0% found this document useful (0 votes)
136 views48 pages

Fdci221, Fdcio221 Technical Manual

fdci221, fdcio221 technical manual
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
136 views48 pages

Fdci221, Fdcio221 Technical Manual

fdci221, fdcio221 technical manual
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 48

FDCI221, FDCIO221

Input module,
input/output module
Technical Manual

A6V10211122_j_en_-- Building Technologies


2012-09-30 Control Products and Systems
Legal notice

Legal notice
Technical specifications and availability subject to change without notice.
© 2008-2012 Copyright by Siemens Switzerland Ltd

Transmittal, reproduction, dissemination and/or editing of this document as well as


utilization of its contents and communication thereof to others without express
authorization are prohibited. Offenders will be held liable for payment of damages.
All rights created by patent grant or registration of a utility model or design patent
are reserved.

Issued by:
Siemens Switzerland Ltd.
Infrastructure & Cities Sector
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41 724-2424
www.siemens.com/buildingtechnologies

Edition: 2012-09-30
Document ID: A6V10211122_j_en_--

2
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Table of contents

1 About this document .........................................................................................5


1.1 Applicable documents ..........................................................................................6
1.2 Technical terms ....................................................................................................7
1.3 History of changes................................................................................................7
2 Safety...................................................................................................................9
2.1 Safety instructions ................................................................................................9
2.2 Safety regulations for the method of operation ..................................................11
2.3 Standards and directives complied with.............................................................13
2.4 Release Notes....................................................................................................13
3 Structure and function.....................................................................................14
3.1 Details for ordering .............................................................................................15
3.2 Product version ES.............................................................................................16
3.3 Setup ..................................................................................................................17
3.3.1 Input module .......................................................................................17
3.3.2 Input/output module ............................................................................18
3.3.3 Printed circuit board view of the input module....................................19
3.3.4 Printed circuit board view of the input/output module.........................20
3.3.5 LEDs ...................................................................................................21
3.4 Function..............................................................................................................22
3.4.1 Block diagram .....................................................................................22
3.4.2 Input ....................................................................................................23
3.4.3 Output (for input/output module only) .................................................24
3.4.3.1 Normal operation (output lines monitored) .........................................25
3.4.3.2 Inverted operation (output lines not monitored)..................................26
3.4.3.3 Output not monitored ..........................................................................27
3.4.4 Line separator .....................................................................................28
3.4.5 Diagnosis levels ..................................................................................28
3.4.6 Behavior in degraded mode................................................................28
3.5 Accessories ........................................................................................................30
3.5.1 Mounting foot FDCM291.....................................................................30
3.5.2 Housing FDCH221..............................................................................30
3.5.3 M20 x 1.5 metal cable gland...............................................................30
3.5.4 M20 x 1.5 metal counter nut ...............................................................30
3.5.5 Connection terminal DBZ1190-AB......................................................31
4 Planning ............................................................................................................32
4.1 Compatibility.......................................................................................................32
4.2 Defining the place of installation ........................................................................32
4.3 Defining the type of monitoring and input configuration.....................................33
4.4 Defining the output configuration .......................................................................33
4.5 Filling out the configuration sheet ......................................................................34

3
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
5 Mounting / Installation .....................................................................................35
5.1 Installation without housing ................................................................................35
5.2 Installation with housing .....................................................................................36
5.3 Connecting the module ......................................................................................37
6 Commissioning.................................................................................................38
7 Maintenance / troubleshooting .......................................................................39
7.1 Performance check.............................................................................................39
7.2 Test mode...........................................................................................................39
7.3 Localization mode...............................................................................................39
7.4 Remedying faults................................................................................................39
8 Specifications ...................................................................................................40
8.1 Technical data ....................................................................................................40
8.2 Dimensions.........................................................................................................42
8.3 Environmental compatibility and disposal ..........................................................43
9 Annex.................................................................................................................44
9.1 Configuration sheet ............................................................................................44
Index ............................................................................................................................45

4
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
About this document
Applicable documents
1

1 About this document


Goal and purpose
This document contains all the information about the input module FDCI221 and
the input/output module FDCIO221. Following the instructions consistently will
ensure that the product can be used safely and without any problems.

Scope
The document is valid for the following modules:
 Input module FDCI221
 Input/output module FDCIO221

Target groups
The information in this document is intended for the following target groups:

Target group Activity Qualification

Product Manager  Is responsible for information  Has obtained suitable specialist training for the
passing between the function and for the products.
manufacturer and regional  Has attended the training courses for Product
company. Managers.
 Coordinates the flow of
information between the
individual groups of people
involved in a project.
Project Manager  Coordinates the deployment of  Has obtained suitable specialist training for the
all persons and resources function and for the products.
involved in the project  Has attended the training courses for Project
according to schedule. Managers.
 Provides the information
required to run the project.
Project engineer  Sets parameters for product  Has obtained suitable specialist training for the
depending on specific national function and for the products.
and/or customer requirements.  Has attended the training courses for Product
 Checks operability and Engineer.
approves the product for
commissioning at the place of
installation.
 Is responsible for
troubleshooting.
Installation personnel  Assembles and installs the  Has received specialist training in the area of
product components at the building installation technology or electrical
place of installation. installations.
 Carries out a performance
check following installation.
Maintenance personnel  Carries out all maintenance  Has obtained suitable specialist training for the
work. function and for the products.
 Checks that the products are in
perfect working order.
 Searches for and corrects
malfunctions.

5
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
About this document
1 Applicable documents

Reference document and source language


 The source language of this document is German (de).
 The reference version of this document is the international version in English.
The international version is not localized.
The reference document has the following designation:
ID_x_en_--
x = modification index, en = English, -- = international

Document identification
The document ID is structured as follows:

ID code Examples

ID_ModificationIndex_Language_COUNTRY A6V10215123_a_de_DE
-- = multilingual or international A6V10215123_a_en_--
A6V10315123_a_--_--

Conventions for text marking


Markups
Special markups are shown in this document as follows:

⊳ Requirement for a behavior instruction

⇨ Intermediate result of a behavior instruction

⇨ End result of a behavior instruction

[➙ X] Reference to a page number

'Text' Quotation, reproduced identically

<Key> Identification of keys

Supplementary information and tips

The 'i' symbol identifies supplementary information and tips for an easier way of
working.

1.1 Applicable documents


Document ID Name

A6V10212086 Input module FDCI221, input/output module FDCIO221, housing


FDCH221
008331 List of compatibility (for 'Sinteso' product line)
A6V10229261 List of compatibility (for 'Cerberus PRO' product line)

6
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
About this document
Technical terms
1

1.2 Technical terms


Term Explanation

ES Product version
FET Field Effect Transistor
LED Light-emitting diode
FDnet/C-NET Addressed detector line
NC Contact: Opener (normally closed)
NO Contact: NO (normally open)

1.3 History of changes


The reference document's modification index applies to all languages into which
the reference document is translated.

The first edition of a language version or a country variant may for example have
the modification index 'd' instead of 'a' if the reference document already has this
modification index.

The table below shows this document's history of changes:

Modification index Edition date Brief description

j 2012-09-30 Voltage information for alternating current corrected to 'max. AC 22 V'


i 2012-09-07 Date format changed to meet ISO 8601 specifications (format
yyyy-mm-dd); in several graphics, note 'Max. voltage 30 V DC or AC'
added
h 10.2011 Marine approvals added, 'Product version' chapter added
g 09.2010 FM approvals added
f 04.2010 Document revised for 'Dual channeling'; minor editorial changes
e 09.2009 LPCB approvals added
d 04.2009 VdS approvals and CPD no. added
Minor editorial changes
c 10.2008 New note in chapter 3.3.3 indicating that the output has to be potential-
free.
b 06.2008 Term 'SynoNET' removed. Extra output configuration added.
New 'Localization mode' chapter added.
Dimensions of module and housing FDCH221 corrected.
a 05.2008 First edition

7
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
About this document
1 History of changes

The table below shows the published language versions with the corresponding
modification index:

Modification index en_-- de_-- fr_-- it_-- es_--

j X X X X X
i X X X X X
h X X X X X
g X X X X X
f X X X X X
e X X – – –
d X X – – –
c X X X X X
b X X X X X
a X X X X X

X = published
– = no publication with this modification index

8
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Safety
Safety instructions
2

2 Safety

2.1 Safety instructions


The safety notices must be observed in order to protect people and property.
The safety notices in this document contain the following elements:
 Symbol for danger
 Signal word
 Nature and origin of the danger
 Consequences if the danger occurs
 Measures or prohibitions for danger avoidance

Symbol for danger

This is the symbol for danger. It warns of risks of injury.

Follow all measures identified by this symbol to avoid injury or death.

Additional danger symbols


These symbols indicate general dangers, the type of danger or possible
consequences, measures and prohibitions, examples of which are shown in the
following table:

General danger Explosive atmosphere

Voltage/electric shock Laser light

Battery Heat

Signal word
The signal word classifies the danger as defined in the following table:

Signal word Danger level

DANGER DANGER identifies a dangerous situation, which will result directly in death or serious injury
if you do not avoid this situation.

WARNING WARNING identifies a dangerous situation, which may result in death or serious injury if
you do not avoid this situation.

CAUTION CAUTION identifies a dangerous situation, which could result in slight to moderately serious
injury if you do not avoid this situation.

NOTICE NOTICE identifies possible damage to property that may result from non-observance.

9
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Safety
2 Safety instructions

How risk of injury is presented


Information about the risk of injury is shown as follows:

WARNING

Nature and origin of the danger


Consequences if the danger occurs
● Measures / prohibitions for danger avoidance

How possible damage to property is presented


Information about possible damage to property is shown as follows:

NOTICE

Nature and origin of the danger


Consequences if the danger occurs
● Measures / prohibitions for danger avoidance

10
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Safety
Safety regulations for the method of operation
2

2.2 Safety regulations for the method of operation


National standards, regulations and legislation
Siemens products are developed and produced in compliance with the relevant
European and international safety standards. Should additional national or local
safety standards or legislation concerning the planning, assembly, installation,
operation or disposal of the product apply at the place of operation, then these
must also be taken into account together with the safety regulations in the product
documentation.

Electrical installations

WARNING

Electrical voltage
Electric shock
● Work on electrical installations may only be carried out by qualified
electricians or by instructed persons working under the guidance and
supervision of a qualified electrician, in accordance with the electrotechnical
regulations.

 Wherever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
 Lock volt-free areas to prevent them being switched back on again by mistake.
 Label the connection terminals with external external voltage using a
'DANGER External voltage' sign.
 Route mains connections to products separately and fuse them with their own,
clearly marked fuse.
 Fit an easily accessible disconnecting device in accordance with IEC 60950-1
outside the installation.
 Produce earthing as stated in local safety regulations.

Assembly, installation, commissioning and maintenance


 If you require tools such as a ladder, these must be safe and must be intended
for the work in hand.
 When starting the fire control panel ensure that unstable conditions cannot
arise.
 Ensure that all points listed in the 'Testing the product operability' section below
are observed.
 You may only set controls to normal function when the product operability has
been completely tested and the system has been handed over to the customer.

11
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Safety
2 Safety regulations for the method of operation

Testing the product operability


 Prevent the remote transmission from triggering erroneously.
 If testing building installations or activating devices from third-party companies,
you must collaborate with the people appointed.
 The activation of fire control installations for test purposes must not cause
injury to anyone or damage to the building installations. The following
instructions must be observed:
– Use the correct potential for activation; this is generally the potential of the
building installation.
– Only check controls up to the interface (relay with blocking option).
– Make sure that only the controls to be tested are activated.
 Inform people before testing the alarm devices and allow for possible panic
responses.
 Inform people about any noise or mist which may be produced.
 Before testing the remote transmission, inform the corresponding alarm and
fault signal receiving stations.

Modifications to the system design and the products


Modifications to the system and to individual products may lead to faults,
malfunctioning and safety risks. Written confirmation must be obtained from
Siemens and the corresponding safety bodies for modifications or additions.

Modules and spare parts


 Components and spare parts must comply with the technical specifications
defined by Siemens. Only use products specified or recommended by
Siemens.
 Only use fuses with the specified fuse characteristics.
 Wrong battery types and improper battery changing lead to a risk of explosion.
Only use the same battery type or an equivalent battery type recommended by
Siemens.
 Batteries must be disposed of in an environmentally friendly manner. Observe
national guidelines and regulations.

Disregard of the safety regulations


Before they are delivered, Siemens products are tested to ensure they function
correctly when used properly. Siemens disclaims all liability for damage or injuries
caused by the incorrect application of the instructions or the disregard of danger
warnings contained in the documentation. This applies in particular to the following
damage:
 Personal injuries or damage to property caused by improper use and incorrect
application
 Personal injuries or damage to property caused by disregarding safety
instructions in the documentation or on the product
 Personal injury or damage to property caused by poor maintenance or lack of
maintenance

12
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Safety
Standards and directives complied with
2

2.3 Standards and directives complied with


A list of the standards and directives complied with is available from your Siemens
contact.

2.4 Release Notes


Limitations to the configuration or use of devices in a fire detection installation with
a particular firmware version are possible.

WARNING

Limited or non-existent fire detection


Personal injury and damage to property in the event of a fire.
● Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
● Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.

NOTICE

Incorrect planning and/or configuration


Important standards and specifications are not satisfied.
Fire detection installation is not accepted for commissioning.
Additional expense resulting from necessary new planning and/or configuration.
● Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
● Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.

13
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Release Notes

3 Structure and function


Input module FDCI221 Input/output module FDCIO221

Input module FDCI221


The FDCI221 input module has 1 input. It allows you to monitor statuses (e.g.
whether a door is closed).

Input/output module FDCIO221


The FDCIO221 input/output module has 1 output and 1 input. With the output,
control functions can be performed. With the input, statuses can be monitored.
The input and output can be operated independently.

Properties
 Communication via the detector line
 Configuration options
 Built-in line separator
 Status indicators (LED)
 Different mounting options
 Monitored input
 FDCIO221: The following configurations are possible with jumpers:
– Bistabile, switched voltage, monitored or non-monitored (external DC 24 V
supply required)
– Potential-free output

14
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Details for ordering
3

The housing FDCH221 is available for fitting the module outside an electric
cabinet. The housing protects the module from dust and dampness and increases
protection.

Housing FDCH221

3.1 Details for ordering


Type Order no. Designation

FDCI221 S54312-F1-A1 Input module


FDCIO221 S54312-F2-A1 Input/output module

15
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Product version ES

3.2 Product version ES


The product version ES provides the technical status of a device in terms of
software and hardware. The product version is provided as a two-digit number.
You will find the details of your device's product version:
 On the packaging label
 On the product label or the type plate

Product version on the packaging label


Details of the product version can be found directly on the packaging label in the
barcode:

ES
Example of a packaging label with details of the product version

Product version on the product label and the type plate


Details of the product version can be found after the device order number:

04

ES

Example of a product label with details of the product version

Depending on the product and various approvals, the product labels may differ in
terms of the information type and layout.
Look for your device's order number on the product label.
You will find the product version after the order number.

16
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Setup
3

3.3 Setup
The modules consist of the module carrier, the printed circuit board and the cover
cap. The printed circuit board includes the LEDs. These indicate the status of the
input, output and localization mode. The cover cap of the printed circuit board is
transparent such that the statuses of the LEDs are visible even when the cover cap
is fitted.
To protect the modules from environmental influences, the FDCH221 housing
types is available.

3.3.1 Input module

Overview of input module

1 Terminals for input 3 Holes for mounting feet

2 Terminals for the detector line

17
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Setup

3.3.2 Input/output module

Overview of input/output module

1 Terminals for input 4 Terminals for output

2 Terminals for the detector line 5 Holes for mounting feet

3 Jumper for output configuration

18
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Setup
3

3.3.3 Printed circuit board view of the input module

1 3

IN1
IN1

LINE –
LINE –
LINE +

2
Printed circuit board view of the input module

1 Terminals for input IN1 3 Red LED for input status and
localization mode

2 Terminals for detector line

19
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Setup

3.3.4 Printed circuit board view of the input/output module


1 5 6 3 4 Z

Z1
J2 1 J2 1 OUT A –

J1 2 J1 2 OUT A +
OUT A
IN1 3 3 ext. DC 24 V –

IN1 4 4 ext. DC 24 V +

J2 1 NO/NC OUT A

J1 2 not used
LINE – 3 COM OUT A
LINE – 4 not used
LINE +
Z2 Max. DC 30 V
Max. AC 22 V

Printed circuit board view of the input/output module

1 Terminals for input IN1 4 Terminals for output OUT A

2 Terminals for detector line 5 Red LED for input status and localization mode

3 Jumper J1/J2 for output configuration 6 Red LED for output status

Assignment of terminals for output OUT A, depending on jumper


position
Cut-out Z Jumper Configuration of the output
position

Z1 J2  Bistable, switched voltage, normal operation (option of


monitoring output lines)
 Bistable, switched voltage, inverted operation (output
lines not monitored)
Z2 J1 Bistable, potential-free contact (output not monitored)

20
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Setup
3

3.3.5 LEDs
The tables below show the meaning of the LED states.

Red LED for the input status and for localization mode
Status LED Meaning

LED off Normal operation


LED flashing every 2 s Input activated
LED flashing every 1 s Localization mode

Red LED for the output status (for input/output module only)
Status LED Meaning

LED off Output not active


LED flashing every 2 s Output active

The LED displays can be deactivated if necessary (e.g. in a cinema).

21
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Function

3.4 Function

3.4.1 Block diagram


– LINE
+ –

IN1 OUT A
LOCATE

1
OC-A 2
OUT A
3
IN1 IC-1 4

J1 J2
µP

Block diagram of input module and input/output module

LINE Detector line OUT A Output


(for FDCIO221 only)

IN1 Input J1, J2 Jumper plug positions


(for FDCIO221 only)

22
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Function
3

OUT A OUT A
Max. DC 30 V
Max. AC 22 V

1 – 1 NO/NC

OUT A
2 not used
2 + µP
µP OUT A
3 COM
3 –
OC-A
OC-A DC 24 V external 4 not used
4 +

J1 J2

J1 J2

FDCIO221 with plugged jumper on J2 FDCIO221 with plugged jumper on J1

The communication with the control panel is performed via the detector line.
Configuration is performed on the control panel. The output must also be
configured with a jumper on the input/output module. The modules are normally in
operating mode.
The modules can be set to test mode or localization mode for service work.
An external DC 24 V supply is only needed for the input/output module FDCIO221
when the jumper is plugged into position J2.

3.4.2 Input
With the input a status can be monitored e.g. whether a door is closed. The input
can be configured as follows:
 Status input or danger input
 Lead monitoring for open line or open line and short circuit
 Active when contact is:
– Open (normally closed NC)
– Closed (normally open NO)

Status inputs and danger inputs


Danger inputs trigger an alarm as soon as the input is activated. Status inputs
trigger a status change as soon as they are activated.

Line monitoring and circuitry


The input lines are monitored for open line or open line and short circuit. To make
this possible, resistors must be connected to the lines of the input. When an open
line or a short circuit occurs on one of the input lines, a fault message is
transmitted to the control panel.
The input must be potential-free.

23
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Function

Circuit
 The input line must be provided with resistors.
 The resistors must be connected at the end of the line.
 Only monitoring resistors with a tolerance of 1 % must be used.
 The configuration of the module must correspond to the actual circuitry.

Input module FDCI221 and input/output module FDCIO221

Connection diagram of input with monitoring for open line

Connection diagram of input with monitoring for open line and short circuit

3.4.3 Output (for input/output module only)


With the exception of the jumper, the output must be configured from the control
panel. To ensure the desired function, the jumper must be plugged locally into the
relevant position on the module.
If the configurations on the control panel and jumper don't match, this is recognized
and an error message is triggered.
The output must be potential-free.

24
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Function
3

3.4.3.1 Normal operation (output lines monitored)


The input/output module output FDCIO221 can be used for control.
In this mode the module switches the externally supplied 24 V voltage to active
status on the output. The externally supplied 24 V voltage is monitored. In the
event of failure, an error message is generated.
In inactive status the output line is monitored for open line and short circuit. This
can be configured and can also be switched off by the control panel.
The jumper on the input/output module must be plugged into J2.

J2 J1
Input/output module jumper position J2

FDCIO221
1 3.3 kO
2 AT
OUT A

3
DC 24 V external
4 +

Connection diagram for normal operation with output line monitored for short circuit and
open line

 The output line must be provided with the resistor.


 The resistor must be connected at the end of the line.
 Only one monitoring resistor with a tolerance of 1 % must be used.
 The diode must be installed in accordance with the connection diagram.

NOTICE

Strong currents in the line circuit


Module overload during a short-circuit
● Provide a 2 AT fuse in the line circuit.

25
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Function

Configuration
The following configurations are possible:
 After activation, the output remains in the following status:
– Permanently active
– Active only for a certain period of time. How long the contact remains active
can also be configured (pulse duration).
 Failsafe behavior when the detector line is current-free or in degraded mode
(e.g. in case of a failure of the processor in the control panel).
The error behavior defines the position of the output in case of an error:
– Output remains in the same position as before the error
– Output is activated in case of an error
– Output is deactivated in case of an error
– Responds to signal 'Degraded mode horn' like other sounders on the
detector line
 Monitoring of the 'on' or 'off' output.

3.4.3.2 Inverted operation (output lines not monitored)


The output of the input/output module FDCIO221 can be used for controlling (e.g.
closing a door).
In this mode the module switches the externally supplied 24 V DC voltage to active
status on the output. The externally supplied 24 V voltage is monitored. In the
event of failure, an error message is generated.
There is no monitoring of the output lines for open line and short circuit.
The jumper on the input/output module must be plugged into J2.

J2 J1
Input/output module jumper position J2

FDCIO221
1
2 AT
OUT A

3
DC 24 V external
4 +

Connection diagram for inverted operation, e.g. when used as door retainer.

 The configuration of the module must correspond to the actual circuitry.

NOTICE

Strong currents in the line circuit


Module overload during a short-circuit
● Provide a 2 AT fuse in the line circuit.

26
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Function
3

In inactive status the 24 V are permanently applied to the output and may keep a
door open, for example. When the output is switched to active, the output goes into
"open" status (= no longer 24 V voltage) and the door closes.

In this example, the door would also close if the 24 V supply were to fail, e.g. due
to a line problem (short-circuit, open line).

Configuration
The following configurations are possible:
 Output monitoring must be 'off'
 After activation, the output remains in the following status:
– Permanently active
– Active only for a certain period of time. How long the contact remains active
can also be configured (pulse duration).
 Failsafe behavior when the detector line is current-free or in degraded mode
(e.g. in case of a failure of the processor in the control panel).
The error behavior defines the position of the output in case of an error:
– Output remains in the same position as before the error
– Output is activated in case of an error
– Output is deactivated in case of an error
– Responds to signal 'Degraded mode horn' like other sounders on the
detector line

3.4.3.3 Output not monitored


This section describes the function mode when control is not monitored. An
externally supplied 24 V voltage is not needed.
Control functions can be performed with the output (e.g. close door). The output is
designed as a potential-free relay contact.
The jumper on the input/output module must be plugged into J1.

J2 J1
Input/output module jumper position J1

Max. DC 30 V
Max. AC 22 V
FDCIO221
2 AT
1 NO/NC
2 not used
OUT A

3 COM
4 not used

Connection diagram for output which is not monitored

27
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Function

NOTICE

Strong currents in the line circuit


Module overload during a short-circuit
● Provide a 2 AT fuse in the line circuit.

Configuration
The following configurations are possible:
 The contact is active when it is in the following status:
– It is closed (normally open NO)
– It is open (normally closed NC)
 After activation, the contact remains in the following status:
– Permanently active
– Active only for a certain period of time. How long the contact remains active
can also be configured (pulse duration).
 Failsafe behavior when the detector line is current-free or in degraded mode
(e.g. in case of a failure of the processor in the control panel).
The error behavior defines the position of the contact in case of an error.
– Contact remains in the same position as before the error
– Contact is activated in case of an error
– Contact is deactivated in case of an error
– Responds to signal 'Degraded mode horn' like other sounders on the
detector line

3.4.4 Line separator


All FDnet/C-NET devices are equipped with a line separator.
The FDnet/C-NET device is equipped with electronic switches which isolate the
defective part in case of a short-circuit on the detector line. The rest of the detector
line remains serviceable. On a loop line all FDnet/C-NET devices remain fully
functional after a simple error.

3.4.5 Diagnosis levels


The FDCI221 input module and the FDCIO221 input/output module largely monitor
their function autonomously. The following diagnosis levels are taken from the
different control measuring processes:
 Normal
 Fault
When a fatal error occurs, which makes the proper function of the module
impossible, a fault message is reported to the control panel.

3.4.6 Behavior in degraded mode


Applicable for the FDnet/C-NET:
When the main processor of the fire control panel fails, the control panel is in
degraded mode operation. Depending on the control panel type, the fire control
panel can continue to perform the most important alarming and signaling functions
in degraded mode operation.

28
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Function
3

Behavior in degraded mode on control panels supporting degraded


operation
 Alarming is still ensured in degraded mode operation. However, in degraded
mode only collective alarming is possible. This means that in the event of an
alarm, it is possible to identify the detector line but not the exact location of the
module triggering the alarm.
 If the output is being used for control (e.g., fire controls), it will take on the
configured default position in the event of a communication failure or current-
free detector line.
 If the output is being used for controlling sounders or other evacuation devices
and degraded mode has been configured correctly, the output will respond to
the "Degraded mode horn" signal in the same way as other sounders on the
detector line.
Degraded mode operation on the FDnet/C-NET is not supported in the same way
by all control panels. The information in the 'List of compatibility' and in the
corresponding control panel documentation must be taken into account during
project planning.

29
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
3 Accessories

3.5 Accessories

3.5.1 Mounting foot FDCM291


 For device installation on a DIN rail TS35
 Two mounting feet must always be used
 Compatible with:
– Input module FDCI22x(-CN)
– Input/output module FDCIO22x(-CN)
– Multi line separator module FDCL221-M
 Order no.: A5Q00003855

3.5.2 Housing FDCH221


 To protect against dust and wetness
 Compatible with:
– Multi line separator module FDCL221-M
– Input module FDCI22x(-CN)
– Input/output module FDCIO22x(-CN)
– Radio gateway FDCW221
 Order no.: S54312-F3-A1

3.5.3 M20 x 1.5 metal cable gland


 For introducing a cable into a housing
 Allows for increased IP protection
 Compatible with:
– M20 x 1.5 metal counter nut
– Manual call point FDM223
– Manual call point FDM224
– Manual call point FDM223H
– Manual call point FDM224H
 Order no.: A5Q00004478

3.5.4 M20 x 1.5 metal counter nut


 For use with metal cable gland M20 x 1.5
 Order no.: A5Q00004479

30
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Structure and function
Accessories
3

3.5.5 Connection terminal DBZ1190-AB


 Auxiliary terminal for connecting cables
 For T-branches of additional cabling e.g. for cable
shielding, detector heating units, sounder base,
external alarm indicators etc.
 For wire diameters of 1…2.5 mm²
 3 poles
 Order no.: BPZ:4942340001

31
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Planning
4 Compatibility

4 Planning
When planning a project, proceed as follows:
1. Take into account the compatibility.
2. Define the place of installation.
3. Define the type of monitoring and configuration of the input.
4. Only for FDCIO221: Determine the output configuration
5. Fill out the configuration sheet.

4.1 Compatibility
Compatible with control panels that support the FDnet/C-NET detector line.

Detector line Control panel


FC20xx FC72x SIGMASYS AlgoRex

FDnet X - – –

C-NET – X – –

X = compatible
– = not compatible
You will find details in the 'List of compatibility'.

4.2 Defining the place of installation


Installation specification for controlling fire protection installations
For the purpose of controlling fire protection installations in accordance with EN 54-
2, the input/output module FDCIO221 must be integrated into the fire control
housing.

Installation specification for controlling the VdS extinguishing


interface
If the input/output module FDCIO221 is used to control the VdS extinguishing
interface, it must be installed in the control panel housing. Details are described in
the control panel documentation.

Defining the place of installation


 Install the module as close as possible to the fire control. This simplifies the
cabling.
 Use the housing FDCH221 for the following installation situations:
– Outside a switch cabinet
– Outside a control panel
– In a wet or dirty environment

32
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Planning
Defining the type of monitoring and input configuration
4

4.3 Defining the type of monitoring and input


configuration
Proceed as follows:
1. Define the type of input (danger input or status input).
2. Define the type of monitoring and the monitoring resistors.
The inputs cannot be monitored for short to ground.
3. Define whether the input is active with open or closed contact. The
configuration of the input must correspond to the actual circuitry.

The resistors must be connected at the end of the lines.

No automatic detectors or manual call points can be connected to the inputs.

4.4 Defining the output configuration


When configuring the outputs, please proceed as follows:
1. Define the type of output:
– Bistable, switched voltage, normal operation (option of monitoring output
lines)
– Bistable, switched voltage, inverted operation (output lines not monitored)
– Bistable, potential-free contact (output not monitored)
2. Plug the jumper onto J2 or J1 depending on your selection.
3. Determine in which position the contact is active. The contact may be active
when it is:
– Closed (NO)
– Open (NC)
4. Define how long the control shall remain active after activation. The control can
be:
– Permanently active.
– Active only for a certain period of time. How long the contact remains active
can be configured as well (pulse duration).
5. Determine the behavior of the control in case of error (e.g. open line to the
control panel).
The following configurations are possible for the behavior in case of a failure
(default positions):
– Control remains the same as before the error
– Control is activated
– Control is deactivated
– Responds to signal 'Degraded mode horn' like other sounders on the
detector line

33
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Planning
4 Filling out the configuration sheet

Pulse duration
The following settings are possible for pulse duration:

1s 2s 3s 5s
10 s 15 s 20 s

See also
 Output (for input/output module only) [➙ 24]

4.5 Filling out the configuration sheet


Proceed as follows when filling out the configuration sheet:
1. Copy out the configuration sheet. You will find it in the appendix.
2. Fill out the configuration sheet.
3. Hand over copies of the completed configuration sheet to the installer and the
service technician.

See also
 Configuration sheet [➙ 44]

34
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Mounting / Installation
Installation without housing
5

5 Mounting / Installation
The procedure followed during mounting and installation depends on whether the
module is used with or without housing.

5.1 Installation without housing

NOTICE

Impairment of module function due to dust or humidity


● The only situation in which the housing FDCH221 should not be used is if the
module is installed in a closed electrical cabinet or in a control panel

In case of an installation without FDCH221 housing, please proceed as follows:


1. Mount the module on an even surface or on a DIN rail with two mounting feet
(see figure). To make sure that the LEDs remain visible at all times, the cover
cap is transparent. Pick a suitable installation position, ensuring that the LEDs
will remain visible at all times during operation.
2. If you are using shielded cable, join the shielding to the DBZ1190-AB
connection terminal. The shielding must not touch any external ground
potentials or metal parts.
3. Connect cables to corresponding terminals (see connection diagram).

Module installation variants

See also
 Connecting the module [➙ 37]

35
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Mounting / Installation
5 Installation with housing

5.2 Installation with housing


The module can be installed at any location, along with the separate FDCH221
housing.
When installing the module in the housing FDCH221, proceed as follows:
1. Break out the required cable entries.
2. Install housing on a flat surface.
3. Insert cables. If necessary, fix the cables using the M20 x 1.5 cable glands or
use a different cable entry.
4. If you are using shielded cable, join the shielding to the DBZ1190-AB
connection terminal. The shielding must not touch any extrinsic ground
potentials or metal parts in the housing.
5. Install the module in the housing using the fixing screws supplied.
6. Connect the cables to the corresponding terminals.
7. Close housing using supplied screws.

Installing the module in the FDCH221 housing

See also
 Dimensions [➙ 42]
 Connecting the module [➙ 37]

36
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Mounting / Installation
Connecting the module
5

5.3 Connecting the module

CAUTION

Electrical voltage on lines


Risk of injury due to electric shock
● During mounting and installation work, electrical voltage must not be applied
to the lines.

Note the positive and negative poles.


Only connect one wire per terminal. This is the only way of ensuring a problem-
free connection over the device's entire service life.
LINE +

LINE +
LINE –
LINE –

LINE –
LINE –
FDCI221 FDCI221
FDCIO221 FDCIO221

+
LINE

Detector line connection diagram

The connection diagram for the input and output depends on the type of use
(monitoring) and configuration. You will find details in the corresponding section.
 Connect the module in accordance with the corresponding connection
diagrams.

See also
 Normal operation (output lines monitored) [➙ 25]
 Inverted operation (output lines not monitored) [➙ 26]
 Output not monitored [➙ 27]
 Input [➙ 23]

37
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Commissioning
6

6 Commissioning
The devices are commissioned via the control panel. The exact procedure is
described in the control panel documentation.
Conduct a performance check once commissioning is complete.

38
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Maintenance / troubleshooting
Performance check
7

7 Maintenance / troubleshooting

7.1 Performance check


The devices are automatically subjected to a performance check during the self-
test. Nevertheless, it is necessary to check the devices on site at regular intervals.

Recommendation:
 Check the devices every year.
 Replace heavily soiled or damaged devices.
 Check cables connected to the terminals and correct connections.
No other special maintenance work is necessary.

7.2 Test mode


For service purposes, the modules can be switched to test mode. In this mode, the
relay is not activated when activating the outputs. Only the LED is activated. You
will find more detailed information in the control panel documentation.

7.3 Localization mode


For service purposes, the modules can be switched to localization mode. In this
mode the input LED flashes continuously once per second.

7.4 Remedying faults


With the FDCIO221 input/output module, the output can be operated using an
external supply. This external supply must be protected by a fuse.
 Check the external fuse of the external supply.

39
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Specifications
8 Technical data

8 Specifications

8.1 Technical data


Detector line Operating voltage DC 12…33 V
Operating current (quiescent):
 FDCI221 Max. 0.3 mA
 FDCIO221 Max. 0.4 mA
Connection factor:
 FDCI221 1
 FDCIO221 1
Address connection factor 1
Separator connector factor 1
Protocol FDnet/C-NET
Compatibility See 'List of compatibility'

Line separator Line voltage:


 Nominal DC 32 V (= Vnom)
 Minimum DC 12 V (= Vmin)
 Maximum DC 33 V (= Vmax)
Voltage at which the line separator opens:
 Minimum DC 7.5 V (= VSO min)
 Maximum DC 10.5 V (= VSO max)
Permanent current when switches are Max. 0.5 A (= IC max)
closed:
Switching current (e.g. in the event of a Max. 1 A (= IS max)
short-circuit)
Leakage current when switches are Max. 1 mA (= IL max)
open:
Serial impedance when switches are Max. 0.5 Ω (= ZC max)
closed:

External alarm indicator Number of external alarm indicators that None


can be connected

Input Monitoring voltage 3 V, unloaded


Monitoring resistors, input:
 FDCI221/FDCIO221 3.3 kΩ/680 Ω; each ±1%; 0.25 W
Line resistance Max. 20 Ω

40
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Specifications
Technical data
8

Output Max. switching performance at ohmic


load at:
 AC voltage Max. 22 V AC; 2 A; 44 VA
Only permitted in potential-free contact.
 DC voltage Max. 30 V DC; 2 A; 60 W
These values do not apply for inductive
or capacitive loads.
Monitoring voltage 3 V, unloaded
Monitoring resistor, output:
 FDCIO221 3.3 kΩ, ±1%; 0.25 W

Connections Design Spring clips


Cross-section 0.2…2.5 mm2

Ambient conditions Operating temperature -25…+70 °C


Storage temperature -30…+75 °C
Air humidity ≤95 % rel.
IP protection:
 Without housing IP30
 With housing FDCH221, screwed IP65
Electromagnetic compatibility:
 1 MHz…1 GHz 50 V/m

Mechanical data Dimensions (L x W x H):


 Module (without housing) 95 x 71 x 24 mm
 Housing FDCH221 207 x 119 x 48 mm
Housing material ABS
Colors:
 Module carrier ~RAL 9010 pure white
 Housing ~RAL 9010 pure white
 Housing cover Transparent

Standards European standards EN 54-14


EN 54-18
International standards IEC 60092-504
IEC 60533
IEC 60529
ISO 9001
ISO 9004
Siemens standards SN 36350

41
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Specifications
8 Dimensions

Approvals EC Certificate of Conformity (construction products):


 FDCI221 0786-CPD-20709
 FDCIO221 0786-CPD-20710
EC-type examination certificate (marine equipment):
 FDCI221 19 485 - 11 HH
 FDCIO221 19 485 - 11 HH
VdS approvals:
 FDCI221 G209066
 FDCIO221 G209067
LPCB approvals:
 FDCI221 531h/01
 FDCIO221 531h/02
FM approvals:
 FDCI221 3038448
 FDCIO221 3038448
Approvals from Germanischer Lloyd:
 FDCI221 19 563 - 11 HH
 FDCIO221 19 563 - 11 HH

8.2 Dimensions

207

48

24

71 91
95
119

Dimensions of installation variants

The dimensions for FDCI221 and FDCIO221 are identical.

42
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Specifications
Environmental compatibility and disposal
8

8.3 Environmental compatibility and disposal


This device is manufactured using materials and procedures which
comply with current environmental protection standards as best as
possible. More specifically, the following measures have been
undertaken:
 Use of reusable materials
 Use of halogen-free plastics
 Electronic parts and synthetic materials can be separated
Larger plastic parts are labeled according to ISO 11469 and ISO 1043.
The plastics can be separated and recycled on this basis.

Electronic parts and batteries must not be disposed of with domestic


waste.
 Take electronic parts and batteries to local collection points or
recycling centers.
 Contact local authorities for more information.
 Observe national requirements for disposing of electronic parts
and batteries.

43
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Annex
9 Configuration sheet

9 Annex

9.1 Configuration sheet


Installation site

Module □ Input module FDCI221


□ Input/output module FDCIO221
Mode of installation □ Without housing
□ with housing FDCH221
Input IN1 monitors ...
Output OUT A controls ...

Configuration for the input

Parameter Value IN1

Type of input Danger input □


Status input □
Input monitoring Open line monitoring □
Open line and short circuit monitoring □
Input active, when contact is: Open □
Closed □

Configuration for the output

Parameter Value OUT A

Output active, when contact is: Open (NC) □


Closed (NO) □
Duration of activation Permanent □
(without control monitoring)
Only for the period of: □ ___ s
Behavior in case of fault Control remains the same as in normal operation □
Control is activated □
Control is deactivated □
'Degraded mode horn' □
Output configuration Bistable, switched voltage: Normal operation, output line □
monitored (J2 jumper)
Bistable, switched voltage: Normal operation, output line not □
monitored (J2 jumper)
Bistable, switched voltage: Inverted operation, output line not □
monitored (J2 jumper)
Bistable, potential-free contact: Output line not monitored □
(J1 jumper)

44
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Index

Index
A J
Approvals, 42 Jumper
Output configuration, 20
C Jumper position J1
Communication Not monitored, 27
Detector line, 23 Jumper position J2
Compatibility, 32 Inverted operation, 26
Compatibility with control panels, 32 Normal operation, 25
Control panel, 38
L
D LED
Degraded mode operation Status displays, 14
Fire control panel failure, 28 Line separator
Detector line Function, 28
Communication, 23 List of compatibility, 6, 29, 32, 40
Disposal, 43 Localization mode
Service work, 23, 39
E
Environmental compatibility, 43 M
ES Maintenance intervals, 39
Product version, 16
N
F Normal operation
Fire control panel failure Jumper position J2, 25
Degraded mode operation, 28 Not monitored
Jumper position J1, 27
I
Input module O
Overview, 17 Output configuration
Printed circuit board view, 19 Jumper, 20
Input monitoring Overview
Resistors, 24 Input module, 17
Input/output module Input/output module, 18
Overview, 18
Printed circuit board view, 20 P
Inverted operation Packaging label
Jumper position J2, 26 Product version, 16
Printed circuit board view
Input module, 19
Input/output module, 20
Product label
Product version, 16

45
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Index

R
Recycling, 43
Resistors
Input monitoring, 24

S
Scope, 5
Service work
Localization mode, 23, 39
Test mode, 23, 39
Short-circuit
Line separator, 28
Standards, 41
Status displays
LED, 14

T
Test mode
Service work, 23, 39
Type plate
Product version, 16

46
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Index

47
Building Technologies A6V10211122_j_en_--
Fire Safety 2012-09-30
Issued by © 2008-2012 Copyright Siemens Switzerland Ltd
Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Infrastructure & Cities Sector
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41-724 24 24
www.siemens.com/buildingtechnologies

Document ID A6V10211122_j_en_-- Manual FD20 / FD720


Edition 2012-09-30 Register 5

You might also like