Sl. No.

Project Specification Proposed Item Specification

Fuel Filling Point Cabinet

1 Locking Fill boxes: Flush Mounting with locking Wall mounted type fuel filling point cabinet provided.
type inner fill cap for standard padlock and Note: A cabinets typically come with standard port
threaded fill-pipe connection sizes of 1 ½” to 4”.

Liquid Level Gauge


Description:
• Calibrated, liquid-level gage system
• For continuous, non-contact level measurement in
complying with probes or other sensors
open or closed containers, tanks or silos. Suitable
and remote annunciator panel.
for liquid.
2 • Annunciator Panel: With visual and
• The device can be easily adjusted even without a
audible, high-tank-level and low-tank-level
medium by means of the programming display
alarms, fuel indicator with registration in
with user-friendly menus. It also serves as a local
liters, and overfill alarm. Include gauge
display.
volume range that covers fuel-oil storage
capacity. • Accuracy ±0.15 % FS
• Controls: Electrical, operating on 230 V ac.
Check Valve

Proposed check valve body cast steel.


3 Cast steel exhibits similar corrosion resistance to that
Suction Strainers and Check Valves: Bronze or
of wrought steel.
corrosion-resistant metal components.
Wall Thickness: API 600 CLASS 150, Test Standard: API
598.

Vent
Weatherproof Vent Cap: Cast- or malleable-iron Proposed Vent body is aluminium. Surface protection
4 increaser fitting with corrosion- resistant wire system is for all ATEX Zone.
screen, with free area at least equal to cross- Vent Valve with end of line flame arrester. The flame
sectional area of connecting pipe and arrester protects tank from outside fire.
threaded-end connection.

Y-Pattern Strainers:

• Body: ASTM A 126, Class B, cast iron with


• Proposed Y Strainer Body Cast Iron (A126 Class
bolted cover and bottom drain connection.
B).
• End Connections: Threaded ends for DN 50
• End connection flanged ANSI B16.1, CLASS 125.
5 and smaller; flanged ends for DN 65 and
larger. • Strainer Screen: 40-mesh
(Stainless Steel Woven Wire Mesh
• Strainer Screen:40 mesh start-up strainer
backed with a perforated sheet).
and perforated stainless-steel basket with
50 percent free area. • 200 Psi Non-Shock Cold Water, Oil or Gas
• CWP Rating: 125 psig (860 kPa)
Ball Valve

• One-Piece, Bronze Ball Valve with Bronze • T Screwed Body Cap, Blowout-proof Stem,
Trim: MSS SP-110. Double
• Body: Bronze, complying with ASTM B 584. • O-ring stem seal.
• Ball: Chrome-plated brass. • Threaded ends to BS21(JIS B0203).

6 • Stem: Bronze; blowout proof. • Body: Brass


• Seats: Reinforced TFE; blowout proof. • Body cap: Brass
• Packing: Separate packnut with adjustable • Stem: Brass (nickel plated)
stem packing threaded ends.
• Ball: Brass (chrome plated)
• Ends: Threaded, flared, or socket as
• Ball seat: PTFE
indicated in the valve schedule.
• O-ring: FKM
• CWP Rating: 600 psig (4140 kPa).
• 40 bars for W.O.G. non-shock, 10 bar at 150C̊
• Service
Fuel Oil Transfer
Mark:Pump Sets
Initials "WOG" shall be
• Standard: ASME B73.1on valve body.
permanently marked •
•• Description:
•• Type: Positive-displacement, rotary type.
• Impeller: Steel gear with crescent
• Housing: Cast-iron foot mounted.
• Bearings: Bronze, self-lubricating.
• Shaft: Polished steel.
• Seals: Mechanical.
• Base: Steel.
• Pressure Relief: Built in.
• Discharge Check Valve: Built in.
• Drive: Direct close coupled.
• Controls: • Casing: Ductile Iron
• Run pumps to maintain minimum manifold • Impeller: AISI 316
pressure with outdoor-air temperature less • Shaft: AISI 316
7 • Mechanical Seal: Graphite/SiC/perfluro metallic
than 55 deg C.
• Run pumps on seven-day schedule. Parts AISI 316.
• Stage pumps on pressure at a common supply • Total set: Pump + motor + base frame + coupling
manifold. • Motor: 11 kw/ 15HP/3ph/60Hz/ 400 V/ 3500
• Alternate pumps to equalize run time. rpm/2P/B3/TEFC/IP55/ Exd IIb T4
• Alarm motor failure.
• Manual reset dry-run protection. Stop pumps
if fuel level falls below pump suction.
• Deenergize and alarm pump locked rotor
condition.
• Alarm open circuit, high and low voltage.
• Indicating lights for power on, run, and off
normal conditions.
• Interface with automatic control system is
indicated as the following:
• Start/stop pump set when required by
schedule, fuel-fired appliance operation, day
tank level control, or weather conditions.
• Operating status.
• Alarm off-normal status.
• Motor: Comply with IEC 34 designation,
temperature rating, service factor, enclosure
type, and efficiency requirements for motors.
• Motor Sizes: Minimum size as indicated. If
not indicated, large enough so driven load
shall not require motor to operate in service
factor range above 1.0.
• Controllers, Electrical Devices, and Wiring:
Comply with requirements for electrical
devices and connections specified in Division
26 Electrical Sections.
• Strainers Furnished with Pumps: Duplex,
basket type with corrosion-resistant-metal-
screen baskets.