TEK-Mate Refrigerant Leak Detector
TEK-Mate Refrigerant Leak Detector
TEK-Mate®
Refrigerant Leak Detector
EU DECLARATION OF CONFORMITY
This declaration is issued under the sole responsibility of the manufacturer INFICON. The
object of the declaration is to certify that this equipment, designed and manufactured by
INFICON, is in conformity with the relevant Community harmonization legislation. It has been
constructed in accordance with good engineering practice in safety matters in force in the
Community and does not endanger the safety of persons, domestic animals or property when
properly installed and maintained and used in applications for which it was made.
2
To get the best performance from your TEK-Mate Leak Detector, please read this
manual carefully before you start using it. If you have any questions or need
additional assistance, please call 800-344-3304. We'll be happy to help you.
Probe Tip/Filter
Sensor Cover
HIGH Indicator
POWER Indicator
LOW Indicator
Power Button
Release Tab
Battery Cover
WARNING
This symbol is used to alert the user to the presence of important operating
and maintenance instructions in the literature accompanying the instrument.
TEK-Mate®,Laboratory Accurate, Toolbox Tough® and INFICON® are trademarks or copyrights of
INFICON GmbH.
3
Getting Started
1. Install the batteries. See How to Install the Alkaline Batteries.
2. Install the sensor. See How to Install or Change the Sensor.
NOTE: Installation of the batteries and sensor is required before use.
3. Long press the power button to turn TEK-Mate On or Off.
4. Wait for TEK-Mate to warm up. All three indicators will illuminate and TEK-Mate
will alarm during warm up. When the HIGH indicator starts flashing and
TEK-Mate beeps about one beep per second, warm-up is complete.
5. To toggle between HIGH and LOW sensitivity modes, press the Power button.
HIGH sensitivity is the default setting.
The INFICON TEK-Mate Refrigerant Leak Detector provides similar responses to
all CFCs, HCFCs, HFCs, HFOs, and refrigerant blends (e.g. R-410A, R407c) as
well as SF6.
4
How to Install the Alkaline Batteries
1. Remove the battery cover by releasing the latch and sliding the cover down and
off the handle. You may need a screwdriver or similar tool to do this.
2. Install two “D” size alkaline batteries as shown in Figure 1.
3. Reinstall the battery cover by aligning it with the handle and sliding it up until
the latch engages.
NOTES:
Low battery is indicated by the green POWER indicator flashing. TEK-Mate
may continue to operate for up to one hour.
Dead battery is indicated by the POWER and HIGH indicators flashing.
Figure 1. Properly Installed Alkaline Batteries
- + -
+
5
How to Install or Change the Sensor
A new TEK-Mate is shipped with its sensor packed separately. The sensor must
be installed before use. This specialized sensor will operate for about 100 hours
before it will need to be replaced.
1. Remove the rubber sensor cover by lifting at the outer edge.
2. If you are replacing a worn out sensor, remove the worn out sensor by pulling
it straight out of the socket and discard it.
WARNING
The worn out sensor may be hot.
3. Remove the new sensor from its packaging and carefully align the three sensor
leads (small wires coming out of the bottom of the “can”) with the three holes in
the sensor socket. Insert the leads into the holes by gently pressing straight
down on the sensor until the sensor leads contact the bottom of the socket. Be
careful not to bend the sensor leads. See Figure 2.
4. Reinstall the rubber sensor cover by pressing it down firmly around the edges.
Be sure the edges of the cover are flat against the surface of the detector.
Figure 2. Installing the Sensor
6
Using your INFICON TEK-Mate
WARNING
Do not operate TEK-Mate in the presence of gasoline, natural gas,
propane, or in other combustible atmospheres.
7
Cleaning and Storage
TEK-Mate's plastic housing can be cleaned with standard household detergent or
isopropyl alcohol. Care should be taken to prevent the cleaner from entering the
instrument. Since gasoline and other solvents may damage the plastic, protect
your INFICON TEK-Mate from contact with these substances.
Troubleshooting
Except for the batteries and the sensor, the internal parts of the TEK-Mate Leak
Detector are not user serviceable. If you experience a problem with TEK-Mate,
see the Troubleshooting Table below to determine how to remedy the problem. If
you cannot remedy the problem, take TEK-Mate to your wholesaler for evaluation.
8
PROBLEM CAUSE REMEDY
4. False alarms - 4a. Sensor leads are 4a. Remove the sensor and
TEK-Mate alarms bent. inspect the leads. Straighten
when the probe is the leads with needle nose
moved or bumped. pliers, if necessary, and
reinstall the sensor.
4b. Moisture was 4b. Run TEK-Mate for at least
absorbed by the 20 minutes. The absorption of
sensor during a long moisture does not affect the
period without use. life or sensitivity of the sensor.
9
Specifications
Usage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Indoor or Outdoor
Minimum sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . High Sensitivity
0.25 oz./yr. (7 g/a)
Operating temperature range. . . . . . . . . . . . . . . . . . -20 to +50 °C (-4 to 122 °F) 1
Storage temperature range . . . . . . . . . . . . . . -20 °C to +60 °C (-4 °F to + 140 °F)
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95% RH NC Max.
Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2000 m (6500 ft.)
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Two “D” cell alkaline batteries
Battery Life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Approximately 16 hours
Pollution degree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Overvoltage category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Weight (with batteries) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.58 kg (1.28 lb.)
1May
be operated for a limited time in lower temperature environments.
10
Replacement Parts and Accessories
Replacement parts and accessories for your INFICON TEK-Mate Refrigerant
Leak Detector are available through the same dealer from whom you bought the
instrument.
Plastic storage case . . . . . . . . . . . 705-700-G1
Replacement sensor . . . . . . . . . . 703-020-G1
Tip filters, package of 20 . . . . . . . 705-600-G1
11