Fdci221, Fdcio221 Technical Manual
Fdci221, Fdcio221 Technical Manual
Input module,
input/output module
Technical Manual
Legal notice
Technical specifications and availability subject to change without notice.
© 2008-2012 Copyright by Siemens Switzerland Ltd
Issued by:
Siemens Switzerland Ltd.
Infrastructure & Cities Sector
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41 724-2424
www.siemens.com/buildingtechnologies
Edition: 2012-09-30
Document ID: A6V10211122_j_en_--
2
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Table of contents
3
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
5 Mounting / Installation .....................................................................................35
5.1 Installation without housing ................................................................................35
5.2 Installation with housing .....................................................................................36
5.3 Connecting the module ......................................................................................37
6 Commissioning.................................................................................................38
7 Maintenance / troubleshooting .......................................................................39
7.1 Performance check.............................................................................................39
7.2 Test mode...........................................................................................................39
7.3 Localization mode...............................................................................................39
7.4 Remedying faults................................................................................................39
8 Specifications ...................................................................................................40
8.1 Technical data ....................................................................................................40
8.2 Dimensions.........................................................................................................42
8.3 Environmental compatibility and disposal ..........................................................43
9 Annex.................................................................................................................44
9.1 Configuration sheet ............................................................................................44
Index ............................................................................................................................45
4
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
About this document
Applicable documents
1
Scope
The document is valid for the following modules:
Input module FDCI221
Input/output module FDCIO221
Target groups
The information in this document is intended for the following target groups:
Product Manager Is responsible for information Has obtained suitable specialist training for the
passing between the function and for the products.
manufacturer and regional Has attended the training courses for Product
company. Managers.
Coordinates the flow of
information between the
individual groups of people
involved in a project.
Project Manager Coordinates the deployment of Has obtained suitable specialist training for the
all persons and resources function and for the products.
involved in the project Has attended the training courses for Project
according to schedule. Managers.
Provides the information
required to run the project.
Project engineer Sets parameters for product Has obtained suitable specialist training for the
depending on specific national function and for the products.
and/or customer requirements. Has attended the training courses for Product
Checks operability and Engineer.
approves the product for
commissioning at the place of
installation.
Is responsible for
troubleshooting.
Installation personnel Assembles and installs the Has received specialist training in the area of
product components at the building installation technology or electrical
place of installation. installations.
Carries out a performance
check following installation.
Maintenance personnel Carries out all maintenance Has obtained suitable specialist training for the
work. function and for the products.
Checks that the products are in
perfect working order.
Searches for and corrects
malfunctions.
5
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
About this document
1 Applicable documents
Document identification
The document ID is structured as follows:
ID code Examples
ID_ModificationIndex_Language_COUNTRY A6V10215123_a_de_DE
-- = multilingual or international A6V10215123_a_en_--
A6V10315123_a_--_--
The 'i' symbol identifies supplementary information and tips for an easier way of
working.
6
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
About this document
Technical terms
1
ES Product version
FET Field Effect Transistor
LED Light-emitting diode
FDnet/C-NET Addressed detector line
NC Contact: Opener (normally closed)
NO Contact: NO (normally open)
The first edition of a language version or a country variant may for example have
the modification index 'd' instead of 'a' if the reference document already has this
modification index.
7
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
About this document
1 History of changes
The table below shows the published language versions with the corresponding
modification index:
j X X X X X
i X X X X X
h X X X X X
g X X X X X
f X X X X X
e X X – – –
d X X – – –
c X X X X X
b X X X X X
a X X X X X
X = published
– = no publication with this modification index
8
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Safety
Safety instructions
2
2 Safety
Battery Heat
Signal word
The signal word classifies the danger as defined in the following table:
DANGER DANGER identifies a dangerous situation, which will result directly in death or serious injury
if you do not avoid this situation.
WARNING WARNING identifies a dangerous situation, which may result in death or serious injury if
you do not avoid this situation.
CAUTION CAUTION identifies a dangerous situation, which could result in slight to moderately serious
injury if you do not avoid this situation.
NOTICE NOTICE identifies possible damage to property that may result from non-observance.
9
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Safety
2 Safety instructions
WARNING
NOTICE
10
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Safety
Safety regulations for the method of operation
2
Electrical installations
WARNING
Electrical voltage
Electric shock
● Work on electrical installations may only be carried out by qualified
electricians or by instructed persons working under the guidance and
supervision of a qualified electrician, in accordance with the electrotechnical
regulations.
Wherever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
Lock volt-free areas to prevent them being switched back on again by mistake.
Label the connection terminals with external external voltage using a
'DANGER External voltage' sign.
Route mains connections to products separately and fuse them with their own,
clearly marked fuse.
Fit an easily accessible disconnecting device in accordance with IEC 60950-1
outside the installation.
Produce earthing as stated in local safety regulations.
11
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Safety
2 Safety regulations for the method of operation
12
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Safety
Standards and directives complied with
2
WARNING
NOTICE
13
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Release Notes
Properties
Communication via the detector line
Configuration options
Built-in line separator
Status indicators (LED)
Different mounting options
Monitored input
FDCIO221: The following configurations are possible with jumpers:
– Bistabile, switched voltage, monitored or non-monitored (external DC 24 V
supply required)
– Potential-free output
14
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Details for ordering
3
The housing FDCH221 is available for fitting the module outside an electric
cabinet. The housing protects the module from dust and dampness and increases
protection.
Housing FDCH221
15
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Product version ES
ES
Example of a packaging label with details of the product version
04
ES
Depending on the product and various approvals, the product labels may differ in
terms of the information type and layout.
Look for your device's order number on the product label.
You will find the product version after the order number.
16
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Setup
3
3.3 Setup
The modules consist of the module carrier, the printed circuit board and the cover
cap. The printed circuit board includes the LEDs. These indicate the status of the
input, output and localization mode. The cover cap of the printed circuit board is
transparent such that the statuses of the LEDs are visible even when the cover cap
is fitted.
To protect the modules from environmental influences, the FDCH221 housing
types is available.
17
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Setup
18
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Setup
3
1 3
IN1
IN1
LINE –
LINE –
LINE +
2
Printed circuit board view of the input module
1 Terminals for input IN1 3 Red LED for input status and
localization mode
19
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Setup
Z1
J2 1 J2 1 OUT A –
J1 2 J1 2 OUT A +
OUT A
IN1 3 3 ext. DC 24 V –
IN1 4 4 ext. DC 24 V +
J2 1 NO/NC OUT A
J1 2 not used
LINE – 3 COM OUT A
LINE – 4 not used
LINE +
Z2 Max. DC 30 V
Max. AC 22 V
2 Terminals for detector line 5 Red LED for input status and localization mode
3 Jumper J1/J2 for output configuration 6 Red LED for output status
20
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Setup
3
3.3.5 LEDs
The tables below show the meaning of the LED states.
Red LED for the input status and for localization mode
Status LED Meaning
Red LED for the output status (for input/output module only)
Status LED Meaning
21
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Function
3.4 Function
IN1 OUT A
LOCATE
1
OC-A 2
OUT A
3
IN1 IC-1 4
J1 J2
µP
22
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Function
3
OUT A OUT A
Max. DC 30 V
Max. AC 22 V
1 – 1 NO/NC
OUT A
2 not used
2 + µP
µP OUT A
3 COM
3 –
OC-A
OC-A DC 24 V external 4 not used
4 +
J1 J2
J1 J2
The communication with the control panel is performed via the detector line.
Configuration is performed on the control panel. The output must also be
configured with a jumper on the input/output module. The modules are normally in
operating mode.
The modules can be set to test mode or localization mode for service work.
An external DC 24 V supply is only needed for the input/output module FDCIO221
when the jumper is plugged into position J2.
3.4.2 Input
With the input a status can be monitored e.g. whether a door is closed. The input
can be configured as follows:
Status input or danger input
Lead monitoring for open line or open line and short circuit
Active when contact is:
– Open (normally closed NC)
– Closed (normally open NO)
23
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Function
Circuit
The input line must be provided with resistors.
The resistors must be connected at the end of the line.
Only monitoring resistors with a tolerance of 1 % must be used.
The configuration of the module must correspond to the actual circuitry.
Connection diagram of input with monitoring for open line and short circuit
24
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Function
3
J2 J1
Input/output module jumper position J2
FDCIO221
1 3.3 kO
2 AT
OUT A
3
DC 24 V external
4 +
Connection diagram for normal operation with output line monitored for short circuit and
open line
NOTICE
25
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Function
Configuration
The following configurations are possible:
After activation, the output remains in the following status:
– Permanently active
– Active only for a certain period of time. How long the contact remains active
can also be configured (pulse duration).
Failsafe behavior when the detector line is current-free or in degraded mode
(e.g. in case of a failure of the processor in the control panel).
The error behavior defines the position of the output in case of an error:
– Output remains in the same position as before the error
– Output is activated in case of an error
– Output is deactivated in case of an error
– Responds to signal 'Degraded mode horn' like other sounders on the
detector line
Monitoring of the 'on' or 'off' output.
J2 J1
Input/output module jumper position J2
FDCIO221
1
2 AT
OUT A
3
DC 24 V external
4 +
Connection diagram for inverted operation, e.g. when used as door retainer.
NOTICE
26
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Function
3
In inactive status the 24 V are permanently applied to the output and may keep a
door open, for example. When the output is switched to active, the output goes into
"open" status (= no longer 24 V voltage) and the door closes.
In this example, the door would also close if the 24 V supply were to fail, e.g. due
to a line problem (short-circuit, open line).
Configuration
The following configurations are possible:
Output monitoring must be 'off'
After activation, the output remains in the following status:
– Permanently active
– Active only for a certain period of time. How long the contact remains active
can also be configured (pulse duration).
Failsafe behavior when the detector line is current-free or in degraded mode
(e.g. in case of a failure of the processor in the control panel).
The error behavior defines the position of the output in case of an error:
– Output remains in the same position as before the error
– Output is activated in case of an error
– Output is deactivated in case of an error
– Responds to signal 'Degraded mode horn' like other sounders on the
detector line
J2 J1
Input/output module jumper position J1
Max. DC 30 V
Max. AC 22 V
FDCIO221
2 AT
1 NO/NC
2 not used
OUT A
3 COM
4 not used
27
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Function
NOTICE
Configuration
The following configurations are possible:
The contact is active when it is in the following status:
– It is closed (normally open NO)
– It is open (normally closed NC)
After activation, the contact remains in the following status:
– Permanently active
– Active only for a certain period of time. How long the contact remains active
can also be configured (pulse duration).
Failsafe behavior when the detector line is current-free or in degraded mode
(e.g. in case of a failure of the processor in the control panel).
The error behavior defines the position of the contact in case of an error.
– Contact remains in the same position as before the error
– Contact is activated in case of an error
– Contact is deactivated in case of an error
– Responds to signal 'Degraded mode horn' like other sounders on the
detector line
28
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Function
3
29
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Accessories
3.5 Accessories
30
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Accessories
3
31
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Planning
4 Compatibility
4 Planning
When planning a project, proceed as follows:
1. Take into account the compatibility.
2. Define the place of installation.
3. Define the type of monitoring and configuration of the input.
4. Only for FDCIO221: Determine the output configuration
5. Fill out the configuration sheet.
4.1 Compatibility
Compatible with control panels that support the FDnet/C-NET detector line.
FDnet X - – –
C-NET – X – –
X = compatible
– = not compatible
You will find details in the 'List of compatibility'.
32
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Planning
Defining the type of monitoring and input configuration
4
33
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Planning
4 Filling out the configuration sheet
Pulse duration
The following settings are possible for pulse duration:
1s 2s 3s 5s
10 s 15 s 20 s
See also
Output (for input/output module only) [➙ 24]
See also
Configuration sheet [➙ 44]
34
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Mounting / Installation
Installation without housing
5
5 Mounting / Installation
The procedure followed during mounting and installation depends on whether the
module is used with or without housing.
NOTICE
See also
Connecting the module [➙ 37]
35
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Mounting / Installation
5 Installation with housing
See also
Dimensions [➙ 42]
Connecting the module [➙ 37]
36
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Mounting / Installation
Connecting the module
5
CAUTION
LINE +
LINE –
LINE –
LINE –
LINE –
FDCI221 FDCI221
FDCIO221 FDCIO221
+
LINE
–
The connection diagram for the input and output depends on the type of use
(monitoring) and configuration. You will find details in the corresponding section.
Connect the module in accordance with the corresponding connection
diagrams.
See also
Normal operation (output lines monitored) [➙ 25]
Inverted operation (output lines not monitored) [➙ 26]
Output not monitored [➙ 27]
Input [➙ 23]
37
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Commissioning
6
6 Commissioning
The devices are commissioned via the control panel. The exact procedure is
described in the control panel documentation.
Conduct a performance check once commissioning is complete.
38
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Maintenance / troubleshooting
Performance check
7
7 Maintenance / troubleshooting
Recommendation:
Check the devices every year.
Replace heavily soiled or damaged devices.
Check cables connected to the terminals and correct connections.
No other special maintenance work is necessary.
39
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Specifications
8 Technical data
8 Specifications
40
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Specifications
Technical data
8
41
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Specifications
8 Dimensions
8.2 Dimensions
207
48
24
71 91
95
119
42
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Specifications
Environmental compatibility and disposal
8
43
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Annex
9 Configuration sheet
9 Annex
44
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Index
Index
A J
Approvals, 42 Jumper
Output configuration, 20
C Jumper position J1
Communication Not monitored, 27
Detector line, 23 Jumper position J2
Compatibility, 32 Inverted operation, 26
Compatibility with control panels, 32 Normal operation, 25
Control panel, 38
L
D LED
Degraded mode operation Status displays, 14
Fire control panel failure, 28 Line separator
Detector line Function, 28
Communication, 23 List of compatibility, 6, 29, 32, 40
Disposal, 43 Localization mode
Service work, 23, 39
E
Environmental compatibility, 43 M
ES Maintenance intervals, 39
Product version, 16
N
F Normal operation
Fire control panel failure Jumper position J2, 25
Degraded mode operation, 28 Not monitored
Jumper position J1, 27
I
Input module O
Overview, 17 Output configuration
Printed circuit board view, 19 Jumper, 20
Input monitoring Overview
Resistors, 24 Input module, 17
Input/output module Input/output module, 18
Overview, 18
Printed circuit board view, 20 P
Inverted operation Packaging label
Jumper position J2, 26 Product version, 16
Printed circuit board view
Input module, 19
Input/output module, 20
Product label
Product version, 16
45
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Index
R
Recycling, 43
Resistors
Input monitoring, 24
S
Scope, 5
Service work
Localization mode, 23, 39
Test mode, 23, 39
Short-circuit
Line separator, 28
Standards, 41
Status displays
LED, 14
T
Test mode
Service work, 23, 39
Type plate
Product version, 16
46
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Index
47
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Issued by © 2008-2012 Copyright Siemens Switzerland Ltd
Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Infrastructure & Cities Sector
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41-724 24 24
www.siemens.com/buildingtechnologies