Calculating Chiller and Cooling Tower Refrigeration in Tons
Calculating Chiller and Cooling Tower Refrigeration in Tons
tons
A ton is the amount of heat removed by an air conditioning system that would melt 1 ton of ice in 24 hours.
h = cp ρ q dt
= 500 q dt (1)
where
Water flows with 1 gal/min and 10oF temperature difference. The ton of cooling load can be calculated as:
= 0.42 ton
The chiller efficiency depends on the energy consumed. Absorption chillers are rated in fuel consumption per
ton cooling. Electric motor driven chillers are rated in kilowatts per ton cooling.
KW/ton = 12 / EER
KW/ton = 12 / (COP x 3.412)
COP = EER / 3.412
COP = 12 / (KW/ton) / 3.412
EER = 12 / KW/ton
EER = COP x 3.412
COP = 3.5
EER = 12
The term kW/ton is commonly used for larger commercial and industrial air-conditioning, heat pump and
refrigeration systems.
The term is defined as the ratio of energy consumption in kW to the rate of heat removal in tons at the rated
condition. The lower the kW/ton the more efficient the system.
kW/ton = Pc / Er (1)
where
The Coefficient of Performance - COP - is the basic parameter used to report efficiency of refrigerant based
systems.
The Coefficient of Performance - COP - is the ratio between useful energy acquired and energy applied and
can be expressed as
COP = Eu / Ea (2)
where
COP can be used to define both cooling efficiencies or heating efficiencies as for a heat pumps.
Cooling - COP is defined as the ratio of of heat removal to energy input to the
compressor
Heating - COP is defined as the ratio of heat delivered to energy input to the
compressor
COP can be used to define the efficiency at single standard or non-standard rated conditions, or as a weighted
average of seasonal conditions. The term may or may not include the energy consumption of auxiliary systems
such as indoor or outdoor fans, chilled water pumps, or cooling tower systems.
COP can be treated as an efficiency where COP of 2.00 = 200% efficiency. For unitary heat pumps, ratings at
two standard outdoor temperatures of 47oF and 17oF (8.3oC and -8.3oC) are typically used.
Energy Efficiency Ratio - EER
The Energy Efficiency Ratio - EER - is a term generally used to define cooling efficiencies of unitary air-
conditioning and heat pump systems.
The efficiency is determined at a single rated condition specified by an appropriate equipment standard and is
defined as the ratio of net cooling capacity - or heat removed in Btu/h - to the total input rate of electric energy
applied - in watt hour. The units of EER are Btu/Wh.
EER = Ec / Pa (3)
where
This efficiency term typically includes the energy requirement of auxiliary systems such as the indoor and
outdoor fans.
h = cp ρ q dt
= 500 q dt (1)
where
where
For room air conditioners the commonly used efficiency ratio is the
These ratings are posted on the Energy Guide Label attached to all new air conditioners.
Some air conditioner manufacturers participates in the voluntary Energy Star labeling program where the
Energy Star label indicates higher EER and SEER ratings.
EER is a measure of how efficiently a cooling system operates when the outdoor temperature is at a specific
level (outdoor conditions commonly used are 95 oF).
EER = qc / p (1)
where
EER is commonly used for room air conditioners ranging 5,000 Btu per hour to 15,000 Btu per hour.
In mild climates air conditioners with EER of at least 9.0 should be selected. In hotter climates air conditioners
with EER over 10.should be selected.
SEER = Qc / P (2)
where
SEER should be at least 10 - there are units where SEER reach ate least 17.
Example - EER
A cooling unit operating at 1 kW/ton would have an EER of 12,000 Btu divided by 1000 watts or 12. This is
mathematically equivalent to multiplying the COP by 3.413. Therefore a small cooling unit operating at 1 kW
(1000 watts) per ton is equivalent to a COP of 3.516, or an EER of 12.
The maximum cooling tower efficiency is limited by the wet-
bulb temperature of the cooling air
Cooling towers use the evaporative cooling principle to cool the circulated water, and
they can achieve water temperatures below the dry bulb temperature - tdb - of the air
cooling air
they are in general smaller and cheaper for the same cooling loads than other cooling
systems
Since a cooling tower is based on evaporative cooling the maximum cooling tower efficiency is limited by
the wet bulb temperature - twb - of the cooling air.
Cooling Tower Efficiency
The cooling tower efficiency can be expressed as
where
The temperature difference between inlet and outlet water (ti - to) is normally in the range 10 - 15 oF.
The water consumption - the make up water - of a cooling tower is about 0.2-0.3 liter per minute and ton
of refrigeration. Compared with the use and waste of city water the water consumption can be reduced
with about 90 - 95%.
Natural draught cooling towers are more dependent on temperature gradients between
air and water and the wind forces than forced draught cooling towers.
The efficiency of natural draught towers are more variable over time and in general
lower.
Note! Be aware that medium temperature systems like cooling towers are known sources of Legionella!
Good cleaning and maintenance systems are important to minimize the potential damage.
Chilled-water systems formulas - evaporator and
condenser flow rates
In a chilled-water system the air conditioner cools water down to 40 - 45oF (4 - 7oC). The chilled water is
distributed throughout the building in a piping system and connected to air condition cooling units wherever
needed.
The total heat removed by air condition chilled-water installation can be expressed as
h = 500 q dt (1)
where
qe = htons 24 / dt (2)
where
qc = htons 30 / dt (3)
where
COP = hh / hw (1)
where
where
If a heat pump delivers 3 units of heat for every unit of energy input - the COP is 3.
Example - COP Heat Pump
Cooling Cycle
A heat pump delivering 60000 Btu/h with a total input of 9 kW:
= 1.95
Heating Cycle
A heat pump delivering 50000 Btu/h with a total input of 7 kW:
= 2.1
EER = hc / Pw (2)
where
Example - EER
An air conditioner or heat pump in cooling modus draws 1000 W to produce 10000 Btu/h cooling. The
EER can be calculated as
= 10
HSPF - Heating Season Performance Factor
The Heating Season Performance Factor - HSPF - is a measure of the overall heating efficiency of a heat
pump.
where
The HSPF can be regarded as an "average" COP for an entire heating season. It is common to compare
BTUs of heat output to watts of electrical energy input. HSPF of 6.8 can be compared with an average
COP of 2 and a HSPF in the range of 5-7 is acceptable.
= 2.3
The SEER should be at least 13 to be sold in the United States. SEER above 20 is a very efficient
system.