10842 9355 2.17 2.64 12477 9282 2.50 3.44
76 7349 5589 1.47 1.28 8674 5569 1.74 1.74 9966 5505 1.99 2.26
78 7403 6048 1.48 1.30 8688 6012 1.74 1.75 10145 6019 2.03 2.33
FB 2 M 221
80 7449 6503 1.49 1.31 8707 6453 1.74 1.75 10111 6441 2.02 2.32
85 7709 7701 1.54 1.40 8877 7616 1.78 1.82 10358 7635 2.07 2.43
76 5604 4210 1.12 0.77 6649 4227 1.33 1.06 7647 4202 1.53 1.38
78 5797 4616 1.16 0.82 6695 4572 1.34 1.08 7733 4559 1.55 1.41
L 158
80 5814 4950 1.16 0.83 6697 4893 1.34 1.08 7811 4918 1.56 1.43
85 5919 5802 1.18 0.86 6925 5800 1.39 1.15 7884 5755 1.58 1.46
76 10055 7812 2.01 2.30 11948 7765 2.39 3.17 13872 7691 2.77 4.19
78 10227 8509 2.05 2.37 12099 8455 2.42 3.24 14018 8381 2.80 4.28
H 340
80 10269 9156 2.05 2.39 12194 9122 2.44 3.29 14139 9057 2.83 4.35
85 10713 10713 2.14 2.58 12502 10821 2.50 3.45 14479 10764 2.90 4.54
76 8816 6795 1.76 1.80 10365 6723 2.07 2.43 12086 6693 2.42 3.24
78 8959 7391 1.79 1.85 10450 7302 2.09 2.47 12207 7286 2.44 3.30
FB 3 M 283
80 9047 7970 1.81 1.88 10607 7907 2.12 2.54 12327 7873 2.47 3.36
85 9371 9371 1.87 2.01 10842 9355 2.17 2.64 12477 9282 2.50 3.44
76 7349 5589 1.47 1.28 8674 5569 1.74 1.74 9966 5505 1.99 2.26
78 7403 6048 1.48 1.30 8688 6012 1.74 1.75 10145 6019 2.03 2.33
L 221
80 7449 6503 1.49 1.31 8707 6453 1.74 1.75 10111 6441 2.02 2.32
85 7709 7701 1.54 1.40 8877 7616 1.78 1.82 10358 7635 2.07 2.43
76 11852 9212 2.37 3.12 14026 9131 2.81 4.28 16462 9096 3.29 5.78
78 12095 10059 2.42 3.24 14365 10013 2.87 4.48 16644 9913 3.33 5.90
H 422
80 12189 10841 2.44 3.29 14425 10779 2.89 4.51 16825 10729 3.37 6.02
85 12811 12811 2.56 3.61 14820 12800 2.96 4.75 17101 12700 3.42 6.21
76 10454 8130 2.09 2.47 12505 8110 2.50 3.45 14435 8003 2.89 4.52
78 10578 8831 2.12 2.52 12501 8765 2.50 3.45 14589 8717 2.92 4.61
FB 4 M 358
80 10749 9558 2.15 2.60 12758 9522 2.55 3.58 14786 9454 2.96 4.73
85 11234 11234 2.25 2.82 12993 11255 2.60 3.71 15029 11187 3.01 4.87
76 8708 6692 1.74 1.75 10262 6642 2.05 2.38 11896 6587 2.38 3.14
78 8796 7257 1.76 1.79 10370 7216 2.07 2.43 11986 7153 2.40 3.19
L 277
80 8882 7827 1.78 1.82 10365 7744 2.07 2.43 12102 7734 2.42 3.25
85 9196 9196 1.84 1.94 10641 9186 2.13 2.55 12241 9113 2.45 3.32
76 16882 12659 3.38 6.81 19879 12593 3.98 9.24 22999 12506 4.60 12.13
78 17017 13699 3.40 6.91 20050 13641 4.01 9.39 23170 13555 4.63 12.30
H 554
80 17140 14731 3.43 7.00 20215 14691 4.04 9.53 23422 14643 4.68 12.55
85 17649 17391 3.53 7.40 20611 17305 4.12 9.88 23846 17271 4.77 12.98
76 14750 11114 2.95 5.29 17425 11077 3.49 7.22 20241 11043 4.05 9.55
78 14968 12072 2.99 5.44 17567 11998 3.51 7.33 20414 11976 4.08 9.71
FB 5 M 470
80 15096 12994 3.02 5.53 17699 12918 3.54 7.43 20594 12916 4.12 9.87
85 15464 15295 3.09 5.78 18119 15253 3.62 7.77 20856 15179 4.17 10.10
76 12446 9346 2.49 3.86 14653 9315 2.93 5.23 17006 9291 3.40 6.90
78 12566 10113 2.51 3.93 14778 10085 2.96 5.31 17158 10076 3.43 7.02
L 377
80 12731 10908 2.55 4.02 14899 10858 2.98 5.39 17147 10789 3.43 7.01
85 12973 12803 2.60 4.17 15132 12753 3.03 5.55 17512 12743 3.50 7.29

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• 0.1 inch of water external static pressure DBT : Entering Dry Bulb Temperature (OF)
• (For lower water pressure drop, special coil T.cap. : Total Cooling Capacity in (Btu/hr)
circuiting please consult PETRA factory). S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

10
RAC
PERFORMANCE DATA TABLES
FB (3-Rows cooling)
Entering Wet Bulb Temperature
Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 17834 13439 3.57 7.54 21057 13374 4.21 10.29 24448 13303 4.89 13.60
78 18146 14622 3.63 7.79 21286 14517 4.26 10.50 24706 14454 4.94 13.87
H 601
80 18290 15727 3.66 7.91 21469 15646 4.29 10.66 24880 15583 4.98 14.06
85 18708 18523 3.74 8.25 21936 18461 4.39 11.10 25379 18401 5.08 14.59
76 16309 12267 3.26 6.38 19238 12208 3.85 8.69 22318 12147 4.46 11.47
78 16421 13265 3.28 6.46 19476 13262 3.90 8.89 22546 13193 4.51 11.69
FB 6 M 533
80 16693 14335 3.34 6.67 19616 14271 3.92 9.01 22632 14184 4.53 11.77
85 17137 16890 3.43 7.00 20034 16824 4.01 9.37 23021 16726 4.60 12.15
76 14104 10604 2.82 4.87 16495 10502 3.30 6.52 19202 10484 3.84 8.66
78 14152 11446 2.83 4.90 16782 11448 3.36 6.73 19458 11417 3.89 8.87
L 441
80 14318 12329 2.86 5.01 16872 12303 3.37 6.80 19477 12244 3.90 8.89
85 14732 14551 2.95 5.28 17162 14471 3.43 7.02 19846 14449 3.97 9.21
76 21769 16086 4.35 12.00 25524 16004 5.11 16.14 29514 15930 5.90 21.16
78 22045 17422 4.41 12.29 25798 17338 5.16 16.46 29877 17299 5.98 21.65
H 693
80 22238 18732 4.45 12.49 26059 18673 5.21 16.77 30022 18590 6.00 21.84
85 22764 22004 4.55 13.04 26488 21913 5.30 17.29 30598 21887 6.12 22.63
76 19418 14380 3.88 9.70 22823 14334 4.57 13.10 26412 14291 5.28 17.20
78 19691 15587 3.94 9.96 23008 15509 4.60 13.30 26629 15477 5.33 17.46
FB 8 M 600
80 19780 16713 3.96 10.04 23178 16675 4.64 13.49 26801 16645 5.36 17.68
85 20202 19627 4.04 10.44 23560 19560 4.71 13.90 27205 19549 5.44 18.18
76 16959 12538 3.39 7.55 19784 12457 3.96 10.05 22940 12448 4.59 13.23
78 17131 13560 3.43 7.69 20060 13515 4.01 10.31 23041 13436 4.61 13.34
L 503
80 17277 14572 3.46 7.81 20137 14505 4.03 10.38 23193 14452 4.64 13.50
85 17468 17018 3.49 7.97 20470 17009 4.09 10.70 23537 16962 4.71 13.88
76 31972 23648 6.39 14.09 37668 23580 7.53 19.13 43565 23475 8.71 25.11
78 32411 25623 6.48 14.45 37933 25504 7.59 19.39 43952 25438 8.79 25.53
H 1036
80 32666 27546 6.53 14.67 38330 27466 7.67 19.77 44304 27381 8.86 25.91
85 33498 32389 6.70 15.37 39101 32291 7.82 20.52 45068 32220 9.01 26.76
76 28985 21371 5.80 11.74 33969 21266 6.79 15.78 39331 21203 7.87 20.74
78 29301 23123 5.86 11.98 34311 23029 6.86 16.07 39636 22950 7.93 21.04
FB 10 M 907
80 29607 24864 5.92 12.21 34622 24772 6.92 16.35 39892 24691 7.98 21.30
85 30285 29178 6.06 12.74 35246 29086 7.05 16.90 40577 29015 8.12 21.99
76 24467 18074 4.89 8.56 28715 18019 5.74 11.54 33103 17943 6.62 15.04
78 24744 19563 4.95 8.75 28944 19486 5.79 11.71 33358 19420 6.67 15.25
L 733
80 24934 21004 4.99 8.87 29194 20963 5.84 11.90 33599 20886 6.72 15.46
85 25405 24614 5.08 9.19 29576 24534 5.92 12.19 34030 24490 6.81 15.83
76 34977 25889 7.00 16.66 41125 25767 8.23 22.55 47739 25697 9.55 29.80
78 35280 27986 7.06 16.93 41554 27931 8.31 22.99 48100 27814 9.62 30.22
H 1165
80 35780 30197 7.16 17.38 41911 30053 8.38 23.36 48469 29968 9.69 30.66
85 36582 35459 7.32 18.12 42774 35347 8.56 24.26 49318 35270 9.86 31.67
76 31478 23230 6.30 13.69 36950 23129 7.39 18.46 42671 22997 8.53 24.16
78 31732 25095 6.35 13.90 37323 25036 7.47 18.81 43020 24918 8.60 24.53
FB 12 M 1009
80 32047 26998 6.41 14.15 37517 26893 7.50 18.99 43358 26822 8.67 24.89
85 32787 31701 6.56 14.77 38264 31593 7.65 19.70 44096 31533 8.82 25.69
76 28021 20665 5.60 11.02 32890 20596 6.58 14.86 37994 20516 7.60 19.44
78 28313 22366 5.66 11.24 33183 22286 6.64 15.10 38267 22186 7.65 19.71
L 869
80 28583 24044 5.72 11.44 33452 23974 6.69 15.33 38573 23885 7.72 20.00
85 29097 28157 5.82 11.82 34047 28123 6.81 15.85 39159 28050 7.83 20.57

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• 0.1 inch of water external static pressure DBT : Entering Dry Bulb Temperature (OF)
• (For lower water pressure drop, special coil T.cap. : Total Cooling Capacity in (Btu/hr)
circuiting please consult PETRA factory). S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

11
RAC
PERFORMANCE DATA TABLES
FB (4-Rows cooling)
Entering Wet Bulb Temperature
Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 9517 7191 1.90 2.53 11271 7188 2.25 3.46 12958 7126 2.59 4.48
78 9640 7802 1.93 2.59 11405 7806 2.28 3.54 13131 7757 2.63 4.59
H 280
80 9740 8395 1.95 2.64 11382 8351 2.28 3.52 13167 8328 2.63 4.62
85 9803 9803 1.96 2.67 11507 9795 2.30 3.60 13258 9760 2.65 4.67
76 7830 5851 1.57 1.77 9217 5851 1.84 2.39 10602 5816 2.12 3.09
78 7956 6354 1.59 1.82 9327 6343 1.87 2.44 10699 6303 2.14 3.14
FB 2 M 218
80 7966 6801 1.59 1.82 9303 6776 1.86 2.43 10787 6790 2.16 3.19
85 8116 7981 1.62 1.89 9512 7981 1.90 2.53 10897 7950 2.18 3.25
76 6010 4420 1.20 1.09 6963 4389 1.39 1.42 8048 4397 1.61 1.86
78 6150 4809 1.23 1.13 7107 4780 1.42 1.48 8143 4769 1.63 1.90
L 156
80 6143 5134 1.23 1.13 7087 5102 1.42 1.47 8099 5077 1.62 1.88
85 6337 6042 1.27 1.20 7230 5983 1.45 1.53 8236 5955 1.65 1.94
76 10965 8333 2.19 3.29 12917 8288 2.58 4.45 14991 8251 3.00 5.87
78 11136 9054 2.23 3.38 13055 8997 2.61 4.54 15082 8937 3.02 5.94
H 336
80 11149 9709 2.23 3.39 13179 9700 2.64 4.62 15173 9631 3.04 6.00
85 11355 11355 2.27 3.51 13328 11384 2.67 4.72 15402 11354 3.08 6.17
76 9517 7191 1.90 2.53 11271 7188 2.25 3.46 12958 7126 2.59 4.48
78 9640 7802 1.93 2.59 11405 7806 2.28 3.54 13131 7757 2.63 4.59
FB 3 M 280
80 9740 8395 1.95 2.64 11382 8351 2.28 3.52 13167 8328 2.63 4.62
85 9803 9803 1.96 2.67 11507 9795 2.30 3.60 13258 9760 2.65 4.67
76 7830 5851 1.57 1.77 9217 5851 1.84 2.39 10602 5816 2.12 3.09
78 7956 6354 1.59 1.82 9327 6343 1.87 2.44 10699 6303 2.14 3.14
L 218
80 7966 6801 1.59 1.82 9303 6776 1.86 2.43 10787 6790 2.16 3.19
85 8116 7981 1.62 1.89 9512 7981 1.90 2.53 10897 7950 2.18 3.25
76 12908 9850 2.58 4.45 15235 9796 3.05 6.05 17766 9762 3.55 8.05
78 13054 10694 2.61 4.54 15416 10646 3.08 6.18 17950 10617 3.59 8.20
H 416
80 13174 11521 2.64 4.62 15472 11447 3.09 6.22 18112 11463 3.62 8.34
85 13388 13388 2.68 4.76 15737 13492 3.15 6.42 18218 13444 3.64 8.43
76 11469 8709 2.29 3.57 13507 8659 2.70 4.84 15625 8603 3.13 6.34
78 11546 9418 2.31 3.62 13658 9406 2.73 4.94 15775 9343 3.16 6.45
FB 4 M 354
80 11572 10110 2.31 3.63 13675 10087 2.74 4.95 15877 10069 3.18 6.53
85 11900 11900 2.38 3.83 13773 11829 2.76 5.02 16014 11823 3.20 6.63
76 9343 7058 1.87 2.45 11064 7059 2.21 3.34 12721 6997 2.54 4.33
78 9540 7685 1.91 2.54 11193 7659 2.24 3.42 12888 7615 2.58 4.44
L 274
80 9560 8244 1.91 2.55 11171 8200 2.23 3.40 12922 8175 2.58 4.46
85 9734 9677 1.95 2.64 11292 9610 2.26 3.47 13010 9575 2.60 4.51
76 18022 13429 3.60 9.37 21132 13356 4.23 12.58 24515 13333 4.90 16.55
78 18182 14512 3.64 9.53 21358 14470 4.27 12.83 24582 14383 4.92 16.64
H 548
80 18313 15595 3.66 9.66 21409 15518 4.28 12.88 24774 15496 4.96 16.88
85 18492 18230 3.70 9.83 21699 18208 4.34 13.21 25025 18164 5.01 17.20
76 15872 11788 3.17 7.42 18603 11740 3.72 9.94 21433 11680 4.29 12.91
78 15951 12712 3.19 7.48 18610 12645 3.72 9.95 21605 12642 4.32 13.10
FB 5 M 464
80 16031 13643 3.21 7.55 18774 13603 3.76 10.11 21709 13580 4.34 13.22
85 16243 15962 3.25 7.74 18925 15906 3.79 10.26 21842 15871 4.37 13.37
76 13352 9869 2.67 5.39 15533 9805 3.11 7.13 17957 9792 3.59 9.31
78 13439 10649 2.69 5.46 15639 10588 3.13 7.22 18015 10554 3.60 9.37
L 373
80 13466 11399 2.69 5.48 15724 11367 3.15 7.29 18185 11373 3.64 9.53
85 13687 13348 2.74 5.65 15911 13296 3.18 7.45 18375 13309 3.68 9.72

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• 0.1 inch of water external static pressure DBT : Entering Dry Bulb Temperature (OF)
• (For lower water pressure drop, special coil T.cap. : Total Cooling Capacity in (Btu/hr)
circuiting please consult PETRA factory). S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

12
RAC
PERFORMANCE DATA TABLES
FB (4-Rows cooling)
Entering Wet Bulb Temperature
Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 19087 14269 3.82 10.42 22488 14225 4.50 14.11 26148 14214 5.23 18.65
78 19289 15451 3.86 10.63 22650 15394 4.53 14.30 26195 15325 5.24 18.72
H 594
80 19465 16620 3.89 10.81 22744 16527 4.55 14.41 26297 16465 5.26 18.85
85 19687 19445 3.94 11.03 23101 19416 4.62 14.83 26636 19360 5.33 19.30
76 17413 12991 3.48 8.80 20529 12971 4.11 11.92 23701 12898 4.74 15.55
78 17561 14042 3.51 8.94 20635 14006 4.13 12.04 23870 13967 4.77 15.76
FB 6 M 527
80 17682 15091 3.54 9.05 20679 15021 4.14 12.08 23935 14989 4.79 15.84
85 17901 17429 3.58 9.26 20946 17611 4.19 12.37 24243 17633 4.85 16.22
76 15028 11172 3.01 6.71 17618 11135 3.52 8.99 20362 11097 4.07 11.74
78 15106 12058 3.02 6.77 17773 12043 3.56 9.14 20465 11994 4.09 11.85
L 436
80 15178 12934 3.04 6.83 17776 12894 3.56 9.14 20556 12885 4.11 11.95
85 15369 15131 3.07 6.99 18006 15113 3.60 9.36 20796 15106 4.16 12.21
76 22971 16929 4.59 16.22 27041 16927 5.41 21.91 31117 16832 6.22 28.38
78 23218 18320 4.64 16.54 27129 18248 5.43 22.04 31360 18219 6.27 28.79
H 684
80 23293 19634 4.66 16.64 27304 19590 5.46 22.30 31453 19535 6.29 28.95
85 23601 22936 4.72 17.05 27607 22908 5.52 22.76 31713 22836 6.34 29.39
76 20491 15108 4.10 13.15 24093 15105 4.82 17.71 27753 15039 5.55 22.98
78 20688 16357 4.14 13.38 24161 16269 4.83 17.80 27914 16249 5.58 23.23
FB 8 M 593
80 20728 17482 4.15 13.43 24367 17484 4.87 18.08 28054 17446 5.61 23.44
85 21033 20449 4.21 13.79 24564 20413 4.91 18.35 28294 20387 5.66 23.81
76 17846 13111 3.57 10.20 20870 13079 4.17 13.60 23873 12975 4.78 17.41
78 18037 14167 3.61 10.40 21012 14123 4.20 13.77 24155 14076 4.83 17.79
L 497
80 18089 15168 3.62 10.46 21136 15151 4.23 13.92 24220 15080 4.84 17.88
85 18247 17675 3.65 10.62 21321 17668 4.26 14.14 24443 17623 4.89 18.19
76 33847 24945 6.77 19.01 39827 24927 7.97 25.67 45976 24833 9.20 33.48
78 34173 26976 6.84 19.35 39990 26869 8.00 25.87 46175 26799 9.24 33.75
H 1023
80 34329 28924 6.87 19.52 40142 28817 8.03 26.05 46382 28785 9.28 34.03
85 34735 33788 6.95 19.94 40612 33726 8.12 26.62 46835 33685 9.37 34.65
76 30510 22448 6.10 15.70 35748 22401 7.15 21.03 41341 22361 8.27 27.51
78 30745 24233 6.15 15.93 35999 24192 7.20 21.30 41617 24157 8.32 27.85
FB 10 M 896
80 30938 26014 6.19 16.11 36202 25961 7.24 21.53 41709 25903 8.34 27.96
85 31334 30396 6.27 16.49 36603 30356 7.32 21.97 42120 30300 8.42 28.47
76 25829 18955 5.17 11.56 30190 18905 6.04 15.40 34661 18810 6.93 19.87
78 25983 20428 5.20 11.68 30302 20361 6.06 15.51 34947 20343 6.99 20.17
L 724
80 26079 21888 5.22 11.76 30454 21841 6.09 15.65 35069 21805 7.01 20.30
85 26413 25561 5.28 12.04 30774 25505 6.16 15.95 35262 25426 7.05 20.51
76 37045 27334 7.41 22.46 43594 27292 8.72 30.34 50461 27211 10.09 39.78
78 37288 29530 7.46 22.73 43849 29462 8.77 30.67 50722 29401 10.14 40.16
H 1151
80 37529 31689 7.51 23.01 44032 31626 8.81 30.91 50930 31565 10.19 40.46
85 38111 37096 7.62 23.67 44535 37005 8.91 31.56 51353 36921 10.27 41.09
76 33279 24483 6.66 18.43 38974 24394 7.80 24.67 44993 24317 9.00 32.17
78 33438 26391 6.69 18.59 39129 26299 7.83 24.85 45233 26259 9.05 32.49
FB 12 M 997
80 33588 28298 6.72 18.75 39429 28272 7.89 25.20 45377 28167 9.08 32.68
85 34062 33100 6.81 19.24 39831 33050 7.97 25.68 45809 32962 9.16 33.26
76 29558 21719 5.91 14.81 34577 21650 6.92 19.78 39985 21629 8.00 25.86
78 29682 23406 5.94 14.93 34772 23372 6.95 19.98 40063 23290 8.01 25.96
L 858
80 29865 25109 5.97 15.10 34960 25073 6.99 20.18 40294 25024 8.06 26.23
85 30291 29366 6.06 15.49 35300 29297 7.06 20.55 40634 29245 8.13 26.64

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• 0.1 inch of water external static pressure DBT : Entering Dry Bulb Temperature (OF)
• (For lower water pressure drop, special coil T.cap. : Total Cooling Capacity in (Btu/hr)
circuiting please consult PETRA factory). S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

13
RAC
PERFORMANCE DATA TABLES (FB)
(3-Rows heating)
Temperature Drop (F)
Model Fan Speed AFR 10 20 30 40
T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD
H 283 16552 3.31 4.91 14812 1.48 1.09 13012 0.87 0.40 11048 0.55 0.18
FB 2 M 221 13001 2.60 3.12 12078 1.21 0.75 10672 0.71 0.28 9139 0.46 0.12
L 158 9552 1.91 1.75 9222 0.92 0.45 8133 0.54 0.17 7036 0.35 0.08
H 340 19008 3.80 6.37 17206 1.72 1.44 15043 1.00 0.53 12522 0.63 0.22
FB 3 M 283 16552 3.31 4.91 14812 1.48 1.09 13012 0.87 0.40 11048 0.55 0.18
L 221 13001 2.60 3.12 12078 1.21 0.75 10672 0.71 0.28 9139 0.46 0.12
H 422 22820 4.56 8.99 20440 2.04 1.99 17877 1.19 0.73 14787 0.74 0.30
FB 4 M 358 19928 3.99 6.96 17961 1.80 1.56 15787 1.05 0.58 13189 0.66 0.24
L 277 16280 3.26 4.76 14498 1.45 1.05 12736 0.85 0.39 10814 0.54 0.17
H 554 30839 6.17 17.67 27795 2.78 3.98 24751 1.65 1.51 21066 1.05 0.66
FB 5 M 470 26436 5.29 13.23 24260 2.43 3.09 21678 1.45 1.18 18688 0.93 0.53
L 377 21918 4.38 9.32 20223 2.02 2.21 18260 1.22 0.86 15862 0.79 0.39
H 601 32586 6.52 19.60 29631 2.96 4.49 26329 1.76 1.70 22154 1.11 0.72
FB 6 M 533 29670 5.93 16.43 26895 2.69 3.75 23967 1.60 1.43 20576 1.03 0.63
L 441 25217 5.04 12.11 23018 2.30 2.80 20659 1.38 1.08 17790 0.89 0.48
H 693 38526 7.71 29.26 35320 3.53 6.84 31712 2.11 2.65 27504 1.38 1.20
FB 8 M 600 33755 6.75 22.85 31317 3.13 5.47 28281 1.89 2.14 24724 1.24 0.99
L 503 29628 5.93 17.91 26981 2.70 4.15 24509 1.63 1.65 21600 1.08 0.77
H 1036 56396 11.28 34.23 51902 5.19 8.03 46660 3.11 3.11 40518 2.03 1.41
FB 10 M 907 50423 10.09 27.75 46620 4.66 6.58 41899 2.79 2.55 36653 1.83 1.17
L 733 42560 8.51 20.20 39054 3.91 4.74 35504 2.37 1.88 31158 1.56 0.87
H 1165 62239 12.45 41.18 57017 5.70 9.57 51122 3.41 3.68 44132 2.21 1.65
FB 12 M 1009 56093 11.22 33.88 50841 5.08 7.73 45735 3.05 2.99 39608 1.98 1.35
L 869 48687 9.74 25.99 45044 4.50 6.17 40646 2.71 2.41 35495 1.78 1.10

(4-Rows heating)
Temperature Drop (F)
Model Fan Speed AFR 10 20 30 40
T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD
H 280 16537 3.31 5.92 15627 1.56 1.48 14007 0.93 0.57 12388 0.62 0.27
FB 2 M 218 13255 2.65 3.93 12684 1.27 1.01 11410 0.76 0.39 10023 0.50 0.18
L 156 9807 1.96 2.25 9261 0.93 0.57 8751 0.58 0.24 7669 0.38 0.11
H 336 19487 3.90 8.03 17975 1.80 1.91 16226 1.08 0.75 14088 0.70 0.34
FB 3 M 280 16537 3.31 5.92 15627 1.56 1.48 14007 0.93 0.57 12388 0.62 0.27
L 218 13255 2.65 3.93 12684 1.27 1.01 11410 0.76 0.39 10023 0.50 0.18
H 416 23381 4.68 11.27 21533 2.15 2.67 19187 1.28 1.02 16661 0.83 0.47
FB 4 M 354 20755 4.15 9.03 18887 1.89 2.10 16942 1.13 0.81 14690 0.73 0.37
L 274 16273 3.26 5.74 15292 1.53 1.42 13866 0.92 0.56 12123 0.61 0.26
H 548 31324 6.27 21.92 29078 2.91 5.30 26384 1.76 2.11 23215 1.16 0.99
FB 5 M 464 26997 5.40 16.63 25292 2.53 4.10 23145 1.54 1.66 20462 1.02 0.78
L 373 22229 4.45 11.61 20914 2.09 2.89 19253 1.28 1.18 17204 0.86 0.57
H 594 33405 6.68 24.70 31004 3.10 5.97 28084 1.87 2.36 24649 1.23 1.10
FB 6 M 527 30424 6.09 20.76 28116 2.81 4.98 25526 1.70 1.98 22478 1.12 0.93
L 436 25632 5.13 15.11 24270 2.43 3.80 22001 1.47 1.51 19479 0.97 0.72
H 684 39240 7.85 36.62 36493 3.65 8.93 33526 2.24 3.64 29768 1.49 1.73
FB 8 M 593 34564 6.91 28.96 33009 3.30 7.43 29923 2.00 2.96 26665 1.33 1.42
L 497 29525 5.91 21.65 27809 2.78 5.42 25797 1.72 2.25 23210 1.16 1.10
H 1023 57815 11.56 43.02 53913 5.39 10.51 49402 3.29 4.25 43855 2.19 2.02
FB 10 M 896 52085 10.42 35.45 48257 4.83 8.57 44370 2.96 3.49 39577 1.98 1.68
L 724 42770 8.55 24.62 40354 4.04 6.17 37214 2.48 2.53 33445 1.67 1.23
H 1151 63987 12.80 51.93 59411 5.94 12.56 54252 3.62 5.05 47845 2.39 2.37
FB 12 M 997 56454 11.29 41.16 52831 5.28 10.12 48363 3.22 4.09 43029 2.15 1.95
L 858 50407 10.08 33.36 46582 4.66 8.03 42861 2.86 3.28 38271 1.91 1.58

(1-Row heating)
Temperature Drop (F)
Model Fan Speed AFR 10 20 30 40
T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD
H 295 8519 1.704 0.781 6427 0.643 0.116 4401 0.293 0.025 2638 0.132 0.005
FB 2 M 230 7229 1.446 0.566 5391 0.539 0.083 3839 0.256 0.020 2381 0.119 0.005
L 165 5708 1.142 0.357 4461 0.446 0.057 3189 0.213 0.014 2049 0.102 0.003
H 354 9655 1.931 0.999 7161 0.716 0.144 4861 0.324 0.031 2825 0.141 0.006
FB 3 M 295 8519 1.704 0.781 6427 0.643 0.116 4401 0.293 0.025 2638 0.132 0.005
L 230 7229 1.446 0.566 5391 0.539 0.083 3839 0.256 0.020 2381 0.119 0.005
H 439 11054 2.211 1.303 8047 0.805 0.180 5455 0.364 0.039 3078 0.154 0.007
FB 4 M 373 9998 2.000 1.070 7345 0.735 0.151 5028 0.335 0.033 2956 0.148 0.007
L 289 8413 1.683 0.762 6240 0.624 0.110 4378 0.292 0.025 2632 0.132 0.005
H 577 15394 3.079 2.678 11942 1.194 0.423 8746 0.583 0.106 5675 0.284 0.027
FB 5 M 488 13835 2.767 2.173 10830 1.083 0.350 7951 0.530 0.088 5310 0.266 0.023
L 392 11941 2.388 1.630 9348 0.935 0.263 6986 0.466 0.069 4734 0.237 0.019
H 625 16230 3.246 2.969 12462 1.246 0.460 9141 0.609 0.115 5940 0.297 0.029
FB 6 M 555 15061 3.012 2.566 11618 1.162 0.401 8558 0.571 0.102 5629 0.281 0.026
L 459 13223 2.645 1.989 10380 1.038 0.323 7672 0.511 0.082 5103 0.255 0.022
H 721 19696 3.939 4.585 15761 1.576 0.775 12020 0.801 0.211 8485 0.424 0.063
FB 8 M 624 17883 3.577 3.799 14475 1.447 0.658 11042 0.736 0.179 7774 0.389 0.053
L 524 15978 3.196 3.051 12901 1.290 0.527 9925 0.662 0.146 7107 0.355 0.045
H 1079 28666 5.733 5.468 22964 2.296 0.926 17598 1.173 0.254 12360 0.618 0.075
FB 10 M 945 26306 5.261 4.625 21175 2.117 0.792 16283 1.086 0.219 11528 0.576 0.065
L 763 22789 4.558 3.498 18471 1.847 0.608 14341 0.956 0.172 10277 0.514 0.052
H 1212 30966 6.193 6.356 24730 2.473 1.069 18808 1.254 0.289 13098 0.655 0.083
FB 12 M 1050 28236 5.647 5.309 22644 2.264 0.901 17322 1.155 0.247 12187 0.609 0.073
L 904 25570 5.114 4.376 20603 2.060 0.751 15860 1.057 0.208 11246 0.562 0.062

AFR: Air Flow Rate (CFM) All capacities are based on


Fan Speed: (L: Low, M: Medium, H: High) • Air temperature 70 °F DB and 60 °F WB
DBT: Entering Dry Bulb Temperature (°F) • 0.1 inch of water external static pressure
T.CAP: Total Cooling Capacity in (Btu/hr) • 180 °F entering water temperature
GPM: Water Flow Rate in Gallon per Minute
WPD: Water Pressure Drop in (ft of water)
14
RAC
PERFORMANCE DATA TABLES
GCC (3-Rows cooling)

Entering Wet Bulb Temperature


Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 9284 7187 1.86 1.98 11041 7157 2.21 2.73 12735 7064 2.55 3.57
78 9411 7811 1.88 2.03 11146 7777 2.23 2.78 12865 7696 2.57 3.64
H 305
80 9473 8412 1.90 2.05 11204 8376 2.24 2.81 13013 8331 2.60 3.72
85 9723 9723 1.95 2.16 11401 9893 2.28 2.90 13267 9872 2.65 3.86
76 7633 5864 1.53 1.37 9006 5828 1.80 1.87 10574 5841 2.12 2.52
78 7781 6405 1.56 1.42 9219 6378 1.84 1.95 10611 6320 2.12 2.54
GCC2 M 237
80 7909 6906 1.58 1.47 9239 6852 1.85 1.96 10733 6835 2.15 2.59
85 8135 8135 1.63 1.55 9425 8089 1.89 2.03 10855 8046 2.17 2.65
76 5978 4486 1.20 0.87 6981 4453 1.40 1.16 7957 4390 1.59 1.48
78 5958 4822 1.19 0.87 7040 4823 1.41 1.18 8131 4806 1.63 1.54
L 169
80 6156 5250 1.23 0.92 7091 5188 1.42 1.20 8165 5164 1.63 1.56
85 6268 6156 1.25 0.95 7186 6087 1.44 1.23 8357 6106 1.67 1.63
76 10717 8312 2.14 2.59 12664 8229 2.53 3.53 14798 8188 2.96 4.73
78 10812 9016 2.16 2.63 12804 8957 2.56 3.61 14956 8918 2.99 4.83
H 367
80 10990 9755 2.20 2.71 12900 9667 2.58 3.66 15109 9649 3.02 4.92
85 11493 11493 2.30 2.95 13232 11471 2.65 3.84 15365 11424 3.07 5.08
76 9284 7187 1.86 1.98 11041 7157 2.21 2.73 12735 7064 2.55 3.57
78 9411 7811 1.88 2.03 11146 7777 2.23 2.78 12865 7696 2.57 3.64
GCC 3 M 305
80 9473 8412 1.90 2.05 11204 8376 2.24 2.81 13013 8331 2.60 3.72
85 9723 9723 1.95 2.16 11401 9893 2.28 2.90 13267 9872 2.65 3.86
76 7633 5864 1.53 1.37 9006 5828 1.80 1.87 10574 5841 2.12 2.52
78 7781 6405 1.56 1.42 9219 6378 1.84 1.95 10611 6320 2.12 2.54
L 237
80 7909 6906 1.58 1.47 9239 6852 1.85 1.96 10733 6835 2.15 2.59
85 8135 8135 1.63 1.55 9425 8089 1.89 2.03 10855 8046 2.17 2.65
76 12498 9749 2.50 3.45 14897 9688 2.98 4.79 17385 9606 3.48 6.41
78 12633 10596 2.53 3.52 15071 10551 3.01 4.90 17581 10484 3.52 6.54
H 454
80 12761 11441 2.55 3.59 15276 11425 3.06 5.02 17777 11349 3.56 6.68
85 13586 13586 2.72 4.03 15571 13514 3.11 5.21 18131 13468 3.63 6.93
76 11128 8633 2.23 2.77 13156 8550 2.63 3.80 15380 8503 3.08 5.09
78 11241 9371 2.25 2.83 13303 9310 2.66 3.88 15546 9267 3.11 5.19
GCC 4 M 386
80 11380 10123 2.28 2.89 13490 10082 2.70 3.98 15619 9990 3.12 5.24
85 12043 12043 2.41 3.22 13794 11936 2.76 4.15 15942 11861 3.19 5.44
76 9128 7069 1.83 1.92 10824 7026 2.17 2.63 12627 6993 2.53 3.52
78 9202 7661 1.84 1.95 10951 7642 2.19 2.69 12755 7610 2.55 3.58
L 299
80 9311 8274 1.86 1.99 11014 8238 2.20 2.72 12793 8190 2.56 3.60
85 9838 9838 1.97 2.20 11205 9722 2.24 2.81 13038 9707 2.61 3.73
76 18234 13642 3.65 8.04 21422 13549 4.28 10.86 24856 13490 4.97 14.34
78 18431 14767 3.69 8.20 21693 14710 4.34 11.12 25111 14645 5.02 14.62
H 597
80 18563 15876 3.71 8.31 21871 15834 4.37 11.29 25320 15790 5.06 14.84
85 19108 18734 3.82 8.77 22296 18644 4.46 11.70 25776 18613 5.16 15.35
76 16018 12001 3.20 6.32 18841 11940 3.77 8.55 21834 11892 4.37 11.25
78 16254 13028 3.25 6.49 19050 12955 3.81 8.72 21995 12879 4.40 11.41
GCC5 M 507
80 16326 13983 3.27 6.54 19194 13942 3.84 8.85 22205 13893 4.44 11.61
85 16685 16453 3.34 6.81 19517 16396 3.90 9.13 22598 16373 4.52 12.00
76 13478 10081 2.70 4.58 15929 10078 3.19 6.25 18377 10018 3.68 8.16
78 13608 10904 2.72 4.66 15986 10875 3.20 6.29 18542 10861 3.71 8.30
L 406
80 13734 11734 2.75 4.74 16053 11674 3.21 6.34 18533 11635 3.71 8.29
85 13964 13590 2.79 4.89 16368 13740 3.27 6.58 18926 13732 3.79 8.62

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• (For lower water pressure drop, special coil DBT : Entering Dry Bulb Temperature (OF)
circuiting please consult PETRA factory). T.cap. : Total Cooling Capacity in (Btu/hr)
S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

15
RAC
PERFORMANCE DATA TABLES
GCC (3-Rows cooling)

Entering Wet Bulb Temperature


Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 19310 14489 3.86 8.95 22805 14423 4.56 12.21 26474 14360 5.30 16.14
78 19541 15714 3.91 9.15 23020 15651 4.60 12.42 26597 15537 5.32 16.28
H 647
80 19800 16943 3.96 9.38 23275 16875 4.66 12.68 26882 16783 5.38 16.60
85 20249 19943 4.05 9.78 23719 19866 4.74 13.14 27363 19789 5.47 17.17
76 17726 13251 3.55 7.63 20876 13191 4.18 10.35 24145 13093 4.83 13.58
78 17851 14324 3.57 7.73 21024 14271 4.21 10.49 24419 14245 4.88 13.87
GCC6 M 575
80 18146 15472 3.63 7.97 21291 15407 4.26 10.74 24534 15310 4.91 13.99
85 18506 18171 3.70 8.27 21672 18128 4.33 11.10 24964 18047 4.99 14.46
76 15260 11413 3.05 5.77 17825 11315 3.57 7.71 20752 11305 4.15 10.24
78 15314 12315 3.06 5.81 18133 12320 3.63 7.96 20950 12261 4.19 10.42
L 474
80 15501 13269 3.10 5.94 18242 13245 3.65 8.05 21027 13178 4.21 10.49
85 15838 15600 3.17 6.18 18485 15542 3.70 8.25 21426 15540 4.29 10.86
76 22982 17003 4.60 13.27 27048 16954 5.41 17.97 31195 16833 6.24 23.45
78 23234 18414 4.65 13.54 27209 18327 5.44 18.17 31497 18262 6.30 23.88
H 745
80 23418 19801 4.68 13.74 27494 19743 5.50 18.53 31833 19702 6.37 24.35
85 23978 23258 4.80 14.36 28099 23231 5.62 19.29 32343 23160 6.47 25.09
76 20637 15275 4.13 10.86 24145 15150 4.83 14.54 27975 15109 5.60 19.14
78 20852 16492 4.17 11.07 24384 16410 4.88 14.81 28261 16386 5.65 19.50
GCC 8 M 646
80 20978 17708 4.20 11.20 24602 17659 4.92 15.06 28431 17615 5.69 19.72
85 21496 20816 4.30 11.72 25038 20745 5.01 15.56 28845 20686 5.77 20.26
76 17868 13234 3.57 8.31 20978 13194 4.20 11.20 24252 13144 4.85 14.67
78 18080 14326 3.62 8.49 21155 14278 4.23 11.37 24387 14214 4.88 14.82
L 540
80 18259 15410 3.65 8.65 21264 15326 4.25 11.48 24625 15318 4.93 15.09
85 18557 18044 3.71 8.92 21675 18006 4.34 11.90 24908 17946 4.98 15.41
76 34080 25175 6.82 16.01 39996 25032 8.00 21.59 46405 24981 9.28 28.50
78 34388 27202 6.88 16.28 40386 27123 8.08 21.98 46682 26984 9.34 28.82
H 1113
80 34836 29318 6.97 16.68 40704 29168 8.14 22.31 47121 29113 9.42 29.33
85 35616 34430 7.12 17.39 41562 34317 8.31 23.19 47892 34215 9.58 30.23
76 30906 22762 6.18 13.35 36256 22668 7.25 17.97 41943 22582 8.39 23.59
GCC 10 78 31293 24645 6.26 13.66 36590 24531 7.32 18.28 42290 24463 8.46 23.96
M 978
80 31500 26469 6.30 13.83 36957 26409 7.39 18.63 42550 26294 8.51 24.23
85 32303 31105 6.46 14.49 37623 30999 7.53 19.26 43360 30945 8.67 25.10
76 26071 19242 5.21 9.73 30492 19145 6.10 13.02 35391 19127 7.08 17.18
78 26338 20814 5.27 9.91 30843 20745 6.17 13.30 35616 20680 7.12 17.39
L 788
80 26532 22347 5.31 10.05 31031 22279 6.21 13.45 35807 22230 7.16 17.56
85 27081 26210 5.42 10.44 31593 26146 6.32 13.90 36327 26085 7.27 18.04
76 37226 27534 7.45 18.88 43837 27426 8.77 25.62 50828 27325 10.17 33.79
78 37682 29832 7.54 19.31 44299 29723 8.86 26.13 51218 29584 10.24 34.28
H 1255
80 38102 32116 7.62 19.72 44710 31996 8.94 26.58 51635 31878 10.33 34.81
85 39023 37731 7.81 20.62 45600 37637 9.12 27.58 52656 37555 10.53 36.11
76 33391 24661 6.68 15.42 39220 24556 7.84 20.81 45497 24496 9.10 27.47
GCC12 78 33771 26705 6.75 15.74 39664 26603 7.93 21.25 45825 26500 9.17 27.84
M 1085
80 34122 28722 6.82 16.05 40052 28647 8.01 21.64 46148 28524 9.23 28.20
85 34879 33732 6.98 16.72 40697 33610 8.14 22.30 46891 33517 9.38 29.06
76 29982 22043 6.00 12.61 35137 21957 7.03 16.95 40632 21874 8.13 22.23
78 30312 23864 6.06 12.87 35475 23772 7.10 17.26 40910 23673 8.18 22.52
L 937
80 30572 25623 6.11 13.08 35801 25569 7.16 17.55 41233 25470 8.25 22.85
85 31150 30028 6.23 13.54 36396 29990 7.28 18.10 41951 29938 8.39 23.60

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• (For lower water pressure drop, special coil DBT : Entering Dry Bulb Temperature (OF)
circuiting please consult PETRA factory). T.cap. : Total Cooling Capacity in (Btu/hr)
S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

16
RAC
PERFORMANCE DATA TABLES
GCC (4-Rows cooling)

Entering Wet Bulb Temperature


Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 10123 7648 2.03 2.84 11873 7597 2.38 3.81 13783 7577 2.76 5.02
78 10171 8265 2.03 2.86 11982 8237 2.40 3.88 13851 8202 2.77 5.07
H 301
80 10211 8871 2.04 2.88 12124 8894 2.43 3.96 13906 8817 2.78 5.11
85 10440 10440 2.09 3.00 12258 10430 2.45 4.04 14125 10388 2.83 5.26
76 8315 6221 1.66 1.97 9794 6219 1.96 2.67 11267 6180 2.25 3.46
78 8455 6758 1.69 2.04 9773 6684 1.96 2.66 11377 6705 2.28 3.52
GCC 2 M 234
80 8464 7239 1.69 2.04 9889 7209 1.98 2.72 11316 7150 2.26 3.49
85 8627 8497 1.73 2.11 10065 8474 2.01 2.81 11468 8405 2.29 3.57
76 6372 4694 1.27 1.21 7385 4661 1.48 1.59 8542 4669 1.71 2.07
78 6377 5043 1.28 1.21 7543 5079 1.51 1.65 8596 5042 1.72 2.10
L 167
80 6516 5454 1.30 1.26 7519 5419 1.50 1.64 8600 5393 1.72 2.10
85 6571 6350 1.31 1.28 7675 6360 1.54 1.70 8746 6332 1.75 2.17
76 11721 8896 2.34 3.72 13801 8843 2.76 5.04 16023 8807 3.21 6.64
78 11801 9622 2.36 3.77 13823 9545 2.77 5.05 16121 9543 3.22 6.72
H 363
80 11881 10354 2.38 3.82 13978 10308 2.80 5.16 16228 10284 3.25 6.80
85 12171 12171 2.43 3.99 14082 12088 2.82 5.23 16381 12083 3.28 6.92
76 10123 7648 2.03 2.84 11873 7597 2.38 3.81 13783 7577 2.76 5.02
78 10171 8265 2.03 2.86 11982 8237 2.40 3.88 13851 8202 2.77 5.07
GCC 3 M 301
80 10211 8871 2.04 2.88 12124 8894 2.43 3.96 13906 8817 2.78 5.11
85 10440 10440 2.09 3.00 12258 10430 2.45 4.04 14125 10388 2.83 5.26
76 8315 6221 1.66 1.97 9794 6219 1.96 2.67 11267 6180 2.25 3.46
78 8455 6758 1.69 2.04 9773 6684 1.96 2.66 11377 6705 2.28 3.52
L 234
80 8464 7239 1.69 2.04 9889 7209 1.98 2.72 11316 7150 2.26 3.49
85 8627 8497 1.73 2.11 10065 8474 2.01 2.81 11468 8405 2.29 3.57
76 13717 10474 2.74 4.98 16218 10414 3.24 6.79 18866 10361 3.77 9.00
78 13733 11303 2.75 4.99 16394 11315 3.28 6.93 18951 11226 3.79 9.07
H 448
80 13889 12192 2.78 5.09 16468 12175 3.29 6.99 19079 12108 3.82 9.19
85 14304 14304 2.86 5.38 16623 14299 3.33 7.11 19241 14233 3.85 9.33
76 12119 9234 2.42 3.96 14314 9184 2.86 5.39 16679 9165 3.34 7.15
78 12222 9997 2.44 4.02 14450 9966 2.89 5.48 16673 9885 3.34 7.15
GCC 4 M 382
80 12320 10760 2.46 4.08 14487 10706 2.90 5.51 16809 10666 3.36 7.26
85 12568 12568 2.51 4.23 14684 12602 2.94 5.65 17013 12565 3.40 7.42
76 9950 7517 1.99 2.75 11671 7472 2.33 3.69 13548 7449 2.71 4.87
78 9997 8123 2.00 2.77 11776 8095 2.36 3.75 13614 8060 2.72 4.91
L 295
80 10035 8719 2.01 2.79 11914 8741 2.38 3.84 13778 8713 2.76 5.02
85 10258 10258 2.05 2.91 12043 10250 2.41 3.91 13877 10206 2.78 5.09
76 19476 14457 3.90 11.09 22815 14383 4.56 14.85 26394 14337 5.28 19.44
78 19479 15556 3.90 11.09 22956 15548 4.59 15.02 26522 15486 5.30 19.62
H 590
80 19637 16727 3.93 11.26 23118 16711 4.62 15.22 26617 16635 5.32 19.75
85 19986 19620 4.00 11.63 23357 19576 4.67 15.51 27006 19541 5.40 20.28
76 17040 12659 3.41 8.67 20133 12673 4.03 11.79 23179 12606 4.64 15.29
78 17279 13727 3.46 8.89 20143 13646 4.03 11.80 23265 13602 4.65 15.40
GCC 5 M 501
80 17305 14688 3.46 8.92 20321 14677 4.06 11.99 23298 14582 4.66 15.44
85 17556 17208 3.51 9.16 20487 17155 4.10 12.17 23630 17133 4.73 15.84
76 14372 10616 2.87 6.34 16774 10562 3.36 8.42 19299 10498 3.86 10.90
78 14471 11455 2.89 6.42 16889 11414 3.38 8.53 19445 11378 3.89 11.05
L 402
80 14551 12282 2.91 6.48 16981 12250 3.40 8.61 19561 12224 3.91 11.18
85 14789 14378 2.96 6.68 17093 14288 3.42 8.72 19780 14313 3.96 11.41

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• (For lower water pressure drop, special coil DBT : Entering Dry Bulb Temperature (OF)
circuiting please consult PETRA factory). T.cap. : Total Cooling Capacity in (Btu/hr)
S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

17
RAC
PERFORMANCE DATA TABLES
GCC (4-Rows cooling)

Entering Wet Bulb Temperature


Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 20688 15398 4.14 12.39 24289 15327 4.86 16.67 28173 15295 5.64 21.93
78 20853 16639 4.17 12.58 24407 16555 4.88 16.82 28275 16511 5.66 22.08
H 640
80 20871 17833 4.17 12.60 24622 17819 4.92 17.09 28387 17735 5.68 22.24
85 21294 20940 4.26 13.07 24797 20839 4.96 17.32 28704 20813 5.74 22.71
76 18844 14008 3.77 10.43 22192 13979 4.44 14.11 25587 13905 5.12 18.35
78 19006 15134 3.80 10.60 22310 15098 4.46 14.25 25786 15050 5.16 18.62
GCC 6 M 568
80 19138 16260 3.83 10.74 22360 16190 4.47 14.31 25859 16148 5.17 18.72
85 19319 18999 3.86 10.92 22653 18973 4.53 14.65 26111 18926 5.22 19.06
76 16232 12027 3.25 7.93 19012 11991 3.80 10.61 21998 11963 4.40 13.88
78 16307 12975 3.26 7.99 19169 12965 3.83 10.77 22059 12904 4.41 13.95
L 469
80 16385 13916 3.28 8.06 19175 13876 3.84 10.77 22158 13860 4.43 14.07
85 16591 16272 3.32 8.25 19423 16256 3.89 11.03 22418 16241 4.48 14.38
76 24328 17955 4.87 18.02 28641 17937 5.73 24.34 32970 17837 6.59 31.56
78 24512 19400 4.90 18.27 28757 19357 5.75 24.52 33257 19318 6.65 32.07
H 737
80 24723 20837 4.95 18.56 28867 20762 5.77 24.70 33366 20721 6.67 32.27
85 24993 24350 5.00 18.94 29238 24302 5.85 25.29 33691 24254 6.74 32.85
76 21845 16065 4.37 14.78 25560 16009 5.11 19.73 29437 15941 5.89 25.60
78 21995 17340 4.40 14.97 25618 17243 5.12 19.82 29629 17227 5.93 25.91
GCC 8 M 638
80 22041 18560 4.41 15.02 25807 18530 5.16 20.09 29691 18462 5.94 26.01
85 22279 21669 4.46 15.32 26078 21655 5.22 20.48 30023 21616 6.01 26.55
76 18992 13943 3.80 11.43 22209 13907 4.44 15.24 25451 13809 5.09 19.58
78 19069 15006 3.81 11.51 22206 14947 4.44 15.23 25715 14969 5.14 19.96
L 534
80 19141 16081 3.83 11.59 22361 16049 4.47 15.43 25803 16046 5.16 20.08
85 19342 18769 3.87 11.82 22542 18719 4.51 15.66 25904 18688 5.18 20.23
76 35981 26521 7.20 21.49 42262 26459 8.45 28.92 48881 26399 9.78 37.85
78 36282 28666 7.26 21.82 42526 28572 8.51 29.26 49138 28513 9.83 38.22
H 1100
80 36549 30778 7.31 22.12 42718 30669 8.54 29.50 49392 30627 9.88 38.59
85 36969 35956 7.39 22.59 43276 35912 8.66 30.22 49892 35851 9.98 39.31
76 32595 23975 6.52 17.91 38344 23973 7.67 24.17 44157 23855 8.83 31.36
78 32877 25895 6.58 18.20 38468 25820 7.69 24.31 44445 25780 8.89 31.74
GCC10 M 967
80 33108 27802 6.62 18.43 38716 27735 7.74 24.60 44578 27637 8.92 31.92
85 33482 32456 6.70 18.82 39085 32392 7.82 25.03 44946 32316 8.99 32.41
76 27551 20201 5.51 13.14 32185 20144 6.44 17.50 37073 20087 7.41 22.71
78 27619 21747 5.52 13.20 32310 21706 6.46 17.62 37249 21674 7.45 22.91
L 779
80 27746 23303 5.55 13.31 32548 23326 6.51 17.86 37403 23248 7.48 23.08
85 28152 27246 5.63 13.67 32785 27184 6.56 18.10 37706 27143 7.54 23.43
76 39559 29144 7.91 25.60 46419 29046 9.28 34.40 53771 28959 10.75 45.16
78 39755 31442 7.95 25.83 46714 31381 9.34 34.81 54066 31298 10.81 45.62
H 1240
80 40045 33757 8.01 26.18 47000 33710 9.40 35.20 54268 33595 10.85 45.94
85 40665 39509 8.13 26.93 47564 39439 9.51 35.99 54863 39364 10.97 46.87
76 35405 26052 7.08 20.86 41493 25961 8.30 27.96 47937 25875 9.59 36.51
78 35600 28110 7.12 21.07 41733 28037 8.35 28.26 48172 27943 9.63 36.84
GCC12 M 1073
80 35782 30141 7.16 21.27 41991 30105 8.40 28.58 48459 30037 9.69 37.25
85 36295 35249 7.26 21.84 42357 35161 8.47 29.04 48832 35114 9.77 37.78
76 31536 23172 6.31 16.85 36938 23106 7.39 22.56 42652 23052 8.53 29.42
78 31783 25029 6.36 17.10 37201 24970 7.44 22.85 42808 24870 8.56 29.62
L 926
80 31929 26829 6.39 17.24 37414 26794 7.48 23.09 43010 26673 8.60 29.87
85 32219 31279 6.44 17.53 37725 31261 7.55 23.45 43526 31270 8.71 30.54

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• (For lower water pressure drop, special coil DBT : Entering Dry Bulb Temperature (OF)
circuiting please consult PETRA factory). T.cap. : Total Cooling Capacity in (Btu/hr)
S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

18
RAC
PERFORMANCE DATA TABLES (GCC)
(3-Rows heating)
Temperature Drop (F)
Model Fan Speed AFR 10 20 30 40
T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD
H 305 17526 3.51 5.47 15787 1.58 1.23 13847 0.92 0.45 11730 0.59 0.20
GCC 2 M 237 13882 2.78 3.53 12747 1.28 0.82 11308 0.75 0.31 9663 0.48 0.14
L 169 10254 2.05 2.00 9724 0.97 0.50 8699 0.58 0.19 7526 0.38 0.09
H 367 20429 4.09 7.30 18307 1.83 1.62 16078 1.07 0.60 13352 0.67 0.25
GCC 3 M 305 17526 3.51 5.47 15787 1.58 1.23 13847 0.92 0.45 11730 0.59 0.20
L 237 13882 2.78 3.53 12747 1.28 0.82 11308 0.75 0.31 9663 0.48 0.14
H 454 24222 4.84 10.06 21727 2.17 2.23 18839 1.26 0.80 15591 0.78 0.33
GCC 4 M 386 21487 4.30 8.02 19031 1.90 1.74 16687 1.11 0.64 13893 0.70 0.27
L 299 17263 3.45 5.31 15477 1.55 1.18 13747 0.92 0.45 11499 0.58 0.19
H 597 33232 6.65 20.77 29952 3.00 4.68 26672 1.78 1.78 22874 1.14 0.79
GCC 5 M 507 28558 5.71 15.63 26170 2.62 3.64 23384 1.56 1.40 20305 1.02 0.63
L 406 23537 4.71 10.88 21778 2.18 2.59 19665 1.31 1.01 17082 0.85 0.46
H 647 35080 7.02 22.99 31899 3.19 5.27 28532 1.90 2.02 23852 1.19 0.85
GCC 6 M 575 32008 6.40 19.36 29015 2.90 4.42 26022 1.74 1.70 22364 1.12 0.76
L 474 27038 5.41 14.11 24741 2.47 3.28 22273 1.49 1.28 19258 0.96 0.57
H 745 40663 8.13 32.35 37324 3.73 7.57 33500 2.23 2.93 29029 1.45 1.32
GCC 8 M 646 35960 7.19 25.71 33158 3.32 6.08 29795 1.99 2.36 26059 1.30 1.08
L 540 31203 6.24 19.72 28810 2.88 4.69 25999 1.73 1.83 22720 1.14 0.84
H 1113 60185 12.04 38.99 55277 5.53 9.11 49645 3.31 3.52 43047 2.15 1.59
GCC 10 M 978 54370 10.87 32.22 49845 4.98 7.52 44896 2.99 2.92 39098 1.96 1.33
L 788 45171 9.03 22.78 41643 4.16 5.38 37883 2.53 2.14 33211 1.66 0.99
H 1255 66503 13.30 47.02 60878 6.09 10.90 54527 3.64 4.19 46382 2.32 1.82
GCC 12 M 1085 58985 11.80 37.54 54200 5.42 8.78 48710 3.25 3.40 42199 2.11 1.53
L 937 52091 10.42 29.74 48026 4.80 7.02 43285 2.89 2.73 37866 1.89 1.26
(4-Rows heating)
Temperature Drop (F)
Model Fan Speed AFR 10 20 30 40
T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD
H 301 17688 3.54 6.71 16799 1.68 1.69 14884 0.99 0.64 12969 0.65 0.29
GCC 2 M 234 14106 2.82 4.41 13341 1.33 1.11 12112 0.81 0.44 10624 0.53 0.21
L 167 10406 2.08 2.51 9881 0.99 0.64 9272 0.62 0.27 8113 0.41 0.13
H 363 21158 4.23 9.36 19262 1.93 2.18 17267 1.15 0.84 15063 0.75 0.39
GCC 3 M 301 17688 3.54 6.71 16799 1.68 1.69 14884 0.99 0.64 12969 0.65 0.29
L 234 14106 2.82 4.41 13341 1.33 1.11 12112 0.81 0.44 10624 0.53 0.21
H 448 24938 4.99 12.71 22865 2.29 2.99 20469 1.37 1.15 17554 0.88 0.51
GCC 4 M 382 21993 4.40 10.06 20049 2.01 2.34 18061 1.20 0.92 15631 0.78 0.41
L 295 17425 3.49 6.52 16464 1.65 1.63 14587 0.97 0.62 12881 0.64 0.29
H 590 33604 6.72 25.56 31136 3.11 6.17 28407 1.89 2.48 25165 1.26 1.17
GCC 5 M 501 29750 5.95 20.39 27309 2.73 4.85 24991 1.67 1.96 22093 1.11 0.93
L 402 24018 4.80 13.72 22494 2.25 3.39 20808 1.39 1.40 18541 0.93 0.67
H 640 35848 7.17 28.82 33405 3.34 7.02 30259 2.02 2.78 26557 1.33 1.29
GCC 6 M 568 32668 6.53 24.25 30304 3.03 5.87 27512 1.83 2.34 24391 1.22 1.11
L 469 27433 5.49 17.55 26107 2.61 4.46 23666 1.58 1.77 20953 1.05 0.84
H 737 41596 8.32 40.77 38841 3.88 10.01 35537 2.37 4.04 31488 1.57 1.92
GCC 8 M 638 37232 7.45 33.21 34407 3.44 8.01 31640 2.11 3.27 28135 1.41 1.56
L 534 31496 6.30 24.38 29725 2.97 6.12 27409 1.83 2.52 24475 1.22 1.21
H 1100 61629 12.33 48.87 57494 5.75 11.94 52564 3.50 4.81 46679 2.33 2.29
GCC 10 M 967 55363 11.07 40.06 51661 5.17 9.81 47467 3.16 3.99 42294 2.12 1.91
L 779 45714 9.14 28.11 43307 4.33 7.09 39815 2.65 2.89 35648 1.78 1.40
H 1240 68935 13.79 60.17 63377 6.34 14.29 57820 3.86 5.73 51186 2.56 2.71
GCC 12 M 1073 60346 12.07 47.00 56393 5.64 11.53 51584 3.44 4.65 45844 2.29 2.21
L 926 53608 10.72 37.74 49805 4.98 9.17 45856 3.06 3.75 40902 2.05 1.80
(1-Row heating)
Temperature Drop (F)
Model Fan Speed AFR 10 20 30 40
T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD
H 317 8967 1.793 0.864 6619 0.662 0.123 4579 0.305 0.027 2703 0.135 0.006
GCC 2 M 246 7555 1.511 0.617 5750 0.575 0.094 3993 0.266 0.021 2442 0.122 0.005
L 176 6030 1.206 0.397 4630 0.463 0.062 3258 0.217 0.014 2115 0.106 0.004
H 381 10118 2.024 1.095 7398 0.740 0.153 5083 0.339 0.034 2955 0.148 0.007
GCC 3 M 317 8967 1.793 0.864 6619 0.662 0.123 4579 0.305 0.027 2703 0.135 0.006
L 246 7555 1.511 0.617 5750 0.575 0.094 3993 0.266 0.021 2442 0.122 0.005
H 471 11628 2.326 1.439 8427 0.843 0.197 5638 0.376 0.041 3237 0.162 0.008
GCC 4 M 400 10389 2.078 1.154 7626 0.763 0.162 5211 0.347 0.035 2945 0.147 0.007
L 310 8848 1.770 0.842 6561 0.656 0.121 4523 0.302 0.027 2649 0.132 0.006
H 619 16507 3.301 3.112 12894 1.289 0.499 9572 0.638 0.128 6340 0.317 0.034
GCC 5 M 525 14864 2.973 2.536 11768 1.177 0.418 8708 0.581 0.107 5918 0.296 0.029
L 421 12822 2.564 1.900 10101 1.010 0.311 7708 0.514 0.085 5257 0.263 0.024
H 671 17407 3.481 3.452 13647 1.365 0.557 10014 0.668 0.140 6691 0.335 0.037
GCC 6 M 596 16161 3.232 2.985 12627 1.263 0.480 9369 0.625 0.123 6282 0.314 0.033
L 492 14234 2.847 2.330 11205 1.120 0.381 8383 0.559 0.100 5681 0.284 0.027
H 774 20598 4.120 5.002 16450 1.645 0.842 12512 0.834 0.228 8668 0.433 0.065
GCC 8 M 670 18814 3.763 4.192 15087 1.509 0.712 11500 0.767 0.194 8100 0.405 0.057
L 561 16619 3.324 3.293 13442 1.344 0.570 10295 0.686 0.157 7349 0.367 0.048
H 1157 30470 6.094 6.191 24286 2.429 1.038 18606 1.240 0.285 13117 0.656 0.084
GCC 10 M 1015 27822 5.564 5.186 22410 2.241 0.889 17241 1.149 0.246 12238 0.612 0.074
L 818 24179 4.836 3.946 19534 1.953 0.682 15075 1.005 0.190 10874 0.544 0.059
H 1301 32718 6.544 7.113 26147 2.615 1.198 19874 1.325 0.323 13909 0.695 0.094
GCC 12 M 1126 29830 5.966 5.940 23876 2.388 1.005 18317 1.221 0.276 12932 0.647 0.082
L 973 27015 5.403 4.897 21826 2.183 0.845 16816 1.121 0.235 11945 0.597 0.070

AFR: Air Flow Rate (CFM) All capacities are based on


Fan Speed: (L: Low, M: Medium, H: High) • Air temperature 70 °F DB and 60 °F WB
DBT: Entering Dry Bulb Temperature (°F) • 180 °F entering water temperature
T.CAP: Total Cooling Capacity in (Btu/hr)
GPM: Water Flow Rate in Gallon per Minute
WPD: Water Pressure Drop in (ft of water)
19
RAC
PERFORMANCE DATA TABLES
GFC (3-Rows cooling)

Entering Wet Bulb Temperature


Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 9284 7187 1.86 1.98 11041 7157 2.21 2.73 12735 7064 2.55 3.57
78 9411 7811 1.88 2.03 11146 7777 2.23 2.78 12865 7696 2.57 3.64
H 305
80 9473 8412 1.90 2.05 11204 8376 2.24 2.81 13013 8331 2.60 3.72
85 9723 9723 1.95 2.16 11401 9893 2.28 2.90 13267 9872 2.65 3.86
76 7633 5864 1.53 1.37 9006 5828 1.80 1.87 10574 5841 2.12 2.52
78 7781 6405 1.56 1.42 9219 6378 1.84 1.95 10611 6320 2.12 2.54
GFC 2 M 237
80 7909 6906 1.58 1.47 9239 6852 1.85 1.96 10733 6835 2.15 2.59
85 8135 8135 1.63 1.55 9425 8089 1.89 2.03 10855 8046 2.17 2.65
76 5978 4486 1.20 0.87 6981 4453 1.40 1.16 7957 4390 1.59 1.48
78 5958 4822 1.19 0.87 7040 4823 1.41 1.18 8131 4806 1.63 1.54
L 169
80 6156 5250 1.23 0.92 7091 5188 1.42 1.20 8165 5164 1.63 1.56
85 6268 6156 1.25 0.95 7186 6087 1.44 1.23 8357 6106 1.67 1.63
76 10717 8312 2.14 2.59 12664 8229 2.53 3.53 14798 8188 2.96 4.73
78 10812 9016 2.16 2.63 12804 8957 2.56 3.61 14956 8918 2.99 4.83
H 367
80 10990 9755 2.20 2.71 12900 9667 2.58 3.66 15109 9649 3.02 4.92
85 11493 11493 2.30 2.95 13232 11471 2.65 3.84 15365 11424 3.07 5.08
76 9284 7187 1.86 1.98 11041 7157 2.21 2.73 12735 7064 2.55 3.57
78 9411 7811 1.88 2.03 11146 7777 2.23 2.78 12865 7696 2.57 3.64
GFC 3 M 305
80 9473 8412 1.90 2.05 11204 8376 2.24 2.81 13013 8331 2.60 3.72
85 9723 9723 1.95 2.16 11401 9893 2.28 2.90 13267 9872 2.65 3.86
76 7633 5864 1.53 1.37 9006 5828 1.80 1.87 10574 5841 2.12 2.52
78 7781 6405 1.56 1.42 9219 6378 1.84 1.95 10611 6320 2.12 2.54
L 237
80 7909 6906 1.58 1.47 9239 6852 1.85 1.96 10733 6835 2.15 2.59
85 8135 8135 1.63 1.55 9425 8089 1.89 2.03 10855 8046 2.17 2.65
76 12498 9749 2.50 3.45 14897 9688 2.98 4.79 17385 9606 3.48 6.41
78 12633 10596 2.53 3.52 15071 10551 3.01 4.90 17581 10484 3.52 6.54
H 454
80 12761 11441 2.55 3.59 15276 11425 3.06 5.02 17777 11349 3.56 6.68
85 13586 13586 2.72 4.03 15571 13514 3.11 5.21 18131 13468 3.63 6.93
76 11128 8633 2.23 2.77 13156 8550 2.63 3.80 15380 8503 3.08 5.09
GFC 4 78 11241 9371 2.25 2.83 13303 9310 2.66 3.88 15546 9267 3.11 5.19
M 386
80 11380 10123 2.28 2.89 13490 10082 2.70 3.98 15619 9990 3.12 5.24
85 12043 12043 2.41 3.22 13794 11936 2.76 4.15 15942 11861 3.19 5.44
76 9128 7069 1.83 1.92 10824 7026 2.17 2.63 12627 6993 2.53 3.52
78 9202 7661 1.84 1.95 10951 7642 2.19 2.69 12755 7610 2.55 3.58
L 299
80 9311 8274 1.86 1.99 11014 8238 2.20 2.72 12793 8190 2.56 3.60
85 9838 9838 1.97 2.20 11205 9722 2.24 2.81 13038 9707 2.61 3.73
76 17741 13371 3.55 7.47 20916 13292 4.18 10.16 24286 13220 4.86 13.43
78 18050 14548 3.61 7.71 21173 14440 4.24 10.39 24542 14364 4.91 13.70
H 597
80 18194 15646 3.64 7.83 21408 15585 4.28 10.61 24747 15500 4.95 13.91
85 18609 18423 3.72 8.16 21903 18388 4.38 11.07 25241 18302 5.05 14.44
76 15767 11837 3.15 5.99 18515 11756 3.70 8.09 21471 11696 4.29 10.67
GFC 5 78 15857 12790 3.17 6.06 18584 12704 3.72 8.14 21688 12705 4.34 10.87
M 507
80 15951 13740 3.19 6.12 18757 13688 3.75 8.29 21762 13652 4.35 10.94
85 16357 16197 3.27 6.42 19136 16137 3.83 8.60 22170 16117 4.43 11.33
76 13264 9950 2.65 4.34 15532 9876 3.11 5.83 17921 9804 3.58 7.61
78 13289 10721 2.66 4.36 15620 10675 3.12 5.89 18116 10650 3.62 7.76
L 406
80 13423 11545 2.69 4.44 15827 11528 3.17 6.04 18286 11486 3.66 7.90
85 13683 13566 2.74 4.60 16103 13559 3.22 6.23 18571 13522 3.71 8.13

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• (For lower water pressure drop, special coil DBT : Entering Dry Bulb Temperature (OF)
circuiting please consult PETRA factory). T.cap. : Total Cooling Capacity in (Btu/hr)
S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

20
RAC
PERFORMANCE DATA TABLES
GFC (3-Rows cooling)

Entering Wet Bulb Temperature


Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 18833 14220 3.77 8.35 22257 14155 4.45 11.41 25857 14063 5.17 15.11
78 19083 15449 3.82 8.56 22445 15342 4.49 11.59 26135 15288 5.23 15.41
H 647
80 19209 16613 3.84 8.66 22734 16570 4.55 11.87 26335 16501 5.27 15.64
85 19781 19621 3.96 9.15 23200 19550 4.64 12.33 26846 19482 5.37 16.21
76 17279 12994 3.46 7.11 20389 12935 4.08 9.68 23665 12869 4.73 12.80
78 17523 14116 3.51 7.30 20596 14035 4.12 9.87 23912 13982 4.78 13.05
GFC 6 M 575
80 17650 15181 3.53 7.40 20775 15118 4.16 10.03 24136 15091 4.83 13.28
85 18180 17923 3.64 7.82 21238 17843 4.25 10.45 24580 17802 4.92 13.74
76 14860 11191 2.97 5.37 17510 11139 3.50 7.29 20357 11101 4.07 9.66
78 15081 12155 3.02 5.52 17698 12080 3.54 7.43 20510 12033 4.10 9.79
L 474
80 15146 13050 3.03 5.56 17832 13008 3.57 7.54 20650 12962 4.13 9.92
85 15481 15354 3.10 5.79 18131 15298 3.63 7.78 21015 15285 4.20 10.25
76 22929 16993 4.59 13.22 27048 16955 5.41 17.98 31195 16834 6.24 23.46
78 23245 18429 4.65 13.56 27291 18354 5.46 18.28 31510 18265 6.30 23.91
H 745
80 23479 19816 4.70 13.81 27506 19745 5.50 18.55 31845 19705 6.37 24.38
85 23988 23278 4.80 14.38 28110 23247 5.62 19.32 32355 23163 6.47 25.12
76 20644 15276 4.13 10.87 24153 15163 4.83 14.56 27975 15110 5.60 19.15
78 20859 16494 4.17 11.08 24392 16411 4.88 14.83 28270 16399 5.65 19.52
GFC 8 M 646
80 20984 17709 4.20 11.21 24609 17661 4.92 15.08 28375 17597 5.68 19.66
85 21502 20818 4.30 11.73 25045 20747 5.01 15.58 28902 20716 5.78 20.35
76 17874 13235 3.58 8.32 20985 13195 4.20 11.21 24260 13154 4.85 14.68
78 18085 14330 3.62 8.50 21162 14279 4.23 11.39 24395 14215 4.88 14.83
L 540
80 18265 15411 3.65 8.66 21271 15327 4.25 11.50 24531 15274 4.91 14.99
85 18562 18046 3.71 8.93 21681 18008 4.34 11.91 24915 17956 4.98 15.43
76 33861 25021 6.77 15.68 39761 24908 7.95 21.17 46007 24778 9.20 27.81
78 34171 27065 6.83 15.95 40148 26971 8.03 21.55 46417 26858 9.28 28.27
H 1113
80 34468 29104 6.89 16.21 40469 29011 8.09 21.88 46746 28920 9.35 28.65
85 35346 34230 7.07 16.99 41334 34140 8.27 22.76 47665 34065 9.53 29.71
76 30705 22653 6.14 13.07 36037 22546 7.21 17.62 41710 22460 8.34 23.15
78 30950 24474 6.19 13.26 36375 24418 7.28 17.93 42057 24336 8.41 23.51
M 978
GFC 10 80 31302 26345 6.26 13.55 36744 26296 7.35 18.27 42319 26168 8.46 23.78
85 32073 30948 6.42 14.18 37412 30850 7.48 18.89 43056 30776 8.61 24.57
76 25947 19160 5.19 9.55 30351 19053 6.07 12.79 35064 18983 7.01 16.74
78 26163 20690 5.23 9.70 30640 20640 6.13 13.02 35382 20572 7.08 17.02
L 788
80 26416 22258 5.28 9.88 30901 22193 6.18 13.22 35662 22130 7.13 17.28
85 26908 26080 5.38 10.22 31389 26021 6.28 13.62 36133 25947 7.23 17.70
76 36964 27365 7.39 18.47 43505 27258 8.70 25.05 50529 27173 10.11 33.14
78 37322 29631 7.46 18.81 43953 29538 8.79 25.53 50919 29423 10.18 33.62
H 1255
80 37755 31930 7.55 19.22 44316 31806 8.86 25.93 51330 31711 10.27 34.14
85 38720 37555 7.74 20.14 45326 37446 9.07 27.04 52250 37321 10.45 35.29
76 33175 24533 6.64 15.10 38990 24417 7.80 20.41 45108 24299 9.02 26.80
78 33474 26518 6.70 15.35 39326 26440 7.87 20.74 45443 26318 9.09 27.17
M 1085
GFC 12 80 33911 28584 6.78 15.73 39636 28436 7.93 21.04 45897 28376 9.18 27.68
85 34672 33573 6.93 16.39 40472 33462 8.09 21.88 46647 33356 9.33 28.54
76 29757 21906 5.95 12.33 34872 21816 6.97 16.57 40352 21739 8.07 21.76
78 30051 23697 6.01 12.55 35143 23586 7.03 16.81 40622 23511 8.12 22.03
L 937
80 30372 25490 6.07 12.81 35492 25392 7.10 17.12 41056 25354 8.21 22.47
85 31020 29898 6.20 13.32 36251 29851 7.25 17.81 41642 29748 8.33 23.08

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• (For lower water pressure drop, special coil DBT : Entering Dry Bulb Temperature (OF)
circuiting please consult PETRA factory). T.cap. : Total Cooling Capacity in (Btu/hr)
S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

21
RAC
PERFORMANCE DATA TABLES
GFC (4-Rows cooling)

Entering Wet Bulb Temperature


Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 10123 7648 2.03 2.84 11873 7597 2.38 3.81 13783 7577 2.76 5.02
78 10171 8265 2.03 2.86 11982 8237 2.40 3.88 13851 8202 2.77 5.07
H 301
80 10211 8871 2.04 2.88 12124 8894 2.43 3.96 13906 8817 2.78 5.11
85 10440 10440 2.09 3.00 12258 10430 2.45 4.04 14125 10388 2.83 5.26
76 8315 6221 1.66 1.97 9794 6219 1.96 2.67 11267 6180 2.25 3.46
78 8455 6758 1.69 2.04 9773 6684 1.96 2.66 11377 6705 2.28 3.52
GFC 2 M 234
80 8464 7239 1.69 2.04 9889 7209 1.98 2.72 11316 7150 2.26 3.49
85 8627 8497 1.73 2.11 10065 8474 2.01 2.81 11468 8405 2.29 3.57
76 6372 4694 1.27 1.21 7385 4661 1.48 1.59 8542 4669 1.71 2.07
78 6377 5043 1.28 1.21 7543 5079 1.51 1.65 8596 5042 1.72 2.10
L 167
80 6516 5454 1.30 1.26 7519 5419 1.50 1.64 8600 5393 1.72 2.10
85 6571 6350 1.31 1.28 7675 6360 1.54 1.70 8746 6332 1.75 2.17
76 11721 8896 2.34 3.72 13801 8843 2.76 5.04 16023 8807 3.21 6.64
78 11801 9622 2.36 3.77 13823 9545 2.77 5.05 16121 9543 3.22 6.72
H 363
80 11881 10354 2.38 3.82 13978 10308 2.80 5.16 16228 10284 3.25 6.80
85 12171 12171 2.43 3.99 14082 12088 2.82 5.23 16381 12083 3.28 6.92
76 10123 7648 2.03 2.84 11873 7597 2.38 3.81 13783 7577 2.76 5.02
78 10171 8265 2.03 2.86 11982 8237 2.40 3.88 13851 8202 2.77 5.07
GFC 3 M 301
80 10211 8871 2.04 2.88 12124 8894 2.43 3.96 13906 8817 2.78 5.11
85 10440 10440 2.09 3.00 12258 10430 2.45 4.04 14125 10388 2.83 5.26
76 8315 6221 1.66 1.97 9794 6219 1.96 2.67 11267 6180 2.25 3.46
78 8455 6758 1.69 2.04 9773 6684 1.96 2.66 11377 6705 2.28 3.52
L 234
80 8464 7239 1.69 2.04 9889 7209 1.98 2.72 11316 7150 2.26 3.49
85 8627 8497 1.73 2.11 10065 8474 2.01 2.81 11468 8405 2.29 3.57
76 13717 10474 2.74 4.98 16218 10414 3.24 6.79 18866 10361 3.77 9.00
78 13733 11303 2.75 4.99 16394 11315 3.28 6.93 18951 11226 3.79 9.07
H 448
80 13889 12192 2.78 5.09 16468 12175 3.29 6.99 19079 12108 3.82 9.19
85 14304 14304 2.86 5.38 16623 14299 3.33 7.11 19241 14233 3.85 9.33
76 12119 9234 2.42 3.96 14314 9184 2.86 5.39 16679 9165 3.34 7.15
78 12222 9997 2.44 4.02 14450 9966 2.89 5.48 16673 9885 3.34 7.15
GFC 4 M 382
80 12320 10760 2.46 4.08 14487 10706 2.90 5.51 16809 10666 3.36 7.26
85 12568 12568 2.51 4.23 14684 12602 2.94 5.65 17013 12565 3.40 7.42
76 9950 7517 1.99 2.75 11671 7472 2.33 3.69 13548 7449 2.71 4.87
78 9997 8123 2.00 2.77 11776 8095 2.36 3.75 13614 8060 2.72 4.91
L 295
80 10035 8719 2.01 2.79 11914 8741 2.38 3.84 13778 8713 2.76 5.02
85 10258 10258 2.05 2.91 12043 10250 2.41 3.91 13877 10206 2.78 5.09
76 18980 14194 3.80 10.31 22362 14146 4.47 13.96 25972 14123 5.19 18.42
78 19180 15367 3.84 10.52 22576 15329 4.52 14.21 26047 15238 5.21 18.52
H 590
80 19354 16531 3.87 10.69 22615 16435 4.52 14.26 26207 16406 5.24 18.73
85 19574 19343 3.92 10.92 22968 19310 4.59 14.67 26482 19240 5.30 19.10
76 16817 12514 3.36 8.25 19694 12444 3.94 11.04 22784 12405 4.56 14.46
78 16926 13509 3.39 8.35 19729 13419 3.95 11.08 22945 13432 4.59 14.65
GFC 5 M 501
80 17032 14505 3.41 8.45 19933 14457 3.99 11.29 23037 14418 4.61 14.75
85 17256 16981 3.45 8.65 20142 16926 4.03 11.51 23247 16901 4.65 15.00
76 14129 10479 2.83 5.99 16570 10452 3.31 8.03 18987 10360 3.80 10.32
78 14185 11289 2.84 6.03 16690 11298 3.34 8.14 19227 11258 3.85 10.56
L 402
80 14374 12162 2.88 6.18 16678 12080 3.34 8.13 19281 12071 3.86 10.62
85 14465 14179 2.89 6.25 16903 14152 3.38 8.33 19468 14129 3.89 10.81

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• (For lower water pressure drop, special coil DBT : Entering Dry Bulb Temperature (OF)
circuiting please consult PETRA factory). T.cap. : Total Cooling Capacity in (Btu/hr)
S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

22
RAC
PERFORMANCE DATA TABLES
GFC (4-Rows cooling)

Entering Wet Bulb Temperature


Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 20260 15153 4.05 11.64 23798 15065 4.76 15.67 27715 15056 5.54 20.78
78 20344 16345 4.07 11.73 23938 16293 4.79 15.84 27744 16235 5.55 20.82
H 640
80 20560 17603 4.11 11.96 24173 17554 4.84 16.13 27879 17457 5.58 21.01
85 20855 20636 4.17 12.28 24467 20591 4.89 16.49 28240 20525 5.65 21.51
76 18578 13835 3.72 9.91 21781 13755 4.36 13.30 25139 13678 5.03 17.34
78 18580 14889 3.72 9.92 21868 14846 4.37 13.40 25343 14816 5.07 17.60
GFC 6 M 568
80 18735 16003 3.75 10.07 22078 15992 4.42 13.64 25436 15921 5.09 17.72
85 19076 18793 3.82 10.41 22237 18700 4.45 13.82 25637 18647 5.13 17.99
76 15877 11835 3.18 7.42 18777 11846 3.76 10.11 21632 11783 4.33 13.13
78 16102 12827 3.22 7.62 18785 12752 3.76 10.12 21808 12761 4.36 13.33
L 469
80 16184 13770 3.24 7.69 18952 13728 3.79 10.29 21741 13635 4.35 13.26
85 16399 16108 3.28 7.88 19106 16052 3.82 10.44 22051 16020 4.41 13.61
76 24337 17969 4.87 18.04 28650 17938 5.73 24.37 33058 17871 6.61 31.74
78 24520 19406 4.90 18.29 28766 19358 5.75 24.55 33267 19319 6.65 32.11
H 737
80 24731 20855 4.95 18.58 28876 20763 5.78 24.73 33376 20723 6.68 32.30
85 25001 24356 5.00 18.96 29247 24317 5.85 25.31 33700 24261 6.74 32.89
76 21851 16066 4.37 14.80 25567 16009 5.11 19.76 29445 15942 5.89 25.63
78 22001 17341 4.40 14.98 25624 17244 5.13 19.84 29636 17242 5.93 25.94
GFC 8 M 638
80 22124 18601 4.43 15.14 25814 18534 5.16 20.11 29698 18474 5.94 26.04
85 22285 21685 4.46 15.34 26084 21660 5.22 20.50 30029 21632 6.01 26.58
76 18922 13914 3.78 11.36 22123 13872 4.43 15.14 25457 13809 5.09 19.60
78 19075 15019 3.82 11.53 22211 14950 4.44 15.25 25622 14933 5.12 19.84
L 534
80 19147 16082 3.83 11.61 22367 16059 4.47 15.45 25809 16047 5.16 20.10
85 19347 18773 3.87 11.83 22607 18758 4.52 15.75 25910 18689 5.18 20.25
76 35807 26416 7.16 21.09 42068 26333 8.41 28.41 48619 26262 9.72 37.13
78 36033 28499 7.21 21.34 42337 28448 8.47 28.74 48868 28370 9.77 37.48
H 1100
80 36240 30594 7.25 21.57 42533 30533 8.51 28.99 49103 30456 9.82 37.82
85 36751 35781 7.35 22.13 42958 35696 8.59 29.53 49527 35629 9.91 38.42
76 32437 23883 6.49 17.58 37987 23788 7.60 23.53 43966 23756 8.79 30.82
78 32721 25801 6.54 17.86 38297 25724 7.66 23.88 44108 25612 8.82 31.01
GFC 10 M 967
80 32852 27635 6.57 18.00 38400 27561 7.68 24.00 44394 27547 8.88 31.38
85 33332 32321 6.67 18.48 38862 32272 7.77 24.54 44767 32193 8.95 31.87
76 27329 20082 5.47 12.82 32061 20072 6.41 17.20 36935 20003 7.39 22.34
78 27561 21699 5.51 13.02 32190 21631 6.44 17.33 37116 21590 7.42 22.54
L 779
80 27640 23222 5.53 13.09 32321 23196 6.46 17.46 37141 23112 7.43 22.57
85 28051 27151 5.61 13.45 32688 27096 6.54 17.83 37530 27035 7.51 23.01
76 39322 28985 7.86 25.08 46207 28903 9.24 33.79 53475 28803 10.70 44.29
78 39598 31314 7.92 25.40 46510 31224 9.30 34.20 53694 31102 10.74 44.63
H 1240
80 39870 33639 7.97 25.73 46699 33498 9.34 34.46 53981 33441 10.80 45.07
85 40433 39344 8.09 26.40 47213 39202 9.44 35.17 54555 39175 10.91 45.96
76 35149 25905 7.03 20.38 41303 25860 8.26 27.46 47681 25743 9.54 35.82
78 35433 27997 7.09 20.69 41453 27867 8.29 27.64 47966 27826 9.59 36.21
GFC 12 M 1073
80 35617 30023 7.12 20.89 41639 29915 8.33 27.87 48155 29868 9.63 36.48
85 36081 35105 7.22 21.39 42182 35034 8.44 28.55 48640 34969 9.73 37.16
76 31411 23075 6.28 16.57 36795 23017 7.36 22.18 42490 22972 8.50 28.94
78 31600 24893 6.32 16.75 36910 24809 7.38 22.31 42653 24766 8.53 29.14
L 926
80 31756 26704 6.35 16.90 37144 26635 7.43 22.57 42776 26553 8.56 29.30
85 32111 31180 6.42 17.25 37602 31167 7.52 23.09 43255 31099 8.65 29.91

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• (For lower water pressure drop, special coil DBT : Entering Dry Bulb Temperature (OF)
circuiting please consult PETRA factory). T.cap. : Total Cooling Capacity in (Btu/hr)
S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

23
RAC
PERFORMANCE DATA TABLES (GFC)
(3-Rows heating)
Temperature Drop (F)
Model Fan Speed AFR 10 20 30 40
T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD
H 283 25087 5.02 10.07 24938 2.49 2.71 22698 1.51 1.06 21154 1.06 0.55
GFC 2 M 221 20042 4.01 6.60 19417 1.94 1.69 18327 1.22 0.71 17323 0.87 0.38
L 158 14825 2.97 3.74 14185 1.42 0.94 13648 0.91 0.41 12995 0.65 0.22
H 340 29545 5.91 13.72 28196 2.82 3.41 26497 1.77 1.42 24643 1.23 0.73
GFC 3 M 283 25087 5.02 10.07 24938 2.49 2.71 22698 1.51 1.06 21154 1.06 0.55
L 221 20042 4.01 6.60 19417 1.94 1.69 18327 1.22 0.71 17323 0.87 0.38
H 422 35763 7.15 19.71 33846 3.39 4.80 31545 2.10 1.97 29244 1.46 1.00
GFC 4 M 358 30889 6.18 14.93 29364 2.94 3.67 27574 1.84 1.53 25703 1.29 0.79
L 277 24548 4.91 9.67 23562 2.36 2.43 22216 1.48 1.02 20832 1.04 0.53
H 554 49070 9.81 39.72 45188 4.52 9.25 42733 2.85 3.91 40090 2.01 2.03
GFC 5 M 470 40989 8.20 28.29 39351 3.94 7.14 37215 2.48 3.02 34973 1.75 1.58
L 377 33672 6.73 19.54 32392 3.24 4.96 30922 2.06 2.14 29209 1.46 1.13
H 601 50865 10.17 42.51 48407 4.84 10.52 45676 3.05 4.42 42740 2.14 2.29
GFC 6 M 533 45897 9.18 35.01 43657 4.37 8.67 41416 2.76 3.69 38692 1.94 1.90
L 441 38903 7.78 25.64 37123 3.71 6.40 35320 2.36 2.74 33316 1.67 1.44
H 693 61509 12.30 65.99 56841 5.68 15.54 54164 3.61 6.68 50936 2.55 3.50
GFC 8 M 600 52309 10.46 48.67 50235 5.02 12.34 48054 3.20 5.35 45327 2.27 2.82
L 503 44777 8.96 36.35 43160 4.32 9.30 41314 2.75 4.04 39142 1.96 2.15
H 1036 87857 17.57 73.85 83973 8.40 18.47 79854 5.32 7.89 75264 3.76 4.15
GFC 10 M 907 78635 15.73 59.93 75063 7.51 14.97 71560 4.77 6.44 67541 3.38 3.39
L 733 64854 12.97 41.71 64518 6.45 11.29 59705 3.98 4.60 56707 2.84 2.45
H 1165 97474 19.50 89.83 93238 9.32 22.46 87945 5.86 9.45 82651 4.13 4.93
GFC 12 M 1009 88171 17.63 74.35 82129 8.21 17.72 78117 5.21 7.58 73303 3.67 3.95
L 869 75457 15.09 55.45 72757 7.28 14.13 69006 4.60 6.02 65254 3.26 3.18

(4-Rows heating)
Temperature Drop (F)
Model Fan Speed AFR 10 20 30 40
T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD
H 280 25341 5.07 12.28 24744 2.47 3.24 23475 1.57 1.39 22457 1.12 0.76
GFC 2 M 218 20463 4.09 8.24 19422 1.94 2.07 18888 1.26 0.93 18128 0.91 0.51
L 156 14738 2.95 4.48 14583 1.46 1.22 13800 0.92 0.52 13476 0.67 0.30
H 336 29997 6.00 16.82 28943 2.89 4.33 27559 1.84 1.87 26032 1.30 0.99
GFC 3 M 280 25341 5.07 12.28 24744 2.47 3.24 23475 1.57 1.39 22457 1.12 0.76
L 218 20463 4.09 8.24 19422 1.94 2.07 18888 1.26 0.93 18128 0.91 0.51
H 416 36375 7.28 24.13 34877 3.49 6.12 32987 2.20 2.61 31096 1.56 1.37
GFC 4 M 354 31415 6.28 18.34 31408 3.14 5.04 28875 1.93 2.04 27266 1.36 1.08
L 274 24843 4.97 11.83 24178 2.42 3.10 23096 1.54 1.35 21976 1.10 0.73
H 548 48035 9.61 45.51 46379 4.64 11.77 44325 2.96 5.12 42146 2.11 2.75
GFC 5 M 464 41463 8.29 34.60 40161 4.02 9.02 38532 2.57 3.96 36740 1.84 2.14
L 373 34001 6.80 23.92 33093 3.31 6.31 33040 2.20 2.98 30424 1.52 1.51
H 594 51699 10.34 52.20 49733 4.97 13.39 47573 3.17 5.83 45009 2.25 3.10
GFC 6 M 527 46760 9.35 43.29 46140 4.61 11.66 42926 2.86 4.83 40770 2.04 2.59
L 436 39181 7.84 31.14 37940 3.79 8.12 36554 2.44 3.59 34969 1.75 1.95
H 684 60102 12.02 75.70 59775 5.98 20.76 55869 3.73 8.69 53227 2.66 4.69
GFC 8 M 593 52862 10.57 59.64 51245 5.13 15.63 49649 3.31 7.00 47493 2.38 3.81
L 497 44886 8.98 44.04 43874 4.39 11.74 43667 2.91 5.53 40595 2.03 2.86
H 1023 89119 17.82 90.16 85941 8.59 23.28 82571 5.51 10.23 78620 3.93 5.51
GFC 10 M 896 79218 15.84 72.41 79140 7.91 19.99 73745 4.92 8.31 70386 3.52 4.50
L 724 65468 13.09 50.80 63451 6.35 13.30 61275 4.09 5.92 58807 2.94 3.24
H 1151 102131 20.43 116.25 95256 9.53 28.16 91072 6.07 12.26 86626 4.33 6.59
GFC 12 M 997 87174 17.44 86.53 84097 8.41 22.36 80699 5.38 9.81 76961 3.85 5.30
L 858 76329 15.27 67.57 73806 7.38 17.57 71056 4.74 7.76 67937 3.40 4.22

(1-Row heating)
Temperature Drop (F)
Model Fan Speed AFR 10 20 30 40
T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD
H 295 8519 1.704 0.781 6427 0.643 0.116 4401 0.293 0.025 2638 0.132 0.005
GFC 2 M 230 7229 1.446 0.566 5391 0.539 0.083 3839 0.256 0.020 2381 0.119 0.005
L 165 5708 1.142 0.357 4461 0.446 0.057 3189 0.213 0.014 2049 0.102 0.003
H 354 9655 1.931 0.999 7161 0.716 0.144 4861 0.324 0.031 2825 0.141 0.006
GFC 3 M 295 8519 1.704 0.781 6427 0.643 0.116 4401 0.293 0.025 2638 0.132 0.005
L 230 7229 1.446 0.566 5391 0.539 0.083 3839 0.256 0.020 2381 0.119 0.005
H 439 11054 2.211 1.303 8047 0.805 0.180 5455 0.364 0.039 3078 0.154 0.007
GFC 4 M 373 9998 2.000 1.070 7345 0.735 0.151 5028 0.335 0.033 2956 0.148 0.007
L 289 8413 1.683 0.762 6240 0.624 0.110 4378 0.292 0.025 2632 0.132 0.005
H 577 15394 3.079 2.678 11942 1.194 0.423 8746 0.583 0.106 5675 0.284 0.027
GFC 5 M 488 13835 2.767 2.173 10830 1.083 0.350 7951 0.530 0.088 5310 0.266 0.023
L 392 11941 2.388 1.630 9348 0.935 0.263 6986 0.466 0.069 4734 0.237 0.019
H 625 16230 3.246 2.969 12462 1.246 0.460 9141 0.609 0.115 5940 0.297 0.029
GFC 6 M 555 15061 3.012 2.566 11618 1.162 0.401 8558 0.571 0.102 5629 0.281 0.026
L 459 13223 2.645 1.989 10380 1.038 0.323 7672 0.511 0.082 5103 0.255 0.022
H 721 19696 3.939 4.585 15761 1.576 0.775 12020 0.801 0.211 8485 0.424 0.063
GFC 8 M 624 17883 3.577 3.799 14475 1.447 0.658 11042 0.736 0.179 7774 0.389 0.053
L 524 15978 3.196 3.051 12901 1.290 0.527 9925 0.662 0.146 7107 0.355 0.045
H 1079 28666 5.733 5.468 22964 2.296 0.926 17598 1.173 0.254 12360 0.618 0.075
GFC 10 M 945 26306 5.261 4.625 21175 2.117 0.792 16283 1.086 0.219 11528 0.576 0.065
L 763 22789 4.558 3.498 18471 1.847 0.608 14341 0.956 0.172 10277 0.514 0.052
H 1212 30966 6.193 6.356 24730 2.473 1.069 18808 1.254 0.289 13098 0.655 0.083
GFC 12 M 1050 28236 5.647 5.309 22644 2.264 0.901 17322 1.155 0.247 12187 0.609 0.073
L 904 25570 5.114 4.376 20603 2.060 0.751 15860 1.057 0.208 11246 0.562 0.062

AFR: Air Flow Rate (CFM) All capacities are based on


Fan Speed: (L: Low, M: Medium, H: High) • Air temperature 70 °F DB and 60 °F WB
DBT: Entering Dry Bulb Temperature (°F) • 180 °F entering water temperature
T.CAP: Total Cooling Capacity in (Btu/hr)
GPM: Water Flow Rate in Gallon per Minute
WPD: Water Pressure Drop in (ft of water)

24
32
RAC
PERFORMANCE DATA TABLES
PCC/PFC (3-Rows cooling)

Entering Wet Bulb Temperature


Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 8226 6596 1.65 1.45 9750 6505 1.95 1.99 11425 6434 2.29 2.69
78 8328 7187 1.67 1.48 9867 7099 1.97 2.04 11702 7099 2.34 2.81
H 305
80 8434 7779 1.69 1.52 9983 7698 2.00 2.08 11689 7641 2.34 2.80
85 8996 8996 1.80 1.71 10336 9212 2.07 2.23 12014 9144 2.40 2.95
76 6789 5419 1.36 1.01 8078 5367 1.62 1.40 9556 5360 1.91 1.92
78 6867 5900 1.37 1.03 8168 5851 1.63 1.43 9602 5827 1.92 1.94
PCC\PFC 2 M 237
80 6963 6390 1.39 1.06 8350 6376 1.67 1.49 9647 6295 1.93 1.95
85 7540 7540 1.51 1.23 8459 7538 1.69 1.53 9952 7537 1.99 2.07
76 5376 4183 1.08 0.65 6225 4097 1.25 0.86 7339 4101 1.47 1.17
78 5418 4535 1.08 0.66 6397 4502 1.28 0.91 7355 4442 1.47 1.18
L 169
80 5454 4884 1.09 0.67 6406 4841 1.28 0.91 7484 4832 1.50 1.21
85 5828 5828 1.17 0.76 6498 5717 1.30 0.93 7569 5706 1.51 1.24
76 9352 7568 1.87 1.84 11188 7493 2.24 2.58 13222 7432 2.64 3.54
78 9476 8252 1.90 1.89 11407 8207 2.28 2.68 13381 8137 2.68 3.62
H 367
80 9585 8935 1.92 1.93 11548 8901 2.31 2.74 13541 8834 2.71 3.70
85 10617 10617 2.12 2.34 11846 10607 2.37 2.88 13893 10569 2.78 3.88
76 8226 6596 1.65 1.45 9750 6505 1.95 1.99 11425 6434 2.29 2.69
78 8328 7187 1.67 1.48 9867 7099 1.97 2.04 11702 7099 2.34 2.81
PCC\PFC 3 M 305
80 8434 7779 1.69 1.52 9983 7698 2.00 2.08 11689 7641 2.34 2.80
85 8996 8996 1.80 1.71 10336 9212 2.07 2.23 12014 9144 2.40 2.95
76 6789 5419 1.36 1.01 8078 5367 1.62 1.40 9556 5360 1.91 1.92
78 6867 5900 1.37 1.03 8168 5851 1.63 1.43 9602 5827 1.92 1.94
L 237
80 6963 6390 1.39 1.06 8350 6376 1.67 1.49 9647 6295 1.93 1.95
85 7540 7540 1.51 1.23 8459 7538 1.69 1.53 9952 7537 1.99 2.07
76 12244 9611 2.45 3.27 14513 9503 2.90 4.49 17060 9451 3.41 6.09
78 12397 10454 2.48 3.34 14687 10357 2.94 4.60 17257 10320 3.45 6.22
H 454
80 12497 11276 2.50 3.39 14816 11194 2.96 4.67 17345 11139 3.47 6.28
85 13341 13341 2.67 3.84 15293 13349 3.06 4.96 17833 13294 3.57 6.62
76 10841 8471 2.17 2.60 12911 8416 2.58 3.61 15104 8364 3.02 4.84
78 11002 9229 2.20 2.67 13140 9205 2.63 3.73 15178 9087 3.04 4.89
PCC\PFC 4 M 386
80 11092 9953 2.22 2.71 13152 9889 2.63 3.74 15344 9844 3.07 4.99
85 11900 11900 2.38 3.10 13504 11755 2.70 3.93 15751 11721 3.15 5.24
76 8954 6969 1.79 1.82 10634 6929 2.13 2.51 12342 6861 2.47 3.32
78 9108 7594 1.82 1.88 10738 7538 2.15 2.55 12470 7474 2.49 3.38
L 299
80 9170 8182 1.83 1.90 10859 8144 2.17 2.61 12623 8101 2.53 3.46
85 9711 9711 1.94 2.12 11056 9625 2.21 2.70 12878 9607 2.58 3.59
76 14713 11729 2.94 4.61 17630 11625 3.53 6.48 20725 11530 4.15 8.79
78 14915 12796 2.98 4.73 17861 12703 3.57 6.64 20985 12617 4.20 9.00
H 597
80 15124 13853 3.03 4.86 18091 13769 3.62 6.80 21245 13692 4.25 9.21
85 16413 16413 3.28 5.66 18588 16402 3.72 7.16 21699 16311 4.34 9.59
76 13108 10376 2.62 3.71 15724 10319 3.15 5.23 18447 10238 3.69 7.06
78 13373 11340 2.68 3.85 15919 11253 3.18 5.35 18667 11188 3.73 7.22
PCC\PFC 5 M 507
80 13546 12278 2.71 3.95 16113 12186 3.22 5.47 18887 12127 3.78 7.38
85 14606 14606 2.92 4.55 16551 14500 3.31 5.75 19256 14413 3.85 7.65
76 11252 8801 2.25 2.79 13322 8711 2.66 3.83 15596 8652 3.12 5.15
78 11427 9592 2.29 2.87 13563 9527 2.71 3.96 15771 9434 3.15 5.25
L 406
80 11591 10372 2.32 2.95 13737 10313 2.75 4.05 15946 10223 3.19 5.36
85 12300 12300 2.46 3.29 14120 12255 2.82 4.27 16308 12159 3.26 5.60

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• (For lower water pressure drop, special coil DBT : Entering Dry Bulb Temperature (OF)
circuiting please consult PETRA factory). T.cap. : Total Cooling Capacity in (Btu/hr)
S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

25
RAC
PERFORMANCE DATA TABLES
PCC/PFC (3-Rows cooling)

Entering Wet Bulb Temperature


Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 19079 14364 3.82 8.64 22531 14291 4.51 11.79 26165 14209 5.23 15.59
78 19259 15548 3.85 8.79 22771 15508 4.55 12.02 26289 15381 5.26 15.73
H 647
80 19480 16760 3.90 8.98 22924 16693 4.59 12.17 26615 16633 5.32 16.10
85 19952 19754 3.99 9.39 23386 19672 4.68 12.64 27104 19631 5.42 16.66
76 17494 13115 3.50 7.35 20633 13057 4.13 10.00 23940 12999 4.79 13.20
78 17684 14213 3.54 7.50 20828 14153 4.17 10.17 24049 14056 4.81 13.31
PCC\PFC 6 M 575
80 17811 15278 3.56 7.60 20949 15223 4.19 10.29 24322 15194 4.86 13.60
85 18339 18035 3.67 8.02 21410 17950 4.28 10.71 24763 17903 4.95 14.06
76 14965 11260 2.99 5.49 17672 11225 3.53 7.49 20526 11192 4.11 9.90
78 15182 12222 3.04 5.64 17812 12154 3.56 7.60 20691 12130 4.14 10.05
L 474
80 15374 13180 3.08 5.78 17943 13084 3.59 7.70 20870 13081 4.17 10.21
85 15668 15480 3.13 5.98 18351 15437 3.67 8.03 21129 15368 4.23 10.45
76 22188 16581 4.44 12.03 26259 16546 5.25 16.48 30484 16469 6.10 21.78
78 22530 18009 4.51 12.38 26566 17957 5.31 16.84 30626 17811 6.13 21.97
H 745
80 22729 19364 4.55 12.59 26744 19311 5.35 17.05 30986 19250 6.20 22.45
85 23239 22768 4.65 13.12 27327 22751 5.47 17.75 31549 22685 6.31 23.22
76 20050 14893 4.01 9.96 23591 14833 4.72 13.49 27358 14783 5.47 17.79
78 20261 16125 4.05 10.16 23801 16061 4.76 13.72 27448 15967 5.49 17.90
PCC\PFC 8 M 646
80 20403 17326 4.08 10.29 24046 17303 4.81 13.98 27733 17227 5.55 18.25
85 20986 20411 4.20 10.85 24448 20324 4.89 14.42 28223 20283 5.65 18.85
76 17350 12934 3.47 7.61 20485 12918 4.10 10.37 23642 12839 4.73 13.55
78 17594 14027 3.52 7.81 20591 13952 4.12 10.47 23867 13926 4.77 13.79
L 540
80 17810 15114 3.56 7.99 20915 15076 4.18 10.78 24017 14985 4.80 13.95
85 18154 17729 3.63 8.28 21213 17681 4.24 11.07 24369 17605 4.87 14.33
76 32688 24357 6.54 14.17 38583 24275 7.72 19.32 44745 24139 8.95 25.50
78 33085 26411 6.62 14.49 38924 26284 7.79 19.64 45091 26181 9.02 25.87
H 1113
80 33411 28422 6.68 14.76 39284 28315 7.86 19.98 45419 28196 9.08 26.22
85 34289 33480 6.86 15.49 40068 33324 8.01 20.73 46439 33306 9.29 27.34
76 29693 22081 5.94 11.84 34938 21980 6.99 16.04 40543 21890 8.11 21.20
78 30038 23928 6.01 12.10 35300 23830 7.06 16.36 40845 23719 8.17 21.49
PCC\PFC 10 M 978
80 30358 25751 6.07 12.34 35530 25625 7.11 16.56 41191 25563 8.24 21.83
85 31045 30265 6.21 12.86 36283 30155 7.26 17.22 41863 30072 8.37 22.51
76 25173 18690 5.04 8.70 29600 18624 5.92 11.77 34218 18538 6.84 15.43
78 25434 20227 5.09 8.87 29861 20161 5.97 11.96 34485 20082 6.90 15.66
L 788
80 25676 21750 5.14 9.03 30101 21684 6.02 12.14 34757 21615 6.95 15.89
85 26298 25585 5.26 9.44 30633 25477 6.13 12.55 35278 25409 7.06 16.34
76 35598 26649 7.12 16.61 42044 26510 8.41 22.69 48882 26386 9.78 30.10
78 36027 28887 7.21 16.99 42523 28778 8.51 23.18 49348 28655 9.87 30.64
H 1255
80 36451 31126 7.29 17.37 42893 31009 8.58 23.56 49814 30902 9.96 31.19
85 37361 36679 7.47 18.19 43866 36579 8.77 24.57 50688 36442 10.14 32.22
76 32073 23891 6.42 13.67 37784 23782 7.56 18.58 43879 23677 8.78 24.58
78 32406 25887 6.48 13.94 38125 25771 7.63 18.89 44280 25688 8.86 25.00
PCC\PFC 12 M 1085
80 32799 27879 6.56 14.26 38472 27759 7.69 19.21 44602 27676 8.92 25.35
85 33630 32816 6.73 14.94 39381 32735 7.88 20.07 45460 32625 9.09 26.27
76 28702 21348 5.74 11.11 33820 21262 6.76 15.10 39179 21174 7.84 19.88
78 29100 23153 5.82 11.40 34195 23057 6.84 15.41 39563 22971 7.91 20.25
L 937
80 29460 24938 5.89 11.67 34465 24806 6.89 15.64 39929 24753 7.99 20.60
85 30088 29289 6.02 12.13 35163 29191 7.03 16.24 40570 29118 8.11 21.22

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• (For lower water pressure drop, special coil DBT : Entering Dry Bulb Temperature (OF)
circuiting please consult PETRA factory). T.cap. : Total Cooling Capacity in (Btu/hr)
S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

26
RAC
PERFORMANCE DATA TABLES
PCC/PFC (4-Rows cooling)

Entering Wet Bulb Temperature


Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 9126 7102 1.83 2.14 10896 7087 2.18 2.97 12640 7012 2.53 3.92
78 9229 7720 1.85 2.18 10979 7690 2.20 3.01 12697 7619 2.54 3.95
H 301
80 9357 8342 1.87 2.24 11007 8273 2.20 3.03 12831 8242 2.57 4.03
85 9816 9816 1.96 2.45 11214 9788 2.24 3.13 12997 9739 2.60 4.12
76 7590 5837 1.52 1.52 9016 5827 1.80 2.09 10440 5785 2.09 2.74
78 7629 6314 1.53 1.53 8990 6276 1.80 2.08 10485 6265 2.10 2.77
RAC 2 M 234
80 7660 6790 1.53 1.55 9071 6776 1.81 2.11 10480 6726 2.10 2.76
85 7959 7959 1.59 1.66 9261 8006 1.85 2.20 10707 7971 2.14 2.88
76 5827 4418 1.17 0.93 6892 4417 1.38 1.27 7951 4390 1.59 1.66
78 5978 4826 1.20 0.98 6982 4795 1.40 1.30 8031 4767 1.61 1.69
L 167
80 5981 5169 1.20 0.98 6961 5130 1.39 1.30 8102 5140 1.62 1.72
85 6061 6058 1.21 1.00 7133 6061 1.43 1.35 8144 6012 1.63 1.73
76 10465 8207 2.09 2.76 12526 8175 2.51 3.85 14637 8130 2.93 5.15
78 10579 8920 2.12 2.81 12664 8904 2.53 3.93 14620 8790 2.92 5.14
H 363
80 10714 9642 2.14 2.88 12645 9560 2.53 3.92 14775 9516 2.96 5.24
85 11405 11405 2.28 3.23 12920 11341 2.58 4.08 15020 11285 3.00 5.40
76 9126 7102 1.83 2.14 10896 7087 2.18 2.97 12640 7012 2.53 3.92
78 9229 7720 1.85 2.18 10979 7690 2.20 3.01 12697 7619 2.54 3.95
RAC 3 M 301
80 9357 8342 1.87 2.24 11007 8273 2.20 3.03 12831 8242 2.57 4.03
85 9816 9816 1.96 2.45 11214 9788 2.24 3.13 12997 9739 2.60 4.12
76 7590 5837 1.52 1.52 9016 5827 1.80 2.09 10440 5785 2.09 2.74
78 7629 6314 1.53 1.53 8990 6276 1.80 2.08 10485 6265 2.10 2.77
L 234
80 7660 6790 1.53 1.55 9071 6776 1.81 2.11 10480 6726 2.10 2.76
85 7959 7959 1.59 1.66 9261 8006 1.85 2.20 10707 7971 2.14 2.88
76 13416 10307 2.68 4.70 15838 10226 3.17 6.39 18545 10211 3.71 8.57
78 13528 11181 2.71 4.77 15987 11106 3.20 6.50 18630 11066 3.73 8.64
H 448
80 13688 12063 2.74 4.88 16082 11971 3.22 6.58 18788 11948 3.76 8.78
85 14122 14122 2.82 5.17 16419 14152 3.28 6.83 19009 14086 3.80 8.98
76 11964 9131 2.39 3.80 14152 9093 2.83 5.19 16497 9069 3.30 6.89
78 11957 9848 2.39 3.80 14141 9808 2.83 5.18 16484 9781 3.30 6.88
RAC 4 M 382
80 12064 10613 2.41 3.86 14324 10599 2.87 5.30 16628 10557 3.33 7.00
85 12254 12254 2.45 3.97 14532 12481 2.91 5.45 16845 12449 3.37 7.17
76 9825 7449 1.97 2.64 11532 7395 2.31 3.55 13373 7364 2.68 4.67
78 9873 8046 1.98 2.66 11642 8021 2.33 3.61 13466 7983 2.69 4.73
L 295
80 9919 8644 1.98 2.69 11688 8622 2.34 3.64 13521 8582 2.70 4.77
85 10143 10143 2.03 2.80 11763 10092 2.35 3.68 13742 10123 2.75 4.91
76 16406 12722 3.28 6.82 19547 12656 3.91 9.45 22875 12593 4.58 12.67
78 16494 13786 3.30 6.89 19648 13713 3.93 9.54 22989 13662 4.60 12.79
H 590
80 16691 14889 3.34 7.05 19873 14830 3.98 9.75 23102 14732 4.62 12.91
85 17521 17521 3.50 7.71 20128 17496 4.03 9.98 23443 17432 4.69 13.27
76 14630 11259 2.93 5.52 17341 11189 3.47 7.57 20261 11142 4.05 10.11
78 14684 12173 2.94 5.55 17425 12118 3.49 7.63 20357 12082 4.07 10.20
RAC 5 M 501
80 14891 13159 2.98 5.70 17476 13036 3.50 7.68 20418 13005 4.08 10.25
85 15432 15432 3.09 6.09 17765 15400 3.55 7.91 20742 15381 4.15 10.56
76 12362 9472 2.47 4.04 14723 9462 2.95 5.58 16977 9356 3.40 7.27
78 12505 10281 2.50 4.12 14782 10237 2.96 5.62 17148 10172 3.43 7.41
L 402
80 12622 11078 2.52 4.20 14837 11010 2.97 5.66 17210 10949 3.44 7.46
85 12831 12831 2.57 4.32 15096 12979 3.02 5.85 17488 12937 3.50 7.69

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• (For lower water pressure drop, special coil DBT : Entering Dry Bulb Temperature (OF)
circuiting please consult PETRA factory). T.cap. : Total Cooling Capacity in (Btu/hr)
S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

27
RAC
PERFORMANCE DATA TABLES
PCC/PFC (4-Rows cooling)

Entering Wet Bulb Temperature


Model Fan AFR DBT 63 65 67
speed
T.cap S.cap GPM WPD T.cap S.cap GPM WPD T.cap S.cap GPM WPD
76 20400 15233 4.08 11.91 24088 15206 4.82 16.19 27867 15142 5.57 21.21
78 20483 16444 4.10 12.00 24210 16430 4.84 16.34 28058 16388 5.61 21.48
H 640
80 20695 17708 4.14 12.23 24322 17652 4.86 16.48 28175 17608 5.64 21.64
85 20985 20741 4.20 12.55 24610 20704 4.92 16.85 28449 20649 5.69 22.03
76 18705 13904 3.74 10.15 21922 13832 4.38 13.60 25410 13808 5.08 17.87
78 18708 14972 3.74 10.15 22108 14973 4.42 13.82 25494 14903 5.10 17.98
RAC 6 M 568
80 18860 16094 3.77 10.30 22213 16078 4.44 13.94 25695 16042 5.14 18.25
85 19197 18881 3.84 10.65 22517 18855 4.50 14.29 25959 18813 5.19 18.60
76 16113 11953 3.22 7.71 18880 11913 3.78 10.32 21747 11844 4.35 13.40
78 16191 12888 3.24 7.78 18885 12819 3.78 10.33 21917 12827 4.38 13.60
L 469
80 16271 13834 3.25 7.85 19048 13788 3.81 10.49 22020 13777 4.40 13.72
85 16482 16181 3.30 8.04 19199 16121 3.84 10.65 22152 16094 4.43 13.87
76 23739 17615 4.75 16.63 27899 17525 5.58 22.41 32267 17472 6.45 29.32
78 23891 19015 4.78 16.83 28117 18977 5.62 22.73 32535 18938 6.51 29.78
H 737
80 24080 20434 4.82 17.08 28248 20374 5.65 22.93 32673 20334 6.54 30.01
85 24415 23914 4.88 17.52 28581 23873 5.72 23.43 32934 23796 6.59 30.45
76 21297 15741 4.26 13.62 24918 15658 4.98 18.19 28836 15623 5.77 23.82
78 21481 17011 4.30 13.83 25122 16941 5.02 18.47 28999 16882 5.80 24.07
RAC 8 M 638
80 21470 18184 4.29 13.82 25239 18181 5.05 18.62 29154 18143 5.83 24.31
85 21841 21314 4.37 14.27 25574 21301 5.12 19.08 29446 21243 5.89 24.76
76 18547 13677 3.71 10.56 21695 13623 4.34 14.09 25015 13576 5.00 18.32
78 18635 14742 3.73 10.65 21704 14663 4.34 14.10 25098 14651 5.02 18.43
L 534
80 18726 15815 3.75 10.75 21887 15767 4.38 14.32 25267 15744 5.05 18.66
85 18913 18452 3.78 10.94 22059 18416 4.41 14.53 25420 18387 5.08 18.87
76 34922 25852 6.98 19.37 40969 25740 8.19 26.02 47569 25698 9.51 34.32
78 35081 27886 7.02 19.53 41243 27820 8.25 26.35 47736 27738 9.55 34.55
H 1100
80 35327 29968 7.07 19.78 41395 29857 8.28 26.53 48022 29831 9.60 34.93
85 35856 35083 7.17 20.33 41931 34990 8.39 27.17 48468 34948 9.69 35.54
76 31619 23387 6.32 16.12 37059 23283 7.41 21.61 42971 23239 8.59 28.43
78 31796 25243 6.36 16.28 37238 25136 7.45 21.81 43129 25086 8.63 28.62
RAC 10 M 967
80 31960 27075 6.39 16.44 37558 27045 7.51 22.16 43341 26950 8.67 28.88
85 32425 31690 6.49 16.88 37887 31608 7.58 22.52 43724 31560 8.75 29.36
76 26748 19722 5.35 11.84 31256 19624 6.25 15.78 36181 19613 7.24 20.68
78 26852 21259 5.37 11.92 31431 21194 6.29 15.94 36247 21128 7.25 20.75
L 779
80 27011 22807 5.40 12.05 31600 22743 6.32 16.10 36454 22706 7.29 20.97
85 27349 26645 5.47 12.33 31951 26606 6.39 16.43 36756 26541 7.35 21.29
76 38126 28321 7.63 22.78 44954 28247 8.99 30.91 52144 28153 10.43 40.70
78 38432 30614 7.69 23.12 45237 30539 9.05 31.27 52379 30424 10.48 41.04
H 1240
80 38665 32881 7.73 23.38 45429 32779 9.09 31.52 52641 32709 10.53 41.43
85 39214 38513 7.84 24.00 46019 38438 9.20 32.28 53169 38340 10.63 42.20
76 34193 25346 6.84 18.62 40175 25227 8.04 25.10 46529 25153 9.31 32.95
78 34422 27366 6.88 18.86 40478 27305 8.10 25.45 46802 27209 9.36 33.31
RAC 12 M 1073
80 34650 29383 6.93 19.09 40700 29323 8.14 25.71 47011 29226 9.40 33.58
85 35141 34417 7.03 19.59 41175 34325 8.24 26.27 47519 34273 9.50 34.26
76 30492 22566 6.10 15.07 35920 22544 7.18 20.40 41481 22454 8.30 26.63
78 30788 24396 6.16 15.34 36065 24316 7.21 20.55 41729 24273 8.35 26.93
L 926
80 30928 26166 6.19 15.47 36275 26110 7.26 20.77 41864 26046 8.37 27.09
85 31326 30610 6.27 15.84 36608 30525 7.32 21.13 42269 30498 8.45 27.57

All data are based on. AFR : Air Flow Rate (CFM)
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High)
• (For lower water pressure drop, special coil DBT : Entering Dry Bulb Temperature (OF)
circuiting please consult PETRA factory). T.cap. : Total Cooling Capacity in (Btu/hr)
S.cap : Sensible Cooling Capacity in (Btu/hr)
GPM : Water Flow Rate in Gallon Per Minute
WPD : Water Pressure Drop in (ft of water)

28
RAC
PERFORMANCE DATA TABLES (PFC)
(3-Rows heating)
Temperature Drop (F)
Model Fan Speed AFR 10 20 30 40
T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD
H 305 16493 3.30 4.51 14729 1.47 0.99 12612 0.84 0.35 10142 0.51 0.14
PCC 2 M 237 13486 2.70 3.09 11993 1.20 0.67 10349 0.69 0.24 8553 0.43 0.10
L 169 10000 2.00 1.76 9090 0.91 0.40 7917 0.53 0.15 6549 0.33 0.06
H 367 19262 3.85 6.05 16927 1.69 1.29 14380 0.96 0.44 11578 0.58 0.17
PCC 3 M 305 16493 3.30 4.51 14729 1.47 0.99 12612 0.84 0.35 10142 0.51 0.14
L 237 13486 2.70 3.09 11993 1.20 0.67 10349 0.69 0.24 8553 0.43 0.10
H 454 24090 4.82 9.81 21465 2.15 2.15 18511 1.23 0.76 15269 0.76 0.31
PCC 4 M 386 21040 4.21 7.60 18808 1.88 1.68 16352 1.09 0.61 13532 0.68 0.25
L 299 17044 3.41 5.11 15304 1.53 1.14 13402 0.89 0.42 10992 0.55 0.17
H 597 30125 6.03 14.98 26499 2.65 3.18 22701 1.51 1.12 18365 0.92 0.44
PCC 5 M 507 26316 5.26 11.60 23384 2.34 2.52 20159 1.34 0.89 16400 0.82 0.36
L 406 21896 4.38 8.19 19665 1.97 1.82 16965 1.13 0.65 14026 0.70 0.27
H 647 34799 6.96 22.38 31712 3.17 5.14 28157 1.88 1.94 23866 1.19 0.84
PCC 6 M 575 32008 6.40 19.12 28848 2.89 4.31 25689 1.71 1.64 21865 1.09 0.72
L 474 26793 5.36 13.70 24603 2.46 3.21 21862 1.46 1.22 18984 0.95 0.55
H 745 40016 8.00 30.47 36570 3.66 7.05 32692 2.18 2.70 27523 1.38 1.16
PCC 8 M 646 35960 7.19 24.94 32597 3.26 5.70 29235 1.95 2.20 25312 1.27 0.99
L 540 30557 6.11 18.38 28185 2.82 4.35 25375 1.69 1.69 22095 1.11 0.77
H 1113 58978 11.80 36.00 53829 5.38 8.28 48036 3.20 3.15 41125 2.06 1.39
PCC 10 M 978 53027 10.61 29.47 48572 4.86 6.84 43482 2.90 2.62 37401 1.87 1.17
L 788 44149 8.83 20.90 40731 4.07 4.93 36402 2.43 1.89 31958 1.60 0.87
H 1255 65142 13.03 43.41 59245 5.92 9.91 52531 3.50 3.72 44923 2.25 1.64
PCC 12 M 1085 57808 11.56 34.67 52631 5.26 7.94 47141 3.14 3.05 40067 2.00 1.32
L 937 52091 10.42 28.51 46942 4.69 6.42 42065 2.80 2.47 36308 1.82 1.10
(4-Rows heating)
Temperature Drop (F)
Model Fan Speed AFR 10 20 30 40
T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD
H 301 17167 3.43 5.82 15580 1.56 1.34 13839 0.92 0.51 11750 0.59 0.22
PCC 2 M 234 13753 2.75 3.85 12586 1.26 0.90 11300 0.75 0.35 9676 0.48 0.16
L 167 10106 2.02 2.17 9592 0.96 0.55 8596 0.57 0.21 7437 0.37 0.10
H 363 20206 4.04 7.90 18107 1.81 1.77 16008 1.07 0.67 13338 0.67 0.28
PCC 3 M 301 17167 3.43 5.82 15580 1.56 1.34 13839 0.92 0.51 11750 0.59 0.22
L 234 13753 2.75 3.85 12586 1.26 0.90 11300 0.75 0.35 9676 0.48 0.16
H 448 24938 4.99 12.51 22606 2.26 2.87 20145 1.34 1.10 17295 0.87 0.49
PCC 4 M 382 21671 4.33 9.63 19828 1.98 2.26 17619 1.18 0.86 15299 0.77 0.39
L 295 17328 3.47 6.35 15952 1.60 1.51 14417 0.96 0.59 12540 0.63 0.27
H 590 31136 6.23 18.95 28236 2.82 4.34 24824 1.66 1.62 21084 1.05 0.70
PCC 5 M 501 27164 5.43 14.68 24701 2.47 3.39 21948 1.46 1.29 18476 0.92 0.55
L 402 22614 4.52 10.43 20692 2.07 2.44 18541 1.24 0.94 15868 0.79 0.42
H 640 35811 7.16 28.38 33220 3.32 6.85 30074 2.01 2.71 26372 1.32 1.26
PCC 6 M 568 32386 6.48 23.55 29975 3.00 5.67 27347 1.82 2.28 24062 1.20 1.06
L 469 27293 5.46 17.15 25565 2.56 4.23 23395 1.56 1.71 20818 1.04 0.82
H 737 41079 8.22 38.55 38201 3.82 9.37 34792 2.32 3.75 30636 1.53 1.76
PCC 8 M 638 36500 7.30 30.96 34038 3.40 7.58 30902 2.06 3.02 27581 1.38 1.45
L 534 31197 6.24 23.16 29725 2.97 5.91 26946 1.80 2.35 24012 1.20 1.13
H 1100 61152 12.23 46.00 56222 5.62 10.90 50814 3.39 4.29 45089 2.25 2.04
PCC 10 M 967 54302 10.86 36.89 50543 5.05 8.96 46208 3.08 3.61 40896 2.05 1.70
L 779 45889 9.18 26.99 42293 4.23 6.45 38802 2.59 2.62 34578 1.73 1.25
H 1240 66963 13.39 54.47 61943 6.19 13.04 56206 3.75 5.17 49303 2.47 2.40
M 1073 59651 11.93 43.92 55152 5.52 10.52 50188 3.35 4.20 44215 2.21 1.96
PCC 12
L 926 52281 10.46 34.38 48801 4.88 8.40 44651 2.98 3.39 39563 1.98 1.60
(1-Row heating)
Temperature Drop (F)
Model Fan Speed AFR 10 20 30 40
T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD T.CAP GPM WPD
H 317 7852 1.570 0.633 5455 0.545 0.079 3385 0.23 0.01 1649 0.082 0.002
PCC 2 M 246 6656 1.331 0.457 4653 0.465 0.058 3024 0.20 0.01 1555 0.078 0.002
L 176 5386 1.077 0.301 3793 0.379 0.039 2540 0.17 0.01 1349 0.067 0.001
H 381 8865 1.773 0.804 6071 0.607 0.098 3709 0.25 0.02 1769 0.088 0.002
PCC 3 M 317 7852 1.570 0.633 5455 0.545 0.079 3385 0.23 0.01 1649 0.082 0.002
L 246 6656 1.331 0.457 4653 0.465 0.058 3024 0.20 0.01 1555 0.078 0.002
H 471 11383 2.277 1.368 8137 0.814 0.182 5346 0.36 0.04 2998 0.150 0.007
PCC 4 M 400 10236 2.047 1.110 7348 0.735 0.149 4938 0.33 0.03 2758 0.138 0.006
L 310 8713 1.743 0.809 6352 0.635 0.112 4305 0.29 0.02 2530 0.127 0.005
H 619 13479 2.696 1.908 9526 0.953 0.248 6182 0.41 0.05 3389 0.169 0.009
PCC 5 M 525 12149 2.430 1.555 8671 0.867 0.206 5635 0.38 0.04 3143 0.157 0.008
L 421 10513 2.103 1.170 7696 0.770 0.163 5058 0.34 0.03 2912 0.146 0.007
H 671 17209 3.442 3.350 13291 1.329 0.525 9723 0.65 0.13 6387 0.319 0.034
PCC 6 M 596 15885 3.177 2.864 12357 1.236 0.456 9107 0.61 0.12 5960 0.298 0.030
L 492 14073 2.815 2.260 11031 1.103 0.366 8160 0.54 0.09 5411 0.271 0.025
H 774 20029 4.006 4.644 15685 1.569 0.750 11746 0.78 0.20 7995 0.400 0.054
PCC 8 M 670 18108 3.622 3.815 14368 1.437 0.633 10822 0.72 0.17 7448 0.372 0.047
L 561 16166 3.233 3.057 12885 1.288 0.513 9753 0.65 0.14 6753 0.338 0.039
H 1157 28974 5.795 5.465 22834 2.283 0.893 17104 1.14 0.23 11701 0.585 0.065
PCC 10 M 1015 26621 5.324 4.632 21089 2.109 0.766 15898 1.06 0.20 10939 0.547 0.057
L 818 23109 4.622 3.515 18467 1.847 0.592 14028 0.94 0.16 9833 0.492 0.047
H 1301 31223 6.245 6.325 24548 2.455 1.027 18348 1.22 0.27 12434 0.622 0.073
PCC 12 M 1126 28465 5.693 5.280 22467 2.247 0.865 16851 1.12 0.23 11542 0.577 0.063
L 973 25931 5.186 4.401 20548 2.055 0.728 15519 1.04 0.19 10679 0.534 0.055

AFR: Air Flow Rate (CFM) All capacities are based on


Fan Speed: (L: Low, M: Medium, H: High) • Air temperature 70 °F DB and 60 °F WB
DBT: Entering Dry Bulb Temperature (°F) • 180 °F entering water temperature
T.CAP: Total Cooling Capacity in (Btu/hr)
GPM: Water Flow Rate in Gallon per Minute
WPD: Water Pressure Drop in (ft of water)
29
RAC
FAN PERFORMANCE
Aluminum Mesh Filter - 4 Rows Synthetic Filter - 4 Rows
FAN Air Flow Rate (CFM) FAN Air Flow Rate (CFM)
MODEL SPEED External Static Pressure (Inch of water) MODEL SPEED External Static Pressure (Inch of Water )
0.10 0.15 0.20 0.25 0.10 0.15 0.20 0.25
H 280 249 209 171 H 268 231 179 143
RAC 2 M 218 190 162 133 RAC 2 M 207 176 139 111
L 156 138 117 101 L 151 128 100 80
H 336 292 245 203 H 319 271 210 170
RAC 3 M 280 249 212 174 RAC 3 M 268 231 180 144
L 218 192 161 132 L 207 178 136 109
H 416 365 307 255 H 398 339 260 211
RAC 4 M 354 310 264 219 RAC 4 339 288 227 181
L 274 240 204 169 L 263 223 173 140
H 548 477 401 329 H 521 443 344 273
RAC 5 M 464 414 352 292 RAC 5 M 447 385 302 245
L 373 328 276 229 L 354 305 234 192
H 594 519 441 366 H 566 482 379 303
RAC 6 M 527 469 394 323 RAC 6 M 506 436 334 268
L 436 379 318 261 L 414 352 273 216
H 684 602 506 420 H 658 559 435 348
RAC 8 M 593 517 439 360 RAC 8 M 564 480 373 298
L 497 443 377 313 L 478 411 324 262
H 1023 902 758 629 H 974 838 651 522
RAC 10 M 896 797 669 549 RAC 10 M 861 741 575 461
L 724 637 535 439 L 696 592 454 364
H 1151 1024 870 713 H 1106 952 748 598
RAC 12 M 997 869 730 606 RAC 12 M 949 808 620 509
L 858 757 643 527 L 827 704 546 442

Aluminum Mesh Filter -3 Rows Synthetic Filter - 3 Rows


FAN Air Flow Rate (CFM) FAN Air Flow Rate (CFM)
MODEL SPEED External Static Pressure (Inch of water) MODEL SPEED External Static Pressure (Inch of Water )
0.10 0.15 0.20 0.25 0.10 0.15 0.20 0.25
H 283 249 209 173 H 268 231 179 143
RAC 2 M 221 196 167 135 RAC 2 M 209 182 141 126
L 158 140 118 103 L 151 130 101 85
H 340 302 254 208 H 322 280 218 174
RAC 3 M 283 251 213 175 RAC 3 M 268 233 181 145
L 221 196 166 138 L 209 182 141 115
H 422 372 316 262 H 401 345 268 220
RAC 4 M 358 318 267 219 RAC 4 M 339 295 229 183
L 277 246 208 171 L 263 228 178 141
H 554 492 413 343 H 526 457 355 288
RAC 5 M 470 414 348 285 RAC 5 M 447 385 299 239
L 377 335 281 233 L 358 311 238 195
H 601 529 453 371 H 571 491 389 311
RAC 6 M 533 473 397 326 RAC 6 M 505 439 341 270
L 441 392 334 277 L 418 364 283 229
H 693 615 517 429 H 657 571 444 356
RAC 8 M 600 530 451 371 RAC 8 M 570 492 383 311
L 503 447 384 319 L 478 415 330 264
H 1036 920 782 649 H 983 855 664 545
RAC 10 M 907 805 676 554 RAC 10 M 860 748 581 465
L 733 651 553 459 L 695 605 475 380
H 1165 1034 869 721 H 1105 961 747 605
RAC 12 M 1009 896 762 632 RAC 12 M 957 833 647 530
L 869 765 643 527 L 826 711 546 437

Above tables include CB, CBP and FB models

30
RAC
MODELS LAYOUTS
Ceiling Basic Models
(Galvanized Steel) (CB)

RE RE
TUR TU
N RN
9.4 [239] L 9.4 [239] 0 L
0.6 [1 .6 [1
5] 5]

0.8 [2 9.8 [249] 0.8 [2


9.8 [249] 0] 0]
8.2 [208]
8.2 [208]
0.8 [2
0]
0.8 [20]

6.7 [170]

6.7 [170] 9.4 [239]


9.4 [239]

SUP A
PLY
W
SUP A
PLY

W
Model L A W
CB 4 27.2 [691] 23.6 [599] 36.3 [922]
CB 5,6 37.2 [945] 33.7 [856] 46.3 [1176]
Model L A W
CB 8 42.8 [1087] 39.3 [998] 51.9 [1318]
CB 2,3 27.2 [691] 23.6 [599] 36.3 [922]

All dimensions are in Inch [mm]. All dimensions are in Inch [mm].

9.4 [239] 0.6 [15]


RET
U RN
9.8 [249] 0.8 [ L
2
8.2 [208] 0]
0.8 [2
0]

6.7 [170]

9.4 [239]

SUP A
PLY
W

Model L A W
CB 10,12 64.1 [1628] 60.6 [1539] 73.2 [1859]

All dimensions are in Inch [mm].

31
RAC
MODELS LAYOUTS
Ceiling Basic Plenum Models
(Galvanized Steel) (CBP)

RET
URN
9.8 [249] L
0.6 [15]
19.7 [500]

9.8 [249] 0.8 [2


0]
8.2 [208]

0.8 [2
0]

6.7 [170]

9.4 [239]

SUP
PLY
A
W

Model L A W
CBP 2,3,4 27.2 [691] 23.6 [599] 39.0 [991]
CBP 5,6 37.2 [945] 33.7 [856] 49.0 [1245]
CBP 8 42.8 [1087] 39.3 [998] 54.6 [1387]
CBP 10,12 64.1 [1628] 60.6 [1539] 75.9 [1928]
All dimensions are in Inch [mm].

Ceiling Cabinet Models


(Galvanized Steel) (GCC)

RN
TU
RE
A
FRONT VIEW

11.4 [290]
11.8 [300] ]
[130
5.1

25.2 [640]
L
22.4 [569] PLY RIGHT-SIDE VIEW
SUP

TOP VIEW

Model L A B LEGEND
GCC 2,3,4 40.5 [1029] 36.9 [937] 1.85 [47] 1 Flexible conduit
GCC 5,6 50.0 [1270] 46.9 [1191] 1.5 [38] 2 Air vent
GCC 8 56.3 [1430] 52.5 [1334] 1.9 [48] 3 Mounting holes
GCC 10,12 72.4 [1839] 68.7 [1745] 1.85 [47] 4 Coil outlet
5 Coil inlet
6 Drain connection

All dimensions are in Inch [mm].

32
22
RAC
MODELS LAYOUTS
Floor Cabinet Models Floor Basic Models
(Galvanized Steel) (GFC) (Galvanized Steel) (FB)

PPLY 4.9 [1
2 5]
L SU W
9.8 [249]
9.8 [249] SUP
PLY
4.9 [1
2 5]

2[50]
5.9 [150]
25.8 [655]

25.8 [655]

URN
RET RET
UR N

Model L
GFC 2,3,4 43.3 [1100] Model L A W
GFC 5,6 52.7 [1339] FB 2,3,4 33.1 [841] 23.2 [589] 39.8 [1011]
GFC 8 59.1 [1501] FB 5,6 42.8 [1087] 33.1 [841] 49.5 [1257]
GFC 10,12 74.2 [1885] FB 8 50.4 [1280] 40.1 [1019] 57.1 [1450]
FB 10,12 65.6 [1666] 55.7 [1415] 72.3 [1836]

LEGEND RIGHT-SIDE VIEW


TOP VIEW Air vent FRONT VIEW 9.8 [249]
Drain pan 0.6 [15]
Coil outlet
Coil inlet 5.9 2
Drain connection 4.9 [125] 4.9 [125] [150] [50]
Switch
1 [25]

4 1

3
22.6 [574]

2
FRONT VIEW RIGHT-SIDE VIEW
6

5
1
4
3

2 3.1 [79]

LEGEND
Air vent
Drain pan
Coil outlet
Coil inlet
Drain connection

All dimensions are in Inch [mm]. All dimensions are in Inch [mm].

33
RAC
MODELS LAYOUTS
Floor Cabinet Models Ceiling Cabinet Models
(Deluxe Models) (PFC) (Deluxe Models) (PCC)

PLY L
SUP

Model L 8.9
PFC 2,3,4,5 40.6 [1031] [226]

PFC 6,8 53.5 [1359]


PFC 10,12 66.5 [1689]

25 [635] PLY
25 [635] SUP

RN
TU
RE
L
RN
RETU 3.1 [79]
Model L
PCC 2,3,4,5 40.6 [1031]
8.9 [226] PCC 6,8 53.5 [1359]
PCC 10,12 66.5 [1689]

All dimensions are in Inch [mm]. All dimensions are in Inch [mm].

PETRA HIGH WALL CHILLED WATER (PWC)


INTRODUCTION
PETRA high wall chilled fan coil units — The indoor unit is provided with a — Very low power consumption.
(PWC) are uniquely designed with an completely concealed control package — Optional communication with BMS
attractive appearance for different that is provided with flexible pipes and — Very efficient filters: Unit is equipped
applications such as homes, offices and shut-off valves for quick and easy with
factories. connection to the system’s water 3-types of filters:
— PETRA focuses on providing the luxury supply, return and drainage. - Bio filter
of individual room control -cooling and - Plastic washable filter
heating - at a very competitive cost. The - Active carbon electrostatic filter.
system can be utilized in a wide variety
of air-conditioned spaces, using
PETRA’s small capacity air-cooled
chillers. (RWC series).

34
RAC
PETRA HIGH WALL CHILLED WATER (PWC)
Unit Dimensions and Components

PWC 12
8.3” 39”

12”

PWC 18 + PWC 24

PWC 30 +36

All dimensions are in inch

General Data Table for (PWC) Units

Power Supply Water Connection Sound Pressure Level


MODEL
(Volt/Ph/Hz) Size (Inch) at 10Ft (dB)

PWC 12 220-240/1/50 OR 60 ½ 37

PWC 18 220-240/1/50 OR 60 ½ 40

PWC 24 220-240/1/50 OR 60 ½ 42

PWC 30 220-240/1/50 OR 60 ¾ 43

PWC 36 220-240/1/50 OR 60 ¾ 43

35
RAC
PERFORMANCE TABLE FOR (PWC)

Entering Wet Bulb Temperature F


Fan
Model AFR Speed EDB 63 65 67
T.CAP S.CAP WFR WPD T.CAP S.CAP WFR WPD T.CAP S.CAP WFR WPD
76 10295 7888 2.06 2.15 12226 7866 2.45 2.97 14094 7777 2.82 3.89
78 10474 8585 2.10 2.22 12344 8536 2.47 3.03 14347 8503 2.87 4.02
330 H
80 10676 9296 2.14 2.30 12509 9249 2.50 3.10 14405 9153 2.88 4.05
85 11021 10990 2.20 2.44 12858 10933 2.57 3.27 14784 10866 2.96 4.26
76 8917 6787 1.78 1.64 10568 6771 2.11 2.26 12280 6753 2.46 3.00
78 9131 7408 1.83 1.72 10751 7383 2.15 2.33 12435 7348 2.49 3.07
PWC12 275 M
80 9323 8019 1.87 1.78 10832 7948 2.17 2.37 12574 7939 2.52 3.13
85 9520 9315 1.90 1.86 11162 9417 2.23 2.50 12869 9406 2.57 3.27
76 8403 6329 1.68 1.47 9858 6289 1.97 1.98 11342 6230 2.27 2.58
78 8514 6863 1.70 1.50 9932 6809 1.99 2.01 11479 6782 2.30 2.64
250 L
80 8617 7394 1.72 1.54 10156 7390 2.03 2.10 11558 7302 2.31 2.67
85 8896 8738 1.78 1.63 10363 8705 2.07 2.18 11939 8684 2.39 2.84
76 19563 13962 3.91 27.13 22551 13914 4.51 35.24 25851 13935 5.17 45.33
78 19771 15054 3.95 27.66 22697 14972 4.54 35.66 26007 14993 5.20 45.83
480 H
80 19823 16069 3.97 27.80 22881 16045 4.58 36.20 26007 15983 5.20 45.83
85 20185 18709 4.04 28.74 23191 18661 4.64 37.10 26425 18653 5.29 47.20
76 17816 12713 3.56 22.84 20516 12664 4.10 29.61 23469 12662 4.69 37.93
78 17981 13687 3.60 23.23 20661 13630 4.13 30.00 23537 13600 4.71 38.13
PWC18 430 M
80 18001 14589 3.60 23.28 20797 14591 4.16 30.36 23654 14552 4.73 38.48
85 18332 16990 3.67 24.07 21023 16938 4.21 30.97 23962 16940 4.79 39.41
76 16662 11901 3.33 20.20 19353 11934 3.87 26.60 22088 11925 4.42 33.92
78 16810 12812 3.36 20.53 19322 12761 3.86 26.52 22179 12811 4.44 34.18
400 L
80 16935 13714 3.39 20.81 19562 13713 3.91 27.13 22257 13687 4.45 34.40
85 17279 15976 3.46 21.60 19786 15929 3.96 27.70 22501 15907 4.50 35.10
76 23669 16869 4.73 38.53 27431 16858 5.49 50.57 31234 16782 6.25 64.27
78 23919 18191 4.78 39.28 27630 18154 5.53 51.24 31547 18127 6.31 65.46
600 H
80 24090 19463 4.82 39.80 27806 19432 5.56 51.85 31673 19385 6.34 65.95
85 24559 22678 4.91 41.24 28317 22664 5.66 53.62 32169 22612 6.43 67.86
76 20874 14917 4.18 30.57 24160 14893 4.83 40.01 27688 14905 5.54 51.44
78 21134 16100 4.23 31.27 24395 16059 4.88 40.73 27886 16059 5.58 52.12
PWC24 520 M
80 21291 17235 4.26 31.70 24470 17160 4.89 40.96 27959 17160 5.59 52.38
85 21660 20061 4.33 32.72 24868 20000 4.97 42.20 28325 19980 5.67 53.65
76 19563 13962 3.91 27.13 22551 13914 4.51 35.24 25851 13935 5.17 45.33
78 19771 15054 3.95 27.66 22697 14972 4.54 35.66 26007 14993 5.20 45.83
480 L
80 19823 16069 3.97 27.80 22881 16045 4.58 36.20 26007 15983 5.20 45.83
85 20185 18709 4.04 28.74 23191 18661 4.64 37.10 26425 18653 5.29 47.20
76 32101 22899 6.42 30.30 37060 22842 7.41 39.50 42303 22777 8.46 50.46
78 32363 24655 6.47 30.75 37280 24556 7.46 39.94 42390 24444 8.48 50.65
800 H
80 32556 26372 6.51 31.09 37623 26343 7.53 40.62 42901 26305 8.58 51.79
85 33074 30662 6.62 32.01 38120 30635 7.62 41.62 43412 30605 8.68 52.93
76 28625 20432 5.73 24.52 32928 20325 6.59 31.75 37751 20357 7.55 40.87
78 28805 21967 5.76 24.81 33274 21925 6.66 32.37 37974 21901 7.60 41.32
PWC30 700 M
80 28985 23493 5.80 25.09 33464 23473 6.69 32.71 38044 23396 7.61 41.46
85 29459 27323 5.89 25.86 34031 27349 6.81 33.74 38629 27285 7.73 42.65
76 26832 19159 5.37 21.77 31034 19142 6.21 28.46 35424 19117 7.09 36.34
78 26989 20591 5.40 22.00 31247 20592 6.25 28.83 35600 20548 7.12 36.67
650 L
80 27173 22023 5.44 22.28 31394 22013 6.28 29.08 35770 21994 7.15 37.00
85 27610 25618 5.52 22.94 31739 25566 6.35 29.67 36178 25573 7.24 37.78
76 33798 24113 6.76 33.32 39042 24039 7.81 43.50 44602 23978 8.92 55.65
78 33973 25908 6.80 33.64 39351 25885 7.87 44.14 44898 25838 8.98 56.34
850 H
80 34403 27811 6.88 34.43 39581 27702 7.92 44.62 45203 27684 9.04 57.05
85 35038 32377 7.01 35.61 40263 32305 8.05 46.05 45832 32255 9.17 58.53
76 30377 21683 6.08 27.36 35091 21626 7.02 35.71 40025 21573 8.01 45.54
78 30596 23323 6.12 27.73 35253 23237 7.05 36.02 40303 23228 8.06 46.13
PWC36 750 M
80 30810 24952 6.16 28.09 35557 24914 7.11 36.59 40563 24886 8.11 46.68
85 31280 29009 6.26 28.88 36122 29033 7.22 37.67 41039 28966 8.21 47.70
76 28625 20432 5.73 24.52 32928 20325 6.59 31.75 37751 20357 7.55 40.87
78 28805 21967 5.76 24.81 33274 21925 6.66 32.37 37974 21901 7.60 41.32
700 L
80 28985 23493 5.80 25.09 33464 23473 6.69 32.71 38044 23396 7.61 41.46
85 29459 27323 5.89 25.86 34031 27349 6.81 33.74 38629 27285 7.73 42.65

All data are based on: AFR : Air Flow Rate (CFM).
• Entering water temperature 45OF Fan Speed : (L: Low, M: Medium, H: High).
• Interpolation is permissible but not extrapolation. DBT : Entering Dry Bulb Temperature (OF).
T.CAP : Total Cooling Capacity in (BTUH).
S.CAP : Sensible Cooling Capacity in (BTUH).
WFR : Water Flow Rate In GPM.
WPD : Water Pressure Drop in (ft of water).

36
RAC
ELECTRICAL DATA TABLES

Power Supply Fan Motor


MODEL MCA MOP
[Volt/Phase/Hz] No. HP FLA

RAC 2

RAC 3

RAC 4

RAC 5

RAC 6

RAC 8

RAC 10

RAC 12

* RAC Include All Models (CB, CBP.....)

• MCA is based on 125% of the RLA for the largest FLA : Full Load Ampere [for each fan motor].
motor plus 100% of the RLA/FLA for MCA : Minimum Circuit Ampacity.
all other loads included in the circuit (NEC-Article 430-24). MOP : Maximum Overcurrent Protection.

• MOP is based on 225% of the RLA for the largest


motor plus 100% of the RLA for all
other loads included in the circuit (NEC-Article 440-22).

37
RAC
SOUND POWER LEVEL dB
Discharge Sound Power Level (Reference To SWL Pico Watt)
Fan Total
MODEL Frequency Band (Hz)
Speed dB(A)
63 125 250 500 1K 2K 4K 8K
L 40 42 44 36 32 25 25 18 39
RAC 2 M 42 44 46 40 36 29 29 22 42
H 44 46 48 44 40 33 33 26 45
L 41 43 44 37 35 27 28 18 40
RAC 3 M 43 45 46 41 39 31 32 22 43
H 45 47 48 45 43 35 36 26 47
L 42 43 44 38 36 29 29 19 41
RAC 4 M 44 45 46 42 40 33 33 23 44
H 46 47 48 46 44 37 37 27 48
L 45 45 46 39 39 32 30 22 43
RAC 5 M 47 47 48 43 43 36 34 26 43
H 49 49 50 47 47 40 38 30 50
L 47 47 48 41 40 34 33 23 45
RAC 6 M 49 49 50 45 44 38 37 27 48
H 51 51 52 49 48 42 41 31 52
L 48 49 51 43 42 35 33 24 47
RAC 8 M 50 51 53 47 46 39 37 28 50
H 52 53 55 51 50 43 41 32 54
L 51 51 54 46 45 37 36 25 50
RAC 10 M 53 53 56 50 49 41 40 29 53
H 55 55 58 54 53 45 44 33 57
L 51 52 55 46 47 37 35 26 51
RAC 12 M 53 54 57 50 51 41 39 30 54
H 55 56 59 54 55 45 43 34 58

Noise data ± 2dB


Data are measured outside the termination of the duct according to ARI 260 Standard

ELECTRIC HEATER CAPACITY


Maximum Electric Heater Capacity (option)

Heating Capacity
MODEL
[kW]
RAC 2 1.50
RAC 3 1.50
RAC 4 2.50
RAC 5 3.00
RAC 6 3.00
RAC 8 4.00
RAC 10 6.00
RAC 12 6.00

• Electric heater is not applicable for PCC / PfC models.


• For other heating capacities please consult factory

38
RAC
WIRING DIAGRAMS
3 Speed Selector Switch

3-way Valve Cooling Only (option)

39
RAC
WIRING DIAGRAMS
3-way Valve (cooling) With Electric
Heater ( Option)

3-way Valve cooling/Heater ( Option)

40
RAC
WIRING DIAGRAMS
3-way Valve cooling/heating With
Electric Heater(Option)

41
RAC