No. 6LP: Instructions For Pipeline Dew Point Detector Tube
No. 6LP: Instructions For Pipeline Dew Point Detector Tube
Instructions for Temperature: Since temperatures affect the tube, multiply the correction factor by the tube reading.
No. 6LP Pipeline Dew Point Detector Tube Temperature C (F) 0(32) 5(41) 10(50) 15(59) 20(68) 25(77) 30(86) 35(95) 40(104)
Correction Factor 1.0 1.0 1.0 1.0 1.0 0.98 0.95 0.93 0.9
FOR SAFE OPERATION:
Carefully read this manual and the instruction manual of your Gastec Gas Sampling Pump.
WARNING: Pressure: To correct for pressure, use the formula below:
1. Use only Gastec detector tubes in a Gastec pump. Tube Reading (LB/MMCF) ×1013 (hPa)
2. Do not interchange or use non-Gastec parts or components in Gastec's detector tube and pump system. Atmospheric Pressure (hPa)
3. Using non-Gastec parts or components in Gastec's detector tube and pump system or using a non-Gastec
detector tube with a Gastec pump or using a Gastec detector tube with a non-Gastec pump may damage your MEASUREMENT PROCEDURE:
detector tube and pump system, or may cause serious injuries, or death to the end-user. It will also void all
warranties, and guarantees regarding performance and data accuracy. CAUTION: Since Tube 6LP is highly sensitive to ambient humidity, you must be
very careful when operating the tube.
CAUTION: If you do not observe the following precautions, you may suffer ① Do not leave the tube exposed to air more than 10 seconds after breaking off the tips.
injuries or damage the product. ② Immediately place the tube into the sampling site. If some stains are observed prior to sampling,
1. When breaking the tube ends, keep away from eyes. the tube must discarded and replace by a new one.
2. Do not touch the broken glass tubes, broken pieces and reagent with bare hand(s). 1. To check the pump for leakage, insert a fresh, sealed detector tube into the pump. Follow the instructions
3. The sampling time represents the time necessary to draw the air sample through the tube. The tube must be provided with the pump operating manual.
positioned in the desired sampling area for the entire sampling time or until the flow finish indicator indicates 2. The Gastec Detector Tube No. 6LP is highly sensitive to ambient humidity. Be very careful when breaking off
the end of the sampling. the tips for sampling.
3. Break off the tip at the top end of a fresh detector tube using the tube tip breaker in the pump.
NOTES: For maintaining performance and reliability of the test results, observe 4. Insert the tube immediately into the pump inlet with the arrow ( ) on the tube pointing toward the pump.
the following. Then, immediately break off the bottom end tip and position the tube and pump toward the sampling site.
1. Use Gastec Gas Sampling Pump together with Gastec Detector Tubes only for the purposes specified in the Please note that once the tube is stained around the zero mark, the tube cannot be used for detecting the Pipe
instruction manual of the detector tube. Line Dew Point.
2. Use this tube within the temperature range of 0 - 40°C (32 - 104°F). 5. Pull the handle all the way out until it locks at the 1 pump stroke (100mL). Wait 1.5 minutes.
3. This tube may be interfered with by the coexisting gases. Please refer to the table “INTERFERENCES” below. 6. For measurements higher than 40 LB/MMCF, prepare a fresh tube, then pull a half pump stroke.
4. The shelf life and storage condition of the tube are marked on the label of the tube box. 7. Immediately after the sampling, read the concentration at the interface of the stained-to-unstained reagent .
8. If necessary, multiply the readings by the correction factors of the temperature, pump strokes and atmospheric
APPLICATION OF THE TUBE: This tube is limited to measuring the humidity in a natural pressure respectively.
gas pipeline.
INTERFERENCES:
SPECIFICATION: (Because of Gastec's commitment to continued improvement, Substance Concentration Interference Interference gas only
specifications are subject to change without notice.) Sulphur dioxide ≦15 ppm No No discolouration
Nitrogen dioxide, Hydrogen sulphide ≦30 ppm No No discolouration
Hydrogen cyanide ≦45 ppm No No discolouration
Methyl ethyl ketone ≦70 ppm No No discolouration
Detecting Layer Ethyl acetate ≦100 ppm No No discolouration
Acrylonitrile ≦55 ppm No No discolouration
Measuring Range 3 - 40 LB/MMCF 40 - 100 LB/MMCF Acetaldehyde ≦50 ppm No No discolouration
Methanol ≧100 ppm + Green
Number of Pump Strokes 1 1/2 Triethylene glycol No No discolouration
Stroke Correction Factor 1 2.5 This table of interference gases primarily expresses the interference of each coexisting gas in the
Sampling Time 1.5 minutes 45 seconds concentration range, that is equivalent to the gas concentration. Therefore, the test result may show positive
results due to other substances not listed in the table. If more information is needed, please contact us or our
Detecting Limit 2 LB/MMCF ( n = 1 ) distributors in your territory.
Colour Change Yellow→ Greenish purple
INSTRUCTIONS ON DISPOSAL: The reagent of the tube does not use toxic substances. When
Reaction Principle H2O+ Mg(CIO4) 2 → Mg(CIO4)2・H2O disposing the tube regardless of whether it has been used or not, follow the rules and regulations of your local
*May become purple with high humidity. government.
** LB/MMCF stands for pound per million cubic feet. 1 mg/L corresponds to 62.3. WARRANTY: If you have any questions regarding gas detection and the quality of the tubes, please feel free
Coefficient of Variation: 10% (for 3 to 10 LB/MMCF), 5 % (for 10 to 40 LB/MMCF) to contact your Gastec representatives.
** Shelf Life: Please refer to the validity date printed on the tube box.
** Store the tubes in a dark and cool place.