TT Mag Issue 003
TT Mag Issue 003
Best Practices
Transformer
Testing, Maintenance
and Monitoring
Interview with John McDonald Testing and Maintenance: Tips for Reducing Wasted Time
GE Grid Solutions Best Practices for a Half Century When Testing Transformers
DeltaStar.com | 800.368.3017
SEARCHING FOR
NEW CUSTOMERS?
LET THEM FIND YOU!
LOOKING FOR
NEW MARKETS?
WE WILL SHOW YOU HOW.
Advertize
with TT
and strengthen your presence
in the transformer market.
Contact
transformer-technology.com
4 Table of
contents
Index Contents
Table of
Table of Contents_04
Transformers_40 30
Bringing Clarity to the Complexity of Best Practices
Condition Monitoring_46 for a Half Century
Transformer Aging, Degradation A well-maintained transformer can last more
than 50 years. If you catch a fault condition
and Online Oil Maintenance_48 early, there are corrective actions you can
take to prevent further damage to the
Balancing the naphthenic, transformer and avoid costly downtime
from catastrophic
paraffinic, and aromatic carbon failure.
transformer life_54
Transformer Technology September 2019 5
Issue 2
40 48
Better Testing Methods Reduced Oil
This article identifies the electrical Degradation & Aging
transformer tests that test equipment
users often struggle to perform efficiently Electric utilities should continually monitor and
and correctly, offering three field-testing reduce the level of contaminants and oil degradation
tips to address the transformer tests that products in transformers in order to maintain the
are often “time-suckers”. equipment’s performance, prevent failure, and
prolong the equipment life. Studies show that by
removing these promoters from the oil, the life of
a transformer can be significantly extended. This
article provides an overview of the aging process
of transformers, the chemistry involved, and which
compounds and byproducts further promote aging.
46
Bringing Clarity to
the Complexity of
Condition Monitoring
54
Transformer
Oil Properties
The composition of transformer oils can play an
important role in determining the performance
and lifespan of transformers. This article
highlights the key properties of transformer oils
with different chemical compositions and the
tests that were undertaken in determining if
oils with a higher paraffinic carbon content can
deliver enhanced performance versus those with
a higher naphthenic carbon content.
6 Table of
contents
Index Contents 62
Transformer
Table of
Transformer Hot Spot Hot Spot
Hunting_62 Hunting
Properly Categorizing Developing
Analysis_66
Withstand Test_72
66
Testing & Inspection Upon Arrival_76
Coming in December_114
72
Tironi 400 kV Natural
Ester Autotransformer:
The Successful Short
Circuit Withstand Test
Transformer Technology September 2019 7
Issue 3
88
Integrated Monitoring
Managing and mitigating the increased and changing risk
profile requires new methodologies for asset owners. Only
when monitoring all the key components and parameters
can the factors of health, risk and reliability be better
understood. A more holistic approach to transformer
monitoring can lead to converting data into more actionable
insights and, ultimately, optimize the maintenance cost and
effectively manage risk.
98
Tecsystem:
76 Make a Safer
World
Better Testing
& Inspections
100
Actions taken (or neglected) in the first
hours after a transformer’s delivery can
have long-term consequences. Here are
some in-depth inspection and testing
precautions that can help maximize
Automated
the transformer’s service life. Thermal
Monitoring
82
This article outlines how the latest
thermal imaging technology can
automate the thermal scanning process
Keeping the providing data that is constant and
more consistent. This allows several
Fleet in View opportunities for utility cost savings
including reduced travel and extended
asset life through conditioned based
maintenance.
8 Editors &
IMPRESSUM
Impressum Editors
Editor in Chief
Alan M. Ross, CRL, CMRP
Editor in Chief
Associate Editor Alan M. Ross CRL, CMRP
Lee Murray Transformer maintenance
Transformer reliability content editor and reliability
26 years industry
Contributing Editors experience
Diego Robalino, PhD, PMP, IEEE Senior
Member
Corné Dames, Independent transformer
consultant
Jon Trout, PE, Electric utility
Alan Sbravati, Global Technical Manager,
Insulating liquids
Contributing Editor
Diego Robalino PhD, PMP
Graphic design
IEEE Senior Member
Bekoncept Communication Boutique
Transformer condition
assessment and
Photo
diagnostics
Shutterstock.com
20+ years industry
Cover Photo Courtesy of The Snell Group,
experience
Barre, VT
Issue 3
transformer-technology.com
Contributing Editor
Alan Sbravati ME, MBA
Transformer insulating
materials
18 years of experience
10 Editor’s
Letter
A Changing Landscape
This issue might well be a keepsake for anyone Being involved with Transformer Technology has
interested in “Best Practices for Testing, Mainte- stretched me much more than I thought it would
nance and Monitoring” of transformers. There is and it has done so in three very distinct ways:
past, current and future “Best Practices”. How can
we have future ones? If they are future practices, 1. I am being challenged technically. While our
then they have not yet been proven or industry- Contributing Editors add technical expertise in
wide accepted. That is what defines a best practice areas I cannot, I am making a commitment to at
by the way. Proven and accepted practices! least understand what our authors are sharing,
to grasp the fundamentals and make sure they
But in the face of advancing technology and new will be of interest to the average reader. We
methodologies, we have to know when to let go are not writing to only the technologists but
of the past and accept new advances. As I read to a broad array of transformer professionals.
Richard Harada with his article on the use of re- To do that, we must be relevant, reliable and
mote infrared monitoring, it is clear that he is make sure we don’t ever use the magazine arti-
sharing a future best practice. Bob Rasor, Jason cles as filler. Our goal is to create a publication
Dennison and Brandon Dupuis shared the best that lives on, one that is shared digitally and in
of the past and current and of course, the moni- print because of the value of the information
toring article from Marco Tozzi hit the nail on the we publish. That leads me to my second area of
head in both current and future technology for growth.
monitoring.
Issue 3
Alan M Ross
the face of Amazon, so accept the change and
embrace it for the opportunity it creates. Every
printed issue is what we aim at to complete a
theme. The first three have been New Technol-
ogy, The Dry Type Revolution and now this edi-
tion themed, Best Practices of Testing, Mainte-
nance and Monitoring.
Magazine
12 AT A GLANCE
At a Glance
Issue 3
Since 2013, Georgia Power has invested more than $4.1 billion in
expanding transmission and distribution infrastructure, replacing
aging transmission assets and strengthening the reliability and
resiliency of the electric grid, and plans to invest an additional
$1.3 billion in a grid investment plan over the next three years.
“It’s been predicted that the smart grid sensor market will reach
$39 billion by 2019,” said Ajay Raghavan, PARC research area
manager and principal investigator leading the effort. “We are
working on innovative low-cost embedded fiber-optic sensors
that can reliably monitor conditions in a broad variety of harsh
environments, including those seen in smart grids, so that we can
understand the real-time state of critical systems.”
Issue 3
He will join ABB on February 1, 2020 and succeed CEO, Peter Voser,
in this role on March 1, 2020. At that time Peter Voser will revert to
his position at ABB solely as Chairman of the Board.
“The Board is pleased that Björn Rosengren will be taking the lead
at ABB, bringing with him a proven track record of value creation
and exactly the managerial skills ABB needs during the next stage
of its transformation,” said ABB Chairman and current CEO, Peter
Voser. “After undertaking a thorough search, the Board is convinced
that Björn Rosengren is the best candidate for the role.”
YOUR PASSION
AND KNOWLEDGE
ARE IMPORTANT
TO US
PUBLISH
WITH TT
Are you passionate and knowledgeable
Contact us at
[email protected]
to find out how you can
become part of the
Transformer Technology
community.
Transformer Technology September 2019 17
Issue 3
Events
CHICAGO, IL
Electric Power
Reliability Summit
September 17-18, 2019
AUSTIN, TX
Coiltech 2019
September 25-26, 2019
PORDENONE, ITALY
Advanced Research
Workshop on
Transformers -
ARWtr 2019
October (6)7-9, 2019
CORDOBA, SPAIN
EuroDoble
Colloquium 2019
October 20–23, 2019
PORTO, PORTUGAL
IEEE Transformers
Committee - Fall
Meeting
October 27 - 31, 2019
COLUMBUS, OH
The Transformer
Experience –
Weidmann 18th
Annual Technology
Photo by Shutterstock
Conference
November 5-7, 2019
SAN ANTONIO, TX
18 AT A GLANCE
The 250 MVA, 400 kV autotransformer was tested at the CESI lab in
Rondissone, Italy. The company will now start a series production
of these autotransformers that will be in service in the Italian
transmission network.
The plans, as they have now been presented, call for reducing
approximately 2,700 jobs worldwide over the course of several
years, with around 1,400 of these jobs being in Germany.
Issue 3
Most of the electricity transmitted by the line will come from the
Zhundong coal-fired power plant in northern Xinjiang.
Source: Reuters
Source: Reuters
ABB has won an order from MHI Vestas Offshore Wind for
the supply of its compact WindSTAR transformers for
installation in wind turbines in the North Sea.
Issue 3
Source: Open4business.com
22 AT A GLANCE
Source: Qualitrol
Issue 3
After the initial test in the Netherlands, the transformer was shipped
back to China for further customer acceptance tests and visual
inspection of the active part, before it received a certificate of short-
circuit performance.
Source: PR Newswire
24
John McDonald
Feature
Interview
Photo: GE
Transformer Technology September 2019 25
Issue 3
John McDonald was in sixth grade when he realized he wanted to be an electrical engineer. A half century
I started adding
intelligence to
the grid in the
work I was doing later, he is a legend in the industry.
Transformer Technology: What are your with me and I don’t work with others.” We will
thoughts on the Smart Grid, and how have you not have a smart grid with proprietarization.
seen technology progress towards that goal How have you been able to bring more of
recently and in the past? an integrated approach to it through your
involvement with IEEE?
John McDonald: About 12, 13, or 14 years ago we
started hearing the term “Smart Grid,” but a lot
of us that had been in the industry a long time
initially kind of took offense to it, because this
JM The days of standalone devices
are long gone. But it only works if
the different vendors with their technology
wasn’t new. I started adding intelligence to the components all comply with the same set of
grid in the work I was doing going back to 1974 standards. There’s much more emphasis today
when I started doing my full-time engineering on industry standards and that’s why IEEE
work. is so important as a standards development
organization. Even though there are 39 societies,
I actually call it the “Smarter Grid.” and 7 councils in IEEE, the Power & Energy
I differentiate what intelligence we have been Society writes over 50 percent of the standards.
adding to the grid over the past 20 to 30 It just shows, with respect to the grid, how
years, and what is so different [now]. The important standards are.
biggest difference is that we have a lot of new
technology that is being developed much more I have chaired the substations committee,
quickly than ever before, and it gives us much and we have 500 experts writing all the
more functionality. There are many, many more standards for the substation. Up until about
things that we can do on the grid than we were the mid-90s, everything was proprietary. The
able to do before. communications and automation were all
proprietary, because we didn’t have standards
Issue 3
I differentiate the
intelligence we have
been adding to the
grid over the past 20
to 30 years from the
technologies that we
have now. What we
have now I call the
“Smarter Grid”.
mutually agreed
upon. That changed
TT Many of the Legends I have spoken to
as part of this series are Eagle Scouts,
and so are you and your son. Tell us about that
part of your life.
in the mid-90s, and
from then on, the JM My father went through scouts
himself and he really, really enjoyed
the benefits of it. My grandparents were
industry requires active, and my dad took my [younger] brother
and me and made sure we were in Cub Scouts.
industry standards My mom was our den mother, so my mom had
the den meetings in the afternoon. My dad
that are not was Scoutmaster for a while in Boy Scouts.
We went through Boy Scouts
proprietary. with a lot of support from
our parents. I’m a kind of
a very driven person, very
competitive. I’m the type of
person who always wants
to see things through. The
challenge of getting the ranks
and the merit badges… that
was important to me.
I became an Eagle Scout and
I found that it really helps.
[It] not only helps you with
your resume, but it also helps
you. In Scouts you’re not only
managing peers, but you’re
also managing adults, the
leaders of the troop. I said that
when I hopefully got married
and had kids of my own, I’d
hopefully have a son, and I
would make sure my son had
the same opportunities [my
parents] gave to my brother
and me.
Transformer Technology September 2019 29
Issue 3
TT You’ve run a
program called
Key Insights in Career
Management for IEEE PES
student members and young
professionals. How did you
do it, and why?
Best Practices
for Transformer
Testing and A well-maintained transformer
can last more than 50 years. If you
Maintenance
catch a fault condition early, there
are corrective actions you can
take to prevent further damage to
the transformer and avoid costly
downtime from catastrophic
by Jason Dennison failure.
and Bob Rasor
Issue 3
Did you know? Convective and conductive forces inside the transformer play a
key role in homogenizing the liquid and its characteristics inside the tank of the
transformer. This homogenous liquid is what you want to send as a representative
sample to an analytical lab.
Issue 3
Transformer oil
testing lab
Liquid Testing
There are a great number of tests that This group of tests is the foundation Other specialized tests exist to
can be performed on dielectric liquids for assessing the health of a determine certain impurities or to
that can help assess the health of a transformer. Depending on the confirm physical properties of the
transformer. The most common tests criticality of a transformer—the liquid, such as Corrosive Sulfur, Flash
are indicators of general aging and estimated impact of potential loss— and Fire Point, Particle Counts, and
contamination, moisture incursion, further testing may be required. Filming Compounds.
and incipient faults. These tests are: These tests can be performed during
• Liquid Screen – A group of tests
that looks for premature aging of
routine testing or when diagnostics
suggest that an issue is present.
This is not an exhaustive list of tests
available, and there are other tests
the dielectric fluid. A liquid screen Some of these tests include: that may be useful too. These tests
can also point to contamination
from internal issues such as
• Power Factor – This test can
indicate liquid breakdown,
are typically ordered based upon
the results from regularly scheduled
coking or sludge, or external issues contamination, and, in some cases, testing.
such as contamination from other moisture.
liquids. • Inhibitor – Transformer oil typically Ultimately, which tests to perform at
• Karl Fischer – This test
determines the presence of
includes an inhibitor to help
prevent oxidation, which can lead
what interval is a decision that asset
owners should make through the
moisture in the dielectric liquid, and to premature aging of the liquid. lens of maximizing the reliable life of
the liquid temperature determines The weight percentage can be the transformer.
the percent saturation of water. determined by this test.
This is an important test because
moisture in dielectric liquids can
• Furan Analysis – A byproduct of
paper degradation is the formation
A transformer powering the light in
the parking lot, for example, would
lead to oxidation and formation of certain compounds, called be considered less critical than a
of acids that degrade the solid furans, which can be correlated transformer that powers a data
insulation. to the tensile strength of the solid center or operating room. It’s also
• Dissolved Gas Analysis (DGA) – insulation in the transformer. important to view the power system
A DGA detects the presence of key
gases that can identify incipient
• Metals in Oil – By burning off
organics in the liquid, this test can
as a whole. Performing an impact
assessment across the power
faults from low- to high-energy determine very low quantities of system can identify opportunities
events and can point towards issues metals such as aluminum, copper, to shore up the reliability in any
with the solid insulation. and iron. operation.
34 BEST PRACTICES
FOR A HALF
CENTURY
Diagnostics
The key
Accurate data alone is not enough is left over from the welding process
to keep an electric power system during manufacturing. Pairing to useful
viable. You don’t need just the the guide recommendations with
data; you need to be able to make practical knowledge, it is possible
good decisions based on that data. to make an informed decision on diagnostics is
Translating data into insights requires whether to perform ongoing DGA to
expertise. be sure that the result is not indicative
of a fault and to establish in understanding
While industry organizations like a baseline for future analysis.
NFPA have standards on manual
sampling, and ASTM has standards Diagnostics should be action the actual
on sampling liquids and performing oriented. It is common for experts
tests, many standards are available
that can assist in diagnosing the
to see early warning indications of
problems in test data, and for them
transformer so
condition of a transformer. IEEE to recommend further action. Often,
guides such as C57.106 and C57.104, however, these warnings are ignored. that the guides,
and IEC guides such as 60567 and Many failures could have been
60599, pertain to acceptance criteria avoided if they had been addressed
and result interpretation. earlier. standards,
The key to useful diagnostics There are thousands of transformers
is in understanding the actual in our database that are more than and practical
transformer so that the guides, 50-years-old. Achieving this length
standards, and practical experience
can be used in concert to assess its
of service depends on the people
responsible for maintenance having a experience
health. For example, without practical reliability mindset and the capability
knowledge of the transformer, the
recommendations in the guides
to address warning signs as early
as possible. Some issues can be
can be used
might state that the level of acetylene fixed without an outage, though
in a DGA of a new oil-filled cabinet many issues do require planning in concert to
transformer is a concern, and a shutdown. While inconvenient, a
recommendations range from “test it planned outage is much more cost-
again” to “purchase a DGA monitor” effective and manageable than assess its
to “shut it down immediately.” an unplanned event that could
But it is possible that the acetylene severely disrupt operations for an
inside the new cabinet transformer undetermined period of time. health.
Monitoring
Issue 3
The advent of continuous monitoring analysis. The best reliability plans will related to its tensile strength.
changes the landscape on the exhibit the flexibility to capitalize on Shorter cellulose molecular chains
quantity of data available by orders both types of data; the pairing of all mean lower tensile strength and
of magnitude. This volume of that data with in-depth knowledge will weaker paper.
data can be a powerful asset for drive an organization toward more
understanding the ongoing condition intelligent decision-making. Oxidation and moisture degradation
of a transformer. It does, of course, weaken the paper insulation. Acids
change some of the skillsets required Oxidation, Aging and are created in transformers due
to care for critical assets. The Reliability to oxidation and will weaken/age
job market for business and data the insulation. Since the insulation
analysts is exploding as companies The paper insulation is what gives strength (DP) is based on the
come on board with data-rich the transformer its mechanical cellulose molecular chain length,
applications. It is no longer enough strength. This remains the most damage from acids (created during
to just acquire data; you must also be prominent factor in the reliable life of oxidation) to the chain results in
able to make it understandable and your transformer. The term “reliable lowered tensile strength for the
actionable. life” refers to the transformer’s ability transformer’s eventual inability to
to take on expected stresses— withstand original design stresses.
Laboratory testing and continuous load variations, surges, lightning, The damage is irreversible.
monitoring are both here for the and temperature variations—
long haul. Traditional laboratory and maintain servicing levels and The paper insulation exists in a
analysis generates high quality, high frequency. mineral oil environment. If the oil
integrity data from systems and stays in acceptable condition, the
processes that have been honed over How Does the Insulation paper has an optimal environment
decades against methods that are Weaken? to maximize its life and reliability.
defined by standards bodies such However, oil is a hydrocarbon
as ASTM. Continuous monitoring Short answer: oxidation and and subject to the chemical laws
as an emerging technology is going moisture degradation. Strength governing it. Heat, moisture, and
to play an increasingly larger role in is measured by the Degree of oxygen are present in transformers
helping asset owners make faster Polymerization (DP). DP is a and cause oxidation where acid is
maintenance decisions, and the measurement of the average length formed, as well as other destructive
volume of the data can be used for of the cellulose molecule chains that oxidation byproducts, including more
trending and for more sophisticated make up the paper and is directly moisture.
Regular intervals of fluid testing true, however, that the paper can a transformer, moisture and heat
are economical and also still the also oxidize independently of the oil. can be reduced. Passive dryers
most commonly used means to 2. Initial small amounts of this acid work, but if load and ambient
monitor transformer reliability. Aging are first absorbed by the paper are driving up temperatures,
indicators include elevated acid, insulation. Oil levels remain in the additional auxiliary cooling may
lowered IFT, elevated moisture and “acceptable” range. At this point, also be needed to reduce these
Liquid Power Factor along with the keeping oxidation inhibitor at the components to oxidation.
creation and presence of furanic proper levels will continue to retard 3. Apply Oxidation Inhibitor to
compounds. When cellulose paper oxidation. the oil. Inhibitor is a primary
degrades, furans are liberated. Furans 3. The “questionable” range is when way to combat oxidation and is
are created from the paper and to take action with oil processing. supported by IEEE C57.106. As
found in the oil. They are measured Keeping the acid below the the oil produces free radicals, the
in parts per billion. Additionally, there damaging range will avoid loss of oxidation inhibitor will react with
are more chronic aging dissolved the paper insulation’s strength. and stabilize them, thus stopping
gases present, such as carbon 4. Once the acid has reached 0.1 mg the oxidation chain reaction in its
monoxide (CO). Electrical testing and KOH/g, damage has begun, and earliest stages. Ideally, oxidation
the strength of the insulation also action is vital. Stop further damage inhibitor levels should be kept at
correlate to Insulation Power Factor. with Hot Oil Cleaning. Despite the 0.3 percent or greater.
name, Hot Oil Cleaning cleans
Typically, the age of a transformer the insulation, not just the oil, by What about damage already done?
does not necessarily affect its ridding the insulation of destructive Once the cellulose is damaged,
performance—unless there is a acids and sludges. At this stage, insulation life cannot be restored. The
fault condition. Severely overheated furans can be rising and may be damage is irreversible. Here are some
transformers can degrade rapidly. 500 ppb or greater. points to consider:
It is important to make sure cooling
packages are working properly and
5. Once furans are over 1,000 ppb,
the paper will show significant
• Hot Oil Cleaning improves the
condition of the insulation. The
levels are maintained. If fluid levels damage. Any action taken can slow smaller the amount of acid in the
drop below the cooling ports, severe further damage but will not recover insulation, the lower and slower is
damage can happen quickly. Visual what has been lost. its destructive effect.
inspections of all the mechanical
aspects of a transformer must be a How is the acid in the transformer
• There is a point whereby, looking
at the condition of the insulation,
part of all sampling and services. corrected? Hot Oil Cleaning and the oil, and results from other
absorptive clay treatments can create important indicators such as IR
Can the Damage from a solvent-like action to dissolve and and electrical testing, the best
Acids Be Limited? remove the acid and sludge. As the oil course of action is to replace the
is heated and cleaned, it also cleans transformer.
Yes, at first. But as time goes on
and corrective action is deferred, the
the paper insulation when done with
the proper treatment recipes. The
• Consider the past furan and DP
levels prior to oil reclamation. Most
acids and other oxidation products controlling factors for effectiveness oil processing with clay filtration
eventually form sludge, which leads are heat, dwell time, and adsorbent such as Hot Oil Cleaning will strip
to localized overheating. Heat is clay in a vacuum oil purifier. furans from the oil.
one of the necessary conditions for
oxidation. Therefore, additional heat How can you slow or prevent Consider the time and temperatures
further intensifies the oxidation, oxidation? Processing services needed for proper and complete
and again, results in more water exist to prevent, slow, or even stop cleaning. Oil can be cleaned in just a
that further intensifies oxidation. oxidation. Here are a few common few passes in lower temperatures.
Servicing the still reliable paper approaches in our industry: It takes more passes at a higher heat
insulation early will limit damage. 1. Control the moisture. Moisture to provide adequate cleaning of the
The acid, being polar, is quickly reduction is key to slowing and paper. If the oil only is cleaned and the
absorbed into the paper and leads stopping oxidation. As much as paper left untreated, within months
to detrimental effects, namely small 75 percent of transformers with the acids will come back out of the
and larger amounts of acid that will oxidation issues in our database paper and oil qualities will again move
eventually cause damage and have an accompanying moisture away from the “acceptable” range.
can be corrected. There are widely presence. It can be a little confusing
accepted stages to this aging as to which came first, since Healthy insulation is promoted by
process: moisture not only causes oxidation, controlling the harmful byproducts
1. Acid is usually first generated in the but is also a byproduct of oxidation. of oil oxidation. This optimizes the
oil by oxidation from the presence 2. Dry and cool the oil. Where strength of the paper insulation which
of heat, oxygen, and moisture. It is oxygen from the air is present in is the reliable life of the transformer.
Transformer Technology September 2019 37
Issue 3
As the oil is
heated and
cleaned, it
also cleans the
paper insulation
The reliable life of the
transformer depends on the
integrity of its paper insulation.
when done
with the proper
Combustible Gas Issues
treatment
Combustible gas levels are an Some leach back is expected for the
indicator of an abnormal condition first several months.
in a transformer. They are created recipes. The
by excessive localized or general Staying ahead of leaks and
overheating. Extreme temperatures
and arcing are identified by a key
maintaining the correct level
is another important aspect of controlling
gas: acetylene. These conditions are reliability in transformers. The regular
typically acute and must be dealt with
immediately. The following are typical
visual inspection assures this. It is
recommended to perform a visual
factors for
steps taken to correct them: inspection no fewer than four times
1. Retest to confirm the condition. a year. The following are some of the effectiveness
2. Arrange an immediate inspection aspects of the inspection:
and include electrical testing,
depending upon the severity. Many
• Level in the transformer. Keep in
mind, some training is required are heat, dwell
issues can be field-corrected. to interpret the level gauge with
Untanking is rarely done in the field, respect to the temperature of the oil.
so there are repairs that require Oil expands 1 percent for every 10 time, and
taking the unit out of service and degrees Celsius. A 25-degree Celsius
shipping it to a repair facility.
3. Drain and perform an internal
measurement is “normal” or “low” if
the oil temperature is significantly adsorbent clay
inspection. higher than 25 degrees Celsius.
4. Make repairs in the field, when • Leak inspections.
in a vacuum oil
possible.
5. Refill the transformer. Care must
• Gauge information. A consistent
“zero” psi on a pressure vacuum
be taken to fill with the proper gauge often indicates a leak, as the purifier.
procedures. Vacuum rated transformer is not holding pressure
transformers must be vacuum or vacuum. A transformer with a
filled if the core has been exposed. leak is “breathing” ambient air and,
UHV units require a complete drain therefore, humidity in and out of
and fill any time the oil is lowered. the transformer. The moisture is
however typically only “in” as the oil
If refilling a lower voltage unit, and insulation have a high affinity
cleaning can be performed with a for moisture.
cartridge filter. Consult with OEM • Paint and rust condition.
requirements. In this case, the oil
will still contain combustible gases
• Bushing and insulator surface
condition.
•
Photo: SDMyers
Whether you’re conducting oil handle changes discovered while Data supports the principles and
processing, doing transformer repair, on site. action-related reliability steps in this
or electrical testing, there are best
practices that are important to follow
• Ask that the provider have an
equipment reliability program to
paper. In a paper published by CIGRE
and the IEEE, which considered 1,500
for safety and reliability. assure excellence in the equipment transformers, the transformers with
being sent including safety gear services to combat oxidation and
It is helpful to define procedures inspection and key calibration moisture showed more than six years
and equipment to optimize the records. of extended life per service rendering.
services rendered. For instance, in
oil processing, it is important to not
• Refer to C57.106, the “Oil Guide,”
which can be used for oil quality
This doubled the life of the average
transformer, which was reported in
just filter oil, but also to address requirements. many studies to be under 20 years.
cleaning the paper insulation. When
oil processing, require pumping
• Follow IEEE C57.93 and C57.140
for field drying and vacuum filling. Additionally, by maintaining frequent
records to assure the temperature Be aware of the required set times visual inspections and regular fluid
and passes will achieve the required after filling before energizing when and electrical testing, the probability
results. Reaching 70 degrees Celsius the core is exposed. of a surprise lapse in reliability is very
is optimal to allow the oil to reach the
aniline point where it can dissolve oil
• Ask that the provider have an
equipment reliability program to
small. As indicators trend toward
aging, plans for contingency and an
generated sludge and acid assure excellence in the equipment acceptable timetable for a planned
being sent, including safety outage will negate further concerns
Additionally, moisture cannot gear inspection (PPE) and key for a lapse in power provision.
be corrected by “pumping” on a calibration records.
transformer, as there is approximately There are transformers backed up
100 times more moisture in the paper Environmental by spares or double-ended subs. We
insulation than there is in the oil. Considerations refer to these more important units as
Instead, use either vacuum dryout being system critical. Units that shut
techniques or online moisture dryers,
as defined by the Field Guide of IEEE,
• Be sure the provider has Field
SPCC (Spill Prevention Control
down operations, or huge segments
of your operation, are considered
C57.140.7. Online dryers are effective and Countermeasures) training, mission critical. This reality takes the
in moisture reduction. including the use of spill berms, units with the mission-critical rank
and that they have a spill kit on and looks at condition or monitoring
Selecting and Working with site. and moves them to the top of the
a Contractor • Process units from lowest to
highest so as to never add to
priority list. Meanwhile, a system-
critical unit in bad shape will also be
It is always important to contract with the PCB content of the next
an experienced provider with a proven transformers. If you have PCBs,
safety record and a well-documented expect some surcharges—there are
training program. There are a number legitimate costs to do it right.
of contractor-related criteria to be
included in the scope of the project.
• Be aware of the advantages of
the new Ester liquids. These are
Always create a written, clear scope popular for a reason as they hold
of work for any bidding purposes. up well. They are fire resistant
This will help avoid short cuts and (Fire Point of 300 degrees Celsius)
define expectations. and they are eco-friendly. Ester
fluids can be processed in most
As mentioned, you should require equipment with a pre- and post-
pumping records to achieve the flushing adder. Getting some
required results when oil processing. esters in oil is not much of an
When electrical testing, make sure it issue, but too much oil (>6 percent)
is defined as who is disconnecting will lower the flash point.
and grounding. When hiring a
contractor, you should:
• Use a filtering clay when oil
processing equipment that
• Define work hours and how
to handle changes that are
improves acid. There are
environmentally friendly solutions
discovered while on site. At a for regeneration that avoid landfill
minimum, have the provider control or incineration of the oily waste.
and monitor moisture and the In general, you can expect a drum
acidity of the oil. of waste for every 3,000 pumping
• Define work hours and how to gallons of oil.
Transformer Technology September 2019 39
Issue 3
Three Tips
for Reducing
Wasted Time
When Testing
Transformers Brandon Dupuis received a B.S. Electrical
Engineering from the University of Maine.
He joined OMICRON electronics Corp. in 2013,
by Brandon Dupuis where he presently holds the position of
Regional Application Specialist for trans-
former testing. Brandon’s focus is currently
on standard and advanced electrical diag-
nostics for power transformers and circuit
breakers. Presently, Brandon is a well-known
OMICRON instructor teaching electrical trans-
former diagnostic testing theory, applica-
tion, and test result analysis, which includes
both presentations and hands-on training.
Brandon is an active member of the IEEE
PES Transformers Committee.
Issue 3
Review the “Power Factor Performing offline electrical tests on transformers can be time-consuming,
Checklist” Prior to Testing especially when the field measurements are not captured correctly the first
time. This article identifies the electrical transformer tests that test equipment
Without a doubt, the transformer users often struggle to perform efficiently and correctly. Three field-testing
test that customers most struggle tips will be provided, to address the transformer tests that are often “time-
with is the transformer Power Factor suckers”. By building awareness, test equipment users can better avoid
test (which includes the Overall the situations where a significant amount of time is lost due to retesting,
Test, the Bushing C1 Test, and the troubleshooting, and collaborating with test equipment manufacturers.
Bushing C2 Test). Unfortunately, the
Power Factor test is highly sensitive
to the test environment, to the test
lead connections, and to the test
• Are the surfaces of the bushings
dry (and reasonably clean)?
in resistor”, which has been
known to influence the Power
specimen’s earth-ground connection, Moisture on the surfaces of Factor measurements, when the
among other things. Since the the bushings can significantly transformer is tested in the neutral
Power Factor measurement is highly influence a Power Factor tap-position. Specifically, Federal
sensitive, obtaining the correct (i.e. the measurement. In most cases, Pioneer Electric and Federal Pacific
valid) Power Factor measurements in using a clean, dry rag to dry Electric transformers with LTCs
the field is challenging. the surfaces of the bushings have been known to exhibit this
is sufficient. In cases where behavior.
The high sensitivity of the Power Factor excessive surface contamination
test is a double-edged sword: On one
hand, the high sensitivity makes the
on the bushing surfaces is
present, using Windex or Collinite
• Ensure that the exterior surface of
the test equipment’s high-voltage
Power Factor test a powerful tool for may be used to clean the surfaces cable is not touching any surface
identifying compromised insulation of the bushings, and thus, of the transformer, at the “far end”
(e.g. moisture ingress, contaminated may improve the Power Factor where the test terminal is being
oil, a “bad bushing”, etc.). On the other measurements. energized.
hand, the high sensitivity makes A conservative approach is to
the Power Factor test prone to
measurement error.
• Are the groups of bushing
terminals short-circuited together?
ensure that the last two feet of
the far end of the test equipment’s
All primary side (H) bushing high-voltage cable is not touching
To save wasted time and prevent terminals must be shorted the transformer tank, the surfaces
from retesting, troubleshooting, and together, and all secondary side of the bushings, etc.
collaborating with test equipment (X) bushing terminals must be
manufacturers, the following Power
Factor Checklist should always be
shorted together. Always use
NON-insulated conductor(s) to
• Be aware that the test
environment can significantly
reviewed, prior to executing any short-circuit the bushing terminals influence a Power Factor
Power Factor measurement: together when performing a Power measurement.
Factor measurement – Do NOT - Do not Power Factor test in the
• Are the transformer tank and the
test-equipment solidly grounded
use insulated shorting leads. If
insulated conductor(s) are used,
rain.
- Avoid testing in high-humidity
to earth-ground potential? then the conductor’s insulation can situations (where excessive
Not connecting the test specimen easily become part of the Power moisture is present).
and the test equipment to a solid Factor insulation measurement. - Avoid Power Factor testing
earth-ground reference is the most Also, connect the shorting when the temperature of the
common mistake test equipment jumpers as tightly as possible transformer oil is below 0°C.
users make in the field. from bushing-terminal to bushing- - Power Factor test after lunch, if
terminal (in other words, do not let possible (which is typically when
• Are the bushing terminals of
the transformer completely
the shorting jumpers sag and/or
touch any surface other than the
the least amount of moisture/
humidity is present).
disconnected and isolated from all terminal being energized).
cable, bus-bar, support insulators, The Power Factor Checklist is
surge arrestors, etc.?
When applying a test-voltage of
• Remove all in-service grounds
from any neutral bushing
intended to help test equipment users
“get the measurement right the first
10 kV, a minimum clearance of 3 terminals. time”, which is the most practical
in. should be established (between For example, remove the in-service strategy to saving wasted time when
the terminal(s) that is energized ground-connection from the X0 testing transformers. In conjunction
and all other surfaces). Avoid bushing terminal, if applicable. with the Power Factor Checklist, the
using a rubber blanket, insulated Variable Frequency Power Factor
gloves, etc. to isolate the bushing • Place the LTC in any off-neutral test can be utilized by test equipment
Photo: Omicron
terminals from external surfaces – tap-position. users, to quickly and easily confirm
the best insulator for Power Factor Some transformer Load-Tap- that the Power Factor measurements
testing is air! Changers (LTCs) utilize a “tie- obtained are indeed correct.
42 BETTER
TESTING METHODS
Issue 3
The best strategy for saturating the test current in the range of 5-10 A secondary side, a test equipment
transformer core quickly, and in turn, is sufficient – most resistance user often has anywhere from
obtaining the correct resistance measurements performed on 57-99 resistance measurements
measurements quickly, is to inject as the primary side (H) winding of a to obtain (that are often well
high of a DC current as possible into transformer have resistance values below 100 mΩ in magnitude). In
the winding under test. The higher the greater than 100 mΩ. these cases, it is important that a
injected test current, the faster the
transformer core saturates, the faster
• Typically, when testing winding
resistances less than 100 mΩ, a
sizeable test-current (e.g. 20-30 A)
is available to the test equipment
the test is performed. The following test current in the range of user, so that they may perform the
guidelines are intended to assist test 20-30 A is ideal – most resistance lengthy test-sequence as quickly,
equipment users with selecting the measurements performed on the and accurately, as possible.
appropriate test current for a given
winding resistance measurement:
secondary side (X) winding of a
transformer have resistance values
• The test-current should not exceed
10% of the rating of the winding
less than 100 mΩ. under test.
• The lower the resistance of the
winding under test, the higher the
• Load-Tap-Changers (LTCs) in
North America are most often
• The test-current multiplied by
the resistance (of the winding
Photo: Omicron
test-current should be. applied to the secondary side (X) under test) should not exceed the
• Typically, when testing winding
resistances greater than 100 mΩ, a
winding of a transformer. In cases
where the LTC is located on the
maximum compliance voltage
rating of the test instrument’s DC
Transformer Technology September 2019 45
Issue 3
Issue 3
THE CHALLENGE
How do you get all the information you need to
understand the condition of your transformers?
You need condition monitoring tools that provide
accurate data, robust analysis and reliable alerts.
This allows you to effectively identify developing
problems, prevent transformer and bushing
failures, and manage risk.
CHOOSE DOBLE
Doble brings clarity to the complexity of condition
monitoring. By choosing a Doble online monitoring
system, you gain the power of knowing:
• Data is accurate and reliable
• Analytics are based on industry standards, best
practices and nearly a century of Doble expertise
• Alerts and alarms are meaningful and useful
• Support is a phone call away
GETTING STARTED
Unsure about where to begin? We want to help make your condition monitoring program a success.
We can work with you to help determine the most effective approach for your organization. We offer
package and custom options to address all situations, whether you are looking to monitor large,
generator step-up transformers or smaller distribution and industrial units. We also provide support
options from commissioning through training and decision support.
www.doble.com
48 REDUCED OIL
DEGRADATION
& AGING
Issue 3
Dr. Bruce Sunga is the Director of the Sub- Dr. Stuart Chambers is the manager of R&D,
stations Technology and Testing sector at Investigation & Consulting, as well as a lead
Powertech Labs. He brings more than 25 for the polymer and materials investigation
years of commercial, industrial and electric facility in Powertech’s Substations Technol-
utility experience in areas of stations and sys- ogy & Testing group. His areas of research
tem planning, analytical studies, asset manage- and development include transformer diag-
ment, project management, design, automa- nostics, insulating paper degradation, aging
tion, R&D, construction, testing, commissioning properties of insulating oils, and polychlorin-
and acceptance, failure investigation and main- ated biphenyls (PCB) decontamination. He
tenance. The Substations Technology and Test- has completed substantial research into in-
Photo: Powertech Labs
ing sector is comprised of two world-renowned sulating solids, fluids and gases for the Elec-
labs, a prestigious R&D and investigations tric Power Research Institute (EPRI), Canadi-
group, a substations studies group, and field an Electrical Association (CEATI), BC Hydro
testing services and asset management group. and other research organizations.
50 REDUCED OIL
DEGRADATION
& AGING
precursors to
sludge.
Photo: Powertech Labs
Transformer Technology September 2019 51
Issue 3
Figure 2. Correlation of the life expectancy of a transformer form from the laminates, spacers,
to the Water Content of the Paper (WCP) glues, and wood. Like moisture,
these contaminants also promote
10000
Adopted from: Lars E. Lundgaard
and increase the rate of aging.
et al, Aging of oil-impregnated A simplified yet comprehensive
paper in power transformers,
IEEE Transactions on Dielectrics
overview of the various contaminants
1000 and Electrical Insulation, Volume that can form is shown in Figure 3,
Life Epectancy (years)
GAS PHASE
ARCING
MINERAL OIL CORONA H2, CH4, C2H2,
ELECTRICAL H2, CH4, C2H6,
H2, C2H2, C,
CO2, Co, C2Hy,
(CxHy) CH4, Co, CO2,
(Ionizing Electrons) Co, CO2, C3Hx
Aromatics
CELLULOSE
Paper DECOMP PYROLYSIS LIQUID
Pressboard THERMAL DEHYDRATION H2, C2H4, CH4, Unsaturates, PHASE
H2O C2H6, Furans, Aromatics, Furals,
(Heat) Co, CO2 Co, CO2 Phenols,
METALS Acids,
Iron Ketones,
CATALYTIC OXIDATIVE
Copper Free Radials, Ketones, Metals, H2O,
OXIDATIvE Polar, Other
Peroxides, Acids, CO2, H2O,
OTHER (O2, Peroxides) Reduced DP Furans
Resin SOLIDS/
Glue CATALYTIC HYDROLYSIS SUSPENDED
Enamel HyDROLyTIC Acids, Furans, Sludge,
Moisture Lower DP, CO2, Phenols, Particles,
(H2O, Acids) Furans Acids Fibers,
Sugars,
Metals
50 100 200 500 1000 1500
Corrosive
LTC Oil Sulfur
Dehydration Regeneration Degassing Purification and
Unit Unit Unit Contaminant
Removal Unit
Issue 3
not only for the purposes of good demonstrated results showing that
dielectric properties, but also for the the transformer oil was cleaned to as
purposes of controlling the promoters. new condition in terms of dielectric
The traditional methodology of strength, acid content, power factor,
maintaining oil quality is to replace color, interfacial tension (IFT), and
the oil, but new online technologies other oil quality parameters. The
have now been developed, meaning an advantages of this technology are:
extended outage is no longer required.
Most of these online technologies
• It can operate online with an in-
service transformer, avoiding
are comparable to the concept of system shutdown.
dialysis—they are devices that are
connected to a transformer in a loop
• It allows for significantly lower cost
than other methods.
arrangement, taking out a small flow
rate of oil, processing it, and returning
• It can be installed in a few hours and
left unattended.
the clean oil to the transformer. The
method by which the oil is processed Specific benefits Powertech added to
is selective adsorption, which allows their Online Oil Decontamination Unit
it to remove specific contaminants. (OODU) system are:
Removing the contaminants not
only reduces the promoters but it
• Safety features which include leak
detection sensors, flow disruption
also improves and regenerates the sensors and solenoid valves as
dielectric oil quality. ways to safely and automatically
shut down the unit.
The Online Maintenance
Industry
• Capability to selectively perform one
or more functions, including removal
of acids, moisture, corrosive sulfur,
Services and equipment that utilize PCBs, or degassing of the oil.
these online oil treatment technologies
to restore oil quality without requiring Conclusions
equipment outages are becoming
more prevalent. However, the majority
By eliminating Many assets were originally designed
of suppliers offer online options only
for dehydration or use a non-selective
moisture, with a lifespan of a few decades in
mind. With aging assets and tighter
adsorbent material for removing the acids, operational and capital budgets,
contaminants from the oil, requiring extending the life of a transformer has
significant amounts of time and and polar been a key topic of research for many
adsorbent. Newer offerings include electrical utilities. Research has found
online oil decontamination systems compounds, that by eliminating moisture, acids, and
which use proprietary absorbent
technologies to selectively remove the life of the polar compounds, the life of the paper
can be extend by several decades. By
other contaminants from the oil of
in-service transformers. These
paper can eliminating acids and polar compounds
the production of sludge can be
systems selectively remove all oil and
paper decomposition products (acids,
potentially prevented. All these contaminants can
be controlled by maintaining the oil in a
polar components, furans, moisture,
particulate matter, and corrosive
be extend pure state, and new technologies have
been developed to do this in an online
sulfur), restoring the oil quality to by several and continuous way.
near new conditions. After restoring
oil properties, the units keep the oil decades. By References
clean and dry at all times, preventing
eliminating
[1] “Aging of oil-impregnated paper
the accumulation of moisture and in power transformers,” IEEE
degradation products from reaching
harmful levels, thereby extending the acids and polar Transactions on Dielectrics and
Electrical Insulation, Volume 19,
life of the transformer.
compounds Issue 1, pp. 230-239, Jan. 2004.
[2] L. Lewand, “What is sludge,” NETA
Powertech has successfully
demonstrated this newer technology
from the oil, World Journal, 2006.
Although
traditional
naphthenic oils
have provided
generally
acceptable
properties for
transformer
oils, tests have
proven that an
oil with a higher
paraffinic carbon
content can
deliver improved
performance
and extended
Photo: Exxon Mobil
transformer life.
Transformer Technology September 2019 55
Issue 3
Introduction
This article highlights the key Several typical transformer oils, all
properties of transformer oils with with a significant naphthenic carbon
different chemical compositions content (represented by the blue bars)
and the tests that were undertaken – see were compared to a new oil
in determining if oils with a higher with a much higher paraffinic carbon
paraffinic carbon content can deliver content (as shown by the green bars),
enhanced performance versus those see Figure 1. The new transformer oil
with a higher naphthenic carbon Figure 1. Percentage of aromatic with higher paraffinic carbon content
carbon content (Ca), naphthenic
content. carbon content (Cn),
was developed to provide improved
and paraffinic carbon content (Cp), properties versus typical naphthenic oil
These key properties include: based on ASTM D2140 performance.
0
loadings and size.
• Material compatibility which can
affect leak prevention.
NapOil2 NapOil4 NapOil3 ParOil
300
oil (shown by the black dot), as
demonstrated in Figure 2. A higher
200 paraffinic carbon content and lower
aromatic carbon content can improve
100 the oxidative stability of the oil to help
maximize transformer lifespan.
Issue 3
Minutes
stress. A negative gassing tendency
300
is advantageous, therefore, in
minimizing the build-up of hydrogen
200
gas because the oil can adsorb gas
under partial discharge conditions in
the presence of gas bubbles. 100
with a negative
-20
-30
gassing tendency -40
indicates that -50
it can adsorb -60
60
40 FAIL
20 PASS
Gassing Tendency, uL/min
-20
-40
-60
-80
-100
0 1 2 3 4 5 6 7
Ca, %
ParOil Spec
58 Transformer
Oil Properties
Weight, %
molecules may also emit hydrogen. 31
As a result, product composition and 30
degassing performance can suffer.
20
To help counter this, the new paraffinic
oil has been developed with a very low 10 6
aromatic carbon content, as shown in 2
Figure 6. This delivers potential safety, 0
health, and environmental (SHE) NapOil2 ParOil
benefits due to lower exposure to Paraffinic Carbon Content Naphthenic Carbon Content
aromatics. Importantly, the aromatics Aromatic Carbon Content
content of the paraffinic oil is also very
consistent, providing a more constant
gassing tendency. Table 1. Viscosity dependence on temperature and composition
Lower viscosity can also improve Figure 7. Mouromtseff number and importance
heat transfer by providing better oil of low viscosity
circulation inside the transformer
to facilitate effective cooling. Figure Mouromtseff Number for comparing
7 illustrates the importance of the heat transfer rates of liquid coolants:
Mouromtseff number and low viscosity.
ρ = density
An oil with a high Mouromtseff ρaKbCpd K = thermal conductivity
number equates to an oil with a good Mo =
Cp = specific heat
heat transfer rate. Because viscosity μe
μ = viscosity
appears in the denominator of the
equation, an oil with a lower viscosity
exhibits better heat transfer and more
effective cooling.
Transformer Technology September 2019 59
Issue 3
0.155
0.150
Thermal Conductivity, W/m.K
0.145
0.140
0.135
The low viscosity
of the paraffinic
0.130
oil at low
0.125 temperatures can
NapOil2 NapOil4 ParOil
be beneficial for
Figure 9. Specific heat versus temperature
by ASTM E1269
the cold-start of
2.20 transformers in
2.15 cold climates.
2.10
Specific Heat, kJ/kg.K
2.05
2.00
1.95
1.90
1.85
1.80
1.75
20 30 40 50 60 70 80 90
Temperature, C
NapOil2 NapOil4 ParOil
60 Transformer
Oil Properties
PF 100
PF 100
oils and the paraffinic oil performed 0.20 5.0
similarly in the overall compatibility 4.0
0.15
testing, the paraffinic oil exhibited a 3.0
0.10 2.0
similar or lower Power Factor @ 100°C 0.05 1.0
(212°F) after the immersion. A lower 0.00 0.0
PF100 is desired because it indicates
Corkprene Nitrile - Comm
lower impurities and, therefore, less
attack on the elastomers. 0.45 0.18
0.40 0.16
0.35 0.14
This is a result of the paraffinic oil 0.30 0.12
PF 100
PF 100
having lower aromatic and naphthenic 0.25 0.10
carbon contents than most naphthenic 0.20 0.08
oils, which decreases the “solvency” 0.15 0.06
0.10 0.04
strength of the oil. The lower solvency 0.05 0.02
strength is also reflected by the 0.00 0.00
higher aniline point of the paraffinic VitonTM Nitrile - High
oil, compared to the naphthenic oils
(which is not shown here). Improved NapOil2 NapOil3 NapOil4 ParOil
material compatibility is a result of
lower solvency strength.
Issue 3
SDMyers.com
Transformer
By Marius Marinoiu
Global Product Manager,
Use of fiber optic sensors Weidmann has the of the transformer OEM
in transformers capability and expertise to insulation package
Fiber optic technology was applied in
transformer hot spot monitoring sev- design, produce and test ensuring that it is
eral decades ago and is continually
being improved and refined. State-of- fiber optic temperature designed specifically for
the-art design and electronic compo-
nents are increasingly used in fiber probes and insulation the transformer type,
optic monitors and controllers. With
appropriate configuration by transfor- assemblies, leading to the and tested to the highest
mer manufacturing personnel and pro-
per installation in the windings, the fiber lowest fiber failure rate. standards.
optic is capable of operating long after
the transformers demise. Therefore today, hot spot fiber optic monitoring
systems are proven and trusted to provide real time, accurate information about
the temperatures inside the transformer tank, specifically in the transformer
windings. However, there are several challenges still to overcome.
Issue 3
A consistent approach
Given the level of standardization applicable to
this topic and existent in industry today, the con-
sistency can be guaranteed only if the assembly
of the fiber optic temperature probe with insula-
tion component is manufactured and tested by
one, specialized entity. This in its turn guarantees
that fiber optic-insulation assemblies perform per
specifications, in the same way, while being sub-
jected to stressing elements specific to trans-
former winding, whether these elements are elec-
tromagnetic stress or physical.
SmartSpacer®
Weidmann SmartSpacer®
As the global leader in transformer insulation design and manufacturing, and
undergoes a rigorous a fiber optic monitoring supplier, Weidmann has the capability and expertise
to design, produce and test fiber optic temperature probes and insulation as-
design, FEA analysis, and semblies, leading to the lowest fiber failure rate. At Weidmann these assemblies
are called SmartSpacer®. It ensures quality and consistency, as well as realizes
thermal, mechanical, savings for both transformer manufacturers and operators.
electrical, and for some Improper installation of the fiber-optic probes in the transformer windings can
result in inaccurate data or can potentially increase localized stresses in the
designs X ray tests to insulation system. Any discontinuity must be avoided during installation, as
well as incompatible materials such as some adhesives, and voids that can
become certified. This reduce the integrity of the overall system. Weidmann SmartSpacer® is designed
to eliminate all these issues.
reduces the risk of
SmartSpacer® provides the manufacturer and end user with the confidence to
incorrect probe installation install fiber optic probes in the windings that will not compromise the integrity
of the insulation system or transformer reliability
and loss of use or potential in the long term. The SmartSpacer®can be pre-
ordered as part of the transformer OEM insula-
reduction of insulation tion package ensuring that it is designed specifi-
cally for the transformer type, and tested to the
system integrity which can highest standards. This minimizes the work re-
quired by the OEM and ensures consistency in
lead to premature failure. the probe assembly and installation leading to a
lower risk of breakage or failure.
maintenance or
troubleshooting
required.
Design: The detailed design of the insulation component and embedded sensor are
compatible with normal and emergency electrical stress limits typically found in EHV
and UHV liquid-immersed power transformer winding designs, as specified by the
transformer manufacturer and operator.
Dielectric Analysis: The component, sensor, and connection system have been ex-
tensively modeled and analyzed using Finite Element (FEA) numerical analysis tech-
niques to ensure that the SmartSpacer® is compatible with electric field stresses in
the winding and support insulation system designs.
Functional Testing: Insulation components and embedded sensors are tested in the
Weidmann or equivalent high-voltage laboratory to demonstrate the output metrics
and applicable tolerances required for the sensor. They are suitable for use in the Marius Marinoiu has almost 20 years tech-
transformer internal environment, in both alternating voltage and impulse conditions, nical and sales experience at a global level
applicable to the BIL voltage class as specified by the power transformer operator. in transformer monitoring applications and
analytical services. He holds an Engineering
Manufacturing Processes: All components meet strict manufacturing process con- degree in Industrial Automation and Robot-
trols in compliance with drawings and specifications that preclude the possibility of ics, and a Master’s Degree in Non-Conven-
electric field stress concentration or negative impact on the transformer dielectric tional Control Systems. At Weidmann he is
system or performance. responsible for assisting in the development
and implementation of strategic sales plans
Quality: Strict conformance to written quality assurance system standards are met for the Transformer Lifecycle Product (TLP)
for components and matching sensors throughout the manufacturing, assembly, Market Segments in North America. Previ-
packaging, and shipping stages. The Weidmann Quality Management System is cer- ously he managed implementation of turn-key
tified to the ISO 9001 Standard. transformer monitoring solutions globally.
Transformer Technology September 2019 65
Issue 3
Power Transformers:
Properly Categorizing
Developing Faults via
Dissolved Gas Analysis
by Randy Cox
chemists and experts willing to assist, with regards to further, or a deeper in-
terpretation.
In this article we will identify some simple guidelines that may be applied
initially is the amount of paper involved in a given fault, if any. These steps
what many consider to be, a very complicated subject; categorizing (or dis-
answers can be rapidly obtained, it can mean the difference between a less
Issue 3
68 BETTER DGA
CATEGORIZATION
30
There are “knowns” in DGA. The
industry is very proficient at
25 identifying overheating in oil filled
20 power transformers. Measuring the
internal oil temperature at 150°C+
15 temperatures is accomplished by
10 the measurement of what is referred
to as the “hot metal gasses.” These
5
gasses are, in order of their initial
0 thermal generation, hydrogen (H2),
H2 CH4 C2H6 C2H4 C2H2 methane (CH4), ethane (C2H6),
ethylene (C2H4) and acetylene (C2H2).
What is not quite as well understood
30 MVA Post Fault
is the diagnosis of paper (the carbon
40
oxide gasses: CO2 and CO). It can be
35 even more challenging if the issue
exists on a paper wrapped lead.
30
To better understand how to arrive at
25 a conclusion regarding an issue, it is
20 important to note that at all working
temperatures, CO is less soluble than
15 CO2 and the higher the temperature,
10 the more CO2 remains in solution
(it will be absorbed from atmosphere
5
if partial pressure of CO2 in
0 atmosphere is greater than partial
H2 CH4 C2H6 C2H4 C2H2 pressure in the oil).
Issue 3
CO2 /CO
140
120
Trending provides critical data for
decision making, as opposed to data 100
that is a simple snapshot in time. In
80
other words, what was it prior to the
problem, or where is its norm? This 60
thinking is new to our industry, as this
ratio is typically referred to in many 40
technical publications and industry 20
guides as a single value for diagnostic
purposes. To demonstrate this more 0
fully, the following transformers both Pre Fault Post Fault
tripped on a transformer differential
relay operation with a very similar CO2 /CO
arcing profile. There’s no question
8
that a flashover occurred in both
transformers as seen in Figure 1 [1]. 7
6
These transformers had very different
problems, evidenced by the post 5
event impact on the CO2/CO ratio 4
as seen in Figure 2, maintaining the
order of these transformers. 3
2
What we now know is that the more
1
paper involved in a fault, the greater
the impact on the CO2/CO ratio. 0
Pre Fault Post Fault
Where the ratio dropped significantly,
a low side winding failure occurred
and where a paper wrapped primary
lead flashed over (minimal paper),
much less impact.
To further illustrate the value of this generated, it did not have a negative
ratio, Table 1 presents the data of impact on the CO2/CO ratio. An
a 10 MVA transformer that tripped internal inspection revealed a failed
on a transformer differential relay de-energized high side tap changer.
operation, to which there was Even though there was no paper
absolutely no impact on this ratio, involved in the fault, when the ratio is
verifying that there was no paper compared to generation of hot metal
involved in the presence of the hot gas, the lack of impact actually tells
metal gas generated, post fault. the story. The issue was in an area
that did not support any paper being
As can be plainly seen in the above involved, thus bare metal, such as a
example, once the hot metal gas de-energized tap changer contact.
Test Date Hydrogen Methane Ethane Ethylene Acetylene CO2 CO CO2/CO Nitrogen Oxygen
8/7/2008 2119 736 44 666 1405 2530 239 10.58577 67189 7881
Issue 3
Issue 3
Dielectric design
• Readily biodegradable as
designated by the Environmental
As to the dielectric design considerations, the main characteristic considered Protection Agency (EPA);
was the greater dielectric permittivity εr of natural ester compared to that of
mineral oil (typically 3.2 vs 2.2). This leads to a more uniform distribution of the
• Non-toxic in both oral toxicity tests
and aquatic toxicity tests;
electric field throughout the insulation, with a reduction of the electric field in the
oil channels and an increase in the electric field in the paper. This gives different
• Has a neutral carbon footprint –
56x less carbon emissions than
proportions between oil and solid insulation if we compare it with an identical mineral oil.
unit in mineral oil.
74 advertorial
Thermal design
The thermal design of the autotransformer is considerably influenced by the
higher viscosity of the natural ester fluid which reduces the flow speed and
therefore the flow rate. This aspect is partially compensated for by the higher
thermal conductivity compared to that of mineral oil; but to maintain an equiva-
lent thermal dissipation with the same temperature gradients, it is necessary to
dimension the oil channels differently.
Mechanical design
Considering the different stability to oxidation of natural ester fluids compared to
mineral oils, it was also necessary to take some precautions in the mechanical
design, foreseeing the use of the rubber bag membrane in the conservator or
an airtight tank with nitrogen cushion. Large power transformers, like this for
Terna, already have the rubber bag but it is also important to remember to install
a “membrane rupture relay” with an alarm to the control associated with the
urgent intervention signalling (IU).
Compared with the “sister unit” with mineral oil, with the same power and voltages,
this new design – which was made with Tironi’s own software and also verified
through third party finite elements software – shows some minor differences in
the oil and overall weights (approx. 55 and 200 tons) while assuring the benefit
of using a natural ester fluid like the Cargill’s Envirotemp FR3.
Oil Plant
A new important investment allows Tironi to have a completely separate oil
plant for natural ester fluids, which allows for a fully independent storage and
treatment plant with separate oil pipes to the filling area. The storage is com-
posed of three separate compartments of 25,000 litres each, with heating ele-
ments and nitrogen generators. The treatment is composed of an adjustable
OTP up to 6,000 lt/h.
Issue 3
Tironi Lab
Another significant new asset of Tironi is their new Oil Lab, a full capability
chemical lab operating within their Quality Management structure. This new lab
has been instrumental in testing new natural esters.
Lab tests, including 11 gas DGA tests, are performed in real-time, and results
immediately shared and analysed with plant technicians. These tests proved
extremely valuable in assisting the decision process during all development
phases. Fine-tuning of treatment settings, definition of operational procedures,
monitoring dielectric efficiency during each treatment step; all took advantage
of the Tironi Lab’s readily available data.
Finally, analytics performed during the experimental phase turned into first-
hand “knowhow”, which is currently being applied to production parameter
monitoring, ensuring the processes keep within fixed boundaries.
ELETTROMECCANICA
C ontact
TIRONI S.r.l.
Via Emilia Est, 1303/D
41122 Modena, Italy
+39 059 282282
[email protected]
76 BETTER TESTING
& INSPECTIONS
Issue 3
A Thorough “Once-Over”
Issue 3
Looking Deeper
Sidebar 1
Once the external condition has
Perform Pressure Check
In order to maximize the life of the
been assessed, it’s time to examine
transformer, we must keep moisture key internal and functional details—
out of the insulation system. Tank all of which further confirm that the
pressure is a critical factor to observe transformer is properly fit for service.
because it serves as an indicator of (Note: Do not attempt electrical
potential moisture ingress into the testing on units in a vacuum state.)
winding insulation.
Short-Term Storage
For units that will be stored for one
to three months, pressurize the tank
with dry gas at approximately 5 psi.
Record the initial pressure, then
check and log pressure levels at least
monthly—with weekly measurements
being preferable. Supply power to
the control cabinet and energize the
heater to prevent condensation – See
Slidebar 3.
Long-Term Storage
For storage periods greater than four
months, the transformer should be
completely assembled (including
radiators), vacuum processed, and Leaving transformers empty
filled with oil above the 77°F/25°C
level, leaving at least 6 inches for oil for an extended period of time
expansion. Pressurize the tank to
approximately 5 psi. Pressure should
is a major risk, due to the threat
be checked and logged at least of moisture damage to the
monthly to ensure that this pressure
is maintained. (All readings should insulation.
Photo: Delta Star
Issue 3
Keeping the
Fleet in View
Transformer Technology September 2019 83
Issue 3
All
around the world, grid operators are being confronted with
the same challenge: the fact that their equipment is reaching
old age. It is no longer uncommon to see power transformers
with a service life of 50 years or more. One of the questions that every
grid operator is faced with is therefore ‘What sort of shape is my fleet in?’
Finding an answer to this question is becoming more and more urgent:
Fluctuating and higher loads resulting from renewable energy sources are
increasingly causing the crucial pieces of equipment needed to ensure a
stable power supply to reach their limits.
Collect Data
A sufficient database is essential to carry out
the condition assessment. To keep disruption
times and assessment work to a minimum,
FLEETSCAN 2D offers three assessment stages.
Depending on how detailed the assessment
needs to be, not all three stages have to be
carried out. Transformer data is already
available in many cases, so the work involved in
recording the data is minimal.
1 2
1st stage: existing data
Everything at a Glance
The operator provides the data which is already
FLEETSCAN 2D makes it possible to clearly
available. This includes, for example, the master
save all collected data using browser-based
data of the transformers, measurements that
software. This enables grid operators to retrieve
have already been carried out, and maintenance
all relevant information for any transformer in
history information.
the fleet at any time.
Regensburg UW CP 1
inspection, an MR expert uses a checklist to Visual Inspection IR Thermography Oil Analysis Measurements
Continue
Status: 0 %
Start
Status: 0 %
Start
Status: 0 %
Start
Home Asset
If, after the first two stages, there are any Transformer Management
Transformer Name Substation Manufacturer Year of M. Rated Voltage (HV) Rated Power Primary Serial Number
T2
UW AB
UW AB
Siemens
ABB
1963
1951
110 kV
110 kV
45 MVA
24 MVA
92456278
21725394
performs targeted testing involving extensive T3 UW AB SGB 1972 110 kV 39 MVA 42521378
Issue 3
Evaluation
Following data recording, it is time to move on to
the core element of FLEETSCAN 2D : the
3 4
Recommendations
FLEETS
CAN 2D
lottenbe
wertung
nach der
Fleetsca
n2D-Me
thod e
en
rmation
iche Info
Zusätzl te
3.4 der Flot
FLEETSCAN 2D
Transformator-Flottenbewertung nach der Fleetscan2D-Methode
Genland, Trafo 12: Lüfertmotoren beidseitig, einige Lüftermotoren werden etwas wärmer, ggf.
Lager defekt, Motoren überprüfen
condition of the fleet, MR recommends that the
Alter.
Die
lichen Alter zu:
Streuun
g FLEETSCAN 2D assessment be repeated every
tatsäch
Seite 16
Seite
1
Your Contact
Photo: Maschinenfabrik Reinhausen
Practice-Oriented
Thanks to a flexible choice of test stages, downtimes are minimal.
Only the tests that are absolutely necessary are carried out. Following
the assessment, service managers and asset managers are presented
with results which they can transfer directly into practice.
Issue 3
SUB
SCR
I B E TO
$75 /year
DIGITAL Subscription includes 4
successive issues per year
FREE
Receive print copies of the
Annual subscription magazine in your letterbox
and enjoy the joy of reading
To subscribe visit
transformer-technology.com
88 INTEGRATED
MONITORING
Risk Management
Requires Actionable Insight:
Introduction
Issue 3
A Holistic Approach
• Provide integrated data to Subject
Matter Experts (SMEs) and
Operation & Maintenance (O&M)
A 2015 transformer reliability survey if we are to consider the key managers that can be easily
published by CIGRE [1] shows components, parameters, external correlated to extract meaningful
that more than 60% of failures in events and operational conditions information
transmission transformers involves
one of the following components:
that can contribute to failure. Figure
1 provides an overall picture of what
• Help the SME and O&M manager
to plan appropriate maintenance
high voltage windings, on-load tap this holistic approach should be, and offline tests
changers (OLTC) and bushings. A
similar percentage can be found
monitoring bushings, main tank,
OLTC, oil conservator and cooling
• Contribute to the identification
of most probable failure mode
in generation transformers with system. In addition, advanced by combining online results with
the difference being that the three modelling and analytics can be offline results and transformer
main components are: low voltage used to aggregate the through fault maintenance history
windings, high voltage windings current events [2], [3], estimate the • Reduce maintenance costs
and bushings. In addition to this,
external short circuits have been
aging factor, hot spots, overloading
capabilities [4], [5] and probability of
• Ultimately allow the asset owner
to manage and mitigate risk
highlighted as one of the major transformer failure.
Photo by Camlin Power
BUSHINGS CONSERVATOR
• Capacitance AND OIL PROTECTION
• Tan delta / Power factor • Oil levels
• Partial discharges • Status
• High energy events • Pressure
• Voltage • Air humidity
• Levels • Buchholz status
• Pressure • Buchholz levels
Issue 3
Case Studies
The following case studies demonstrate successful examples when the utility was able to
plan preventive actions and maintenance thanks to the study of the correlation of two or more
parameters.
Case Study #1
KEPCO successfully replaces 345 kV bushing thanks to online monitor
showing capacitance increase and high energy events
Bushing and partial discharge monitoring was installed in 2015 on a single-phase transformer
bank in Ulsan, South Korea. The installed device was continuously monitoring the currents from
the bushings and the partial discharges from both the main tank and bushings using properly
designed tap adaptors installed at the bushing test taps. The acquisition was continuous
(not scheduled) and simultaneous in all phases with the results summarized every hour. The
bushings, from NGK, were 30 years old, OIP, 345 kV, around 430 pF of capacitance.
On February 2015, a sudden step increase of the capacitance (C1) in bushing A was detected by
the monitoring system, estimating a capacitance change in the order of 1.7% which corresponds
to a rough increase of 7 pF. Such a small change could have been caused by a partial short circuit
between two layers in the condenser core, considering >60 control layers for 345 kV bushings.
KEPCO planned an offline test to confirm the online readings, but the results proved difficult to
interpret. Indeed, the absolute value of bushing A capacitance had not changed significantly
from the previous measurements, as shown in Table 1.
Table 1. Offline results before (2012, 2104) and after (2015) the online alarm
345 kV NGK Bushing OFFLINE Capacitance C1 [pf] 345 kV NGK Bushing OFFLINE Capacitance C1 [pf]
Increase Increase
2012 2014 2015 2012 2014 2015
since 2012 since 2012
Bushing A 435 429 438 0.60% Bushing A 435 429 438 0.60%
Figure 2. Regional
Bushing B market
433for dry-type
430 426 -1.60% Bushing B 433 430 426 -1.60%
transformers, 2019
Bushing C 432 NA 430 -0.46% A-B +2 pF -1 pF +12 pF 2.7%
However, it was noticed that while the increase of capacitance in bushing A was quite small, both
bushings B and C were showing a decrease of capacitance. This led to the assumption that the
test setup was different when readings were taken. In order to take this into consideration, the
relative difference between capacitance A and B was analysed over time. It was then possible
to spot that this difference was quite constant in 2012 and 2014 (below 2 pF), while it was
significantly high in 2015, exceeding 12 pF (roughly equal to 2.7% of capacitance increase).
This offline test was not conclusive but led to further investigation of the online data.
It was then found that at the precise moment of the bushing capacitance increase, a high energy
event (partial discharge activity with significantly high magnitude, generally equal or higher than
20 V peak-peak [6]) was recorded in the same phase (from same sensor) by the online monitoring
system. In this case, the recorded event had just 8 pulses per second and it happened just once.
The fact that this event was recorded in conjunction with the capacitance increase was an
important detail that prompted an additional offline test: oil sampling from the bushing and
Dissolved Gas Analysis (DGA). Table 2 reports the results of the DGA analysis for bushings A and C.
It can be clearly seen that the amount of acetylene in bushing A is well above the tolerance
values, being 76 ppm; while level of acetylene in bushing C was zero, as expected.
Following the results shown in Table 2, KEPCO promptly planned and executed the bushing
replacement within a few months, thus saving the bushing from a potentially catastrophic
incident. It must be noted that the repetition rate for both the capacitance change and the
high energy event were quite small in terms of absolute magnitude. But being able to detect
both these phenomena online and see that they occurred in the same moment provided crucial
information enabling KEPCO to take a very successful action.
C2H6 32 62
CO 71 53
N2 150.862 156.665
O2 10.280 4.337
Case Study #2
345 kV bushing in North America replaced for capacitance increase and high
energy events
Bushing and partial discharge monitoring was installed in 2018 on 504 MVA three-phase
transformer in North America. The installed device had the same characteristics of the asset in
Case #1 and was installed on a voltage tap on Westinghouse 1979 OIP bushings.
Similarly to Case #1, a sudden step increase of the capacitance (C1) in bushing H2 was detected
by the monitoring system, estimating a capacitance change in the order of 2.9%, which can
correspond to a short circuit between two layers.
By looking at the data it was observed, once again, that a high energy event was recorded in
conjunction with the capacitance increase in the same phase. Figure 4 shows the recorded
data (not averaged, published every hour) and the partial discharge pattern. The event was
characterized by impulses with significant magnitude (60 V peak-peak) and very small repetition
rate (just 6 pulses per second), almost describing a sudden arcing activity. Recognizing the
same correlation pattern (capacitance change + high energy event) seen in the KEPCO case, it
was then suggested to the utility to take an oil sample of the bushings.
Transformer Technology September 2019 93
Issue 3
H1 H2
H2 20 85
CH4 8 167
C2H2 <2 21
C2H6 14 65
CO 75 714
N2 51.800 84.300
O2 7.490 29.600
Table 3 reports the comparison between the DGA from bushing H2 and H1, showing the
acetylene concentration exceeding 20 ppm in the bushing where the capacitance change and
high energy events have been detected, confirming the online analysis and enabling the utility
to immediately plan the bushing replacement. The correlation of partial discharges and bushing
monitoring data, along with proper offline tests, was successful in identifying the problem at a
very early stage, optimizing the maintenance (in this case truly condition-based) and ultimately
saving the transformer.
Most important:
•The absolute intensity of the capacitance increase and the partial discharges were so small that
if they were only considered individually and separately they would cause little concern.
•The combination of the two small deviations/anomalies occurring at the same time, plus
the experience from previous similar cases, suggested the choice of the DGA oil sampling as
confirmation test.
•It must be noted that DGA on bushings is not a routine test for the utility’s policy and it is carried
out only in very exceptional cases.
Case Study #3
25 MVA GSU with unknown defect under investigation through DGA, partial
discharge, and temperature and bushing monitoring
A 25 MVA GSU transformer was installed in 1986 in a hydro plant in Europe. In 2018 the
transformer underwent regular maintenance with the OEM who carried out the following actions:
• Oil degassing. The transformer had a history of abnormal but stable levels of hot gases due to
a thermal issue such ethylene and methane. The fact that the gases were stable for a long time
indicated that the defect was likely not active anymore.
• Replacement of the glass inspection window in the bushings.
The transformer was originally not equipped with any monitoring system. After the maintenance,
an oil sample was taken which showed abnormal levels of H2 in the range of a few hundred ppm.
The OEM speculated that this could have been related to the same defect that generated the
ethylene increase previously and was likely to be associated with hot spots.
Issue 3
Since the new gas pattern was not actually showing “hot metal” gases and considering that
the H2 increase was significant and coincidently occurring right after the maintenance, the
generation company suspected that the defect was somehow related to the latest maintenance.
The utility equipped the transformer with a comprehensive transformer monitoring system
that included a five-gas monitor and modules for monitoring moisture, partial discharges, and
bushings, as well as analytics capabilities and temperature readings.
The first speculative analysis, after having looked at the online data, was leading towards the
Photo by Camlin Power
possibility that the defect was likely to be due to the last oil filling process that apparently had
not been carried out under vacuum (due to the fact that gaskets are not suitable for the vacuum
process).
96 INTEGRATED
MONITORING
Due to an absence of hot and arcing gases, the perfect condition of the bushings (in terms of
capacitance and tan delta) as well as the absence of a clear correlation with load or temperature,
the utility decided to:
• Keep the transformer monitored and under control in order to analyse the gas and partial discharge
development during the next few months.
• Plan the gasket replacements in order to perform a proper oil treatment and refilling under vacuum
to remove any possible trapped bubble.
• Agree that maintenance was to be planned. However, this could be deferred to the next stop of the
generator considering that:
• the overall picture provided by the online monitor indicated that the transformer was not in a
critical condition, and
• the transformer was continuously monitored so any unexpected change in the condition would
promptly notify the Subject Matter Expert.
In this case (which still under investigation at the time of publication) the use of the total
transformer monitoring not only aims at optimizing and deferring the maintenance to the best
possible moment (generator annual stop) but is also a means to resolve the controversy between
the OEM, responsible for the maintenance and oil process, and the transformer owner.
Figure 7. PRPD pattern of the stable partial discharge activity in Phase A1 (left) and the sporadic activity overlap (right)
Conclusion References
[1] Transformer Reliability Survey,
The use of a more holistic and The correlation of the different CIGRE TB 642, WG A2.37.
integrated approach to transformer parameters such as DGA, partial [2] F. Scatiggio, C.A. Serafino, M. Tozzi,
monitoring can significantly help discharges, bushing capacitance E. Savorelli and A. Salsi, “TERNA
to optimize maintenance and etc. plays a fundamental role. Transformer Fleet Knowledge
mitigate risk. Holistic means the However, the key point that has Management through the use of
treatment of the whole transformer, been shown in the case studies is on-line Monitors,” presented at D1-
taking into account operational that the correlation and occurrence 313, CIGRE, Paris, France, 2018.
data, environmental data, external of these events can sometimes [3] K. Yule, D. Brock and J. Purdy,
factors and previous experiences, be even more important than “Accountability and Evaluation
rather than just a single diagnostic their absolute magnitude. A small of Aggregate Effects of Through
parameter such as DGA. The capacitance increase and a few Faults on Power Transformers,”
chances of identifying the failure partial discharge pulses can be Unclassified Open Source.
mode or defect can dramatically easily neglected, ignored, or treated [4] IEEE Guide for Loading Mineral-Oil-
increase, allowing asset owners to as insignificant if considered Immersed Transformers and Step-
understand their risk and ultimately individually. The outcome obtained Voltage Regulators, IEEE C57.91-2011.
make prompt and better-informed by the correlation of all these small [5] Power transformers - Part 7: Loading
decisions. The planning and the events can have a huge impact guide for mineral-oil-immersed
use of valuable offline techniques on risk assessment process and power transformers, IEC 60076-6.
(DGA in bushings, SFRA, DFR, failure identification processes, and [6] M. Tozzi, C. McIlrory, C. A. Serafino
etc.) can be better informed by facilitate better decision making. and M. Rebolini, “Condition
the information provided by the Based Maintenance on 400 MVA
monitors. The monitor’s role is Autotransformers: A Case Study,”
not to replace the offline methods presented at CIGRE VII Workspot,
but to optimize their use and A2, PS1, Rio de Janeiro, Brazil, 2014.
effectiveness.
Transformer Technology September 2019 97
Issue 3
98 advertorial
Since 1980, Tecsystem SRL – an Our R&D department designs and implements solutions suitable for all electric
Italian factory - has continued to machine types with the ability to operate in any application sector (railway, air-
develop technologies aimed at port, shipping, building, construction, food, subway, alternative energy and others).
temperature control - data collection
and analysis of electrical machines. Security and reliability are our guidelines, granted by ISO 9001 certification and by
specific certification related to each product.
With headquarters in Italy and
branches in Egypt, China and Brazil, Thanks to the progressive evolution of our temperature monitoring technologies,
we are positioned in strategic places we are now working to create increasingly digitalized devices that interface easily
around the world so we can respond and immediately with any kind of existing systems.
promptly to every need of our local
customers. We have created a network In this case, digitalization is a technological progress which revolutionizes the ap-
of services suitable for accompanying proach to parameter control and allows the operator to act remotely, planning
every user in their projects. maintenance interventions in advance (predictive / preventive maintenance).
Thanks to the dual connection method (Ethernet or Wi-Fi), our devices can be im-
plemented in any system, immediately and without changes to the existing one.
Data flows are immediately usable and manageable in an intuitive and simple way
(in some cases even from Mobile or Tablet), thanks to specially designed graphic
interfaces.
Transformer Technology September 2019 99
Issue 3
CONNECTIVITY AND
DATA MANAGEMENT:
INDUSTRY 4.0
From the concept of simple remote In this way the User, using the wide range of data in a predictive way, can work to
control, we have moved on to a wider improve the basic concepts of Reliability, Maintenance and Efficiency.
reality more attentive to the needs
of today and tomorrow: supplying At Tecsystem, we are able to keep abreast of the times, and we have developed
information according to a standard two product lines which meet the new needs:
valid for all models, using the
most widespread communication
protocols and technologies (Modbus,
• ETH(ernet) LINE: equipped with Ethernet output with Modbus TCP / IP
protocol - to display, program and collect temperature parameters. Suitable
Ethernet, WiFi). This allows for the for systems where wired networks for the acquisition and remote control
implementation of results and data of information are available: it is a widely used technology for industrial
coming from centralized processing networks.
and analytic systems.
Among this LINE we present the T1048 ETH * which is UL certified and best fea-
tures are the following:
• WS LINE: equipped with a simple graphic interface for displaying and ana-
lyzing the temperature information detected, as well as a small antenna for
Wi-Fi connection, it offers the possibility of intervening for the programming
and configuration of the system, without having to install dedicated Apps or
Software, on any Internet Browser.
New “SMART” products for a market even more attentive to an energy wastage
both in the environment and resources, as well as being sensitive to a now ne-
tecsystem.it cessary concept such as predictive maintenance!
Introduction
Issue 3
Being able
to monitor your
substation
Richard Harada has more than 20 years of
remotely is one
experience in industrial networking commu-
nications and applications. Prior to joining
of the keys to
Systems With Intelligence, Richard worked
at RUGGEDCOM and Siemens Canada, where
going touchless.
he focused on industrial communications
in the electric power market. Richard is an
electronic engineering technologist and has
a Bachelor of Science degree in computer
science from York University in Toronto.
102 Automated Thermal
Monitoring
Issue 3
and efficiency. The system analytics Data points can be trended over
automatically detect temperature time to establish a health index and
abnormalities in the system and the graphs and current readings
send alarm messages. The data can be accessed via an information
can be stored locally at the site dashboard (Figure 2). Visual and
and communicated directly to the thermal sensors can send their data
control center SCADA or to asset wirelessly to the cloud for remote
management systems for real time sites that have limited connectivity
situational awareness. (Figure 3).
Reliability
through areas of a substation. Using processing that minimizes the staff (or they use professional
high resolution imaging and the amount of traffic that needs to flow contractors) to perform thermal
appropriate lens, the temperature on over the network. Utilities with no site inspections. However, there
even a small object can be measured wired connection to their remote are many advantages to using
from up to 50 meters away. Data sites can utilize modern 3G and 4G continuous, automated thermal
processing can be done at the edge wireless networks that provide high scanning given the advancements
of the network to improve reliability speed connectivity. in thermal scanning technology.
Transformer Technology September 2019 105
Issue 3
Issue 3
27–31,
OCTOBER
2019
TRANSFORMERSCOMMITTEE.ORG
108 PRE-EVENT
Face-to-face
in a digital world – the value
of industry events
Issue 3
Motivation!
Some events are considered expensive, requiring time
away from the office, and the return-on-investment isn’t
always clear. But they provide opportunities that you
simply cannot get elsewhere.
Networking, in person!
In a digital world, networking in person is becoming
more and more difficult. We often forget how effective
in-person interaction can be.
Francis Fisher
is the Head of Global Marketing at
Weidmann Electrical Technology.
Since receiving his bachelor’s degree
in business from the University of
Huddersfield, UK in 2002, he has
worked in a variety of commercial
roles within the energy sector
spanning multiple continents and
regions, including Asia Pacific,
Americas and Europe, Middle East
& Africa
About Weidmann
Electrical Technology:
Weidmann has been at the heart
of the global transformer industry
for over 140 years. With deep
rooted knowledge in the design,
development and operation of
transformers, Weidmann is a leading
integrated solutions provider for
specialized product and services in
the energy sector. Working closely
with our customers, Weidmann
continues to lead the global market
delivering high quality, innovative
product and service solutions.
JOIN US ON THE SAN ANTONIO RIVER WALK FOR THE 18TH WEIDMANN ANNUAL TECHNICAL CONFERENCE
Informative presentations from EMERGING technologies and services EXPO featuring leading Manufacturers
industry EXPERTS for transformer life extension from around the world
Feature presentations on alternative Insider look & information from Expert panel discussions &
transformer fluids with audience Q&A contributors to the new IEEE DGA GUIDE NETWORKING EVENTS
For more information, the full agenda and registration details please visit:
https://www.weidmann-electrical.com/the-transformer-experience
or search: ‘Weidmann Transformer Experience’ Official Media Partner
Transformer Technology September 2019 111
Issue 3
It’s easy
to keep in
the loop!
WITH
Discover
the latest transformer
tech innovations at
2019
Issue 3
Make sure you attend: For the most part we are redesigning systems,
DESCC, Wednesday 09/18/2019 - 9:00am – 4:30pm
not designing from scratch, adding technological
Pre-booking required.
advances while integrating new technology
into old systems. Transformer Technology
Venue
Donald E. Stephens Convention Center
5555 North River Road
Rosemont Illinois 60018 USA
Opening times
September 17, 2019 – 10am – 5pm
September 18, 2019 – 9am – 3pm
Transformer
Failures:
Causes and
Prevention
THINK ABOUT...
Don`t
think
about
MARKETING
LET US DO IT FOR YOU
ALL-INCLUSIVE TRANSFORMER
MONITORING PROGRAM
WWW.DOBLE.COM/DOBLEASSURANCE