Modeling of Different Tower Grounding Systems Using Hybrid Continuous Circuit-Trapezoidal Integration Method
Modeling of Different Tower Grounding Systems Using Hybrid Continuous Circuit-Trapezoidal Integration Method
1 Introduction
The impulse impedance of grounding systems in transmission line towers is
an important parameter in lightning withstand levels of transmission lines. A
determining factor in transferring lightning current, when striking to the towers
or protective wires, is tower grounding systems [1]. The overvoltage produced in
such situations can cause back flashover and may flow through the transmission
line. The geometrical shape of the conductor and the soil resistivity are amongst
the most critical factors in electrical operation of a grounding system. Exact
characteristics and optimal structure of the grounding system in power frequency
(50 and 60 Hz) are discussed in [2, 3], where the tower grounding system is
modeled as lumped resistance. On the other hand, in transient conditions such as
lightning faults, the inductive and capacitive properties of conductors play a key
225
M. Asadpourahmadchali, M. Niasati, Y. Alinejad-Beromi
role. The modeling in these conditions is more sophisticated than that of a power
frequency modeling. Also, the lightning current shape and soil frequency
dependency are affective [4 6]. Impulse impedance is the most notable feature
of the grounding system in such circumstances. It is defined as the ratio of peak
voltage to peak current. Numerous methods have been proposed for transient
modeling of grounding systems so far. A summary of the methods is represented
as follows.
Transmission Line Method (TLM) models the grounding system similar to
wave propagation in the transmission line. This method can be solved in time and
frequency domains and can be implemented in numerical analysis software such
as EMTP [7 10]. Moreover, electrical parameters in this method can be
conducted by auxiliary software such as the finite element method. The coupling
between the conductor segments is taken into account and the accuracy of the
method is observed by comparing with experimental results. Another method is
Nodal Frequency Analysis Method which examines various structures of the
grounding systems in the frequency domain. However, this method is prone to
errors in the Fourier Transform. Thus, the high-frequency harmonics that can
miscalculate the impulse impedance is observed [11 14]. FDM and FEM solve
Maxwell equations around the grounding conductors by establishing meshes in
this volume to calculate voltage and electric field strength. Minimal
simplification and good accuracy are among the benefits of this method. On the
other hand, these methods are not suitable for practical applications as they are
complicated and time-demanding [15 17]. HCCTIM is the most recent method
in analyzing the grounding system, which adopts the continues circuit method
and the trapezoidal integration method [18, 19]. Electrical parameters are
calculated by integration rules. The accuracy of this method is verified with other
experimental results and modeling methods. Due to satisfactory required time and
the obtained results, the grounding system modeling in this paper employs the
HCCTIM.
This paper aims at comparing four common tower grounding structures:
counterpoise, crow’s foot, square and square with additional wires, modeled
using the HCCTIM method proposed in [18]. The validation of this method to
model the mentioned structures is verified by the CDEGS software. Moreover, to
compare these structures, the total length of the conductors is fixed and the
impulse impedance is calculated. Also, the effects of lightning current shape
properties, waveform rise time, and soil resistivity are evaluated. Based on these
results, the best structure is distinguished. The combined analyses of soil
resistivity and waveform rise time are also carried out.
The paper is organized as follows. In Section 2, the modeling procedure of
the HCCTIM is explained. In Section 3, the validity of the HCCTIM to model the
four common tower grounding structures is conducted with the CDEGS software.
226
Modeling of Different Tower Grounding Systems Using Hybrid Continuous Circuit…
2 Modeling Details
The procedure for grounding system is based on the Continues Circuit solved
with Trapezoidal Integration method as introduced below in summary.
2.1. Grounding system modeling
In the Continues Circuit method, grounding conductors are divided into
small segments called dl. Fig. 1 shows the electrical parameters between two
segments of a grounding system [18].
227
M. Asadpourahmadchali, M. Niasati, Y. Alinejad-Beromi
1
t 2C
Y1 t Re Le , Y2 Ge e ,
2 t
1
t N 1
I1 A Re Le Re (t ) I e (t nt ) ,
2 n 1
1
t N 1
I 2 A Re Le AT (t )Vn (t nt ) ,
2 n 1
N 1
I 3 0.25 A Ge A V (t nt ) ,
T
n
n 1
N 1
I 4 0.5 A I g (t nt ) I j (t ) .
n 1
where
N 1
2C
I1 2Ge Vn (t nt ) and I 2 Ge e Vn (t ) .
n 1 t
2.2 Lightning current waveform modeling
The lightning current waveform is represented by the Heidler function as
follows [11],
I 0 t 1
2
i (t ) e t 2 , (4)
1 t 1 2
228
Modeling of Different Tower Grounding Systems Using Hybrid Continuous Circuit…
exp 1 2 2 2 1 .
The parameters to make different lightning current waveforms are presented
in Table 1.
Table 1
Different lightning current waveform parameters (10 kA amplitude).
Waveform type [μs] I 0 [A] 1 [μs] 2 [μs]
0.25/100 9930 0.0075 140
1/100 9820 0.07 170
2.6/100 9700 0.238 140
5/100 9600 0.69 135
10/100 9430 2 125
3 Validation of HCCTIM
To validate the proposed model, CDEGS software is used to simulate a
counterpoise grounding system presented in Fig. 2. The CDEGS software can
simulate the impulse characteristics of grounding systems in the frequency
domain [20, 21]. The length, radius, and burial depth of the grounding wire are
20, 0.01 and 0.8 m, respectively. The resistivity of the soil is 150 Ωm and the
length of each element of the wire, (dl), is 4 m.
229
M. Asadpourahmadchali, M. Niasati, Y. Alinejad-Beromi
In Fig. 3, the GPR calculated by CDEGS software and the proposed method
is 193.5 kV and 203.6 kV, respectively. Moreover, the impulse impedance (ratio
of peak voltage to peak current) calculated by CDEGS software and the proposed
method is 19.4 and 20.4 Ω, respectively. The error rate for the proposed method
compared to CDEGS software is 5.2%, which is calculated by (6):
Z c Z c
. (6)
Zc
15
CDEGS Result
200
Proposed Method
Current (KA)
GPR (KV)
150 10
100
5
50
0 0
0 1 2 3 4 5
Time (sec)
230
Modeling of Different Tower Grounding Systems Using Hybrid Continuous Circuit…
counterpoise, crow’s foot, square and square with additional wires. Fig. 4 shows
these types of structures.
The impulse impedances of these structures differ in a definite condition. The
first stroke lightning with a current of 10 KA and 10/100 μs is applied to each of
these structures. To better compare the impulse impedance of these four
structures, the total length of the conductor in each structure is set 64 m. This
means that the length of the counterpoise wire is 64 m, the length of each branch
of the crow’s foot structure is 21.3 m, the length of each side of the square
structure is 16 m and the length of each side and the additional wire of the square
structure with additional wires are 8 m. The soil resistivity is assumed 150 Ωm
and other parameters are the same as Fig. 2. The GPR of these structures is shown
in Fig. 5.
100
Counterpoise
Crow Foot
80 Square
Square with Additional Wire
GPR (KV)
60
40
20
0
0 4 8 12 16 20
Time (sec)
Fig. 5 The GPR of the four mentioned structures.
231
M. Asadpourahmadchali, M. Niasati, Y. Alinejad-Beromi
Impulse Impedance ( )
Counterpoise Counterpoise
Crow Foot
Square
125 Crow Foot
Square
150 Square with Additional Wire
100 Square with Additional Wire
125
100 75
75 50
50
25 25
200 400 600 800 1000 200 400 600 800 1000
Soil Resistivity ( .m) Soil Resistivity ( .m)
(a) T = 0.25 μs (b) T = 1 μs
Impulse Impedance ( )
Counterpoise
Crow Foot
70 Square
Square with Additional Wire
60
50
40
30
20
10
200 400 600 800 1000
Soil Resistivity ( .m)
(c) T=2.6 μs
Fig. 6 Impulse impedance of grounding systems at soil resistivity of 50 m to 100 m
and lightning current rise-time of: (a) 0.25 μs; (b) 1 μs; (c) 2.6 μs.
Impulse Impedance ( )
Impulse Impedance ( )
Counterpoise Counterpoise
Crow Foot Crow Foot
50 Square 40 Square
Square with Additional Wire Square with Additional Wire
40 30
30
20
20
10 10
200 400 600 800 1000 200 400 600 800 1000
Soil Resistivity ( .m) Soil Resistivity ( .m)
(a) T = 5 μs (b) T = 10 μs
233
M. Asadpourahmadchali, M. Niasati, Y. Alinejad-Beromi
5 Conclusion
Reducing impulse impedance of the grounding system is one of the solutions
to decrease the possibility of occurrence of back flashovers in overhead
transmission lines. Various parameters affect the impulse impedance, such as soil
resistivity, lightning current waveform rise-time and grounding system structure.
In term of the type of grounding structure, four common ones, counterpoise,
234
Modeling of Different Tower Grounding Systems Using Hybrid Continuous Circuit…
crow’s foot, square and square with additional wires are modeled using the recent
accurate and truthful method, called HCCTIM. Also, the validity of the method
is confirmed using the CDEGS software. Soil resistivity is a significant parameter
due to its direct impact on the amount of leakage current flowing into the earth.
As a result, at high soil resistivity (1000 Ωm), the counterpoise structure provides
better performance thanks to having a longer conductor to pass the leakage
current to the earth. Nonetheless, at lower soil resistivity, the square with
additional wire structure is the best option. Moreover, decreasing the rise-time of
lightning waveform increases the impulse impedance of the grounding system as
it increases the inductance of grounding the system. In fact, in lower lightning
current rise-time, higher frequencies appear in the applied current which increase
the inductive impedance of grounding system. It is concluded that at low time
lightning current rise-time, the square with additional wire structure has the
lowest impulse impedance. However, it has been shown that the ratio of lightning
current rise time and soil resistivity should be investigated in grounding system
analysis at the same time. From this aspect, at a lower ratio, all of the mentioned
structures present the same impulse impedance. For ratios between 20 to 56, the
counterpoise structure shows a higher impulse impedance; however, other
structures show the same impulse impedance value. On the other hand, at higher
ratios, the square with additional wires has better performance or lower impulse
impedance. In conclusion, the results show that the square with additional wire
structure has the least impulse impedance compared to other conventional
structures.
6 References
[1] A.F. Otero, J. Cidras, J.L. del Alamo: Frequency-Dependent Grounding System Calculation
by Means of a Conventional Nodal Analysis Technique, IEEE Transactions on Power
Delivery, Vol. 14, No. 3, July 1999, pp. 873 878.
[2] IEEE Guide for Safety in AC Substation Grounding, IEEE Std 80-2000, IEEE, New York, 2000.
[3] C.- H. Lee, C.- N. Chang: Comparison of the Safety Criteria Used for Grounding Grid Design
at 161/23.9-kV Indoor-Type Substation, International Journal of Electrical Power & Energy
Systems, Vol. 49, July 2013, pp. 47 56.
[4] R. Rudenberg: Grounding Principles and Practices I - Fundamental Considerations on Ground
Currents, Electrical Engineering, Vol. 64, No. 1, January 1945, pp. 1 13.
[5] E.D. Sunde: Surge Characteristics of a Buried Bare Wire, Electrical Engineering, Vol. 59,
No. 12, December 1940, pp. 987 991.
[6] B.R. Gupta, B. Thapar: Impulse Impedance of Grounding Grids, IEEE Transactions on Power
Apparatus and Systems, Vol. PAS-99, No. 6, November 1980, pp. 2357 2362.
[7] A.P. Meliopoulos, M.G. Moharam: Transient Analysis of Grounding Systems, IEEE Transactions
on Power Apparatus and Systems, Vol. PAS-102, No. 2, February 1983, pp. 389 399.
[8] F.E. Mentre, L.D. Grcev: EMTP-Based Model for Grounding System Analysis, IEEE
Transactions on Power Delivery, Vol. 9, No. 4, October 1994, pp. 1838 1849.
235
M. Asadpourahmadchali, M. Niasati, Y. Alinejad-Beromi
236