Iastructe Crossfall Newsletter 31-01-20231675188723
Iastructe Crossfall Newsletter 31-01-20231675188723
NEWSLETTER
A PUBLICATION OF INDIAN ASSOCIATION OF STRUCTURAL ENGINEERS
Volume : 1 Issue : 2 October – December, 2022
REPORT No. CF - 05
1. Introduction
Mechanically Stabilized Earth (MSE) or Reinforced Soil structures are composite structures consisting of
alternating layers of compacted backll and soil reinforcement elements that are xed to a facing. The
stability of MSE structures is derived from the interaction between the backll and soil reinforcements,
involving friction and tension. The facing is relatively thin and is intended to perform the primary
function of preventing erosion of the structural backll. The signicant relative cost saving that can be
realized when this system is used compared to traditional RCC retaining structures, combined with
ease of construction has resulted in widespread adoption of this technology in India and around the
world.
The standards to be followed for the design of reinforced soil walls and slopes nd mention in Clause 3100
of the Ministry of Road Transport & Highways (MoRT&H) Specications for Road & Bridge Works (5th
Revision) as well as IRC: SP 102-2014. MoRT&H Clause 3100 allows for the design to be done as per BS
8006:2010 as well as FHWA-NHI-0024. Since BS 8006:2010 does not cover the design checks to be carried
out in seismic conditions, the general design approach involves conducting the design checks for the static
case as per BS 8006 while the design checks for the seismic case are carried out as per the Mononobe-Okabe
pseudo-static approach presented in FHWA-NHI-10-024.
MSE structures designed by adopting this design approach have been found to perform satisfactorily
when subjected to static and seismic loading conditions provided that recommended practices are
adopted during their construction.
In most MSE systems with fascia panels, the reinforcing elements are connected to the MSE facing by
means of a mechanical connection. Depending on the extensibility of the reinforcing element, the type of
facing element, and the position of the mechanical connection along the height of the MSE structure, the
load on the connection varies from 75% to 100% of the maximum tensile force to be resisted by the
corresponding reinforcing layer.
Hence, the mechanical connection is one of the most critical components in an MSE system that has to be
designed to accommodate the anticipated connection loads. Recent experiences suggest that incorrectly
designed mechanical connections were the fundamental reason for the failure of several MSE structures in
India.
This report presents case studies of unsatisfactory performance of some MSE structures with failure
resulting primarily due to decient connection performance.
2. Case Studies
2.1. Case Study No. 1 : (Ref. Fig.1)
System : Geogrid with Concrete Panels
Probable reasons for Failure:
• Primary Cause:
• Connection failure, poor connection system and design
• Other added factors
• inadequate detailing
• Drainage criteria not examined
• Poor construction quality
Fig. 1 : Failure of MSE Wall for Case Study
2.2. Case Study No. 2 : (Refer Fig. 2)
System Adopted: Polymeric strap + Toggle and loop steel connector
Probable reasons for failure:
• Connection failure
• Corrosion at connection
• Can be either poor quality of galvanization or aggressive backll
• Collapsed after 15 years- Long term durability issue
3. Lessons Learnt :
The primary cause for the failure, generally termed as "Loss of
Fascia", in majority of failed MSE walls is poor connection
system with other contributory reasons such as poor quality of
work, lack of detailing, and inadequate design. Only a few Fig. 3 : Failure of MSE Wall due to connection
examples are presented here. More focus needs to be given to
the connection system and the long-term performance of the connectors.
The connection design of MSE systems is a critical aspect of MSE structure design and is also observed to be
the most overlooked in terms of testing. Rigorous connection testing, through reputed institutes like CRRI
and IITs, combined with the development of a comprehensive database of connection failures and forensic
study ndings is very crucial in enhancing understanding of the mechanics at play which can in turn result
in scientically backed stipulations in Indian codes.
The other important topic is the long-term durability of the connection system, which is generally
neglected. This is critical with the use of steel components in any connection system. All steel components
must be hot dip galvanized if they are exposed to the backll. The electrochemical properties of the backll
must be in compliance with the specication.
REPORT No. CF - 06
c) As per the provisions of National Building Code -2016, physical inspection for buildings mentioned
in clause 12.2.5.1 needs to be performed every 3 to 5 years and documented for future use and record.
However, building owners are not following the same for want of a regulation mechanism. Some
building owners/associations are unable to follow the guidelines as mentioned in the National
Building Code-2016 of conducting periodical physical inspection as they do not have in their
possession copies of the structural drawings. Structural drawings are important for performing the
detailed structural safety checks. Non-implementation of this provision of NBC-2016 compromises
the safety of the buildings & its occupants as important safety checks may not be performed
adequately.
NOTE : It is applicable for buildings which are 15 m or more in height and for special buildings like
educational, assembly, institutional, business, mercantile, industrial, storage and hazardous and mixed
occupancies having a covered area of more than 500 sqm.
2.1. Basement:
(a) There has evidence of some basement roof beams being supported by fabricated steel supports to
have been installed post-construction of the concrete members. As per the owners these steel
supports existed in the building since the day, they occupied the building.
(b) There is evidence of a concrete core-cut sample to have been taken from one beam, probably for
testing the concrete strength of the beam. The date when this concrete core-cut sample has been
extracted could not be ascertained.
(i) Ascertain the concrete strength of the oor slab by extracting a concrete core-cut cylinder from the
oor slab in the area showing structural distress (cracks) and testing the same in presence of
witnesses representing the residents in an accredited concrete test laboratory.
(ii) One of the two things will happen when testing personnel from the concrete test laboratory come to
the site to extract the concrete core from the oor slab. Either they will be successful in extracting a
concrete cylinder core using the core cutting machine that they will bring along, in which case the
prepared concrete cylinder should be tested using the prescribed Indian Standard procedure by
applying a gradually increasing load until the point of failure which would determine that existing
concrete compressive strength. The second scenario can be that when the concrete core cut is being
attempted the concrete will just crumble and dissipate implying the testing team will not be
successful in extracting the concrete cylinder from the oor slab for further laboratory testing. In this,
case it should be inferred that the RCC Floor Slab has a negligible residual load carrying capacity
unless further tests/checks prove otherwise. The building containing this oor slab should be
considered unsafe as the weak oor slab/s can potentially fail/collapse under service loads.
Occupants should vacate and the distressed oor/is s propped with steel supports from below. The
paperwork along with photographs should be reported to the concerned authorities for further
action.
(d) A detailed chemical analysis of existing pieces of concrete will determine the extent of carbonation of
concrete if the concrete has been exposed to chloride or sulphate attack or Alkali-Silica/Alkali-
Carbonate reaction amongst many others that can accelerate the deterioration in concrete.
3. Recommendations
(a) Urgent and immediate Non-Destructive Test (within one week of issue of this report) for the oor
slabs showing structural distress were recommended. The concrete strength of the oor slab should
be ascertained by extracting a concrete core-cut cylinder from the oor slab in the area showing
structural distress (cracks) and testing the same in presence of witnesses representing the residents in
an NABL accredited laboratory.
(b) In the event the concrete just crumbles and dissipates while the concrete core-cut is being attempted
on the oor slab, implying that the testing team is not successful in extracting the concrete core-cut
cylinder from the oor slab for further laboratory testing. In this case, it should be inferred that the
RCC Floor Slab has a negligible residual load carrying capacity unless further tests/checks prove
otherwise. The building containing this oor slab should be considered unsafe as the weak oor
slab/s can potentially fail/collapse under service loads. Occupants should vacate and the distressed
oor/s be propped with steel supports from below. The paperwork along with photographs should
be reported to the concerned authorities for further action.
(c) The engineer had visited only three ats of many that exist in the building. The same or similar
structural vulnerability may be existing in many other areas/ats. Resident Welfare Association
should get all the ats inspected and record the areas that are showing similar signs of structural
distress by taking photographs and reporting the same to the concerned authorities.
(d) The Resident Welfare Association should order a comprehensive structural investigation of the
building as explained in this report. For a comprehensive structural audit to take place the
Resident Welfare Association will need to obtain all the structural drawings from the concerned
authorities.
Fig. 1 : Some basement beams are supported by Fig. 4 : Indoor view of ground oor at
fabricated steel columns.
Fig. 2 : Side view of the steel column supporting Fig. 5 : visible cracks on the roof slab
the basement beam.
Fig. 3 : Concrete Core cut sample has been taken from Fig. 6 : Indoor view of ground oor at
basement beam.
REPORT No. CF - 07
Poor Detailing causes Severe Corrosion in
Steel Piers of a Flyover
The reporter, in this case, is a structural engineer who has reported severe corrosion in the Steel Pier Base
Plate of an existing yover in one of the busiest metro cities, located in a very busy road crossing.
2. The Problem:
It is a case of a serious level of corrosion in the gridded Base Plate of steel box type pier. The probable cause
of corrosion is the poor detailing of the steel pier. There was no provision kept for drainage of any seepage
water from inside the box-type steel piers. Fig. 2 below shows some photographs from inside the pier.
3. The Diagnosis:
Faulty detailing in the gridded portion in the base plate is the cause that leads to retention of the water that
percolated inside the pier box section through gaps at the end of the different splice joints. It is obvious that
while fabricating pier base using steel plates to form grids, a number of separated compartments will form.
Unless some drainage slots/openings are left at the bottom corner of each plate and also in the main plates
(4 sides), percolated water will automatically get accumulated inside the pier box.
REPORT No. CF - 08
There is, however, another avoidable common reason i.e., the unsafe conditions created around the
structures, some of which are man-made and often deliberate.
a. instances of damage caused due to the growth of greens on the structure, (Fig. 1 to 4)
b. informal settlers using the underside of the bridge as their habitat unimpeded, (Fig. 5 & 6)
c. use of the underside of the structure for residential, commercial and industrial purposes, ofcially
sanctioned by the authorities, (Fig. 7 to 9)
d. instances where the design and detailing of structure does not permit essential maintenance work to
be done because of a lack of access to such location. (Fig. 10 to 14)
A. Instances of damage caused due to the growth of greens on the structure-plants have caused
corrosion and spalling of concrete cover.
Fig. 1 Fig. 2
Fig. 3 Fig. 4
B. Informal settler used the underside of the bridge without any interference - leading to severe
damages
Fig. 5 Fig. 6
C. Use the underside of the structure for residential, commercial and industrial purposes, with
ofcial sanction - leading to permanent damage
Fig. 7 Fig. 8
Fig. 9
D. Instances where the design and detailing of structure do not permit essential maintenance work to
be done because of a lack of access to such location
Case 1 : Bridge across electried railway tracks does not permit any inspection & maintenance work
to be done- corrosion started due to lack of concrete ow due to congestion of Rods/PSC wires
Fig. 10 Fig. 11
Fig. 12
Case 2 : No access to underside of bridge left damages unnoticed leading to catastrophic failure of
poorly designed gussets.
Fig. 13 Fig. 14
2. Lessons Learnt:
It is essential that the statutory responsibility for avoidance of such damage is assigned to the authorities
in-charge and their designers. The designers should be made responsible for the preparation of the
maintenance manual with a specic schedule for undertaking inspection and recommended corrective
procedures/ rehabilitation work. Access to all parts of the bridge should be ensured during the design
stage and provisions for the same must be kept. Owner agencies should carry out regular inspections and
maintenance.
Fantastic initiative. Kindly let me include in the This is a fantastic effort. Kudos to you and your team. All
circulation list. In turn, I will attempt to report a few the best.
failures that I have witnessed and studied in -Prof. Prem Krishna
Buildings Segment. If there is a subscription let me Retd. Professor, IIT, Roorkee
know.
- Mr Girish Dravid Congratulations and thanks for 1st inaugural issue of
Director, Sterling Engineering Consultancy Services CROSFALL.
- Er. Rajesh Gangwar
Consulting Engineers
This is an excellent initiative Mr. Alok. Hearty
compliments to you & team. It's very essential for the
This is very good. Congratulations for coming out with
fraternity.
such a publication.
– Mr. Ramachandra V.
- Mr Deepak Singh
Head – Tech Services, UltraTech Cements
Lead DRM Specialist at World Bank
Congratulations to CROSFALL! Very interesting and Many practical aspects and details are being explained
helpful. by experts with condence, these aspects are not
available in a single book and most of the civil
I just came back from a 6 months sabbatical named
Engineering professional may not have heard of all the
“building in Africa”. We drove by car from Cape Town
issues discussed in this program. Wonderful, keep it up.
to Cairo. Now I need to get started here again but I will
May God Bless you and you keep on serving the
keep my eyes open regarding your request.
fraternity. Regards. Jai Hind.
- Dr. Mike Schlaich
-Mr. I. J. Ghai
Partner at Schlaich Bergermann Partner
Consulting Engineers Associates (C.E.A.)
This is a commendable initiative, Er. Alok Bhowmick Ji. Many thanks for sharing this Newsletter. This is an
Hearty congratulations on this maiden issue. excellent imitative! Well done.
- Er. H.R. Girish, - Ms Henrike Brecht
Chairman, ICI-Bengaluru Centre Senior DRM Specialist, World Bank
Disclaimer :
The objective of this newsletter is to help professionals to make structures safer. This is achieved by publishing information about failures, based
on the condential reports received by IAStructE and information available in the public domain. IAStructE can not be held liable for the
veracity of the information given by the reporter. As this document is based on the Condential reporting system, the reporter's name and
identity as well as the project name, location and identity will not be divulged under any circumstances. Expert Panel opinions given in this
document are those of the group of individual experts in the eld and not that of the association. IAStructE cannot be held liable for the opinions
expressed herein. This newsletter is intended for those who will evaluate the signicance and limitations of its contents and take responsibility
for its use and application. No liability (including negligence) for any loss resulting from opinions/informations given in this newsletter is
accepted.