L&T CONSTRUCTION

WATER & EFFLUENT TREATEMENT IC


DOCUMENT NO. DATE
RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
10-06-24
(Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SPP

1.0 INTRODUCTION:
1.1 General
This document covers the Design of Pumping station of Right command of Lower suktel UGPL
irrigation project. This design document includes the design of sump walls,sump raft,
below Ground level beams, columns, footing and staircase.

1.2 Material Specifications for Design Purpose


a) Grade of Concrete M30 for sump walls, raft and M25 for beams, columns and footings .
b) Grade of steel - High yield strength deformed bars with yield stress of 500 N/mm2

1.3 Reference Codes


a) IS:456- 2000 - Plain & reinforced concrete - Code of Practice
b) IS: 875 (Part-1) : Indian Standard Code of Practice for Design Loads
(other than Earthquakes) for Buildings and Structures(Prt-1)Dead Loads
c) IS: 875 (Part-2) : Indian Standard Code of Practice for Design Loads (Other than
Earthquakes) for Buildings and Structures (Part-2) Imposed Loads
d) IS: 875 (Part-3) : Indian Standard Code of Practice for Design Loads (Other than
Earthquakes) for Buildings and Structures (Part-3) Wind Loads
e) IS:1893(Part-1) - : Indian Standard Criteria for Earthquake resistant design of
2016
structures General provisions and building.

f) SP: 16 : Design Aids for reinforced concrete to IS 456


g) SP: 34 -1987 Hand Book on Concrete Reinforcement and Detailing.
h) IS:3370 - 2009 - Code of practice for concrete structures for the Storage of Liquids
Part I - General Requirements
Part II - Reinforced Concrete Structures
i) IS 800 -2007- Code of practice for use of structural steel in general building construction
IS 13920 : 2016 - Ductile Design and Detailing of Reinforced Concrete Structures Subjected to
j)
Seismic Forces

1.4 Reference Documents and Drawings


Mechanical Dwg. LE22M794- M - LW - WS - GA - 2008 (Sheet- 1,2)
Electrical Dwg LE22M794- E - LW - WS - DG - 4009 (Sheet- 1,2)
1.5 Material Properties :
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
10-06-24
(Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SPP

Material Property Value Units Remarks


Density 25 kN/m3 IS:875 (Part 1) - 1987
Characteristic
30/25 N/mm2 IS 456-2000
Strength
Concrete,
Modulus of
M30,M25 27386/25000 N/mm2 IS 456-2000
Elasticity

Coefficient of
Thermal 10 x 10-6 Per o C IS 456-2000
Expansion
Density 78.5 kN/ m3
High yield
strength Characteristic
500 N/mm2 IS 1786
Reinforcement Strength
bars Modulus of
200000 N/mm2
Elasticity
Brick Density 19 kN/m3 IS:875 (Part 1) - 1987
Density 78.5 kN/ m3 IS:875 (Part 1) - 1987
Yield Strength 250 N/mm2 IS 2062 – 1999
Modulus of
2 x 105 N/mm2 IS 800
Structural Steel Elasticity
Poission's ratio 0.3 IS 800
Coefficient of
Thermal 12 x 10-6 Per o C IS 800
Expansion
Saturated Soil Density 21 kN/m3
Dry Soil Density 18 kN/m3
Water Density 10 kN/m3

1.6 Plant Site Information :


Location of the Site : Balangir
Basic Wind speed : 44 m/s (considered)
As per DBR
Seismic Zone : Zone II
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
10-06-24
(Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SPP

1.7 Soil Properties :(Refer Geotechnical Investigations report)

R.L of Raft (m) SBC (kN/m2)

190.5 600
199 300
196 300

1.8 Software Reference:


(A) STAAD - Pro Connect edition, Bentley Systems, Inc.
The above software package is renowned and well used and accepted internationally for
similar type of structural analysis.

h = 4.675m
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
PROJECT:
RIGHT COMMAND OF LOWER SUKTEL UGPL
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004 (Part-I) 10-06-24

DESIGNED CHECKED Approved


STRUCTURE: Pump house - Design calculation
MSR SYAM SPP

1(a) Technical data


The dimensions of pump house, Electrical building & PLC room is 51.235 m X 28.15m
The proposed pump house is of RCC framed structure consisting of pump house, Electrical
switch gear room, Maintanence bay , PLC and office room covered with RCC slab.

Fig-1:Plan of Pump house @ 207.5m "Level


L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
PROJECT:
RIGHT COMMAND OF LOWER SUKTEL UGPL
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004 (Part-I) 10-06-24

DESIGNED CHECKED Approved


STRUCTURE: Pump house - Design calculation
MSR SYAM SPP

Fig-2: Section of Pump house


L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
PROJECT:
RIGHT COMMAND OF LOWER SUKTEL UGPL
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004 (Part-I) 10-06-24

DESIGNED CHECKED Approved


STRUCTURE: Pump house - Design calculation
MSR SYAM SPP

Details.
Pump floor level = 207.500 m
Finished Ground level (FGL) = 207.000 m
Natural Ground level (NGL) = 206.000 m
Max water level(MWL) in pump sump = 206.000 m
Sump Bottom Level = 191.500 m
Low water level (LWL) = 197.000 m
Pump house
length of the building along X-axis = 51.235 m
width of the building along Z-axis = 28.150 m
Pump floor / Service bay floor level = 207.500 m
Capacity of EOT crane = 500 kN
Type of foundation adopted = Raft&Isolated

Electrical Building
length of the building along X-axis = 27.050 m
width of the building along Z-axis = 11.900 m

PLC control room:


length of the building along X-axis = 11.385 m
width of the building along Z-axis = 11.900 m
Pump floor / Service bay floor level = 207.500 m
2. LOAD CALCULATION
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
PROJECT:
RIGHT COMMAND OF LOWER SUKTEL UGPL IRRIGATION
PROJECT LE22M794-C-LW-WS-DC-3004
10-06-24
(Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SPP

2.0 Load calculations


2.1 Dead Load Calculations:
Self weight of beams, columns and sump are considered in STAAD using 'SELFWEIGHT'
command. Apart from self weight of beams, columns and sump following are the dead loads
considered for the analysis.
a) Floor load calculations :
Self weight of Roof slab and water proofing load of PLC, Pump house & switchgear room
(0.125x25+1.8)= 4.925 kN/m2
Self weight of floor slab and Floor Finish load of PH on sump,maintance bay
(0.175x25+1.25)= 5.625 kN/m2
Self weight of floor slab and floor finish load of PLC, cable cellar & switchgear room
(0.15x25+1.25)= 5 kN/m2
Load for roof slab projection 600mm & parapet wall
0.6x(0.125x25+1.8)+(1x0.115x19)+(0.04x21x1))= 6.0 kN/m
Moment due to roof slab projection
(0.6x(0.125x25+1.8))*0.6/2= 0.9 kN-m/m
Moment due to Parapet wall
((1x0.115x19)+(0.04x21x1))x(0.6)= 1.8 kN-m/m

False Flooring on PLC room = 2.000 kN/m2


False Ceiling on PLC room = 2.000 kN/m2
Dead load on Platform Beam
Dead load (0.15x25)+1.2 = 4.950 kN/m2

Pedestal load below water tank = 0.3mx 25 = 7.5 kN

b) Brick Load Calculations :


i) 230 thick brick wall
Load coming from brick wall on beams (Including Plastring)
Self weight of brick load acting on members
Floor beam @ 207.45 m lvl
=(0.23x2.75x19)+(0.04x21x2.75)= 14.40 kN/m
Tie beam @210.7 m lvl
=(0.23x2.5x19)+(0.04x21x2.5)= 13.10 kN/m
Electrical Building Floor beams @ 213.7 lvl
=(0.23x2.15x19)+(0.04x21x2.15)= 11.30 kN/m
Electrical Building Tie beams @ 216.35 lvl
=(0.23x2.38x19)+(0.04x21x2.38)= 12.40 kN/m
Pumphouse Tie beams @ 219.225 lvl
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
PROJECT:
RIGHT COMMAND OF LOWER SUKTEL UGPL IRRIGATION
PROJECT LE22M794-C-LW-WS-DC-3004
10-06-24
(Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SPP

=(0.23x2.78x19)+(0.04x21x2.78)= 14.50 kN/m


Pumphouse Tie beams @ 222.5 lvl
=(0.23x2.28x19)+(0.04x21x2.28)= 11.90 kN/m

Floor beam under Rolling shutter


=(0.23x5.75x19)+(0.04x21x5.75)= 30.00 kN/m
=(0.23x3.55x19)+(0.04x21x3.55)= 18.50 kN/m
Self weight of solar panel on PH roof = 3 kN
=(3/6)= = 0.50 kN
Self weight of pressure filter (3 bolts *2 PF) = 13.33 kN

c) Pump and Motor Loads:


For sump 1-5
Static load of pump = 684.38 kN
i) Standby Pumps
Static load of Pump =684.375= = 684.38 KN
Load acting on each beam =684.38/4= = 171.1 KN
ii) Working Pumps
Dynamic load of Pump = 991.58 KN
Dynamic Load acting on each beam =991.575/4 (Vertical down)= 247.9 KN
Horizontal load of Pump = 1262.29 KN
Load acting on each beam =1262.2875/4 = 315.58 KN
Moment acting about center of pipe = 2019.66 KNm
This moment is applied as a push and pull(couple) for 3.1 m c/c bolt distance
Upward/Downward force 2019.66/3.1 = 651.503 KN
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
PROJECT:
RIGHT COMMAND OF LOWER SUKTEL UGPL IRRIGATION
PROJECT LE22M794-C-LW-WS-DC-3004
10-06-24
(Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SPP

2.2 Live Load Calculations:


a) Floor load calculations :
Load on Roof Slab of Switchgear Room = 1.5 kN/m2
Load on Roof Slab of PLC Room = 1.5 kN/m2
Load on Roof Slab of pump house = 1.5 kN/m2
Load for roof slab projection 600mm
0.6x1.5= 0.9 kN/m
Moment due to roof slab projection
(0.6x1.5)*0.6/2= 0.3 Kn-m/m
Load on Floor Slab of Switchgear Room = 5.0 kN/m2
Load on Floor Slab of PLC Room = 5.0 kN/m2
Load on Floor Slab of cable cellar Room = 1.5 kN/m2
Load on Pump Floor Slab above Sump = 10 kN/m2
Load due to OHT = 150 kN
(3 Nos of 5000 lt capacity)
Load on slab of area due to OHT = 50/(3*3) = 5.556 kN/m2
Live load on Platform Beam = 5 kN/m2
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
RIGHT
PROJECT: COMMAND OF LOWER SUKTEL UGPL IRRIGATION PROJECT
LE22M794-C-LW-WS-DC-3004
10-06-24
(Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SPP

2.3 Wind Load on PH Roof Truss:

Basic wind speed (Vb) = = 39 m/s


Risk coefficient (k 1) =Table-1 of IS-875)
(Ref = 1.06
Terrain height, structure size factor (k2Table-2
(Ref )= of IS-875) = 1.07
(for category - 2)
Topography factor (k3) = 1
Importance factor for the cyclonic region,k4 (Ref Cl. 6.3.4) = 1
Design wind speed (Vz) = Vbxk1xk2xk3xk4 = = 44.23 m/s
Wind pressure, Pz = 0.6 x Vz2 = = 1173.78 N/m2

Wind directionaliy Factor, kd (Ref Cl. 7.2.1) = 1


Area averaging factor, ka (Ref Cl. 7.2.2) = 1
Combination factor, kc (Ref Cl. 7.3.3.13) = 1

Design Wind Pressure, Pd = kdxkaxkcxPz = 1173.78 N/m2


Length of the building (l) = = 67 m
Width of the building = = 15 m
Height of the building (h) = = 17.65 m
Span Of Truss(w) = 15 m
h/w=17.65/15= = 1.18
Wind Load Calculation For Roof Truss

0 Degree PRESSURE
EF Pressure coefficient for rectangular clad building FACE A (+VE) 1.548
Designed Wind pressure intensity = 1.817 KN/m2
Mid purlin Err:509 = Err:509 kN/m
End purlin Err:509 = Err:509 kN/m

GH Pressure coefficient for rectangular clad building FACE B (+VE) 1.087


Designed Wind pressure intensity = 1.276 KN/m2
Mid purlin Err:509 = Err:509 kN/m
End purlin 1.276/2 = Err:509 kN/m

Sensitivity: LNT Construction Internal Use


#
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
RIGHT
PROJECT: COMMAND OF LOWER SUKTEL UGPL IRRIGATION PROJECT
LE22M794-C-LW-WS-DC-3004
10-06-24
(Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SPP

90 Degree PRESSURE
EG Pressure coefficient for Roof Truss (+VE) 1.300
Designed Wind pressure intensity = 1.526 KN/m2
Mid purlin Err:509 = Err:509 kN/m
End purlin 1.526/2 = Err:509 kN/m

FH Pressure coefficient for Roof Truss (+VE) 1.100


Designed Wind pressure intensity = 1.291 KN/m2
Mid purlin Err:509 = Err:509 kN/m
End purlin 1.291/2 = Err:509 kN/m
0 Degree SUCTION

EF Pressure coefficient for Roof Truss (-VE) 0.548


Designed Wind pressure intensity = 0.643 KN/m2
Mid purlin Err:509 = Err:509 kN/m
End purlin 0.643/2 = Err:509 kN/m

GH Pressure coefficient for Roof Truss (-VE) 0.087


Designed Wind pressure intensity = 0.102 KN/m2
Mid purlin Err:509 = Err:509 kN/m
End purlin 0.102/2 = Err:509 kN/m
90 Degree SUCTION

EG Pressure coefficient for Roof Truss (-VE) 0.3


Designed Wind pressure intensity = 0.352 KN/m2
Mid purlin Err:509 = Err:509 kN/m
End purlin 0.352/2 = Err:509

FH Pressure coefficient for Roof Truss (-VE) 0.1


Designed Wind pressure intensity = 0.117 KN/m2
Mid purlin Err:509 = Err:509 kN/m
End purlin 0.117/2 = Err:509

Sensitivity: LNT Construction Internal Use


#
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
PROJECT:
RIGHT COMMAND OF LOWER SUKTEL UGPL IRRIGATION
PROJECT LE22M794-C-LW-WS-DC-3004
10-06-24
(Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SPP

2.3 Seismic Load Calculations:


Seismic Load (EL) for PH
Seismic zone = II
Damping percentage = 5%
Importance factor (I) = 1.5
Response reduction factor (R) = 5
Ref IS 1893
(Part 1) :2002
Zone factor (Z) = 0.1

Z I Sa
Horizontal Seismic Coefficient (Ah)=
2 R G
The approximate fundamental natural period of vibration ( Ta ), in seconds
with brick infill panels, = 0.09 h / Sqrt(d)
Z - direction
Where d = Base dimension of the building at the plinth level, in m, along the
considered direction of the lateral force = 28.150 m.
h = 18.030 m.
Ta = 0.306 sec.
Corresponding value of Sa/g for soil type: Rocky or hard soil
Sa/g = 1 + 15 T 0.000 ≤ T≤ 0.100
2.50 0.100 ≤ T≤ 0.400
1.00 / T 0.400 ≤ T≤ 4.000
0.25 T˃ 4.000
Hence Sa / g = 2.50
Horizontal Seismic Coefficient (Ah) = 0.1 x 1.5 x 2.5 / (2 x 5) = 0.038
X - direction
Where d = Base dimension of the building at the plinth level, in m, along the
considered direction of the lateral force = 51.235 m.
h = 18.030 m.
Ta = 0.227 sec.
Hence Sa / g = 2.50
Seismic parameters are given and analysed in response spectrum method
using Staad commands
Co-efficient in X and Z direction = Z I = 1.5x0.1
2 R 2x5
= 0.015
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
RIGHT
PROJECT: COMMAND OF LOWER SUKTEL UGPL IRRIGATION PROJECT
LE22M794-C-LW-WS-DC-
10-06-24
3004 (Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SRS

2.5 Sub Structure load


Case 15) Pump Sump full with soil outside & water inside (Hydrotest)
Floor lvl. 207.50 m
FGL 207.000 m

16.00

191.50 m 335.50
160.00 3.07 160.00
160.00
b) a) c) d) e)

Depth of the water = (207.5-191.5) = 16.00 m


Unit weight of water = 10 kN/m3
a) Water pressure at base of the wall(Sump Inside)
(16x10) = 160.00 kN/m2
b) Load on PH Raft Inside (16x10) = 160.00 kN/m2
Height of soil above base of pump sump upto FGL = 15.50 m
Unit weight of saturated soil = 21 kN/m3
Unit weight of submerged soil = 11 kN/m3

Coefficient of earth pressure (ka) = 0.307


Surcharge load (q) = 10 kN/m2

c) Surcharge Pressure 10x0.307 = 3.07 kN/m2

Load acting on Pump Sump

d) Soil pressure at the base of wall

0.307*21*15.5 = 99.93 kN/m2

c) Load on Raft projection =15.5x21 +10 = 335.50 kN/m2

Sensitivity: LNT Construction Internal Use


#
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
RIGHT
PROJECT: COMMAND OF LOWER SUKTEL UGPL IRRIGATION PROJECT
LE22M794-C-LW-WS-DC-
10-06-24
3004 (Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SRS

Case 18) Pump Sump Empty- With outside Dry Soil with surcharge:

FGL 207.000 m

15.50

191.500 m
289.00
3.07 85.65
d)
b)
a) sump upto FGL
Height of soil above base of pump = 15.50 m
Unit weight of water = 10 kN/m3
From DBR Unit weight of saturated soil = 21 kN/m3
Unit weight of dry soil = 18 kN/m3
From DBR Surcharge load (q) = 10 kN/m2
Coefficient of earth pressure (ka) = 0.307
a) Surcharge Pressure 0.307x10 = 3.07 kN/m2
Load acting on Pump Sump
b) Soil pressure at the base of wall
0.307x(18)x15.5 = 85.65 kN/m2
c) Load on Raft projection =15.5x(18)+10 = 289.00 kN/m2

Case
Pump Sump full up to MWL + outside saturated soil upto FGL with surcharge (Working)
16,17,18)

FGL 207.000 m

MWL 206.000 m 15.50


14.50

191.50 m
145.00 145.00 3.07 99.93 335.50
a) b) c) d) e)
Height of soil above raft top of pump sump upto FGL = 15.50 m
)
Height of water above inside raft top sump upto MWL = 14.50 m
Load acting on Pump Sump
a) Water pressure at base of the wall(Sump Inside)
Sensitivity: LNT Construction Internal Use
#
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
RIGHT
PROJECT: COMMAND OF LOWER SUKTEL UGPL IRRIGATION PROJECT
LE22M794-C-LW-WS-DC-
10-06-24
3004 (Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SRS

(14.5x10) = 145.00 kN/m2


b) Load on PH Raft Inside (14.5x10) = 145.00 kN/m2
c) Surcharge Pressure 0.307x10 = 3.07 kN/m2
d) Soil pressure at the base of wall
0.307*21*15.5 = 99.93 kN/m2
e) Load on Raft projection =15.5x21 +10 = 335.50 kN/m2

Sensitivity: LNT Construction Internal Use


#
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
RIGHT
PROJECT: COMMAND OF LOWER SUKTEL UGPL IRRIGATION PROJECT
LE22M794-C-LW-WS-DC-
10-06-24
3004 (Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SRS

Sensitivity: LNT Construction Internal Use


#
L&T CONSTRUCTION
WATER & EFFLUENT TREATMENT IC
DOCUMENT NO. DATE
PROJECT:
RIGHT COMMAND OF LOWER SUKTEL UGPL
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
6/10/2024
(Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SPP

2.4 Sub Structure load

i)Sump full upto Pump floor level (Hydrotest)

Floor lvl. 207.50 m

16.00

191.500 m 160.00
160.00

a) b)

Depth of the water = (207.5-191.5) = 16.00 m

Unit weight of water = 10 kN/m3

a) Water pressure at base of the wall(Sump Inside)


(16x10) = 160.00 kN/m2

b) Load on PH Raft Inside (16x10) = 160.00 kN/m2

ii)Sump full upto MWL (Working condition)

Floor lvl. 207.50 m

MWL 206.00 m

14.500

B.O.S 191.500 m 145.00


145.00

a) b)

Height of Water outside till MWL = 14.500 m

Unit weight of water = 10 kN/m3


L&T CONSTRUCTION
WATER & EFFLUENT TREATMENT IC
DOCUMENT NO. DATE
PROJECT:
RIGHT COMMAND OF LOWER SUKTEL UGPL
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
6/10/2024
(Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SPP

a) Water pressure at base of the wall(Sump Inside)


(14.5x10) = 145.00 kN/m2

b) Load on PH Raft Inside (14.5x10) = 145.00 kN/m2

iii) Soil outside + water table upto MWL (Submerged condition):

Unit weight of water = 10 kN/m3

From DBR Saturated Unit weight of soil = 21 kN/m3

Coefficient of Earth pressure at Rest (ko) = 0.47

FGL 207.000 m

MWL 206.000 m
15.5
14.5
BOS 191.5 m

74.97 145 9.87 325.5


a b c d
Height of Water outside till MWL = 14.5 m

Height of soil above base of pump sump upto FGL = 15.5 m

a) Soil pressure (submerged) at the base of wall


0.47x (21-10)x14.5 = 74.97 kN/m2
b) Water pressure on sump wall (outside) till MWL
10 * 14.5 = 145 kN/m2
c) Soil pressure(saturated) at the base of wall in soil side
0.47x (21)x1 = 9.87 kN/m2
d) Load on Raft projection
(10 * 14.5) + ((21-10)x14.5 ) + (21x1 ) = 325.5 kN/m2
L&T CONSTRUCTION
WATER & EFFLUENT TREATMENT IC
DOCUMENT NO. DATE
PROJECT:
RIGHT COMMAND OF LOWER SUKTEL UGPL
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
6/10/2024
(Part-I)
DESIGNED CHECKED APPROVED
STRUCTURE: Pump house - Design calculation
MSR SYAM SPP

iv) Surcharge load

FGL 207.000 m

MWL 206.000 m
15.5
14.5
BOS 191.5 m

9.4 20

From DBR Surcharge load (q) = 20 kN/m2

a) Surcharge pressure acting on wall


0.47x 20 = 9.4 kN/m2
b) Surcharge Load on Raft projection
= 20 kN/m2

v) Sump Empty with outside soil + water table upto MWL (Saturated condition)

Unit weight of water = 10 kN/m3

From DBR Saturated Unit weight of soil = 21 kN/m3

Coefficient of Earth pressure at Rest (ko) = 0.47

FGL 207.000 m

MWL 206.000 m
15.5
14.5
BOS 191.5 m

153
325.5
a d

Height of soil above base of pump sump upto FGL = 15.5 m

a) Soil pressure at the base of wall


0.47x (21)x15.5 = 153 kN/m2
d) Load on Raft projection
(21x15.5 ) = 325.5 kN/m2
L&T CONSTRUCTION
WATER & EFFLUENT TREATMENT IC
DOCUMENT NO. DATE
RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT
LE22M794-C-LW-WS-DC-3004 10-Jun-24

TITLE : DESIGNED CHECKED APPROVED


Pump house - Design calculation
MSR SYAM/ADR PSP
2.7 DYNAMIC LOAD DUE TO SOIL AND SURCHARGE

Sump with soil upto FGL


Top level of sump wall = 207.50 m
Top level of Foundation = 191.50 m
Finished Ground level = 207.00 m
Height of wall = 16.00 m
Height of Soil to the footing top = 15.5 m

Density of soil = 21.0 KN/m3


Density of water = 10.0 KN/m3
Surcharge Pressure = 20.0 KN/m2
Angle of friction between wall & earthfill δ = 0 deg.
Slope of earth fill i = 0 deg.
Angle of internal friction φ = 32 deg.
Inclination of wall with vertical α = 0 deg.

Seismic Zone = II
Importance Factor = (I) = 1.5
Zone Factor = (Z) = 0.1
Sa / g = 2.5
Response reduction Factor = R = 5
Horizontal Seismic Coefficient (Ah) = = 0.1x1.5x2.5/(2x5)
Z I Sa / (2 Rg) = 0.038

Vertical seismic coefficient may be taken as Av = Ah* 2/3


Av = 0.025
+Ah/(1+Av) = 0.040
+Ah/(1-Av) = 0.040

λ (corresponding to +Av) = 2.29


λ (corresponding to -Av) = 2.29

Considering soil outside case


For +αv :

Cos(φ - λ - α) Cos(32-2.29-0) = 0.869


Cos(δ + α + λ) Cos(0+0+2.29) = 0.999
Sin(φ - i - λ) Sin(32-0-2.29) = 0.496
Cos λ Cos(2.29) = 0.999
Cos α Cos(0) = 1.000
Cos(α - i) Cos(0-0) = 1.000
Sin(φ + δ) Sin(32+0) = 0.530

Page 14
L&T CONSTRUCTION
WATER & EFFLUENT TREATMENT IC
DOCUMENT NO. DATE
RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT
LE22M794-C-LW-WS-DC-3004 10-Jun-24

TITLE : DESIGNED CHECKED APPROVED


Pump house - Design calculation
MSR SYAM/ADR PSP

2
= (1+0.0253)*0.869^2 1
x
(0.999x1^2x0.999) 1+((0.53x0.496)/(1x0.999))^0.5

= 0.780 x 0.437 = 0.341

For -αv :

Cos(φ - λ - α) Cos(32-2.29-0) = 0.869


Cos(δ + α + λ) Cos(0+0+2.29) = 0.999
Sin(φ - i - λ) Sin(32-0-2.29) = 0.496
Cos λ Cos(2.29) = 0.999
Cos α Cos(0) = 1.000
Cos(α - i) Cos(0-0) = 1.000
Sin(φ + δ) Sin(32+0) = 0.530

(1-0.0253)*0.869^2 1 2
= x
(0.999x1^2x0.999) 1+((0.53x0.496)/(1x0.999))^0.5

0.74 x 0.437 = 0.323

For αh = αv = λ = 0

Cos(φ - λ- α) Cos(32-0-0) = 0.848


Cos(δ + α + λ) Cos(0+0+0) = 1.000
Sin(φ - i - λ) Sin(32-0-0) = 0.530
Cos λ Cos(0) = 1.000
Cos α Cos(0) = 1.000
Cos(α - i) Cos(0-0) = 1.000
Sin(φ + δ) Sin(32+0) = 0.530

Page 15
L&T CONSTRUCTION
WATER & EFFLUENT TREATMENT IC
DOCUMENT NO. DATE
RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT
LE22M794-C-LW-WS-DC-3004 10-Jun-24

TITLE : DESIGNED CHECKED APPROVED


Pump house - Design calculation
MSR SYAM/ADR PSP

2
(1+0)*0.848^2 1
= x
(1x1^2x1) 1+((0.53x0.53)/(1x1))^0.5

= 0.72 x 0.427 = 0.308

[cos⁡𝛼/(cos⁡(𝛼−𝑖))]
Distribution of the ratio due to active earth pressure = 3 ( Ca - K a ) x

(For +αv ) 3x(0.341-0.308) = 0.10


(For -αv ) 3x(0.323-0.308) = 0.05

The maximum value considered for the design = 0.10

Static and Dynamic Pressure distribution diagrams due to soil

0.10 0 0 0

0.05
15.50 162.75
x = 8.06 50.1

7.75

0 325.5 0 100.3
(21x15.5) (0.308x21x15.5)
Distribution Vertical Dynamic earth Static earth
of Ratio Effective pressure pressure pressure

Page 16
L&T CONSTRUCTION
WATER & EFFLUENT TREATMENT IC
DOCUMENT NO. DATE
RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT
LE22M794-C-LW-WS-DC-3004 10-Jun-24

TITLE : DESIGNED CHECKED APPROVED


Pump house - Design calculation
MSR SYAM/ADR PSP

[cos⁡𝛼/(cos⁡(𝛼−𝑖))]
Distribution of the ratio due to surcharge = 2 ( Ca - K a ) x

(For +αv ) 2x(0.341-0.308) = 0.066


(For -αv ) 2x(0.323-0.308) = 0.030

The maximum value considered for the design = 0.066

Static and Dynamic Pressure distribution diagrams due to surcharge load

(20x0.066)
0.066 20 1.32 6.16

0.033
16 20 0.66
x = 6.16

7.75

0 20 0 6.16
(0.308x20)
Distribution Surcharge Dynamic sur. Static sur.
of Ratio pressure pressure pressure

Dynamic load due to soil and surchrarge is very less and compared to soil load
calculated

Page 17
L&T Construction
WATER & EFFLUENT TREATMENT IC

DOCUMENT NO. DATE


RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
6/10/2024
(Part-I)
DESIGNED CHECKED APPROVED
TITLE : Pump house - Design calculation
MSR SYAM/ADR PSP

2.5 HYDRODYNAMIC LOAD CALCULATION

Design Data:

Sump Particulars:

Length of wall in X-Direction (Clear) = 25 m

Length of wall in Z-Direction (Clear) = 12.15 m

Top of wall = 207.5 m


Full supply level = 206 m

Top of Raft = 191.5 m

Height of wall = 16 m

Height of water = 14.5 m

Thickness of Wall at top = 0.75 m

Thickness of Wall at bottom = 1m


2
fck = 30 N/mm
2
fy = 500 N/mm
3
Unit weight of concrete = 25 kN/m
3
Unit weight of water = 10 kN/m
L&T Construction
WATER & EFFLUENT TREATMENT IC

DOCUMENT NO. DATE


RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
6/10/2024
(Part-I)
DESIGNED CHECKED APPROVED
TITLE : Pump house - Design calculation
MSR SYAM/ADR PSP
Height of Water for Hydrodynamic Design:

height of water (h) = 14.5 m

height of wall (hw) = 16 m

0.75
1
X

0.75 12.15 Raft

25
1 Toe Slab RC Wall

0.75 207.50 m

206.00 m

14.5 RC Wall

1 Raft

Weight Calculations:

Weight of Tank wall = (25*((1*7*(25+12.15+12.15))


= 20591.875 kN
+(0.75*9*(25+12.15+12.15)+(0.75*16*12.15)))=

Mass of Tank wall,mw = 20591.875x 1000/9.81 = 2099070 kg

Volume of Water = 25 x 12.15 x 14.5 = 4404.375 Cum


L&T Construction
WATER & EFFLUENT TREATMENT IC

DOCUMENT NO. DATE


RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
6/10/2024
(Part-I)
DESIGNED CHECKED APPROVED
TITLE : Pump house - Design calculation
MSR SYAM/ADR PSP

Weight of water inside the sump (4404.375 x 10) = 44043.8 kN

Mass of water,m = 44043.8 x 1000/9.81 = 4489684 kg

For mass calculations, average height of wall and water are considered.

Analysis along X-Direction:

Parameters of Spring Mass Model:

For h/L = 14.5/25 0.580


Ref. Fig 3 of IS
1893 (Part mi/m = 0.610
2) :2014 pg. 4
mi 0.61 x 4489684 = 2738707 kg

mc/m = 0.430

mc 0.43 x 4489684 = 1930564 kg

hi/h = 0.375

hi = 5.438 m

hc/h = 0.605

hc = 8.771 m

For this case, h/L = 0.58, 43% of Liquid mass participates in convective mode

and about 61% of liquid mass contributes to impulsive mode.

Sum of total convective and impulsive mass is about -4%more than total liquid mass.

Time period:

Time period in Impulsive mode =

where,

d - deflection of the tank wall on the vertical centre-line at a height h when loaded by a

uniformly distributed pressure q,

where,
L&T Construction
WATER & EFFLUENT TREATMENT IC

DOCUMENT NO. DATE


RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
6/10/2024
(Part-I)
DESIGNED CHECKED APPROVED
TITLE : Pump house - Design calculation
MSR SYAM/ADR PSP

mw - mass of one tank wall perpendicular to direction of loading

Weight of one wall =12.15*((0.75*9)+(1*7))*25= = 4176.5625 kN

Mass of one wall,mw = 4176.6x 1000/9.81 = 425746 kg

Hence,

h= (2738707/2x5.438)+(425746x14.5/2) = 5.87 m

(2738707/2)+425746

q= (2738707/2+425746)x9.81 = 99957.01 N/m2

12.15 x 14.5

q= = 100.00 kN/m2

Deflection of the wall due to the pressure 'q' :

For simplified approach, the UDL is converted into a concentrated load acting at h:

Concentrated force, P = qxhx1

100 x 16 = 1600 kN

Length of the Cantilever is h = 5.87 m

1600

5.87

Deflection of the wall =

where,

E= 5000 x (30^0.5) = 27386.2 N/mm2

= 27386200 kN/m2

Moment of Inertia of Cantilever 1 x (1^3)/12 = 0.08333333 m4

Hence deflection, d = = 4.73E-02 m


L&T Construction
WATER & EFFLUENT TREATMENT IC

DOCUMENT NO. DATE


RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
6/10/2024
(Part-I)
DESIGNED CHECKED APPROVED
TITLE : Pump house - Design calculation
MSR SYAM/ADR PSP

Time period in Impulsive mode, Ti = 0.437 s


L&T Construction
WATER & EFFLUENT TREATMENT IC

DOCUMENT NO. DATE


RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
6/10/2024
(Part-I)
DESIGNED CHECKED APPROVED
TITLE : Pump house - Design calculation
MSR SYAM/ADR PSP

Time period in convective mode =


Ref. Fig 3 of IS
1893 (Part For h/L = 14.5/25 0.58
2) :2014 pg. 4
Kc = 2284019

Time period in Convective mode, Tc = 5.78 s

Calculation for Design Horizontal Seismic Coefficient:

As per design Seismic zone = II

basis report Damping percentage = 5%

Importance factor (I) = 1.5


Ref IS 1893
(Part 1) :2002 cl. Response reduction factor (R) = 5
6.4.2 of pg. 14
Zone factor (Z) = 0.1

Design Horizontal Coefficient for Impulsive mode:

Design Horizontal Seismic Coefficient in Impulsive Mode=

Time period in Impulsive mode, Ti = 0.437 sec.

Corresponding value of Sa/g for soil type: Rocky or hard soil

Sa/g = 2.5 T< 0.400


1.00 / T T≥ 0.400
Hence Sa / g = 2.29

Damping in the impulsive mode = 5%

Ref IS 1893 Horizontal Seismic Coefficient (Ah)i = 0.1 x 1.5 x 2.29 / (2 x 5) = 0.0344
(Part 2) :2014
cl. 4.4 of pg. 7

Design Horizontal Coefficient for Convective mode:

Design Horizontal Seismic Coefficient in Convective Mode=

Time period in Impulsive mode, Tc = 5.780 sec.


L&T Construction
WATER & EFFLUENT TREATMENT IC

DOCUMENT NO. DATE


RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
6/10/2024
(Part-I)
DESIGNED CHECKED APPROVED
TITLE : Pump house - Design calculation
MSR SYAM/ADR PSP

Corresponding value of Sa/g for soil type: Rocky or hard soil

Sa/g = 2.50 T< 0.400

1.00 / T T≥ 0.400

Hence Sa / g = 0.2500

Damping in the convective mode = 0.5 %

Ref IS 1893 Multiplying factor of 1.75 is used to obtain Sa /g


(Part 2) :2014 cl. values for 0.5 % damping from that for 5 % = 1.75
4.4 of pg. 7 damping.

(Sa/g)c = 0.438

Horizontal Seismic Coefficient (Ah)c = 0.1 x 1.5 x 0.44 / (2 x 5) = 0.007

Hydrodynamic Pressure:

Impulsive Hydrodynamic Pressure on wall:

where,

Qiw(y) - Coefficient of impulsive pressure on tank wall

ρ - Mass density of the Liquid

y - Vertical distance of a point on tank wall from the bottom of tank wall

Pressure piw at, y


14.50 m. i.e. at FSL 0.00 kN/m2
=

Pressure piw at, y


0.00 m. i.e. at the base of the wall 3.84 kN/m2
=
L&T Construction
WATER & EFFLUENT TREATMENT IC

DOCUMENT NO. DATE


RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
6/10/2024
(Part-I)
DESIGNED CHECKED APPROVED
TITLE : Pump house - Design calculation
MSR SYAM/ADR PSP

Impulsive Hydrodynamic Pressure on Base slab:

Impulsive Hydrodynamic Pressure on Base Slab:

where,

Qib(x) - Coefficient of impulsive pressure on tank base


Pressure pib at, y
0.00 m. i.e. on top of base slab 4.43 kN/m2
=
Convective Hydrodynamic Pressure on Wall:

The hydrodynamic pressure on the wall pcw, is given by:

where,

Qcw(y) - Coefficient of convective pressure on tank wall

Pressure pcw at, y


0.00 m. i.e. at the base of the wall 0.23 kN/m2
=
Pressure pcw at, y
14.50 m. i.e. at FSL 0.72 kN/m2
=

Convective Hydrodynamic Pressure on Base Slab:

The pressure on the base slab (y = 0 ) is given by:

where,

Qcb(x) - Coefficient of convective pressure on tank base

Pressure pcb at, y


0.00 m. 0.88 kN/m2
=

Pressure due to Wall Inertia:

Pressure on tank wall due to its inertia is given by:

where,

ρm = mass density of tank wall;

t = wall thickness.

Pressure on tank wall due to its inertia = 0.0344 x (0.875) x 25 0.76 kN/m2

This pressure is Uniformly distributed along the wall height.


L&T Construction
WATER & EFFLUENT TREATMENT IC

DOCUMENT NO. DATE


RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
6/10/2024
(Part-I)
DESIGNED CHECKED APPROVED
TITLE : Pump house - Design calculation
MSR SYAM/ADR PSP

Pressure due to Vertical Excitation:

Hydrodynamic pressure on tank wall due to vertical ground acceleration is given by

where,

y = vertical distance of point under consideration from bottom of tank wall, and

Damping in the impulsive mode = 5%


Time period of vertical mode of vibration for 5%
= 0.300 sec.
Damping
Corresponding value of Sa/g for soil type: Rocky or hard soil

Sa/g = 2.5 T< 0.400

1.00 / T T≥ 0.400

Hence Sa / g = 2.50

Design vertical seismic coefficient, Av = 0.0250

Pressure at, y = 0.00 m. i.e. at the base of the wall 3.56 kN/m2

Pressure at, y = 14.50 m. i.e. at FSL 0.00 kN/m2

Maximum value of hydrodynamic pressure:

The maximum value of hydrodynamic pressure,

((3.84+0.76)^2+0.23^2+3.56^2 = 5.82 kN/m2

This hydrodynamic pressure is about 4.1% of hydrostatic pressure


L&T Construction
WATER & EFFLUENT TREATMENT IC

DOCUMENT NO. DATE


RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
6/10/2024
(Part-I)
DESIGNED CHECKED APPROVED
TITLE : Pump house - Design calculation
MSR SYAM/ADR PSP
Hydrodynamic Pressure distribution on wall
Maximum hydrodynamic pressure,

Impulsive Convective Pressure due to


Pressure due to Max. hydrodynamic
Height of tank hydrodynamic hydrodynamic vertical
wall inertia, Pww pressure on wall,P
from base (m) pressure, Piw pressure, Pcw excitation, Pv
(kN/m2) (kN/m2)
(kN/m2) (kN/m2) (kN/m2)

0.0 3.84 0.23 0.76 3.56 5.82


0.5 3.83 0.23 0.76 3.44 5.74
1.0 3.82 0.23 0.76 3.31 5.66
1.5 3.79 0.23 0.76 3.19 5.56
2.0 3.76 0.23 0.76 3.07 5.47
2.5 3.72 0.24 0.76 2.95 5.37
3.0 3.67 0.24 0.76 2.82 5.26
3.5 3.61 0.25 0.76 2.70 5.14
4.0 3.54 0.26 0.76 2.58 5.02
4.5 3.47 0.26 0.76 2.46 4.90
5.0 3.38 0.27 0.76 2.33 4.76
5.5 3.28 0.28 0.76 2.21 4.61
6.0 3.18 0.30 0.76 2.09 4.47
6.5 3.07 0.31 0.76 1.96 4.32
7.0 2.94 0.32 0.76 1.84 4.15
7.5 2.81 0.34 0.76 1.72 3.98
8.5 2.52 0.37 0.76 1.47 3.61
9.5 2.19 0.41 0.76 1.23 3.22
10.5 1.83 0.45 0.76 0.98 2.81
11.5 1.43 0.51 0.76 0.74 2.37
12.5 0.99 0.57 0.76 0.49 1.90
13.5 0.52 0.64 0.76 0.25 1.45
14.5 0.00 0.72 0.76 0.00 1.05
Hydrodynamic pressure on base slab:
The maximum value of hydrodynamic pressure,

= ((4.43+0.76)^2+0.88^2+3.56^2 = 6.35 kN/m2

Maximum hydrodynamic pressure on base slab is 6.4 kN/m2.

Hydrodynamic pressure acting on walls and base slab are less than considered for Hydrotest/Working
condition. Hence water pressure during working condition is only considered for Earthquake load cases
for design of sumpwall.
L&T Construction
WATER & EFFLUENT TREATMENT IC

DOCUMENT NO. DATE


RIGHT COMMAND OF LOWER SUKTEL UGPL
PROJECT:
IRRIGATION PROJECT LE22M794-C-LW-WS-DC-3004
6/10/2024
(Part-I)
DESIGNED CHECKED APPROVED
TITLE : Pump house - Design calculation
MSR SYAM/ADR PSP

Sloshing Wave Height

Maximum sloshing wave height,

dmax = (Ah)c x R x L / 2

= 0.007 x 5 x 25 / 2

dmax = 0.4375 m

Free board provided = 1.5 m

Sloshing wave height is less than free board. Hence OK.

Anchorage Requirement

h/L = 14.5 / 25 = 0.58

1/Ahi = 1 / 0.0344 = 29.07

As h/L < 1/Ahi, No Anchorage is required.


L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
PROJECT: RIGHT COMMAND OF LOWER SUKTEL UGPL IRRIGATION PROJECT LE22M794-C-LW-WS-
10-Jun-24
DC-3004 (Part-I)
DESIGNED CHECKED APPROVED
TITLE Pump house - Design calculation
MSR SYAM SPP
Staircase Load- Switchyard flight-01
Design data :
Charc. strength of concrete, fck = 25 N/mm²
Yield strength of steel, fy = 550 N/mm²
Tread , T = 275 mm
Rise , R = 170.0 mm
Thickness of Waist slab , D = 200 mm

Dead load :
On landing area, T = 275
Self wt.of slab = 5.00 KN/m²
Finish load = 1.20 KN/m² R=
Total dead load = 6.20 KN/m² W= 170
323
On Stair area,
Flight load =
1
( DxW )  (TxR / 2)x25
T
= 1 / 0.28 ( 0.20x0.32 + 0.28x0.17 / 2 ) x 25
= 8 KN/m²
Live load :
On landing & stair area = 4 KN/m²

Total load :
On landing area, DL = 6.20 KN/m²
LL = 4 KN/m²
On Stair area, DL = 8.0 KN/m²
LL = 4 KN/m²

Span for stair area = 2.20 m


Span for landing area, L1 = 1.5 m
Span for landing area, L2 = 1 m

4 KN/m²
LL: Live load

6.200 KN/m² 8 KN/m² 6.2 KN/m²


DL: Dead load
1.500 m (L1) 2.20 m 1.000 m (L2)
4.70 m

DL : 16.339 kN 16.761 kN
LL : 9.400 kN 9.400 kN

Sensitivity: LNT Construction Internal Use


#
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
PROJECT: RIGHT COMMAND OF LOWER SUKTEL UGPL IRRIGATION PROJECT LE22M794-C-LW-WS-
10-Jun-24
DC-3004 (Part-I)
DESIGNED CHECKED APPROVED
TITLE Pump house - Design calculation
MSR SYAM SPP
Staircase Load- Switchyard flight-02
Design data :
Charc. strength of concrete, fck = 25 N/mm²
Yield strength of steel, fy = 550 N/mm²
Tread , T = 275 mm
Rise , R = 170.0 mm
Thickness of Waist slab , D = 200 mm

Dead load :
On landing area, T = 275
Self wt.of slab = 5.00 KN/m²
Finish load = 1.20 KN/m² R=
Total dead load = 6.20 KN/m² W= 170
323
On Stair area,
Flight load =
1
( DxW )  (TxR / 2)x25
T
= 1 / 0.28 ( 0.20x0.32 + 0.28x0.17 / 2 ) x 25
= 8 KN/m²
Live load :
On landing & stair area = 4 KN/m²

Total load :
On landing area, DL = 6.20 KN/m²
LL = 4 KN/m²
On Stair area, DL = 8.0 KN/m²
LL = 4 KN/m²

Span for stair area = 2.50 m


Span for landing area, L1 = 1.5 m
Span for landing area, L2 = 1 m

4 KN/m²
LL: Live load

6.200 KN/m² 8 KN/m² 6.2 KN/m²


DL: Dead load
1.500 m (L1) 2.50 m 1.000 m (L2)
5.00 m

DL : 17.525 kN 17.975 kN
LL : 10.000 kN 10.000 kN

Sensitivity: LNT Construction Internal Use


#
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
PROJECT: RIGHT COMMAND OF LOWER SUKTEL UGPL IRRIGATION PROJECT LE22M794-C-LW-WS-
10-Jun-24
DC-3004 (Part-I)
DESIGNED CHECKED APPROVED
TITLE Pump house - Design calculation
MSR SYAM SPP
Staircase Load- Electrical room panel landing platform
Design data :
Charc. strength of concrete, fck = 25 N/mm²
Yield strength of steel, fy = 550 N/mm²
Tread , T = 250 mm
Rise , R = 165.0 mm
Thickness of Waist slab , D = 225 mm

Dead load :
On landing area, T = 250
Self wt.of slab = 5.63 KN/m²
Finish load = 1.20 KN/m² R=
Total dead load = 6.83 KN/m² W= 165
300
On Stair area,
Flight load =
1
( DxW )  (TxR / 2)x25
T
= 1 / 0.25 ( 0.23x0.30 + 0.25x0.17 / 2 ) x 25
= 8.8 KN/m²
Live load :
On landing & stair area = 4 KN/m²

Total load :
On landing area, DL = 6.83 KN/m²
LL = 4 KN/m²
On Stair area, DL = 8.8 KN/m²
LL = 4 KN/m²

Span for stair area = 4.25 m


Span for landing area, L1 = 1.25 m
Span for landing area, L2 = 0 m

4 KN/m²
LL: Live load

6.825 KN/m² 8.8 KN/m² 6.825 KN/m²


DL: Dead load
1.250 m (L1) 4.25 m 0.000 m (L2)
5.50 m

DL : 22.012 kN 23.919 kN
LL : 11.000 kN 11.000 kN

Sensitivity: LNT Construction Internal Use


#
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
RIGHT
PROJECT: COMMAND OF LOWER SUKTEL UGPL IRRIGATION PROJECT
LE22M794-C-LW-WS-DC-3004 (Part-I) 06/10/2024

DESIGNED CHECKED APPROVED


STRUCTURE: Pump house - Design calculation
MSR SYAM SRS

2.5 Sub Structure load


Case 11) Pump Sump full with no soil & water outside (Hydrotest)
Floor lvl. 207.50 m

16.00

191.50 m 160.00
160.00
a) b)

Depth of the water = (207.5-191.5) = 16.00 m


Unit weight of water = 10 kN/m3
a) Water pressure at base of the wall(Sump Inside)
(16x10) = 160.00 kN/m2
b) Load on PH Raft Inside (16x10) = 160.00 kN/m2

Case 12) Pump Sump Empty- With outside Soil & water upto FGL with surcharge:

FGL 207.000 m

15.50

191.500 m

3.3 51.15 155 320.00


b) c) d)
a) sump upto FGL
Height of soil above base of pump = 15.50 m
Unit weight of water = 10 kN/m3
From DBR Unit weight of soil = 20 kN/m3
From DBR Surcharge load (q) = 10 kN/m2
Coefficient of earth pressure at rest (ko) = 0.33
a) Surcharge Pressure 0.33x10 = 3.3 kN/m2
Load acting on Pump Sump
b) Soil pressure at the base of wall
0.33x(20-10)x15.5 = 51.15 kN/m2

Sensitivity: LNT Construction Internal Use


#
L&T CONSTRUCTION
WATER & EFFLUENT TREATEMENT IC
DOCUMENT NO. DATE
RIGHT
PROJECT: COMMAND OF LOWER SUKTEL UGPL IRRIGATION PROJECT
LE22M794-C-LW-WS-DC-3004 (Part-I) 06/10/2024

DESIGNED CHECKED APPROVED


STRUCTURE: Pump house - Design calculation
MSR SYAM SRS

c) water pressure at the base of wall


15.5x10 = 155 kN/m2
c) Load on Raft projection =15.5x(20-10)+15.5x10+10 = 320.00 kN/m2

Case 13) Pump Sump full up to MWL + outside soil upto FGL with surcharge(Working)
FGL 207.000 m

MWL 206.0 m
15.50
14.50

191.50 m
145.00 145.00 3.3 51.15 155.00 320.00
a) b) c) d) e) f)
Height of soil above raft top of pump sump upto FGL = 15.50 m
Height of water above inside raft top sump upto MWL = 14.50 m
Load acting on Pump Sump
a) Water pressure at base of the wall(Sump Inside)
(14.5x10) = 145.00 kN/m2
b) Load on PH Raft Inside (14.5x10) = 145.00 kN/m2
c) Surcharge Pressure 0.33x10 = 3.3 kN/m2
d) Soil pressure at the base of wall
0.33x(20-10)x15.5 = 51.15 kN/m2
e) Water pressure at base of the wall (Sump Outside)
(10x15.5) = 155.00 kN/m2
f) Load on Raft projection =15.5x(20-10)+15.5x10+10 = 320.00 kN/m2