0% found this document useful (0 votes)
563 views67 pages

Carrier Manual .2

This document provides an operator's manual for trailer and rail refrigeration units with Advance microprocessors. It contains instructions for daily operation, safety procedures, troubleshooting tips, and maintenance schedules. The manual guides the operator to properly use and care for the refrigeration unit.

Uploaded by

Alex Gutierrez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
563 views67 pages

Carrier Manual .2

This document provides an operator's manual for trailer and rail refrigeration units with Advance microprocessors. It contains instructions for daily operation, safety procedures, troubleshooting tips, and maintenance schedules. The manual guides the operator to properly use and care for the refrigeration unit.

Uploaded by

Alex Gutierrez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 67

Trailer And Rail

R
Refrigeration

-20.0 +34.5° F
↑↓ TO SCROLL, THEN = TO SAVE

OPERATOR’S MANUAL
for
Ultima 53, Ultra/UltraXL,
Extra, Ultra/Ultima XTC
With
Advancet Microprocessor
Trailer And Rail Refrigeration Units

62--10646 Rev G
OPERATOR’S
MANUAL
TRAILER AND RAIL
REFRIGERATION UNITS
With Advance
Microprocessor
Ultima 53
Ultra and Ultra XL
Extra
Ultra XTC And Ultima XTC
CONTENTS
Page
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Unit Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Unit Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Manual Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Pretrip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Changing Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Start-Stop Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Continuous Run Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Sleep Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Manual Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Trip Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Alarm List - View Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Unit Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Functional Change (Parameters) . . . . . . . . . . . . . . . . . . . . . . . . 34
Two--Way Remote Communication . . . . . . . . . . . . . . . . . . . . . . 40
Remote Monitoring Control Box . . . . . . . . . . . . . . . . . . . . . . . . . 42
Mode Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Restart And Battery Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . 44
Resetting The Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Momentary Shut Off Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
IntelliSet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Current IntelliSet Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Changing IntelliSets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Stopping Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Recommended Transport Temperatures . . . . . . . . . . . . . . . . . . 51
Pre-Trip Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Product Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Unit Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Unit Maintenance Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Priming Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Emergency Road Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
OPERATOR’S MANUAL
This guide has been prepared for the operator of units supplied with
the Advance Microprocessor: Ultima 53, Ultra and Ultra XL, Ex-
tra, and Ultra XTC and Ultima XTC Carrier Transicold diesel trail-
er and rail refrigeration units. It contains basic instructions for the
daily operation of the refrigeration unit as well as safety information,
troubleshooting tips, and other information that will help you to de-
liver the load in the best possible condition. Please take the time to
read the information contained in this booklet and refer to it when-
ever you have a question about the operation of your Carrier Tran-
sicold unit.

Your refrigeration unit has been engineered to provide long,


trouble-free performance when it is properly operated and main-
tained. The checks outlined in this guide will help to minimize over-
the-road problems. In addition, a comprehensive maintenance pro-
gram will help to insure that the unit continues to operate reliably.
Such a maintenance program will also help to control operating
costs, increase the unit’s working life, and improve performance.

This guide is intended as an introduction to your unit and to provide


general assistance when needed. More comprehensive informa-
tion can be found in the Operation & Service Manual for your unit.
This manual can be obtained from your Carrier Transicold dealer.

When having your unit serviced, be sure to specify genuine Carrier


Transicold replacement parts for the highest quality and best reli-
ability.

At Carrier Transicold, we are continually working to improve the


products that we build for our customers. As a result, specifications
may change without notice.

1 62--10646
SOFTWARE
It is strongly advised that all units be upgraded to Advance Software
Version 04.03.00. This manual is written for Software version
04.03.00 and above.

NOTE
Once 04.03.00 is installed into an Advance Controller, it will
no longer be possible to load any versions of 03.xx.xx soft-
ware into that microprocessor. Future version releases
may be loaded as they are released.

NOTE
Certain new software features contained within the
04.03.00 version will not be functional without the Reefer-
Manager PC program. It is recommended that ReeferMa-
nager be used when setting Functional Parameters, Con-
figurations, IntelliSets, etc. once 04.03.00 has been
installed.

62--10646 2
UNIT IDENTIFICATION

Each unit is identified by a decal attached to the frame of the unit.


This decal is on the roadside vertical frame post behind the
roadside side door. The decal identifies the complete model
number of the unit, the serial number, the type of refrigerant and
quantity, and the date the unit was placed in service.
If a problem occurs, please refer to the information on this decal,
and make a note of the model and serial number before calling for
assistance. This information will be needed when you contact a
technician or Carrier Transicold Service Engineer so that they may
properly assist you.

62--10646 4
Serial Number
and Bar Code Nameplate

Ultra XTC Shown


Nameplate Location Similar
For All Units

5 62--10646
SAFETY
Your Carrier Transicold refrigeration unit has been designed with
the safety of the operator in mind. During normal operation, all
moving parts are fully enclosed to help prevent injury. During all
pre-trip inspections, daily inspections, and problem
troubleshooting, you may be exposed to moving parts; please stay
clear of all moving parts when the unit is in operation and when the
Start/Run--Off Switch is in the START/RUN position.

NOTE
Refer to the Operation and Service Manual for a complete
list of Safety Precautions.

AUTO-START
Your refrigeration unit is equipped with Auto-Start in both
Start--Stop and Continuous Run modes. The unit may start at any
time, a buzzer will sound for 5 seconds before the unit is started.
When performing any check of the refrigeration unit (e.g., checking
the belts, checking the oil), make certain that the Start/Run--Off
Switch is in the OFF position.

NOTE: Where DataTrakt software and two--way


communication equipment is installed, the Mode Switch on
the Remote Monitoring Control Box must be in the
Maintenance Mode position prior to performing any work
on the unit.

RT2000 UNIT

62--10646 6
ENGINE COOLANT
The engine is equipped with a pressurized cooling system. Under
normal operating conditions, the coolant in the engine and radiator
is under high pressure and is very hot. Contact with hot coolant can
cause severe burns. Do not remove the cap from a hot radiator; if
the cap must be removed, do so very slowly in order to release the
pressure without spray.

REFRIGERANTS
The refrigerant contained in the refrigeration system of your unit
can cause frostbite, severe burns, or blindness when in direct
contact with the skin or eyes. For this reason, and because of
legislation regarding the handling of refrigerants during system
service, we recommend that, whenever your unit requires service
of the refrigeration system, you contact your nearest Carrier
Transicold authorized repair facility for service.

BATTERY
This unit is equipped with a lead-acid type battery. The battery
normally vents small amounts of flammable hydrogen gas. Do not
smoke when checking the battery. A battery explosion can cause
serious physical harm and/or blindness.

7 62--10646
UNIT OPERATION

STARTING UNIT - AUTO

MODE LIGHTS
DISPLAY

-20.0 + 3 4 .5 ° F

MessageCentert
1. Place the START/RUN - OFF
switch to START/RUN position.
DOOR

WARNING
Under no circumstances should
ether or any other starting aids be
used to start engine.

62--10646 8
The microprocessor controller will run a self test. All of the mode
lights will illuminate, all of the segments on the display will be turned
on, and all of the Liquid Crystal Displays (LCDs) in the message
center will be turned on.
The display will then show the setpoint temperature on the left and
the box temperature on the right. The last character (after the
degree symbol) shows the temperature units as
F (Fahrenheit) or C (Celsius).
The MessageCenter will show “STATUS OK” or other user--defined
message unless there is an alarm stored in the controller. If there
is an alarm stored in the controller, an alarm message will be
displayed on the MessageCenter and the Alarm LED will flash for
5 seconds.
The glow plugs will energize, the buzzer will sound, and the diesel
engine will start.

9 62--10646
MANUAL START (GLOW & CRANK)

-20.0 3 4 .5 ° F

1. Hold GLOW/CRANK switch


in the GLOW position.2. Place START/RUN--OFF switch
to the START/RUN position.
3. Continue to hold GLOW/CRANK switch in
the GLOW position for up to 15 seconds,
based on the temperature table below.
4. Then crank the engine by holding the
GLOW CRANK
GLOW/CRANK switch in the
CRANK position until the engine
starts or for a maximum of 10 sec-
onds.
Side of Control Back of Control Box
Box Ultima only All Other Units CRANK

WARNING GLOW
Under no circumstances should
ether or any other starting aids be
used to start engine.

62--10646 10
Glow Time
Glow Time in Seconds
Engine Coolant Temperature TV/Short DI/
(Default) Long
Less than 32_F (0_C) 15 55
33_F to 50_F (1_C to 10_C) 10 40
51_F to 77_F (11_C to 25_C) 5 25
Greater than 78_F (26_C) 0 10
The diesel engine may be manually started using the
GLOW/CRANK switch and the START/RUN -- OFF switch.
When the micro powers up, “MANUAL START MODE SELECTED”
will appear in the MessageCenter and the Alarm LED will blink for
5 seconds.

NOTE: Manual Start will automatically put the unit in


Continuous Run mode. Placing the unit in Start--Stop will
automatically put it back into Auto Start operation.

NOTE: Manual Start Mode will automatically be cancelled


when the Start/Run--Off Switch is toggled to Off and then
back to Start/Run.

11 62--10646
PRETRIP

-20.0 +34.5° F
T EST #1

1. Press the SELECT key until the


MessageCenter displays
“PRESS = TO START PRETRIP”.
2. Press the = key to start PRETRIP.

3. Verify that during TEST#1 the complete display is


turned on, that the buzzer comes on, that all lights
on the Light Bar come on and that the AutoFresh
air port opens and closes (option for XTC units
only).
4. The remainder of Pretrip will take 7 to 15 minutes,
and will run itself automatically.
5. Pretrip cannot be started when:
SThere is an active Shutdown Alarm
SThe unit is in PC Mode
SThe unit is in Defrost
NOTE: The Start/Run---Stop Switch must be in the
Start/Run position in order to start Pretrip.

62--10646 12
The PRETRIP mode is for checking unit operation and evaluating
operation of all modes and indicating a failure when detected.

TIP: A Pretrip can be started at any box temperature and


will cause the unit to start if it is in an off cycle.
The MessageCenter displays the current test and the % complete
of the test. When the Pretrip tests are complete the
MessageCenter will display “PRETRIP PASS”. If “PRETRIP FAIL
IN TEST “X” or PRETRIP FAILED & COMPLETE” is displayed the
ALARM light will flash. Press the ALARM LIST key to review the
alarms set by the Pretrip tests.
TIP: “PRETRIP PASS” or “PRETRIP FAIL” will remain in
the display until any key is pressed.

Once Pretrip is started, the control panel keys are disabled until
Pretrip ends.
Pretrip will be delayed in the following situations:
SThe unit is in Warm--up Mode.
SThe unit is in Defrost.
SThe battery is fully charged
SThe box temperature is at setpoint
TIP: “CANNOT START PRETRIP” will be displayed in the
MessageCenter when Pretrip cannot be started.

13 62--10646
CHANGING SETPOINT

-20.0 34.5° F
↑↓ TO SCROLL, THEN = TO SAVE

1. With the setpoint displayed, press the UP or


DOWN ARROW key to change the set point
to the desired value. The display will flash to
indicate that the setpoint reading being
displayed is a non-entered value. The
MessageCenter will show
“↑↓ TO SCROLL, THEN = TO SAVE”. The
setpoint display will flash for 5 seconds or
until the = key is pressed

2. Press the = key to save the new setpoint.

New setpoint will flash and then return to original


setpoint if ENTER key is not pressed.

62--10646 14
Setpoints of --22°F to +89.6°F (--30°C to +32°C) may be entered
via the keypad. The controller always retains the last entered
setpoint in memory. Depending on Microprocessor set--up, the
setpoint may be changed up or down in either 0.1° (one--tenth of
a degree) or 1° (one full degree) increments by pressing and
releasing either the UP ARROW or DOWN ARROW key.

TIP: If the message “MAX SETPOINT HAS BEEN


REACHED” or “MIN SETPOINT HAS BEEN REACHED”
is displayed, the setpoint range has been locked within set
minimum and maximum limits, and cannot be changed
beyond those settings.

You can not change setpoint when unit is in Pretrip or Sleep Mode
or when viewing Alarm List, Data List or Functional Parameters.
Pressing the = key will cause the new displayed setpoint value to
become active and “SET POINT CHANGED” is displayed. If the
display is flashing and the new value is not entered, after 5 seconds
of no keyboard activity, the display and Light Bar will both flash for
15 seconds with “SET POINT NOT CHANGED” displayed and then
revert back to the last setpoint. All other keys are active at this time
and may be pushed while the display is flashing.

TIP: You may press and hold the UP ARROW or DOWN


ARROW key to quickly change the setpoint. The longer
the key is held, the faster the setting will change.

15 62--10646
START-STOP OPERATION
START/STOP LIGHT

-20.0 34.5° F
ST ART / ST O P MO DE SELECT ED

1. Press the START-STOP/CONTINUOUS


key until the START-STOP Light on the
controller illuminates.
2. Verify that START/STOP MODE SELECTED is
displayed on the MessageCenter for five seconds
and that the START-STOP light is illuminated. The
unit is now in Start-Stop operation.

Automatic start/stop is provided to permit starting/restarting of the


diesel-driven compressor as required. This gives the
microprocessor automatic control of starting and stopping the
diesel engine. The main function of automatic start-stop is to turn
off the refrigeration system near the setpoint to provide a fuel
efficient temperature control system and then restart the engine
when needed. Start-Stop operation is normally used for frozen
loads. Refer to RECOMMENDED TRANSPORT TEMPERATURES (See Page
51).

62--10646 16
Start-Stop and Continuous operation may be tied to the setpoint
ranges for frozen and perishable loads. The
START-STOP/CONTINUOUS key is locked out if “START-STOP
LOCKED” appears in the MessageCenter when the unit is in
Start--Stop Mode or “CONTINUOUS LOCKED” appears in the
MessageCenter when the unit is in Continuous Run Mode.
Any time the ambient temperature is below 35°F (2°C) the unit will
not operate in High or Low Speed Cool. High and Low Speed Heat
cycles will operate at all ambient temperatures.
The microprocessor controller monitors box temperature, battery
voltage, and engine coolant temperature
Whenever the unit starts in Start--Stop, it will run until:
SIt has run for the predetermined minimum run time
SThe engine coolant temperature is above 122°F (50°C)
SThe battery is fully charged as indicated in the MessageCenter by
“OK” after the voltage value AND the charging amps must be less
than the value selected in the configuration list (Factory setting is
6.5 amps.)
SThe box temperature is at setpoint
A restart will be initiated when one of the following conditions
occurs:
SBox temperature has moved away from setpoint by 4° to 18°F (2°
to 10°C) depending on the Functional Parameter settings.
SThe minimum Off Time has expired and the box temperature has
moved away from setpoint by more than 4°F (2°C).
SEngine coolant temperature drops below 34°F (1°C)
SThe battery voltage falls below 12.2 VDC
Maximum Off Time ensures that the entire load stays within safe
temperature range. The unit will start after a pre--selected
maximum off time--regardless of any change in box temperature.

If the unit fails to start three consecutive times, the “FAILED TO


START -- AUTO MODE” alarm is activated.
If all safety conditions are met while the unit is running and the unit
fails to run for the minimum run time three consecutive times, the
“FAILED TO RUN MINIMUM TIME” alarm is activated.

17 62--10646
CONTINUOUS RUN OPERATION

CONTINUOUS RUN LIGHT

-20.0 34.5° F
CO NT I NUO US RUN MO DE SELECT ED

1. Press the START-STOP/CONTINUOUS


key until the CONTINUOUS RUN Light
on the controller illuminates.

2. Verify that “CONTINUOUS RUN MODE


SELECTED” is displayed on the MessageCenter
and that the CONTINUOUS RUN light is
illuminated. The unit is now in Continuous Run
operation.

62--10646 18
In the Continuous Run mode, the diesel engine will run
continuously -- providing constant air flow and temperature control
to the product. Continuous Run operation is normally used for
perishable loads. Refer to RECOMMENDED TRANSPORT TEMPERATURES
(See Page 51).
Start-Stop and Continuous operation may be tied to the setpoint
ranges for frozen and perishable loads. The
START-STOP/CONTINUOUS key is locked out if “START-STOP
LOCKED” appears in the MessageCenter when the unit is in
Start--Stop Mode or “CONTINUOUS LOCKED” appears in the
MessageCenter when the unit is in Continuous Run Mode.
The unit will remain in low speed after the engine start--up for the
number of minutes selected in the functional parameters when the
Continuous Run setpoint is < 10°F (--12°C).
Also, any time the ambient temperature is below 35°F (2°C) the unit
will not operate in High Speed Cool. Low Speed Cool, High and
Low Speed Heat cycles will operate at all ambient temperatures.

19 62--10646
SLEEP MODE

SLEEP MODE: YES

1. Press the SELECT key until the MessageCenter


displays “PRESS ↑↓ TO VIEW
SETTINGS”.
2. By pressing the UP or DOWN ARROW key, you
will move through the Function List until “SLEEP
MODE: NO” appears in the MessageCenter.
3. Press the = key “↑ ↓ TO SCROLL, THEN = TO SAVE”
will appear in the MessageCenter. Press either the UP
or DOWN ARROW key to change Sleep Mode to YES.
4. Press the = key to select Sleep Mode.
SLEEP MODE OFF
1. To take the unit out of Sleep Mode, place the
START/RUN - OFF switch to OFF position, then
back to Start/Run.

62--10646 20
Sleep Mode is used generally in cold ambients when the unit may
be OFF for an extended period of time. In Sleep Mode the unit will
“Wake Up” periodically and run to keep the battery charged and the
engine warm. There is NO temperature control in Sleep Mode
and it should never be used for hauling perishable or frozen
products.
While the unit is running in Sleep Mode, “WARNING: NO TEMP
CONTROL” will be displayed in the MessageCenter. No setpoint
or box temperature will be shown, as the unit is not running to
control the box temperature.
While the unit is cycled off in Sleep Mode, “SLEEP MODE, OFF/ON
TO WAKE” will be shown in the MessageCenter. To exit Sleep
Mode, you can use the instructions on the preceding page, or
Repeat Steps 1 thru 3 on preceding page, then press UP ARROW
key until “NO” is showing. Press the = key to exit.

NOTE: If the unit is equipped with remote two--way


communication capabilities, the Microprocessor may not
power down when the switch is turned off. Should this
occur, locate the Remote Monitoring Control Box and:
1. Move the Mode Switch behind the toggle guard to
Maintenance Mode.
2. Turn the Start/Run -- Off Switch to the Off position, then
back to the Start/Run position.
3. Move the Mode Switch back to the Remote On position.

21 62--10646
MANUAL DEFROST

DEFROST LIGHT

-20.0 dF
DEF RO ST CYCLE ST ART ED

1. Press the MANUAL DEFROST key. The DEFROST


light will come on and the MessageCenter will display
“DEFROST CYCLE STARTED” for 5 seconds, or
flash “CANNOT START DEFROST CYCLE” for 5
seconds.

62--10646 22
Check DTT1 and DTT2 temperatures in Data List (DTT2 only for
XTC units). The defrost mode may be initiated in three different
ways if the evaporator coil is below 40°F (4.4°C) OR the SAT is
below 45°F (7.2°C) for XTC units:
1. Defrost is initiated automatically at preset intervals by defrost
timer in the microprocessor.
2. Defrost is initiated by the defrost air switch.
3. The defrost mode may be manually initiated by pressing the
Manual Defrost Key.
If “CANNOT START DEFROST CYCLE” is displayed:
S The coil temperature is above 40°F (4.4°C). Run the unit to lower
temperature below 40°F (4.4°C) and then restart defrost.
SThe unit has not run 15 seconds after starting
SThe unit is in PC Mode
SThe unit is in Pretrip.
SThere is an active shutdown Alarm
SDefrost will be started but delayed if unit is in Warm--up mode.
The defrost mode terminates when the evaporator temperature is
higher than 55°F (12.8°C). Should the defrost cycle not complete
within 45 minutes, the defrost cycle is terminated. “DEFROST NOT
COMPLETE” will be in the MessageCenter.
After the 45 minute termination, the controller will wait 1.5 hours of
engine running time before attempting an automatic defrost cycle.
Pressing the manual defrost key will override this mode and start
a defrost cycle.
If a shutdown alarm occurs, defrost will be terminated, the unit will
remain off for 15 minutes and then restart.

23 62--10646
TRIP START

-20.0 34.5° F
T RI P ST ART ENT ERED

1. Press the SELECT key until the


MessageCenter displays
“PRESS = TO MARK TRIP
START”.
2. Press the = key.

3. If trip start is acknowledged by the data recorder,


“TRIP START ENTERED“ will be displayed for 5
seconds and then the display will revert back to
the normal display. In unlikely situation that data
recorder is not functioning properly “CANNOT
ENTER TRIP START” will flash and then the
display will revert back to the normal display.

62--10646 24
Trip start places a time stamp in the data recorder memory to allow
easy review of the data from the last trip, and to allow downloading
data from a specific trip.
Trip start tells the recorder that the present date and time is the
beginning of a new trip.

25 62--10646
ALARM LIST - VIEW ALARMS
ALARM LIGHT

-20.0 34.5° F
NO ACT I VE ALARMS

1. Press the ALARM LIST key. If there are no


active alarms, the MessageCenter will
display “NO ACTIVE ALARMS” for 5 sec.
2. If there are active alarms, the display will be
‘A’ and the alarm number and message.
The last Alarm that occurred will be the first
Alarm displayed.
3. Press the ALARM LIST or UP ARROW
key to scroll through the list of alarms.
4. When you reach the end of the alarm list,
“LIST END, = TO CLEAR ALARMS” is displayed.
5. To clear the active alarm list, press the = key while
“LIST END, = TO CLEAR ALARMS” is being
displayed.

62--10646 26
ALARMS & DEFAULT MESSAGES
Unit problems detected by the controller are stored in the Alarm List
in the controller. Stored alarms may be viewed in the
MessageCenter.
At most times, the STATUS OK or other user--defined message will
be shown in the MessageCenter.
If there is a problem with the data recorder, DATA RECORDER
FAILURE will be shown.
If a problem begins to develop one of the following messages may
be shown:
LOW FUEL LEVEL WARNING means that the fuel level in the fuel
tank needs to be checked and fuel added.
CHECK ENGINE OIL LEVEL means that the engine oil level needs
to be checked and oil added.
LOW COOLANT LEVEL means that the engine coolant level
needs to be checked and coolant (anti--freeze) added.
SLEEP MODE, OFF / ON TO WAKE will appear when the unit is
in Sleep Mode, and the engine has cycled off. (See page 20 for
more information on Sleep Mode.
WARNING: NO TEMP CONTROL will be displayed when the unit
is in Sleep Mode, and the unit has temporarily “awakened” and is
running. (See page 20 for more information on Sleep Mode.)
CHECK DOOR will be displayed if the trailer door is opened, and
your trailer has an optional door switch to notify you when the door
is opened or not closed tightly.
UNIT SHUTDOWN -- DOOR OPEN will be displayed if the trailer
door is opened, and your trailer has an optional door switch to shut
the unit down when the door is opened, or not closed tightly.
CHECK REMOTE SWITCH 1 (2) will be displayed if an optional
remote control switch is installed as a warning device (for
example--a second door switch, or remote toggle OFF/ON switch),
and the switch is in the OFF position.

27 62--10646
UNIT SHUTDOWN--REMOTE SWITCH 1 (2) will be displayed if an
optional remote control switch is installed and configured to shut
the unit down when it is turned OFF (for example--a second door
switch, and the door is opened) whenever the door is opened or not
tightly closed.
CHECK AT NEXT SERVICE INTERVAL is shown when:
1) There is an active non--shutdown alarm present (the alarm
condition is present but is not serious enough to stop the unit).
These alarms may be viewed by pressing the Alarm List Key.
The message will clear itself when the condition is corrected.

TIP: To clear active alarms, turn the microprocessor OFF


and then back ON using the START/RUN-OFF switch.
If there is a safety shutdown, UNIT SHUTDOWN -- SEE ALARM
LIST will be shown. Pressing the Alarm List Key will bring any
Active Alarms into the MessageCenter.

62--10646 28
UNIT DATA

-20.0 34.5° F
PRESS ↑ ↓ TO VIEW DATA

1. Press the SELECT key until the


MessageCenter displays
“PRESS ↑↓ TO VIEW DATA”.
2. By pressing the UP ARROW key, you will
move through the Data List beginning at the
top and moving toward the bottom, or by
pressing the DOWN ARROW key, you will
move through the Data List beginning at the
bottom, and moving toward the top.
3. To lock a Data List item in the MessageCenter, press
the = key. The Data item will flash continuously to in-
dicate it is locked. Press any key to stop flashing and
unlock the item.
4. Pressing UP or DOWN key will move to the next
data item.

62--10646 30
UNIT DATA
UNIT DATA
DATA DEFINITION
SUCTION Compressor suction pressure
PRESSURE
DISCHARGE Compressor discharge pressure
PRESSURE
ENGINE Engine coolant temperature
COOLANT TEMP
RETURN AIR Return (air entering evaporator) air temperature
TEMP
SUPPLY AIR Supply (air leaving evaporator) air temperature
TEMP
DELTA--T Return air temperature minus Supply air
temperature.
AMBIENT AIR Ambient (air entering condenser) air temperature
TEMP
DEFROST TERM Defrost termination temperature #1 --
TEMP 1 Temperature in Blower Housing (Non XTC units
only)
DEFROST TERM Defrost termination temperature #2 -- Evaporator
TEMP 2 Coil Temperature
COMP Compressor discharge temperature
DISCHARGE
TEMP
BATTERY Battery voltage
CURRENT DRAW Current (amp) draw of the electrical circuits
ENGINE RPM Engine revolutions per minute
% of fuel in tank. (This is only shown when 0 to
FUEL LEVEL
100% sensor is configured ON)
SUCTION MOD % open of SMV or CLOSING
VALVE XTC ONLY
START MODE AUTO if the engine will start automatically
MANUAL if the engine must be started manually
INSTALLED This is only shown if software options have been
OPTIONS installed in the Microprocessor.
•IntelliSet
•DataTrak
SOFTWARE Revision of the software that is operating the
REVISION Microprocessor

31 62--10646
UNIT DATA
DATA DEFINITION
DISPLAY Revision of the software that is operating the
SOFTWARE REV display
CONTROL Serial Number of the Microprocessor
SERIAL #
TRAILER ID # Trailer ID (as entered by the user)
UNIT SERIAL # Unit serial number
UNIT MODEL # Unit model number (selected through
configurations)
HOURS TO Number of engine hours until the next
ENGINE MAINT programmed engine maintenance.
HOURS TO UNIT Number of switch--on hours until the next
MAINT programmed general unit maintenance.
TIME LEFT TO Number of hours until the next programmed PM
PM (1--5) maintenance.
ProductShield Indicates that unit has IntelliSet installed and
SETUP: is configured for Product Shield
•ProductShield Indicates if ProductShield Econo is OFF or
Econo: GO TO S/S or GO TO CONTINUOUS
•Econo Min Minimum ambient temperature of range for
Temp activation of ProductShield Econo (Will only
be displayed if Econo is NOT OFF)
•Econo Max Maximum ambient temperature of range for
Temp activation of ProductShield Econo (Will only
be displayed if Econo is NOT OFF)
•Econo Delta--T Delta--T value for activation of ProductShield
Econo (Will only be displayed if Econo is
NOT OFF)
•ProductShield Indicates if Product Shield High Air is ON or
High Air: OFF
•High Air Min Minimum ambient temperature of range for
Temp activation of Product Shield High Air (Will
only be displayed if High Air is ON)
•High Air Max Maximum ambient temperature of range for
Temp activation of Product Shield High Air (Will
only be displayed if High Air is ON)
•High Air Delta--T value for activation of Product
Delta--T Shield High Air (Will only be displayed if
High Air is ON)

62--10646 32
UNIT DATA
DATA DEFINITION
•ProductShield Indicates if ProductShield Winter is OFF or,
Winter: if temperature is displayed, indicates
ProductShield Winter is ON and the dis-
played temperature is controlling
ProductShield Winter
RANGE 1 LOCK OFF -- Temperature Range 1 Lock is turned off.
CONTINUOUS -- When the Set Point is set
between Range 1 Minimum & Maximum
Temperatures, the unit is set to operate only in
Continuous Run.
START--STOP -- When the Set Point is set
between Range 1 Minimum & Maximum
Temperatures, the unit is set to operate only in
Start/Stop.
RANGE 1 This is the lower limit for Range 1.
MINIMUM TEMP
RANGE 1 This is the upper limit for Range 1.
MAXIMUM TEMP
RANGE 2 LOCK OFF -- Temperature Range 2 Lock is turned off.
CONTINUOUS -- When the Set Point is set
between Range 2 Minimum & Maximum
Temperatures, the unit is set to operate only in
Continuous Run.
START--STOP -- When the Set Point is set
between Range 2 Minimum & Maximum
Temperatures, the unit is set to operate only in
Start--Stop.
RANGE 2 This is the lower limit for Range 2.
MINIMUM TEMP
RANGE 2 This is the upper limit for Range 2.
MAXIMUM TEMP
REMOTE This is the temperature at remote Temperature
SENSOR (1--3) Sensor 1, 2, and 3. (These sensors are optional,
and may not be applicable to your unit. Up to 3
remote sensors may be listed.)
DATALOGGER This is the current Date and Time that the Data
Recorder is using. This may be different than
your actual time, depending on the Time Zone
and daylight--saving time selections made by the
owner of the unit.

33 62--10646
FUNCTIONAL CHANGE (PARAMETERS)

-20.0 34.5° F
PRESS ↑ ↓ TO VIEW SETTINGS

1. Press the SELECT key until the MessageCenter


displays PRESS ↑↓ TO VIEW SETTINGS.

2. Press the UP or Down keys to scroll through the


functional parameters list.

3. To change one of the Functions, bring the Function you wish to


change into the MessageCenter, and press = key.
“↑ ↓ TO SCROLL, THEN = TO SAVE” will appear in the
MessageCenter. Pressing either UP or DOWN ARROW key will
begin to change the Function setting. The MessageCenter will
flash, indicating that a change has been made that has not been
entered into memory.

4. Continue pressing UP or DOWN ARROW key until the desired value


is showing, then press the = key. The MessageCenter will stop
flashing. The new value is now in memory. If the = key is not pressed
within 10 seconds, the MessageCenter will change to
“FUNCTION NOT CHANGED”. This will appear for 5 seconds, then
return to the last Functional Parameter shown. If no further keys are
pressed, the default display will return in another 10 seconds.

NOTE: Any Function shown with a lock


symbol can not be changed from the keypad.

62--10646 34
FUNCTIONAL
SELECTIONS DESCRIPTION
PARAMETER
DEFROST 1.5HRS The defrost timer will automatically
TIMER SET 3HRS put the unit into the defrost cycle at
FOR 6HRS the interval selected if DTT1 or DTT2
12HRS is below 40°F (4.4°C).
Shorter times are generally used for
warm, humid products like produce.
Longer times can be used for dry and
frozen products.
SET S/S PARAMETERS Time and Temperature values that
(These may be displayed control the Automatic Start/Stop op-
individually as 8 parameters (4 eration are set in this section. When
PERISH and 4 FROZEN), or 4 “TOGETHER” is selected in Configu-
parameters (with no rations, only Perishable Settings are
designation.) used.
S (PERISH / 4MINS This determines the minimum run
FROZEN) TO time for perishable/frozen setpoints
MIN RUN 60MINS in start/stop mode.
TIME:
(in 1 minute
increments)
S (PERISH / 10MINS This determines the minimum off
FROZEN) TO time for perishable/frozen setpoints
MIN OFF 90MINS in start/stop mode.
TIME:
20MINS
default
(in 1 minute
increments)
S (PERISH / 3.5°F (2°C) This defines how far away the active
FROZEN) TO temperature must be from the
OVERRIDE 18°F (10°C) setpoint before the minimum off time
TEMP: can be overridden in start/stop mode
11°F (6°C) for perishable/frozen setpoints.
default
(in 0.5 degree
increments)

35 62--10646
FUNCTIONAL
SELECTIONS DESCRIPTION
PARAMETER
S (PERISH / OFF OFF -- There is no maximum off time.
FROZEN) 10MINS
TO When a minute value is selected, this
MAX OFF
255MINS is the longest amount of time the unit
TIME:
will remain off during a (Perishable or
(in 1 minute Frozen or both) Auto Start/Stop Off
increments) Cycle. When this time expires, the
unit will restart and run for the
Minimum Run Time, regardless of
any temperature change inside the
box.
FROZEN 0°F (0°C) This only applies to Frozen Setpoints
SHUTDOWN TO in Start--Stop operation.
OFFSET: 3.6°F (2°C) This offset is the number of degrees
below setpoint that the unit will run
(in 0.1 degree before cycling off. This will allow for a
increments) lower average box temperature
when considering temperature rises
during off cycles.
TEMP RETURN AIR Indicates the number of probes utilized to
CONTROL SUPPLY AIR control system temperature. RETURN AIR is
control via a single return air probe. SUPPLY
AIR controls via two probes.
STANDARD ENGLISH The display will show temperatures &
UNITS UNITS pressures in either English (°F &
SELECT METRIC psig) or Metric (°C & Bars)
UNITS
OUT OF English Metric Once the unit is at setpoint, then
RANGE OFF OFF drifted away for more than 30
ALARM: 4°F 2°C minutes, an Out--Of--Range Alarm
5.5°F 3°C will come on. (Or, if configured for
7°F 4°C Out Of Range Shutdown, after 45
minutes the unit will shut down.) This
setting determines how far away
from setpoint the temperature must
move before the timer is started. 4°F
(2°C) may be used for very critical
temperature products, 7°F (4°C) may
be used for less critical products.
The alarm may be turned off by
selecting the OFF setting.

62--10646 36
FUNCTIONAL
SELECTIONS DESCRIPTION
PARAMETER
AIR FLOW NORMAL The Normal selection allows the unit
HIGH to cycle from High Speed to Low
Speed, depending on how close the
box temperature is to setpoint. Some
products generate a considerable
amount of heat (heat of respiration)
during transportation. This
frequently occurs with produce. The
High selection can be used for these
loads, since continuous high air flow
may be required to keep the entire
load at a constant temperature. The
engine will remain in High Speed
when High is selected. NOTE: HIGH
AIR FLOW does not work with
setpoints below +10.4°F (--12°C).
FRESH 0 -- OFF Operates in Return Air Temperature
PROTECTt 1 -- A Control only. Used to limit supply air
2 -- B temperatures. Places a flexible limit
3 -- C on how far below setpoint the SAT
4 -- D can drop while unit is operating in
5-- E Cool Mode.
AutoFresh Air 0 = CLOSED Opens and closes the air exhaust
1 = OPEN and intake ports intermediately to
XTC ONLY 2 = CFM allow the correct amount of air
CONTROL exchange.
Factory Uses values
Installed shown Closed -- AutoFresh Air Exchange is
Option below closed all the time.
Open -- AutoFresh Air Exchange is
open all the time .
CFM Control -- Uses valve selected
below to open and close air
exchange.
AutoFresh Air 5 To 50 CFM When CFM Control (Above) is
Control 25 CFM selected, this setting is used to open
and close air exchange.
XTC ONLY in 5 CFM
increments
Factory
Installed
Option
UNLOADER 0 The recommended setting for this is
PRESSURE --5 0. This setting should not be
CONTROL +5 changed unless discussed with a
Carrier Transicold Factory or Field
Service Engineer.

37 62--10646
FUNCTIONAL
SELECTIONS DESCRIPTION
PARAMETER
SLEEP MODE NO NO -- is the normal operating
YES selection.
YES-- selects Sleep Mode. In this
mode the unit will operate only as
needed to keep the engine warm,
and the battery charged. There is NO
TEMPERATURE CONTROL in
Sleep Mode.
* OVERRIDE NO NO -- allows the door switch to shut
DOOR YES the unit down whenever the trailer
SHUTDOWN door is opened and the door switch is
configured for shutdown..
YES -- allows you to over--ride the
trailer door shutdown switch, and
allow the unit to continue to run, even
with the trailer door open.
* OVERRIDE NO NO -- allows remote switch (1 and/or
REMS (1--2) YES 2) to shut the unit down whenever
SHUTDOWN trailer door is open or the switch is
turned OFF.
YES -- allows you to over--ride
remote switch (1 and/or 2), and allow
the unit to continue to run, even with
the remote switch in the OFF position
or the trailer door is open.
LANGUAGE/ ENGLISH ENGLISH-- All information displayed
IDIOMAS: SPANISH in the MessageCenter will be shown
FRENCH in English.

ESPANOL-- All information displayed


in the Message Center will be shown
in Spanish.

FRENCH-- All information displayed


in the Message Center will be shown
in French.
HIGH SPEED DELAY
(LOW SPEED START--UP)
•CONTIN-- Off or 1 to Allows user to set the
All h number b
UOUS: 255 minutes of minutes the unit will run in
low speed every time the en-
•START-- OFF or 1 to gine starts.
STOP 255 minutes
(10 min)

62--10646 38
FUNCTIONAL
SELECTIONS DESCRIPTION
PARAMETER
TIME SELECTION Allows user to set time.
•MONTH 1--12 Allows user to set time.
•DAY 1--31
•YEAR 1998--2037
Allows user to set time.
time
•HOURS 0--23
•MINS 0--59
Selections in BOLD are the factory settings.
* This Functional Parameter may not appear in the list for your unit,
depending on how the Microprocessor has been configured.

39 62--10646
OPTIONS

TWO--WAY REMOTE COMMUNICATION


Units equipped with the DataTrak software option and two--way
communication capabilities can be identified by the presence of a
Remote Monitoring Control Box and/or a large decal on the front
doors.

When working with two--way communication equipment, it is


important to understand certain terms:
Local Physically at refrigeration unit loca-
tion.
Remote Monitoring or working with the refrig-
eration unit via the internet.
Remote Monitoring Control
Box The interface between the two--way
device and the refrigeration unit.
Mode Switch This switch is located under the metal
switch guard on the front of the Re-
mote Monitoring Control Box.
Reset Switch This switch is located on the left side
of the Remote Monitoring Control
Box.
With the two--way communication equipment, the location and op-
eration of the refrigeration unit can be monitored and controlled
from any location in the world. The use of an internet site, DataTrak
software, and two--way communication equipment allows equip-
ment owners and operators to watch over the entire fleet from any
location, or from multiple locations.
Remote users can control and make changes to their refrigeration
unit’s settings. From their internet web site they are able to change
the setpoint, reset active alarms, start a defrost cycle or pretrip test,
and start or turn off the unit, regardless of the position of the
Start/Run--Off Switch.

62--10646 40
WARNING: UNITS EQUIPPED WITH REMOTE
TWO--WAY COMMUNICATION CAPABILITIES MAY
HAVE THE ABILITY TO BE STARTED OR TUNED OFF
REMOTELY EVEN IF THE START/RUN--OFF SWITCH
(SROS) IS IN THE OFF POSITION.
The unit is controlled locally and there can be no
two--way communication when the Mode Switch on
the Remote Monitoring Control Box is in
MAINTENANCE MODE. Therefore, when performing
maintenance on the unit place the Mode Switch in
MAINTENANCE MODE. After the unit is serviced,
return the Mode Switch to REMOTE ON.

Whenever a technician is working on a refrigeration unit equipped


with any two--way communication equipment, remote monitoring
should be disabled to prevent any accidental starting of the unit.

The system can be easily disabled by moving the Mode Switch on


the Remote Monitoring Control Box to the Maintenance Mode
position. The Maintenance Mode is intended to be used whenever
maintenance is being performed on the unit. While in Maintenance
Mode, the remote monitoring equipment cannot receive nor
transmit unit information.

Once the maintenance is completed, the Mode Switch should be


moved into the Remote On position. This is the normal position of
the switch. The Remote On position allows two--way
communication to and from the refrigeration unit and the remote
user.

NOTE: All units equipped with remote monitoring


equipment must have the mode switch in Remote On
position for proper operation during loading and
unloading, and while in--transit.

41 62--10646
REMOTE MONITORING CONTROL BOX

Located above the microprocessor behind the


upper roadside door on XTC units.

62--10646 42
MODE SWITCH

MAINTENANCE
MODE POSITION

MODE
SWITCH

REMOTE ON
POSITION

1. When the Mode Switch is in Maintenance


Mode, the local (on--site) technician or
operator can control the unit operation using
the Start/Run--Off Switch. The satellite
cannot control the operation of the unit with
the switch in this position.

2. When the Mode Switch is in Remote On, the


unit will run normally. However, the unit may
also be controlled (started, stopped, setpoint
changed, etc.) via two--way communication
equipment. Remote On is the normal position
for this switch.

43 62--10646
RESTART AFTER BATTERY DISCONNECT
MAINTENANCE MODE
MODE POSITION SWITCH

OFF
KEY

REMOTE MONITORING REMOTE ON


CONTROL BOX POSITION

Whenever the refrigeration unit battery is disconnected,


or the unit battery is discharged, or a service repair has
been performed on the two--way communication
system, the following procedure MUST be performed to
assure a successful restart of the two--way system:
1. Remove the 8--pin communications cable from
the Remote Monitoring Control Box.
2. Insert the OFF key (a wire jumper) between
pins 3 & 5 on the 8--pin circular connector.
3. Move the Mode Switch to the Maint. Mode
position.
4. Depress the RESET button on the side of the
Remote Monitoring Control Box for 15 sec-
onds.
5. Remove the OFF key and reconnect the con-
nector. The two--way communication system
will reboot.
6. Move the Mode Switch to the desired position.

62--10646 44
RESETTING THE CONTROL BOX

RESET SWITCH

REMOTE ON POSITION

1. Place the Mode Switch into the Remote On


position.

2. Press and hold the reset switch for 5 seconds.

45 62--10646
MOMENTARY SHUT-- OFF/KILL SWITCH

MOMENTARY SHUT DOWNLOAD


OFF SWITCH PORT
The Momentary Shut Off Switch should be used
whenever it is necessary to shut off the unit
immediately, and the unit is continuing to run,
even with the Start/Run--Off Switch in the Off
position.

1. The Momentary Shut Off Switch is typically


located next to the data Download Port behind
the Keypad door.
2. To stop the unit, press the Momentary Shut
Off Switch. The unit will immediately shut off.
Not all units with DataTrak two--way
communication are equipped with a
Momentary Shut Off Switch.

NOTE: For units equipped with DataTrak software and


two--way remote communication equipment, the
remote monitoring system must be reset before
the unit can be started again when the unit is
shut down using the Momentary Shut Off/Kill
Switch. (See instructions on page 45.)

62--10646 46
INTELLISETT
T
The Advancet Microprocessor offers over 48
parameters that may be set depending on the product
being carried.
Available with the Advance Microprocessors is the
IntelliSet Option. IntelliSet allows the owner to pre--program
specific product settings into the microprocessor and give
the settings a name. The driver may then call up these
settings by simply selecting the IntelliSet name.
For example: Apples may require continuous operation
at 35°F (1.7°C) with a defrost every 3 hours while a load of
cheese may require the same operation with setpoints
ranging from 35°F to 42°F (1.7°C to 5.6°C) and a load of
ice cream requires start/stop operation at --22°F (--30°) with
defrost at 12 hour intervals. The settings required for each
product may be entered into the microprocessor and then
locked so they cannot be changed. In the case of the
cheese, the range of setpoints may be locked, leaving the
driver the ability to change the setpoint within the locked
range.
When a load of apples is going to be picked up, the
driver simply selects “APPLES” from the IntelliSet menu;
for cheese, “CHEESE” is selected and the setpoint reset as
required; for ice cream, “ICE CREAM” is selected. With
each selection, the microprocessor automatically
re--programs the settings to provide the best temperature
control, fuel economy, and performance for that particular
product.

NOTE: Intelliset #31 is pre--programmed as “IntelliSleep”


which allows Sleep Mode (See Page 20) to be entered by
simply changing to that IntelliSet.
NOTE: The above settings are examples of possible
settings. Except for #31, IntelliSets are not factory set.
They are developed by individual customers.

47 62--10646
CURRENT INTELLISET SELECTION

35.0 34.5° F
APPLES ACTIVE

DURING START UP
Observe the MessageCenter during the Power--Up
process. If the unit is equipped with IntelliSet, the
name of the active or modified IntelliSet will be
displayed for approximately 10 seconds before
the engine starts.
DURING OPERATION
Press the = key to view current IntelliSet (Enable
IntelliSet at = Key must be configured on.) Press
either the Up or Down ARROW Key to scroll through
list of IntelliSets. The current IntelliSet will have either
the word ACTIVE or MODIFIED after it. MODIFIED
indicates that one or more of the IntelliSet settings
(other than setpoint) have been changed. To change
MODIFIED to ACTIVE, press = key while the
IntelliSet is shown in the MessageCenter.

62--10646 48
CHANGING INTELLISETS

-20.0 34.5° F
PRESS ↑ ↓ TO VIEW INTELLISETS

1. Press the = key to display current IntelliSet.


(Enable IntelliSet at = Key must be configured
on.)
2. Press the UP OR DOWN ARROW key, to move
through the IntelliSet List. The current IntelliSet
will have either ACTIVE or MODIFIED to the
right of the name.
3. To choose a different IntelliSet, bring the IntelliSet you
wish to use into the MessageCenter and press the =
Key.

49 62--10646
STOPPING UNIT

-20.0 + 3 4 .5 ° F

1. To stop the unit, place the


START/RUN-OFF switch to OFF
position.

2. If unit does not stop, see Momentary Shut--Off,


Page 49 and/or Mode Switch, Page 46.
For XTC units only: The diesel engine will stop and the
microprocessor controller will display “MICRO WILL STOP IN XX
SECONDS”. (XX is countdown of seconds while the SMV is
closing.) The Microprocessor main display and MessageCenter will
then turn off. All lights on the optional Light Bar will turn off. If the
Start/Run--Off Switch is turned to ON while this message is being
displayed, the MessageCenter continues to count down to zero.
At that point it will blank out for a few seconds to allow the controller
to reset, then power back up and proceed with the start up
messages.
All other units: The diesel engine will stop and the Microprocessor
main display and MessageCenter will then turn off. All lights on the
optional Light Bar will turn off.

62--10646 50
RECOMMENDED TRANSPORT TEMPERATURES
Below are some general recommendations on product transport
temperatures and operating modes for the unit. These are included
for reference only and should not be considered preemptive of the
set point required by the shipper or receiver.
More detailed information can be obtained from your Carrier
Transicold dealer.

Set Point Range


Product Operating Mode1
°C °F
Bananas 13 to 14 56 to 58 Continuous
Fresh fruits and
0.5 to 3 33 to 38 Continuous
vegetables
Fresh meats and Auto-Start/Stop or
--2 to 0 28 to 32
seafood Continuous
Auto-Start/Stop or
Dairy Products 0.5 to 3 33 to 38
Continuous
Ice --10 to --7 15 to 20 Auto-Start/Stop2
Frozen fruits and --23 to
--10 to 0 Auto-Start/Stop2
vegetables --18
Frozen meats and --23 to
--10 to 0 Auto-Start/Stop2
seafood --18
--29 to --20 to
Ice Cream Auto-Start/Stop2
--26 --15

1 During delivery cycles that include frequent stops and door


openings, it is recommended that the unit always be operated in the
continuous run mode to help insure product quality. If it is possible,
the unit should be turned off during the time the trailer doors are
open to help conserve the product temperature.
2 Variations may be necessary for very high or very low ambient
temperatures. 7.

51 62--10646
PRE-TRIP INSPECTION
The pre-trip inspection should be performed before picking up any
load. This inspection is essential to anticipate and help minimize the
possibility of “over-the-road” problems. These checks take only a
few minutes.
1. Place the Start/Run--Off Switch in the OFF position.
2. Fuel -- drain any water and impurities from the sump of the
refrigeration unit fuel tank by opening the drain-cock located on
the bottom of the tank (if so equipped). Close the valve when
only pure fuel emerges. Check the fuel level in the tank,
ensuring that the fuel supply is adequate for unit operation.
Refuel if necessary. Dispose of fuel properly. Don’t drain waste
fuel onto ground.
3. Belts -- Check the belt tension by depressing the belt with your
thumb, near the center of the longest free run of each belt.
Under moderate pressure each belt should deflect
approximately 1/4 inch to 1/2 inch (6 mm to 13mm). If the belts
deflect more than this they should be tightened (loose belts may
slip, generating heat and reducing belt life). If the belts are too
tight they should be loosened; tight belts can reduce bearing
life.
4. Battery -- on unit equipped with serviceable batteries, the level
of the electrolyte in each of the cells should be checked. If the
level is low, distilled water should be added to the correct level.
Most units, however, are equipped with low or no-maintenance
batteries; these should be inspected to ensure that the
connections are clean and tight, and the battery hold-down
should be checked for tightness.
5. Engine Oil -- the engine oil should be checked last since it is
necessary for oil to drain down from the block and into the oil
pan to obtain a correct reading. Unscrew and remove the
dipstick. Wipe the dipstick clean and insert it into the oil fill tube
without threading it all the way back into the tube. Remove the
dipstick again and check oil level. DO NOT add oil if the level
is in the “safe” range. If needed, add oil as indicated by markings
on dipstick until level is in the “safe” range. (See page 60)

62--10646 52
6. Over-all Unit -- visually inspect the entire unit for leaks, loose
bolts, frayed, loose, or broken wires, etc. The
radiator/condenser coils of the unit should be free of dirt,
insects, cardboard, or any other debris that may obstruct
airflow across the coils. The evaporator (located inside the
trailer) should be free of debris also, especially stretch-wrap,
which is often used during transport to prevent cargo shifting.
7. Start a Pretrip Check (See Page 12).

53 62--10646
PRODUCT LOADING
BEFORE LOADING:
D Pre-cool the trailer. This will remove much of the heat from the
inside of the trailer, and give the product better protection when
it is loaded.
D If possible, Place the unit in a defrost cycle immediately before
loading. This
will remove moisture accumulated on the evaporator coil.
DURING LOADING:
D Place the Start/Run--Off Switch in the Off position.
D Check product temperature during loading.
D Ensure that the air return and supply opening remain
unobstructed.
D Leave approximately 4 to 5 inches (100 to 125 mm) between the
load and the front wall for air return to the unit.
D Leave at least 10 to 12 inches (250 to 300 mm) between the top
of the load and the ceiling to ensure that there is nothing to
prevent airflow to the rear of the body
D Load product on pallets to provide free air return to unit and
improve product protection.
Proper air circulation in the trailer, air that can move around and
through the load, is a critical element in maintaining product quality
during transport. If air cannot circulate completely around the load,
hot spots or top-freeze can occur.
The use of pallets is highly recommended. Pallets, when loaded so
air can flow freely through the pallets to return to the evaporator, help
protect the product from heat passing through the floor of the trailer.
When using pallets, it is important to refrain from stacking extra boxes
on the floor at the rear of the trailer as this will cut off the airflow.

62--10646 54
Product stacking is another important factor in protecting the
product. Products that generate heat -- fruits and vegetables, for
example -- should be stacked so the air can flow through the product
to remove the heat; this is called “air stacking” the product.
Products that do not create heat -- meats and frozen products --
should be stacked tightly in the center of the trailer. All products
should be kept away from the side-walls of the body, to allow air flow
between the body and the load; this prevents heat filtering through
the walls from affecting the product.
It is important to check the temperature of the product being loaded
to ensure that it is at the correct temperature for transport. The
refrigeration unit is designed to maintain the temperature of the
product at the temperature at which it was loaded; it was not
designed to cool warm product.

55 62--10646
PROBLEMS
Everything possible has been done to ensure that your unit is the
most reliable, trouble-free equipment available today. If, however
you run into problems the following section may be of assistance.
If you do not find the trouble that you have experienced listed,
please call your Carrier Transicold dealer for assistance.

General Problems
Unit won’t crank. Check battery condition.
Check battery connections.
Check all fuses
Unit won’t start. Check fuel level.
Check all fuses
Unit won’t run. Check fuel level.
Check engine oil level.
Check all fuses
Unit stops operating. Check belts.
Check engine oil level.
Check coolant level.
Check fuel level.
Check all fuses.
Unit not cooling properly. Defrost unit.
Check evaporator for airflow restriction.
Check condenser for airflow restriction.
Check body for damage or air leaks.

62--10646 56
FUSES

The fuses that protect the circuits of the Microprocessor control


system are located in the control box on the roadside of the unit.
They may be accessed by loosening the screws that hold the
control panel closed.

F4 RUN RELAY

F3 SPEED RELAY
F5

AutoFresh RELAY
F2

F10

CLUTCH
RELAY F8

PC
CARD F6
SLOT

F7

F1

62--10646 58
Fuse Purpose Amps
F1 Microprocessor Fuse 7.5A
F2 Speed Control Solenoid 10A
F3 Fuel Solenoid / Fuel Pump 7.5A
F4 Evap Fan Clutch 7.5A
Glow Plug, Control Circuit &
F5 80A
Starter Solenoid
F6 Buzzer, SV1 to SV4 & Unloaders 15A
F7 Micro, Glow & Crank 5A
F8 Fuel Heater (Option) 20A
Light Bar
F9 (Located in Engine Harness 3A
Outside of Control Box)
AutoFresh
F10 (Located in Engine Harness) 40A
Option on XTC

59 62--10646
UNIT MAINTENANCE 8.

Engine oil -- the oils recommended for use in your refrigeration unit
must comply with the American Petroleum Institute’s (API) CI or
higher rating. The use of any oil that does not meet this rating may
affect the warranty on the engine in the unit. The use of oil of the
proper weight (viscosity) is also essential. The following chart
indicates the SAE Weight Rating of the oil to be used in various
climates:

°F
- 20 - 10 0 10 20 30 40 50 60 70 80 90 100
30W, 10W-30, or 15W--40
10W-30, or 15W--40
10W--20, or
5W--30
°C
- 28 - 23 - 17 12 - 7 - 1 - 4 10 16° 21 27 32 38
30W, 10W-30, or 15W--40
10W-30, or 15W--40
10W--20, or
5W--30
The following oils are approved for use in the unit:
(API) class CI or higher or
Mobil Delvac 1 (synthetic)
Cap To check the engine oil level: Run the
Dipstick unit to bring the engine up to operating
temperature, shut the unit off, and remove
the cap/dipstick. Wipe the dipstick clean
and insert it into the oil fill tube without
threading it all the way back into the tube.
Remove the dipstick again and check oil
level. DO NOT add oil if the level is in the
“safe” range. If needed, add oil as
indicated by markings on dipstick until
level is in the “safe” range.

SAFE 1 2 QTS
DIPSTICK

62--10646 60
UNIT MAINTENANCE SCHEDULE
For the most reliable operation and for maximum life, your unit
requires regular maintenance. This includes oil and filter changes,
fuel and air filter replacement, coolant replacement. Maintenance
should be performed on the following schedule:

SERVICE
D Prior to S/N JAB90602792 drain the engine
oil, replace oil filter and by-pass filter (if so
equipped).*
Every 2000 Hours D Beginning with S/N JAB90602792 drain 2--3
oz. of fuel off bottom of filter in order to re-
or 1 year move water and sediment.
D Check engine cooling system using re-
fractometer --P/N 07--00435--00.
D Check air cleaner.
D Check all bolts, screws and unit mounting
bolts for tightness. Tighten as required.
D Check all belts.
D Clean fuel pump filter.
D Check battery terminals and fluid level.
D Check compressor oil level.
D Check alternator brushes.
D Check engine thermostat.
D Check defrost:
-- Check defrost air switch calibration
-- Check timer setting and function
-- Check refrigerant control valves
-- Defrost ends automatically
-- Water drains from evaporator
D Clean radiator/condenser.
D Check engine speed under load
D Pre--Trip Inspection.

61 62--10646
SERVICE
Every 3000 Hours D Beginning with S/N JAB90602792 drain the
(In addition to 2000 engine oil, replace ESI oil filter.*
Hour list above) D Beginning with S/N JAB90602792 replace
ESI fuel filter. ***
D Check alternator.
D Clean and adjust fuel injectors.
D Clean crankcase breather.
D Pre--Trip Inspection.
Every 6000 hours D Change anti-freeze. **
(In addition to 2000 D Check and adjust rocker arms.
and 3000 Hour list D Pre--Trip Inspection.
above.
*Units lubricated with synthetic oil (Mobil Delvac 1) and equipped
with a bypass filter require an oil change every 4000 hours or 2
years, without a bypass filter -- 3000 hours or 2 years. New oil filters
are required at 1 year intervals
**12,000 hours with Texaco (Havoline) extended life coolant.
***Beginning with S/N JAB90602792 the ESI oil filters are good for
2 years or 4000 hours.

These maintenance schedules are based on the use of approved


oils and regular Pre-Trip inspections of the unit. Failure to follow the
recommended maintenance schedule may affect the life and
reliability of the refrigeration unit.
In addition to the above service requirements please adhere to the
following:
S Non--synthetic engine oil should be changed at least once
a year and synthetic engine oil should be changed at least
once every 2 years, even if the engine has not run the
necessary number of hours.

S Standard coolant should be replaced every two years.


Extended life coolant should be replaced every five years.
A more detailed description of service requirements and
procedures can be found in the Service and Operations Manual for
your unit. This manual may be obtained from any Carrier Transicold
dealer.

62--10646 62
PRIMING FUEL SYSTEM
The mechanical fuel lift pump is mounted on the engine next to the
injection pump. This pump has a manual plunger for priming the fuel
system when the fuel tank has been run dry.
To prime the fuel system, use the following steps:
1. Turn the bleed valve (Red) counter-clockwise until fully
opened.
2. Turn the top of the manual fuel pump plunger
counter-clockwise to unlock it. S--L--O--W--L--Y (up/down once
per second) pump the manual plunger until positive pressure
(resistance) is felt. This may take up to 200 strokes. This will
indicate fuel flow.
3. Continue to pump S--L--O--W--L--Y (up/down once per second)
approximately 100 more strokes to fill the filter and bleed the air
out of the lines.
4. Start engine. It may be necessary to continue to pump until the
engine starts.
5. Depress and turn the top of the manual plunger clockwise to
lock in place.
6. When engine is running smoothly, turn bleed valve clockwise
until fully closed.

Red
Fuel Bleed
Valve

Manual
Fuel Pump
Plunger

63 62--10646
EMERGENCY ROAD SERVICE
At Carrier Transicold we’re working hard to give you complete
service when and where you need it. That means a worldwide
network of dealers that offer 24-hour emergency service. These
service centers are manned by factory trained service personnel
and backed by extensive parts inventories that will assure you of
prompt repair.
Should you experience a unit problem with your refrigeration unit
during transit, follow your company’s emergency procedure or
contact the nearest Carrier Transicold service center. Consult the
Shortstop Service Centers directory to locate the service center
nearest you. This directory may be obtained from your Carrier
Transicold dealer.
S If you are unable to reach a service center,
call our 24-hour Action Line: (800)448-1661
When calling, please have the following information ready for
fastest service:
S Your name, the name of your company, and your location.

S A telephone number where you can be called back.

S Refrigeration unit model number and serial number.

S Box temperature, set point and product.


Brief description of the problem you are having, and what you have
already done to correct the problem.
We will do everything we can to get your problem taken care of and
get you back on the road.

62--10646 64
Index

A I
Alarm List -- View Alarms, 26 IntelliSet, 47
Alarms & Default Messages,
27
M
Manual Defrost, 22
C Manual Start (Glow & Crank),
10
Changing IntelliSets, 49
Mode Switch, 43
Changing Setpoint, 14
Momentary Shut Off Switch,
Continuous Run Operation, 46
18
Current IntelliSet Selection,
48 P
Pre--Trip Inspection, 52

D Pretrip, 12
Priming Fuel System, 63
DataTrak Satellite Operation, Problems, 56
40
Product Loading, 54

E R
Emergency Road Service, 64 Recommended Transport
Temperatures, 51
Remote Monitoring Control
F Box, 42
Resetting The Control Box,
Functional Change (Parame- 45
ters), 34
Restart After Battery Discon-
Fuses, 58 nect, 44

Index -1
Index
S T
Trip Start, 24
Safety, 6

Sleep Mode, 20 U
Software, 2 Unit Data, 30
Unit Identification, 4
Start--Stop Operation, 16
Unit Maintenance, 60
Starting Unit -- Auto, 8 Unit Maintenance Schedule,
61
Stopping Unit, 50 Unit Operation, 8

Index -2
CALIFORNIA
Proposition 65 Warning
Diesel engine exhaust and some of its
constituents are known to the State
of California to cause cancer, birth defects,
and other reproductive harm.

North America Central America


Carrier Transicold and Mexico
700 Olympic Drive Ejercito Nacional No. 418 Carrier Transicold Division,
Athens, GA 30601 USA Piso 9, Torre Yumal Carrier Corporation
Tel: 1--706--546--6469 Col. Chapultepec Morales Truck/Trailer Products Group
Fax: 1--706--546--5207 11570 Mexico, D.F. P.O. Box 4805
Tel: (5255) 9126.0300 Syracuse, N.Y. 13221 U.S A
Fax: (5255) 9126.0373
www.carrier.transicold.com

A member of the United Technologies Corporation family. Stock symbol UTX


2005 Carrier Corporation D Printed in U. S. A. 0505

You might also like