ELECTRICAL POWER REQUIREMENT FOR DAIKIN VRV X OUTDOOR UNITS

RECOMMONDED POWER SUPPLY IS 3PH + N, 380 – 415 VAC, 50Hz. WITH EARTHING.
EARTH LEAKAGE CKT. BRAKER 300mA FOR EACH ODU IS MANDATORY.

Nominal size of Cu
MCB (Amp) ELCB (Amp)
SR. POWER CONSUMPTION (KW) RLA MFA TOCA MCA conductor, 4core XLPE
MODEL 4 Pole (300mA,4-Pole)
NO. insulated armoured cables
130% 120% 110% 100% Amps. Amps. Amps. Amps. Amps. Amps. SQ. MM.
1 RXYQ6ARY6 3.43 3.42 3.4 3.38 4.7 20 17 16.1 20 25 6
2 RXYQ8ARY6 5.25 5.23 5.21 5.17 7.4 20 17 16.1 20 25 6
3 RXYQ10ARY6 6.8 6.81 6.83 6.84 9.7 25 20.8 21.2 25 25 6
4 RXYQ12ARY6 8.65 8.66 8.68 8.7 13.2 25 20.8 22.5 25 25 6
5 RXYQ14ARY6 10.6 10.7 10.7 10.7 14.4 30 34.4 26.9 32 32 10
6 RXYQ16ARY6 13.1 13 13 12.9 19 35 34.4 30.2 40 40 10
7 RXYQ18ARY6 15.5 15.4 15.4 15.3 23.6 35 37.8 30.2 40 40 10
8 RXYQ20ARY6 17.9 17.8 17.8 17.7 26.4 45 41.7 38.9 63 63 10

IMPORTANT NOTE:-
1. RLA is based on Indore temp. 27ºc and outdoor temp. 35ºc
2. Max. aloowable voltage variation between phase is 2%
3. Select wire size based on the larger value of MCA or TOCA
4. MFA is used to select circuit breaker and the ground fault circuit interrupter(ELCB)
SYMBOLS:-
MCA:- Min. circuit amps.
TOCA:- Total over current amps.
MFA:- Max. fused amps.
RLA:- Rated load amps.
Safety Measures:-
1) Time delay of atleast 20 seconds is required in between power switchovers. In case time delay is not possible reverse phase protection is required
2) Auto phase change over switch should be installed in main panel to automatically change the phase sequence and
to avoid tripping of outdoor units in case of power switchovers
DAIKIN VRV-X INDOOR UNITS
RECOMMONDED POWER SUPPLY IS 1PH + N , 240 VAC , 50Hz. WITH EARTHING.
PROVIDE INDEPENDENT DB PANEL FOR VRV INDOOR UNITS.
EARTH LEAKAGE CKT. BRAKER 300mA PER PHASE IS MANDATORY.

FXCQ –M CEILING MOUNTED DOUBLE FLOW CASSETTE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXCQ 20 MVE 0.5 0.01 0.4 77 6 Amps 3C X 1.5 sq.mm.
2 FXCQ 25MVE 0.5 0.015 0.4 92 6 Amps 3C X 1.5 sq.mm.
3 FXCQ 32MVE 0.5 0.015 0.4 92 6 Amps 3C X 1.5 sq.mm.
4 FXCQ 40MVE 0.8 0.02 0.6 130 6 Amps 3C X 1.5 sq.mm.
220~240
5 FXCQ 50MVE 0.8 0.02 0.6 130 6 Amps 3C X 1.5 sq.mm.
6 FXCQ 63MVE 0.9 0.03 0.7 161 6 Amps 3C X 1.5 sq.mm.
7 FXCQ 80MVE 1.1 0.05 0.9 209 6 Amps 3C X 2.5 sq.mm.
8 FXCQ 125MVE 1.3 0.085 1 256 6 Amps 3C X 2.5 sq.mm.

FXFQ-SVM CEILING MOUNTED MULTIFLOW CASSETTE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXFQ 25SVM 0.3 0.048 0.2 31 15 Amps 3C X 1.5 sq.mm.
2 FXFQ 32SVM 0.3 0.048 0.2 31 15 Amps 3C X 1.5 sq.mm.
3 FXFQ 40SVM 0.4 0.048 0.3 41 15 Amps 3C X 1.5 sq.mm.
4 FXFQ 50SVM 0.6 0.048 0.5 80 15 Amps 3C X 1.5 sq.mm.
220~240
5 FXFQ 63SVM 0.8 0.048 0.6 95 15 Amps 3C X 1.5 sq.mm.
6 FXFQ 80SVM 0.8 0.048 0.6 95 15 Amps 3C X 1.5 sq.mm.
7 FXFQ 100SVM 1.4 0.106 1.1 194 15 Amps 3C X 2.5 sq.mm.
8 FXFQ 125SVM 1.6 0.106 1.3 219 15 Amps 3C X 2.5 sq.mm.

FXFSQ-ARV16 CEILING MOUNTED MULTIFLOW CASSETTE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXFSQ 25ARV16 0.3 0.053 0.2 28 6 Amps 3C X 2.5 sq.mm.
2 FXFSQ 32ARV16 0.3 0.053 0.2 28 6 Amps 3C X 2.5 sq.mm.
3 FXFSQ 40ARV16 0.4 0.053 0.3 35 6 Amps 3C X 2.5 sq.mm.
4 FXFSQ 50ARV16 0.6 0.053 0.5 56 6 Amps 3C X 2.5 sq.mm.
5 FXFSQ 63ARV16 220~240 0.6 0.053 0.5 61 6 Amps 3C X 2.5 sq.mm.
6 FXFSQ 80ARV16 1 0.053 0.8 92 6 Amps 3C X 2.5 sq.mm.
7 FXFSQ 100ARV16 1.4 0.106 1.1 164 6 Amps 3C X 2.5 sq.mm.
8 FXFSQ 125ARV16 1.6 0.106 1.3 170 10 Amps 3C X 2.5 sq.mm.
9 FXFSQ 140ARV16 1.8 0.106 1.4 194 10 Amps 3C X 2.5 sq.mm.

FXZQ-AVM CEILING MOUNTED COMPACT CASSETTE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXZQ20 AVM 0.3 0.055 0.2 43 6 Amps 3C X 2.5 sq.mm.
2 FXZQ25 AVM 0.3 0.055 0.2 43 6 Amps 3C X 2.5 sq.mm.
3 FXZQ32 AVM 220~240 0.4 0.055 0.3 45 6 Amps 3C X 2.5 sq.mm.
4 FXZQ40 AVM 0.4 0.055 0.3 59 6 Amps 3C X 2.5 sq.mm.
5 FXZQ50 AVM 0.6 0.055 0.5 92 6 Amps 3C X 2.5 sq.mm.

FXKQ-AV16 CEILING MOUNTED CASSETTE CORNER UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


3 FXKQ 32AV16 0.4 0.61 0.3 24 6 Amps 3C X 2.5 sq.mm.
4 FXKQ 40AV16 0.5 0.61 0.4 29 6 Amps 3C X 2.5 sq.mm.
220~240
5 FXKQ 50AV16 0.7 0.61 0.5 37 6 Amps 3C X 2.5 sq.mm.
6 FXKQ 63AV16 0.8 0.61 0.6 53 6 Amps 3C X 2.5 sq.mm.
FXDQ-PDV36,FXDQ-NDV36 SLIM CEILING MOUNTED DUCT TYPE

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXDQ 20PDV36 0.8 0.055 0.6 86 6 Amps 3C X 2.5 sq.mm.
2 FXDQ 25PDV36 0.8 0.055 0.6 86 6 Amps 3C X 2.5 sq.mm.
3 FXDQ 32PDV36 0.8 0.055 0.6 89 6 Amps 3C X 2.5 sq.mm.
220~240
4 FXDQ 40NDV36 1 0.055 0.8 160 6 Amps 3C X 2.5 sq.mm.
5 FXDQ 50NDV36 1 0.085 0.8 165 6 Amps 3C X 2.5 sq.mm.
6 FXDQ 63NDV36 1.1 0.085 0.9 181 6 Amps 3C X 2.5 sq.mm.

FXMQ-P, FXMQPB CEILING MOUNTED DUCT TYPE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXMQ 20PAVE 0.6 0.09 0.5 81 6 Amps 3C X 2.5 sq.mm.
2 FXMQ 25PAVE 0.6 0.09 0.5 81 6 Amps 3C X 2.5 sq.mm.
3 FXMQ 32PAVE 0.6 0.09 0.5 85 6 Amps 3C X 2.5 sq.mm.
4 FXMQ 40PBV36 1.4 0.14 1.1 128 6 Amps 3C X 2.5 sq.mm.
5 FXMQ 50PBV36 1.6 0.35 1.3 138 6 Amps 3C X 2.5 sq.mm.
220~240
6 FXMQ 63PBV36 1.8 0.35 1.4 151 6 Amps 3C X 2.5 sq.mm.
7 FXMQ 80PBV36 2.3 0.35 1.8 185 6 Amps 3C X 2.5 sq.mm.
8 FXMQ 100PBV36 2.9 0.35 2.3 215 6 Amps 3C X 2.5 sq.mm.
9 FXMQ 125PBV36 3.4 0.35 2.7 284 10 Amps 3C X 2.5 sq.mm.
10 FXMQ140PBV36 3.4 0.35 2.7 405 10 Amps 3C X 4 sq.mm.

FXMQ-AR CEILING MOUNTED DUCT TYPE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXMQ 40ARV16 0.8 0.055 0.65 160 6 Amps 3C X 2.5 sq.mm.
2 FXMQ 50ARV16 1.0 0.08 0.83 185 6 Amps 3C X 2.5 sq.mm.
3 FXMQ 63ARV16 220~240 1.2 0.1 0.92 210 6 Amps 3C X 2.5 sq.mm.
4 FXMQ 80ARV16 1.6 0.13 1.3 300 6 Amps 3C X 2.5 sq.mm.
5 FXMQ 100ARV16 1.6 0.18 1.3 345 6 Amps 3C X 2.5 sq.mm.

FXMQ-NV CEILING MOUNTED DUCT TYPE UNIT

SR NO MODEL VOLTAGE MCA IFM(kw) F L A Watts MCB Cable size


1 FXMQ 170NVE6 4.9 0.375X1 3.0 900 15 amps 3C X 4 sq.mm.
2 FXMQ 200NVE6 8.2 0.75X1 6.3 1100 15 amps 3C X 4 sq.mm.
3 FXMQ 250NVE6 10.9 0.45X2 9.0 1650 15 amps 3C X 4 sq.mm.

FXAQ – ARV WALL MOUNTED TYPE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXAQ 20ARVE6 0.3 0.04 0.2 17 6 Amps 3C X 2.5 sq.mm.
2 FXAQ 25ARVE6 0.4 0.04 0.3 19 6 Amps 3C X 2.5 sq.mm.
3 FXAQ 32ARVE6 0.4 0.04 0.3 21 6 Amps 3C X 2.5 sq.mm.
220~240
4 FXAQ 40ARVE6 0.4 0.04 0.3 22 6 Amps 3C X 2.5 sq.mm.
5 FXAQ 50ARVE6 0.5 0.04 0.4 27 6 Amps 3C X 2.5 sq.mm.
6 FXAQ 63ARVE6 0.7 0.048 0.6 56 6 Amps 3C X 2.5 sq.mm.
FXMQ –MFV1 OUTDOOR AIR PROCESSING UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXMQ 125NFRV16 1.9 0.38 1.5 359 10 Amps 3C X 4 sq.mm.
2 FXMQ 200NFRV16 220~240 3.3 0.38 2.6 548 15 Amps 3C X 4 sq.mm.
3 FXMQ 250NFRV16 3.8 0.38 3 638 15 Amps 3C X 4 sq.mm.

RECOMMONDED POWER SUPPLY IS 3PH + N , 380V to 415V , 50Hz. WITH EARTHING.


PROVIDE INDEPENDENT DB PANEL FOR VRV INDOOR UNITS.
EARTH LEAKAGE CKT. BRAKER 300mA PER PHASE IS MANDATORY.

FXVQ-N FLOOR STANDING DUCT TYPE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXVQ 125NY1 2.4 0.75 2 530 16 amps 4C X 6 Sq.mm.
2 FXVQ 200NY1 4.4 1.5 3.5 1330 16 amps 4C X 6 Sq.mm.
3 FXVQ 250NY1 380~415 4,4 1.5 3.5 1610 16 amps 4C X 6 Sq.mm.
4 FXVQ 400NY1 9.9 3.7 7.9 3970 25 amps 4C X 6 Sq.mm.
5 FXVQ 500NY16 13.6 5.5 10.9 5250 40 amps 4C X 6 Sq.mm.

MCA : MINIMUM CIRCUIT AMPS. FLA : FULL LOAD AMPS.


MFA : MAX FUSE AMPS.
IFM : FAN MOTOR RATED OUTPUT KW.

PLEASE NOTE THE ABOVE DATA IS IN DESIGN CONDITIONS WITH 39 DEGREE CENTIGRADE AMBIENT
CONDITIONS & 25 DEGREE CENTIGRADE INDOOR TEMPREATURE (CONDITIONED AREA).
NOTE:- 1. Max. allowable voltage unbalance between phases is 2%
2. MCA= 1.25 x FLA
3. MFA ≤ 4 X FLA
4. Select wire size based on the MCA
5. Instead of fuse, use circuit breaker based on MFA