Modbus
Modbus
Modbus is a data communications protocol originally published by Modicon (now Schneider Electric) in
1979 for use with its programmable logic controllers (PLCs). Modbus has become a de facto standard
communication protocol and is now a commonly available means of connecting industrial electronic
devices.[1]
Modbus is popular in industrial environments because it is openly published and royalty-free. It was
developed for industrial applications, is relatively easy to deploy and maintain compared to other standards,
and places few restrictions on the format of the data to be transmitted.
The Modbus protocol uses character serial communication lines, Ethernet, or the Internet protocol suite as a
transport layer. Modbus supports communication to and from multiple devices connected to the same cable
or Ethernet network. For example, there can be a device that measures temperature and another device to
measure humidity connected to the same cable, both communicating measurements to the same computer,
via Modbus.
Modbus is often used to connect a plant/system supervisory computer with a remote terminal unit (RTU) in
supervisory control and data acquisition (SCADA) systems. Many of the data types are named from
industrial control of factory devices, such as ladder logic because of its use in driving relays: a single-bit
physical output is called a coil, and a single-bit physical input is called a discrete input or a contact.
The development and update of Modbus protocols have been managed by the Modbus Organization[2]
since April 2004, when Schneider Electric transferred rights to that organization.[3] The Modbus
Organization is an association of users and suppliers of Modbus-compliant devices that advocates for the
continued use of the technology.[4] Modbus Organization, Inc. is a trade association for the promotion and
development of the Modbus protocol.[2]
Limitations
Since Modbus was designed in the late 1970s to communicate to programmable logic
controllers, the number of data types is limited to those understood by PLCs at the time.
Large binary objects are not supported.
No standard way exists for a node to find the description of a data object, for example, to
learn that a register value represents a temperature between 30 and 175 degrees.
Since Modbus is a client/server (formerly master/slave) protocol,[5] there is no way for a field
device to get data by the event handler mechanism (except over Ethernet TCP/IP, called
open-mbus) as the client node must routinely poll each field device and look for changes in
the data. This consumes bandwidth and network time in applications where bandwidth may
be expensive, such as over a low-bit-rate radio link.
Modbus is restricted to addressing 247 devices on one data link, which limits the number of
field devices that may be connected to a parent station (again, Ethernet TCP/IP is an
exception).
Modbus protocol itself provides no security against unauthorized commands or interception
of data.[6]
Protocol versions
Versions of the Modbus protocol exist for serial ports, and for Ethernet and other protocols that support the
Internet protocol suite. There are many variants of Modbus protocols:
Modbus RTU (Remote Terminal Unit) – used in serial communication, and is the most
common implementation available for Modbus. Modbus RTU makes use of a compact,
binary representation of the data for protocol communication. The RTU format follows the
commands/data with a cyclic redundancy check checksum as an error check mechanism to
ensure the reliability of data. A Modbus RTU message must be transmitted continuously
without inter-character hesitations. Modbus messages are framed (separated) by idle (silent)
periods.
Modbus ASCII – used in serial communication and makes use of ASCII characters for
protocol communication. The ASCII format uses a longitudinal redundancy check checksum.
Modbus ASCII messages are framed by a leading colon (":") and trailing newline (CR/LF).
Modbus TCP/IP or Modbus TCP – a Modbus variant used for communications over TCP/IP
networks, connecting over port 502.[8] It does not require a checksum calculation, as lower
layers already provide checksum protection.
Modbus over TCP/IP, Modbus over TCP, or Modbus RTU/IP – a variant that differs from
Modbus TCP in that a checksum is included in the payload, as with Modbus RTU.
Modbus over UDP – some have experimented with using Modbus over UDP on IP networks,
which removes the overhead of TCP.[9]
Modbus Plus (Modbus+, MB+, or MBP) – Modbus Plus is proprietary to Schneider Electric
and unlike the other variants, it supports peer-to-peer communications between multiple
clients.[10] It requires a dedicated co-processor to handle fast HDLC-like token rotation. It
uses twisted pair at 1 Mbit/s and includes transformer isolation at each node, which makes it
transition/edge-triggered instead of voltage/level-triggered. Special hardware is required to
connect Modbus Plus to a computer, typically a card made for the ISA, PCI, or PCMCIA bus.
Pemex Modbus – an extension of standard Modbus with support for historical and flow data.
It was designed for the Pemex oil and gas company for use in process control and never
gained widespread adoption.
Enron Modbus – another extension of standard Modbus developed by Enron with support for
32-bit integer and floating-point variables, and historical and flow data. Data types are
mapped using standard addresses.[11] The historical data serves to meet an American
Petroleum Institute (API) industry standard for how data should be stored.
Data models and function calls are identical for the first four variants listed above; only the encapsulation is
different. However the variants are not interoperable, nor are the frame formats.
In Modbus RTU, Modbus ASCII, and Modbus Plus (which are all RS-485 single-cable multi-drop
networks), only the node assigned as the 'client' may initiate a command.[5] All other devices are 'servers'
and respond to requests and commands. (Note that this client/server naming convention inverts the common
English understanding and Latin origin that there are multiple clients and only one server/patron/business.
To avoid this confusion, the RS-485 transport layer uses the terms 'node' or 'device' instead of 'server', and
the 'client' is not a 'node').
Nomenclature is the same as for the protocols using Ethernet, such as Modbus TCP. Here any device can
send out a Modbus command, and as is usual in computer networks, the device sending the command is the
'client' and the response comes from a 'server'.[12]
Many modems and gateways support Modbus, as it is a simple and often-copied protocol. Some of them
were specifically designed for this protocol. Different implementations use wireline or wireless
communication, such as in the ISM radio band, and even Short Message Service (SMS) or General Packet
Radio Service (GPRS).
Commands
Modbus commands can instruct a Modbus device to:
change the value in one of its registers, by write to Coil or Holding register
send back one or more contained values, by read from Coil or Holding register
read a physical input port, by read from Discrete Input or Input register
A Modbus command contains the Modbus address of the device it is intended for (1 to 247). Only the
addressed device will respond and act on the command, even though other devices might receive it (an
exception is specific broadcastable commands sent to node 0, which are acted on but not acknowledged).
All Modbus commands contain checksum information to allow the recipient to detect transmission errors.
Frame formats
A Modbus "frame" consists of an Application Data Unit (ADU), which encapsulates a Protocol Data Unit
(PDU):[8]
In Modbus data frames, the most significant byte of a multi-byte value is sent before the others.
This format is primarily used on asynchronous serial data lines such as RS-485/EIA-485. Its name refers to
a remote terminal unit.
Start 3.5 x 8 At least 31⁄2 character times (28 bits) of silence (mark condition)
Address 8 Station address
Data n×8 Data + length will be filled depending on the message type
CRC 16 Cyclic redundancy check
End 3.5 x 8 At least 31⁄2 character times (28 bits) of silence (mark condition) between frames
CRC calculation:
Data n×2 Data + length will be filled depending on the message type
End 2 Carriage return + line feed (CR/LF) pair (ASCII values 0D16 and 0A16)
Address, Function, Data, and LRC are ASCII hexadecimal encoded values, whereby 8-bit values (0–255)
are encoded as two human-readable ASCII characters from the ranges 0–9 and A–F. For example, a value
of 122 (7A16 ) is encoded as two ASCII characters, "7" and "A", and transmitted as two bytes, 55 (3716 ,
ASCII value for "7") and 65 (4116 , ASCII value for "A").
LRC is calculated as the sum of 8-bit values (excluding the start and end characters), negated (two's
complement) and encoded as an 8-bit value. For example, if Address, Function, and Data are 247, 3, 19,
137, 0, and 10, the two's complement of their sum (416) is −416; this trimmed to 8 bits is 96 (256 × 2 − 416
= 6016 ), giving the following 17 ASCII character frame: :F7031389000A60␍␊. LRC is specified for
use only as a checksum: because it is calculated on the encoded data rather than the transmitted characters,
its 'longitudinal' characteristic is not available for use with parity bits to locate single-bit errors.
Unit identifier is used with Modbus/TCP devices that are composites of several Modbus devices, e.g.
Modbus/TCP to Modbus RTU gateways. In such a case, the unit identifier is the Server Address of the
device behind the gateway. Natively Modbus/TCP-capable devices usually ignore the Unit Identifier.
The commands to read and write these entities are summarized in the following table.[7] The most primitive
reads and writes are shown in bold.
Some sources use terminology that differs from the standard; for example Force Single Coil instead of Write
Single Coil.[13]
There are three categories of Modbus function codes: public, user-defined and reserved.
Public Modbus function codes
Function
Function type Function name Comment
code
Read Device
43
Identification
Encapsulated Interface
Other 43
Transport
Request:
Normal response:
Number of bytes of coil/discrete input values to follow (8-bit)
Coil/discrete input values (8 coils/discrete inputs per byte)
Value of each coil/discrete input is binary (0 for off, 1 for on). First requested coil/discrete input is stored as
least significant bit of first byte in reply. If number of coils/discrete inputs is not a multiple of 8, most
significant bit(s) of last byte will be stuffed with zeros.
For example, if eleven coils are requested, two bytes of values are needed. Suppose states of those
successive coils are on, off, on, off, off, on, on, on, off, on, on, then the response will be 02 A7 03 in
hexadecimal.
Because the byte count returned in the reply message is only 8 bits wide and the protocol overhead is 5
bytes, a maximum of 2008 (251 x 8) discrete inputs or coils can be read at once.
Request:
Request:
The value of each coil is binary (0 for off, 1 for on). The first requested coil is stored as the least significant
bit of the first byte in the request. If a number of coils is not a multiple of 8, the most significant bit(s) of the
last byte should be stuffed with zeros. See example for function codes 1 and 2.
Normal response:
Request:
Normal response:
Number of bytes of register values to follow (8-bit)
Register values (16 bits per register)
Because the maximum length of a Modbus PDU is 253 (inferred from the maximum Modbus ADU length
of 256 on RS485), up to 125 registers can be requested at once when using the RTU format, and up to 123
over TCP.[7]
Request:
Request:
Because the maximum length of a Modbus PDU is 253 (inferred from the maximum Modbus ADU length
of 256 on RS485), up to 123 registers can be written at once.[7]
Normal response:
Exception responses
For a normal response, the server repeats the function code. Should a server want to report an error, it will
reply with the requested function code plus 128 (hex 0x80) (3 becomes 131 = hex 0x83), and will only
include one byte of data, known as the exception code.
1 Illegal Function Function code received in the query is not recognized or allowed by server
Data address of some or all the required entities are not allowed or do not exist in
2 Illegal Data Address
server
Server Device Unrecoverable error occurred while server was attempting to perform requested
4
Failure action
Server has accepted request and is processing it, but a long duration of time is
required. This response is returned to prevent a timeout error from occurring in
5 Acknowledge
the client. client can next issue a Poll Program Complete message to determine
whether processing is completed
8 Memory Parity Error Server detected a parity error in memory; client can retry the request
Gateway Path
10 Specialized for Modbus gateways: indicates a misconfigured gateway
Unavailable
Gateway Target
11 Device Failed to Specialized for Modbus gateways: sent when server fails to respond
Respond
The Modbus application protocol defines the PDU addressing rules: In a PDU, each data
item is addressed from 0 to 65535.
It also defines a MODBUS data model composed of four blocks that comprise several
elements numbered from 1 to n.
In the Modbus data model, each element within a data block is numbered from 1 to n.
Some conventions govern how Modbus entities (coils, discrete inputs, input registers, holding registers) are
referenced.
Entity numbers combine entity type and entity location within their description table
Entity address is the starting address, a 16-bit value in the data part of the Modbus frame,
ranging from 0 to 65,535 (0000 to FFFF in the packets)
In the traditional convention, entity numbers start with a digit representing the entity type, followed by four
digits representing the entity location:
For data communications, the entity location (1 to 9,999) is translated into a 0-based entity address (0 to
9,998) by subtracting 1. For example, in order to read holding registers starting at number 40001, the data
frame will contain function code 3 (as seen above) and address 0. For holding registers starting at number
40100, the address will be 99.
This limits the number of addresses to 9,999 for each entity. A de facto standard extends this to 65,536[14]
by adding one digit to the previous list:
When using extended referencing, all number references must have exactly 6 digits to avoid confusion
between coils and other entities. For example, to distinguish between holding register #40001 and coil
#40001, if coil #40001 is the target, it must appear as #040001.
Another way to note the data addresses is to use the hexadecimal value, which clarifies the use of the four
digits in the traditional convention mentioned previously.
The advantage of this notation is that the same numbers are found when decoding Modbus packets.
JBUS mapping
Another de facto protocol closely related to Modbus appeared later, and was defined by PLC maker April
Automates, the result of a collaborative effort between French companies Renault Automation and Merlin
Gerin et Cie in 1985: JBUS. Differences between Modbus and JBUS at that time (number of entities,
server stations) are now irrelevant as this protocol almost disappeared with the April PLC series, which
AEG Schneider Automation bought in 1994 and then made obsolete. However, the name JBUS has
survived to some extent.
JBUS supports function codes 1, 2, 3, 4, 5, 6, 15, and 16 and thus all the entities described above, although
numbering is different:
Number and address coincide: entity #x has address x in the data frame.
Consequently, entity number does not include the entity type. For example, holding register
#40010 in Modbus will be holding register #9, at address 9 in JBUS.
Number 0 (and thus address 0) is not supported. The server should not implement any real
data at this number and address, and it can return a null value or throw an error when
requested.
Implementations
Almost every implementation has variations from the official standard. Different varieties might not
communicate correctly between equipment of different suppliers. Some of the most common variations are:
Data types
IEEE 754 floating-point number
32-bit integer
8-bit data
Mixed data types
Bit fields in integers
Multipliers to change data to/from integer. 10, 100, 1000, 256, ...
Protocol extensions
16-bit server addresses
32-bit data size (1 address = 32 bits of data returned)
Word-swapped data
Modbus Plus
Despite the name, Modbus Plus[15] is not a variant of Modbus. It is a different protocol, involving token
passing. It is a proprietary specification of Schneider Electric, though it is unpublished rather than patented.
It is normally implemented using a custom chipset available only to partners of Schneider.
See also
CAN bus
References
1. Drury, Bill (2009). Control Techniques Drives and Controls Handbook (https://app.knovel.co
m/kn/resources/kpCTDCHE08/toc) (PDF) (2nd ed.). Institution of Engineering and
Technology. pp. 508–.
2. "Modbus home page" (https://modbus.org/). Modbus. Modbus Organization, Inc. Retrieved
2 August 2013.
3. "Modbus FAQ" (https://modbus.org/faq.php). Modbus. Modbus Organization, Inc. Retrieved
1 November 2012.
4. "About Modbus Organization" (https://modbus.org/about_us.php). Modbus. Modbus
Organization, Inc. Retrieved 8 November 2012.
5. "Modbus Organization Replaces Master-Slave with Client-Server (press release)" (https://m
odbus.org/docs/Client-ServerPR-07-2020-final.docx.pdf) (PDF). modbus.org. 9 July 2020.
Retrieved 11 July 2023.
6. Palmer; Shenoi, Sujeet, eds. (23–25 March 2009). Critical Infrastructure Protection III. Third
IFIP WG 11. 10 International Conference. Hanover, New Hampshire: Springer. p. 87.
ISBN 978-3-642-04797-8.
7. "Modbus Application Protocol V1.1b3" (https://modbus.org/docs/Modbus_Application_Proto
col_V1_1b3.pdf) (PDF). Modbus. Modbus Organization, Inc. Retrieved 2 August 2013.
8. Modbus Messaging on TCP/IP Implementation Guide V1.0b (https://modbus.org/docs/Modb
us_Messaging_Implementation_Guide_V1_0b.pdf) (PDF), Modbus Organization, Inc.,
October 24, 2006, retrieved 2017-01-07
9. "Java Modbus Library - About" (http://jamod.sourceforge.net). 2010. Retrieved 2017-02-07.
10. "What is the difference between Modbus and Modbus Plus?" (https://www.se.com/ca/en/faq
s/FA198221/). Schneider Electric. 21 August 2004. Retrieved 2017-02-07.
11. "Simply Modbus - About Enron Modbus" (https://www.simplymodbus.ca/Enron.htm). Simply
Modbus. Retrieved 2017-02-07.
12. Prat, Jérôme (13 February 2017). "Crash Course: Client/Server/Master/Slave" (https://www.p
rosoft-technology.com/insights/technology-focus/#). ProSoft Technology. Retrieved
2022-10-17.
13. Clarke, Gordon; Reynders, Deon (2004). Practical Modern Scada Protocols: Dnp3, 60870.5
and Related Systems (https://books.google.com/books?id=ENqyW8fExswC&pg=PA45).
Newnes. pp. 47–51. ISBN 0-7506-5799-5.
14. "Modbus 101 – Introduction to Modbus" (https://www.csimn.com/CSI_pages/Modbus101.htm
l). Control Solutions, Inc.
15. "Modbus Plus - Modbus Plus Network - Products overview - Schneider Electric United
States" (https://www.se.com/us/en/product-range/576-modbus-plus/). Schneider-
electric.com. Retrieved 2014-01-03.
External links
Specifications
Other