6262 Riverwalk LN Unit 4 Isn 1353 003533 227610 205613
6262 Riverwalk LN Unit 4 Isn 1353 003533 227610 205613
Agents
http://www.guardianangelinspections.com
(561) 512-7854
[email protected] Adrienne Dixon
Inspectors
Clients
Gil Bofill
Amy Teitscheid
Freddy Ramirez
4. HEATING AND COOLING 5. PLUMBING 6. ELECTRICAL 7. INSULATION AND VENTILATION 8. INTERIOR 9. APPLIANCES
Water Test Performed? Air Quality Test Performed? WDO Inspection Performed?
No No Yes
All components of the home listed below were inspected and reported on with the information provided. While the inspector makes every effort to find all areas of concern, some areas can go
unnoticed or may be concealed at the time of the inspection. This is particularly common when the home is occupied or furnished, as the inspector cannot move personal items. Please be aware that
the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further
inspection or repair issues as they relate to the comments in this inspection report.
Comments in red text are considered to be either a major defect OR directly related to a 4pt inspection defect that may cause delay in securing homeowner's insurance.
TABLE OF CONTENT
12. Appliances
Page 2 of 27
COMMENT KEY OR DEFINITION OF RECOMMENDATION
1. Inspected(IN) Item(s) inspected and were deemed functional at the time of the inspection
3. Not Present(NP) Item was not present on the premises at the time of the inspection
The inspection item was found to have adverse conditions rendering the unit in need of
4. Repair or Replace further inspection by a qualified professional that can repair or replace the inspection
item.
INTRODUCTION REPORT SUMMARY 1. ROOF 2. EXTERIOR 3. BASEMENT, FOUNDATION, CRAWLSPACE AND STRUCTURE
4. HEATING AND COOLING 5. PLUMBING 6. ELECTRICAL 7. INSULATION AND VENTILATION 8. INTERIOR 9. APPLIANCES
REPAIR OR REPLACE
2. EXTERIOR
2.1.1 Wood Deterioration Siding
Wood deterioration was noticed on the trim and siding on patio of the home. Recommend replacing as necessary.
2.2.1
Recommend replacing weatherstripping on front entry door.
2.2.2
Master bedroom balcony screen door was off the track. Recommend installing.
Page 3 of 27
2.2.3
Screen door was missing from first floor sliding glass doors.
2.5.1
Patio wall composite board was damaged in several areas. Recommend repair by licensed contractor.
4.5.2
Return vent hinges were damaged/not secured. Recommend licensed contractor repair as needed.
5. PLUMBING
5.2.1 TPR Valve No Extension Pipe
The TPR (Temperature Pressure Relief) valve on the water heater did not have an extension pipe. A pipe to extend within 6 inches of floor
or the exterior of the home is required. Recommend repair by a licensed plumber.
5.3.1
Sink stopper for master bathroom sink was not attached properly.
5.5.1
Upstairs guest bathroom would not flush properly. Recommend licensed plumber evaluate and repair as needed.
5.6.1
Recommend sealing patio spigot at wall entrance.
Page 4 of 27
6. ELECTRICAL
6.5.1
Rear patio light fixture was not working and front entry light fixture was missing bulb. Recommend replacing bulbs.
8. INTERIOR
8.3.1 Loose/Hollow Tiles
Loose/Hollow floor tiles were noticed in the upstairs bedrooms.
8.4.1
Recommend installing handrail for top portion of stairs.
8.4.2
Front cap for stairs was loose on several steps. Recommend licensed contractor secure loose caps.
8.5.1
Upstairs guest bathroom vanity drawers hit door molding when opening.
8.5.2
Upstairs guest bathroom center drawer base missing bottom.
8.7.1
Upstairs guest bedroom was missing closet doors.
9. APPLIANCES
9.2.1
Oven door had rust on bottom support.
INTRODUCTION REPORT SUMMARY 1.ROOF 2.EXTERIOR 3.BASEMENT, FOUNDATION, CRAWLSPACE AND STRUCTURE
4.HEATING AND COOLING 5.PLUMBING 6.ELECTRICAL 7.INSULATION AND VENTILATION 8.INTERIOR 9.APPLIANCES
Page 5 of 27
ROOF SECTION STANDARD
Roof Standards
The inspector shall inspect from ground level or eaves: The roof covering, gutters, downspouts, vents, flashings, skylights, chimney
and other roof penetrations. The general structure of the roof from the readily accessible panels, doors or stairs.
The inspector is not required to: Walk on any roof surface, predict the service life expectancy, inspect underground downspout diverter
drainage pipes, remove debris or other conditions that prohibit the observation of the roof surfaces, move insulation, inspect antennae,
satellite dishes, lightning arresters, or similar attachments. Walk on any roof areas that appear, in the opinion of the inspector to be unsafe,
and or cause damage. Perform a water test, warrant or certify the roof. Confirm proper fastening or installation of any roof material.
Confirm the presence or past presence of rodents and/or any other animal activity.
ROOF MATERIAL
Roof Covering Type Roof Covering Age Viewed Roof Covering From
Single Wraps No
Page 6 of 27
ROOF SECTION REPORT
No. Section Items IN NI NP
1.1 Roof Covering
1.2 Gutters and Downspouts
1.3 Flashing
1.4 Vents, Skylights, Chimney, and other roof penetrations
1.5 Eaves, Soffits & Fascia
1.6 Roof Structure and Attic
Page 7 of 27
INTRODUCTION REPORT SUMMARY 1.ROOF 2.EXTERIOR 3.BASEMENT, FOUNDATION, CRAWLSPACE AND STRUCTURE
4.HEATING AND COOLING 5.PLUMBING 6.ELECTRICAL 7.INSULATION AND VENTILATION 8.INTERIOR 9.APPLIANCES
EXTERIOR MATERIAL
Driveway Siding Material
Page 8 of 27
EXTERIOR SECTION REPORT
No. Section Items IN NI NP
2.1 Wall Covering, Flashing and Trim
2.2 All Exterior Doors
2.3 Adjacent Walkways and Driveways
2.4 Stairs, Steps, Stoops, Stairways and Ramps
2.5 Porches, Patios, Decks, Balconies and Carports
2.6 Railings, Guards, Handrails and Fence
2.7 Windows and Screens
Vegetation, Surface Drainage, Retaining Walls, Grading of the property, where they may adversely affect the
2.8
structure due to moisture intrusion
Page 9 of 27
2.2.1 All Exterior Doors
Recommend replacing weatherstripping on front entry door.
Page 10 of 27
INTRODUCTION REPORT SUMMARY 1.ROOF 2.EXTERIOR 3.BASEMENT, FOUNDATION, CRAWLSPACE AND STRUCTURE
4.HEATING AND COOLING 5.PLUMBING 6.ELECTRICAL 7.INSULATION AND VENTILATION 8.INTERIOR 9.APPLIANCES
No crawlspace
Page 11 of 27
INTRODUCTION REPORT SUMMARY 1.ROOF 2.EXTERIOR 3.BASEMENT, FOUNDATION, CRAWLSPACE AND STRUCTURE
4.HEATING AND COOLING 5.PLUMBING 6.ELECTRICAL 7.INSULATION AND VENTILATION 8.INTERIOR 9.APPLIANCES
The inspector is not required to: Inspect or evaluate interiors of flues or chimneys, fire chambers, heat exchangers, humidifiers,
dehumidifiers, electronic air filters, solar heating systems, solar heating systems or fuel tanks. Inspect underground fuel tanks. Determine the
uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the heating system. Light or ignite pilot
flames. Activate heating, heat pump systems, or other heating systems when ambient temperatures or when other circumstances are not
conducive to safe operation or may damage the equipment. Override electronic thermostats. Evaluate fuel quality. Verify thermostat
calibration, heat anticipation or automatic setbacks, timers, programs or clocks. Determine the uniformity, temperature, flow,
balance, distribution, size, capacity, BTU, or supply adequacy of the cooling system. Inspect window units, through-wall units, or electronic
air filters. Operate equipment or systems if exterior temperature is below 60 degrees Fahrenheit or when other circumstances are not
conducive to safe operation or may damage the equipment. Inspect or determine thermostat calibration, heat anticipation or automatic
setbacks or clocks. Examine electrical current, coolant fluids or gasses, or coolant leakage.
Page 12 of 27
HEATING AND COOLING MATERIAL
Ductwork Filter Type Number of HVAC Units
4.5.1 Distribution Systems (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators,
fan coil units and convectors)
AC filter was missing. Recommend installing proper size filter.
Page 13 of 27
4.5.2 Distribution Systems (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators,
fan coil units and convectors)
Return vent hinges were damaged/not secured. Recommend licensed contractor repair as needed.
Page 14 of 27
INTRODUCTION REPORT SUMMARY 1.ROOF 2.EXTERIOR 3.BASEMENT, FOUNDATION, CRAWLSPACE AND STRUCTURE
4.HEATING AND COOLING 5.PLUMBING 6.ELECTRICAL 7.INSULATION AND VENTILATION 8.INTERIOR 9.APPLIANCES
Page 15 of 27
PLUMBING MATERIAL
Water Heater Power Source Water Heater Capacity Water Heater Manufacturer
Water Heater Age Water Heater Location Visible Plumbing Water Distribution
(inside home)
2023 Closet downstairs
Copper
Page 16 of 27
COMMENTS : Next Section
5.5.1 Toilets/Bidets
Upstairs guest bathroom would not flush properly. Recommend licensed plumber evaluate and repair as needed.
Page 17 of 27
5.7.1 Drainage, Waste and Vent System
Corrugated drain piping was noticed under the kitchen and upstairs bathroom sink(s). Drain piping should have smooth walls to allow proper
drainage. Recommend replacing corrugated lines with smooth walled piping.
Page 18 of 27
INTRODUCTION REPORT SUMMARY 1.ROOF 2.EXTERIOR 3.BASEMENT, FOUNDATION, CRAWLSPACE AND STRUCTURE
4.HEATING AND COOLING 5.PLUMBING 6.ELECTRICAL 7.INSULATION AND VENTILATION 8.INTERIOR 9.APPLIANCES
ELECTRICAL MATERIAL
Branch Wiring Wiring Methods Panel capacity
Page 19 of 27
ELECTRICAL SECTION REPORT
No. Section Items IN NI NP
6.1 Service Entrance Conductors, Service Drop
6.2 Electric Meter and Base, Main Disconnect, Main and Distribution Panels, Grounding
6.3 Circuit Breakers, Fuses and Compatibility of their Amperage and Voltage
6.4 Switches, Receptacles, Light Fixtures and Visible Wiring
6.5 Exterior & Garage Switches, Receptacles, Fixtures and Visible Wiring
6.6 Low Voltage Wiring and Outlets (Cable, Phone, Doorbell etc)
6.7 Ceiling Fans
Polarity and Grounding of Receptacles within 5 feet of Interior Plumbing Fixtures and all Receptacles in
6.8
Garage, Carport, Exterior Walls of Inspected Structure
6.9 Location of Main and Distribution panels
6.10 Smoke Detectors
6.5.1 Exterior & Garage Switches, Receptacles, Fixtures and Visible Wiring
Rear patio light fixture was not working and front entry light fixture was missing bulb. Recommend replacing bulbs.
Page 20 of 27
INTRODUCTION REPORT SUMMARY 1.ROOF 2.EXTERIOR 3.BASEMENT, FOUNDATION, CRAWLSPACE AND STRUCTURE
4.HEATING AND COOLING 5.PLUMBING 6.ELECTRICAL 7.INSULATION AND VENTILATION 8.INTERIOR 9.APPLIANCES
Page 21 of 27
INTRODUCTION REPORT SUMMARY 1.ROOF 2.EXTERIOR 3.BASEMENT, FOUNDATION, CRAWLSPACE AND STRUCTURE
4.HEATING AND COOLING 5.PLUMBING 6.ELECTRICAL 7.INSULATION AND VENTILATION 8.INTERIOR 9.APPLIANCES
The home inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and
floors; Carpeting; or Draperies, blinds, or other window treatments.
The inspector shall: Open and close a representative number of doors and windows. Inspect the walls, ceilings, steps, stairways, and
railings. Report as in need of repair any windows that are obviously fogged or display other evidence of broken seals.
The inspector is not required to: Inspect paint, wallpaper, window treatments or finish treatments. Inspect safety glazing. Evaluate the
fastening of countertops, cabinets, sink tops and fixtures, or firewall compromises. Move drop ceiling tiles. Inspect or operate equipment
housed in the garage except as otherwise noted. Operate or evaluate security bar release and opening mechanisms, whether interior or
exterior, including compliance with local, state, or federal standards. Operate any system, appliance or component that requires the use of
special keys, codes, combinations, or devices. Inspect elevators. Inspect remote controls. Inspect appliances. Inspect items not
permanently installed. Examine or operate any above-ground, movable, freestanding, or otherwise non-permanently installed pool/spa,
recreational equipment or self-contained equipment, come into contact with any pool or spa water in order to determine the system structure
or components. Determine the structural integrity or leakage of a pool or spa.
It is important to note that not every square inch of an occupied interior can be inspected, as there may be concealed areas
due to personal belongings or storage items. The inspector is NOT allowed to move furniture, personal or stored
items/clothing, appliances or any coverings like carpets or rugs (in order to inspect the concealed floor structure.)
Page 22 of 27
INTERIOR MATERIAL
Countertop Cabinetry Window Types
Page 23 of 27
COMMENTS : Next Section
8.3.1 Floors
Loose/Hollow floor tiles were noticed in the upstairs bedrooms.
8.3.2 Floors
Cracked floor tiles were noticed in the upstairs guest bedroom.
8.4.1 Stairs, Steps, Landings, Stairways and Ramps and Railings, Guards and Handrails
Recommend installing handrail for top portion of stairs.
Page 24 of 27
8.4.2 Stairs, Steps, Landings, Stairways and Ramps and Railings, Guards and Handrails
Front cap for stairs was loose on several steps. Recommend licensed contractor secure loose caps.
8.7.1 Doors
Upstairs guest bedroom was missing closet doors.
Page 25 of 27
INTRODUCTION REPORT SUMMARY 1.ROOF 2.EXTERIOR 3.BASEMENT, FOUNDATION, CRAWLSPACE AND STRUCTURE
4.HEATING AND COOLING 5.PLUMBING 6.ELECTRICAL 7.INSULATION AND VENTILATION 8.INTERIOR 9.APPLIANCES
APPLIANCES MATERIAL
Clothes Dryer Brand Washing Machine Brand Refrigerator Brand
Dishwasher Brand
GENERAL ELECTRIC
Page 26 of 27
APPLIANCES SECTION REPORT
No. Section Items IN NI NP
9.1 Dishwasher
9.2 Ranges/Ovens/Cooktops
9.3 Garbage Disposal
9.4 Built In Microwave
9.5 Refrigerator
9.6 Washing Machine
9.7 Clothes Dryer
9.8 Central Vacuum System
COMMENTS :
9.2.1 Ranges/Ovens/Cooktops
Oven door had rust on bottom support.
Page 27 of 27