GENERAL SPECIFICATIONS
S. No. Particulars
1.01
1 Rated KVA 3300
2 Service Outdoor
3 Type Core Type-Oil Immersed
4 Duty Inverter Duty
5 Rated Frequency Hz 50
6 Number of phase
a)HV Side 3
b)LV side 3
c)Neutral 1
7 Winding Conductor Electrolytic Copper
8 Insulation Class CLASS-A
9 Rated Voltage
a) HV winding kV 33000
b)LV winding kV 0.4
10 Vector Group Dyn11
11 Type of Cooling ONAN
12 Insulation Level
One minute power Frequency withstand voltage
a
(KVrms)
HV 70
LV 3
b Impulse Withstand Voltage (KVp)
HV 170KV
LV Not applicable
13 Method of Earthing NA
14 Short circuit level As Per IS:2026
15 Off circuit tap changer
a) Range % 10% to -10%
b) In steps of 2.50%
c)Tapping provided on HV side Yes
16 Tap changer type
Impedance voltage at rated voltage and rated
17 current at principal tap
Impedance 6.25%
18 Temperature rise above 50°C ambient
a) Top of oil by thermometer °C 50
b) Womdomg by resistance °C 55
19 Terminal Details
a)HV Termination Bare Bushings
b)LV Termination Cable Box
c)LV Neutral termination
20 Losses (at 75°C and principal tapping)a)