Replacement of a

PowerTag Link or
PowerTag Link HD by a
EcoStruxure Panel Server
Design procedure
March 2023
revision2

Public
The information provided in this documentation contains general descriptions and/or technical
characteristics of the performance of the products contained herein. This documentation is not
intended as a substitute for and is not to be used for determining suitability or reliability of these
products for specific user applications. It is the duty of any such user or integrator to perform the
appropriate and complete risk analysis, evaluation and testing of the products with respect to the
relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or
subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have
any suggestions for improvements or amendments or have found errors in this publication, please
notify us.

You agree not to reproduce, other than for your own personal, noncommercial use, all or part of this
document on any medium whatsoever without permission of Schneider Electric, given in writing. You
also agree not to establish any hypertext links to this document or its content.
Schneider Electric does not grant any right or license for the personal and noncommercial use of the
document or its content, except for a non-exclusive license to consult it on an "as is" basis, at your
own risk. All other rights are reserved.

All pertinent state, regional, and local safety regulations must be observed when installing and using
this product. For reasons of safety and to help ensure compliance with documented system data, only
the manufacturer should perform repairs to components.

When devices are used for applications with technical safety requirements, the relevant instructions
must be followed.

Failure to use Schneider Electric software or approved software with our hardware products may
result in injury, harm, or improper operating results.

Failure to observe this information can result in injury or equipment damage.

2 revision2

Public
Table of Contents

Introduction .............................................................................................................................................4

Baseline ..................................................................................................................................................4

Related Documents ................................................................................................................................ 4

PowerTag Link Gateways Functionalities not covered by ESX Panel Server (firmware 1.4.0) ..............5

Product View and connectors .................................................................................................................6

Power Supply .........................................................................................................................................8

Ethernet connectivity .............................................................................................................................. 9

Environmental Characteristics ..............................................................................................................10

revision2 3

Public
Replacement of a PowerTag Link or PowerTag Link HD by a EcoStruxure Panel Server

Introduction
This guide is intended to help Engineer to replace a PowerTag Link gateway (standard or HD) by a ESX
Panel Server gateway in case of:

- Retrofit operation of existing installation with the objective to minimize the modification/
commissioning workload,

- New design with the objective to minimize the cost.

The goal is to help engineer:

- to validate the possibility to replace the PowerTag Link by an ESX Panel ServerPAS600

- to select the reference of Panel Server sized for the need.

- to compare the characteristics (functional, mechanical, electrical and environmental) of the two
gateways

In case of missing characteristics in this document, please refer to the user guides of PowerTag Link
and ESX Panel Server for information and details.

Please also refer to document “Replacement of a PowerTag Link Gateway by a Universal Panel Server
-Commissioning procedure” for the commissioning steps in case of installation retrofit.

Baseline
This document refers to the next firmware:

Device Part number Firmware version

PowerTag Link A9XMWD20 002.001.005


PowerTag Link HD A9XMWD100 (Or higher)

Ecostruxure Panel Server PAS600 (Universal Panel 001.005.001


Server) (Or higher)

Related Documents

Title of documentation Reference number Download Link

EcoStruxure Panel DOCA0172 https://www.se.com/ww/en/download/docu


Server User Guide ment/DOCA0172EN/

PowerTag Link Gateway DOCA0157 https://www.se.com/ww/en/download/docu


user Guide ment/DOCA0157EN/

Replacement of a Rev2
PowerTag Link or a
PowerTag Link HD by a
Universal Panel Server
Gateway -Commissioning
procedure

4 revision2

Public
Replacement of a PowerTag Link or PowerTag Link HD by a EcoStruxure Panel Server

PowerTag Link Gateways Functionalities not covered by ESX Panel Server (firmware 1.4.0)
For development load reasons, some functionalities available on PowerTag Link gateway are not yet implemented in ESX
Panel Server.

The table hereunder synthetize all the functionalities available in PowerTag Link and not proposed today in ESX Panel
server.

Before physical replacement of the PowerTag Link gateway by ESX Panel Server, check this list to identify if missing
functionalities are implemented in the targeted installation.

In case of missing functionalities available in a future version, define if it is acceptable to start without.

PowerTag Link Functionalities ESX Panel server PAS600 Alternative solutions

Designation PowerTag Page Limitation Availability


Link Status
user Guide
paragraph
PowerTag Display PowerTag 17 not implemented Unknown Switch to another local display. Check feasibility with
(ref A9XMWRD) Link display FDM128
pairing
PowerTag Control Load 75 Not implemented In a future Replace PowerTag Control modules by SmartLink
(ref A9XMC1D3 Monitoring version Modbus connected to PAS600 for digital Input/Output
/A9XMC2D3) pairing and control management
Maximum Number of Maximum 13 Maxi: 40 PowerTag Improvement Install several ESX Panel Server and divide Wireless
Wireless devices up number of energy Sensor / 65 In a future products on it.
to 85 for PowerTag wireless Ambient sensors version
Link HD devices CL110/TH110
Minimum PowerTag - - Min supported version Never Version 004.000.429 is the PowerTag 63A firmware
Energy Sensor 63A 004.000.429 version for who all the performance and features of
Firmware version Panel Server are tested and guaranteed.
However:
- Version 004.000.424 is compatible
- Version 001.000.310 / 001.000.315 / 002.000.344 /
003.000.388 and 003.000.396 can be also paired to
Panel Server with lower wireless discovery timing
performance.
Modbus synthesis Modbus 123 not implemented In a future Modify the upper system to request individually each
table Synthesis version product though its individual Modbus ID
table
BOOTP mode (IPV4 IP 55 Not implemented Never propose to switch in DHCP mode or in static IP
parameters sent by configuration address
BOOTP server)
IP Port reallocation IP Network 57 Not implemented in a future use the default values
(502/ Modbus, 443/ Services version
https, 80/http)

Modbus TCP/IP Modbus 61 Not implemented in a future implement the IP filtering at a higher level (router,
Filtering TCP/IP version switch, firewall…)
filtering
User management User 62 Not implemented in a future convince customer to start with only one
(including guest user) Management version administrator user and schedule an update with the
future version
Modbus Function Table of 148 Not implemented unknown Specific Function code. Check if they are really used
code supported: Modbus for the communication
1- Read n Output or Functions
internal bits
2- Read n input bits
5- Write 1 bit
8- Modbus diagnostic
data
15- Write n bits
43-15 – Write
identification

revision2 5

Public
Replacement of a PowerTag Link or PowerTag Link HD by a EcoStruxure Panel Server

Product View and connectors

Reference PowerTag Link ESX Panel Server PAS600 Note

Power supply On top of the product On top of the product Similar


position

Ethernet port One Ethernet port on bottom Two Ethernet ports on Use port ETH1
of the product bottom of the product

PowerTag Link ESX Panel Server PAS600

Front view Bottom view

6 revision2

Public
Replacement of a PowerTag Link or PowerTag Link HD by a EcoStruxure Panel Server

Mechanical substitution (a similar footprint)

Reference PowerTag Link ESX Panel Server PAS600 Note

Mounting DIN rail DIN rail Similar

Width 72 mm 71.8mm Confirm that there is enough


space for mounting in your
existing panels

Height 105 mm 104,2 mm

(including connectors) (including connectors)

Front Face height 45 mm 45.5 mm

Depth 71mm 70.2mm

Ethernet Port On the top of the gateway On the bottom of the Confirm that there is enough
position gateway space for this wiring in your
existing panels

PowerTag Link ESX Panel Server PAS600

• Weight: • Weight:
133 g 250 g
• Enclosure IP Level: • Enclosure IP Level:
On the front panel (wall-mounted enclosure): IP40 Front face: IP40
Connectors/other parts: IP20 Connectors and case: IP20
Other face: IP30

revision2 7

Public
Replacement of a PowerTag Link or PowerTag Link HD by a EcoStruxure Panel Server

Power Supply

Reference PowerTag Link ESX Panel Server PAS600

Power Supply Voltage 110-230VAC 100-277VAC


100-277VDC

Frequency 50-60Hz 50-60Hz

Tolerance +/-20% +/-10%

Consumption 5VA 5W max

PowerTag Link ESX Panel Server PAS600

8 revision2

Public
Replacement of a PowerTag Link or PowerTag Link HD by a EcoStruxure Panel Server

Ethernet connectivity

Reference PowerTag Link ESX Panel Server PAS600

Physical position On the bottom of the product On the bottom of the product

Link Speed 10 Mbps or 100 Mbps 10 Mbps or 100 Mbps

PowerTag Link ESX Panel Server PAS600

revision2 9

Public
Replacement of a PowerTag Link or PowerTag Link HD by a EcoStruxure Panel Server

Environmental Characteristics

Gateway PowerTag Link ESX Panel Server PAS600

Ambient Operating -25 °C to +60 °C (-13 °F to +158 °F) -25 °C to +70 °C (-13 °F to +158 °F)
Temperature

Storage Temperature -40 °C to +85 °C (-40 °F to +185 °F) -40 °C to +85 °C (-40 °F to +185 °F)

Humidity Rating Treatment 2 (relative humidity of 93% at 5–95 % relative humidity (without
40°C) condensation) at 55 °C (131°F)

Tropicalization IEC60068-2-30

Pollution Degree Level 2 Level 2