Testing and Adjusting (CDVR)
Testing and Adjusting (CDVR)
March 2009
SpeciÞcations
Systems Operation
Testing and Adjusting
Caterpillar Digital Voltage Regulator
(CDVR)
SAFETY.CAT.COM
i01658146
Table of Contents
SpeciÞcations Section
Electrical ................................................................. 4
Dimensions ............................................................. 7
Index Section
Index ..................................................................... 85
4 RENR7941-05
SpeciÞcations Section
SpeciÞcations Section
i03213848
Electrical
SMCS Code: 4467
Table 1
SpeciÞcations
Regulation 0.25% from no load to full load.
Regulator temperature drift Less than ±1% for any 40 °C (72 °F) change over the ambient operating
temperature range.
ConÞgurable Volts/Hz characteristic Two slope ranges adjustable from 1 to 10 V/Hz. See the Regulation
Characteristic Illustration.
Regulator response time Maximum of 10 milliseconds.
Regulator sensing True RMS 3-phase sensing is standard. Single phase sensing is available.
Variable sense range: 90 to 600 volts.
Regulator stability The regulator maintains stable output voltage within 0.25% for total
harmonic distortion of the generator output voltage waveform up to 30%,
and within 0.50% for total harmonic distortion of the generator output
voltage waveform up to 40%. These values are based on a typical 6 SCR
bridge.
Telephone inßuence factor (TIF) Less than 50. Complies with MIL STD 461C Part 9 and VDE 0875 level N.
Fine voltage adjust range ± 10% of regulator sensing voltage.
Regulator voltage gain (Line loss compensation) Adjustable from 0 to 10%.
Fault detection and identiÞcation Diagnostics identify operation outside of programmed limits. SpeciÞc
fault information is available even after the unit has been powered down.
CANBUS only.
Harmonic tolerance For total harmonic distortion of the generator output voltage waveform up
to 30%, the regulator maintains stable output voltage within 0.25%. For
total harmonic distortion of the generator output voltage waveform up to
40%, the regulator maintains stable output voltage within 0.50%. These
values are based on a typical 6 SCR bridge.
Reactive droop adjustment Adjustable from 0 to 10%.
Overexcitation protection Shuts off generator output when excitation current exceeds normal
operating currents for 10 seconds or instantaneous shutoff if output current
exceeds approximately 28 Amperes.
Ambient operating temperature í40 °C (í40 °F) to +70 °C (+ 158 °F).
Storage temperature range í40 °C (í40 °F) to +85 °C (+ 185 °F).
Power dissipation 5 watts at idle, 55 watts at rated output.
Shock Withstands up to 20 g's in three mutually perpendicular planes .
Vibration Withstands 4.5 g's at frequencies between 18 and 2000 Hz in three
mutually perpendicular planes.
Salt fog 5% salt spray for 48 hours at 38 °C (100.4 °F) at 115% of the nominal
operating voltage.
Weight 1.47 kg (3.24 lb.).
Electromagnetic compatibility Meets 89/336/EEC Electromagnetic Compatibility Directive.
Power supply 24 ± 6 volt DC power supply required (0.5 amp).
(continued)
RENR7941-05 5
SpeciÞcations Section
(Table 1, contd)
SpeciÞcations
Conformity UL UL Recognized per Standard 508, UL File No. E97035.
CSA CertiÞed per Standard CAN/CSA-C22.2 No. 14-95, CSA Dile No. LR
23131.
CE Conforms to the following standards: Radiated Emissions EN50081-2,
Radiated Immunity (electric Þeld) EN61000-4-3 (10 V/m), Radiated
Immunity (conducted) EN61000-4-6 (10 VRMS), Conducted Emissions
EN50081-2 (EN55011, Class A), ESD Immunity EN50082-2 (4 KV contact,
8 KV air), EFT Immunity EN50082-2 (2 KV coupling clamp), Magnetic
Immunity EN50082-2 (30ARMS, 50 Hz), Safety EN61010-1.
g01040043
Illustration 1
Regulation Characteristic
6 RENR7941-05
SpeciÞcations Section
Table 2
Summary of Operating Parameters
Parameter SpeciÞcations
Voltage Regulation 120 to 15000 Volts
Rating
Generator Type PM
SE
Internal Excitation (IE)
Power Input Voltage(1) Frequency Burden (Continuous)
80 to 264 Volts (3Ø) 50 to 400 Hz 1150 VA (63 VDC applications) or 1900
100 to 280 Volts (1Ø) VA (125 VDC applications)
Output Rating Maximum Continuous Maximum Forcing (10 Seconds)
Voltage Current Voltage Current
63 or 125 Volts 12 or 10 Amperes 125 or 250 Volts 25 or 20 Amperes
Sensing Voltage Maximum VA Burden per Ø
90 to 600 Volts 1 VA
Reactive Droop Maximum Current Maximum VA Burden
5 Amperes 1 VA
Exciter Field Minimum Resistance Maximum Resistance
Resistance
3 Ohms 39 Ohms
(1) As the CDVR input voltage increases, the PWM duty cycle decreases. As PWM duty cycle decreases, system stability may decrease as
well. Powering the CDVR with a voltage closer to the low end of this range is preferred.
RENR7941-05 7
SpeciÞcations Section
i02852265
Dimensions
SMCS Code: 4467
g01415745
Illustration 2
Dimensions of the Caterpillar Digital Voltage Regulator
(A) 276.4 mm (10.88 inch)
(B) 190.5 mm (7.50 inch)
(C) 139.7 mm (5.50 inch)
(D) 162.1 mm (6.38 inch)
(E) 72.9 mm (2.87 inch)
(F) 71.4 mm (2.81 inch)
(G) 15.0 mm (0.59 inch)
(H) 4.06 mm (0.16 inch)
8 RENR7941-05
Systems Operation Section
General Information
SMCS Code: 4467
g01118951
Illustration 3
(1) “P6” Connector (3) “P12” Connector (5) “J4” Connector
(2) LED Indicator (4) “P9” Connector
The Caterpillar Digital Voltage Regulator (CDVR) is Connector “P6” is a six-pin header that mates with
a microprocessor based voltage regulator. The main a six-pin connector. Connector “P9” is a nine-pin
purpose of a digital voltage regulator is to regulate header that mates with a nine pin connector.
the output voltage of a generator that is used with an Connector “P12” is a twelve pin header that mates
engine generator set. Control power for the Digital with a twelve pin connector.
Voltage Regulator is supplied from an external 24
DCV source. The power stage of the Digital Voltage The regulator has a nine pin D sub connector that is
Regulator can be supplied from a multi-pole, high labeled “J4”. This connector is used for interface with
frequency, permanent magnet generator (PMG), IBM compatible personal computers.
from the generator output (shunt excitation), or
from auxiliary windings that are included on some Note: The Caterpillar Digital Voltage Regulator
generators. Connections to the Digital Voltage should be hard wired to earth ground with at least a
Regulator are made through three multi-pin, plug type 16 AWG copper wire that is attached to the ground
connectors. The communication between the Digital terminal “P6-6”.
Voltage Regulator and a service tool is accomplished
using a CANBUS protocol. Note: When the unit is conÞgured in a system with
other devices, a separate lead should be used to
The Caterpillar Digital Voltage Regulator has three ground the bus from each device.
multiple-pin, plug-type connectors. These connectors
are labeled “P6”, “P9”, and “P12”. See illustration 3.
RENR7941-05 9
Systems Operation Section
Table 3
Connector “P12”
P6 Terminal Functions
Terminal Function
P6-1 Power Input (single phase)
P6-2 Power Input (single phase)
P6-3 Power Input
P6-4 F-
P6-5 F+
P6-6 Chassis Ground
g01013628
Illustration 6
Pin out for the “P12” Connector on the CDVR
10 RENR7941-05
Systems Operation Section
i02848546
i02847653
g01012488
Illustration 7
The parameters that are related to the loading and When the generator is running and if a large load is
stopping proÞle are listed below. applied, the frequency and voltage will drop. The
loading/stopping function minimizes the amount of
• Generator Output Voltage time that it takes the engine and generator to recover
and increases the ability to pick up large loads.
• Knee Frequency
As a large load is applied, the engine speed will begin
• Decreasing V/Hz Slope 1 to drop (frequency decreases). As the frequency
decreases below the knee frequency, the voltage
• Decreasing V/Hz Slope 2 reference will decrease on a Volts/Hz slope according
to the decreasing slope 1 value. If the frequency
• Minimum Voltage decrease continues beyond the knee frequency
minus 5 Hz, then the voltage reference will decrease
• Underfrequency Point on a Volts/Hz slope according to the decreasing
slope 2 value until the minimum voltage level is
Voltage regulators are generally of the volts per hertz reached. The digital voltage regulator will try to
type or the constant voltage type. The digital voltage regulate the generator output voltage at the minimum
regulator can perform as a constant voltage regulator voltage, unless the underfrequency point is reached
or a volts per hertz type regulator depending on where the generator output voltage will decrease to a
user conÞguration. Volts per hertz type regulators minimum value.
are commonly used with reciprocating internal
combustion engine driven generator sets because As the engine recovers from the load increase,
they provide an automatic means for the engine to the voltage will increase in the reverse order as it
recover from a large block load. In the digital voltage decreased, unless the frequency dropped below
regulator, the block load recovery performance is the underfrequency point. If the frequency dropped
conÞgurable so that it may be Þeld optimized for each below the underfrequency point, the startup proÞle
speciÞc application. will be used for the recovery.
12 RENR7941-05
Systems Operation Section
In some applications it is desirable to maintain Once startup has been achieved and the generator
a constant voltage at the possible sacriÞce of a output frequency is above the corner frequency, the
larger frequency dip during load transients. The regulator will normally act to keep the generator
digital voltage regulator can accommodate these output voltage constant. As changes in generator
applications if the knee frequency is conÞgured for loading cause the voltage to sag or rise, the regulator
a lower value than normal. The actual value will will automatically adjust generator excitation to
depend on the speciÞc application. When used in this maintain the output voltage. If loading causes
application, the load transients must be kept small in the generator frequency to drop below the knee
order to allow the engine to recover without dropping frequency, the loading and stopping proÞle as
below the knee frequency. previously described will be followed. See System
Operation, “Loading And Stopping ProÞle”.
When a large block load is switched on to the system,
the engine speed temporarily decreases as the The CDVR can be connected to a “Manual
engine produces the additional power requirement Voltage Control”. For a wiring diagram of “Manual
by burning more fuel. If the regulator is set to act Voltage Control” see Testing and Adjusting, “Wiring
as a volts per hertz type, it will reduce the output diagrams”.
voltage according to the slope of the V/Hz curve. The
reduction in voltage reduces the power requirement A remote voltage adjust toggle switch may be used
of the load, thus allowing the engine to recover faster to Þne tune the generator output voltage. When
for a given block load. If the regulator is set to act as used, the active value of voltage reference may be
a constant voltage type, the regulator will not reduce adjusted ±10%.
the output voltage for a change in speed (addition of
block load). Therefore, it will take the engine a longer Voltage can be changed in the software.
time to regain speed and supply the total power
requirement of the load. If the regulator is set to act 1. The voltage can be changed at the “Settings”
as a constant voltage type, care must be taken to screen or the “Metering” screen in the CDVR.
keep block load applications small enough so that
the engine can recover in acceptable time. 2. The voltage can be changed at the “Voltage
Regulator Control Parameters” screen with the
use of Cat ET.
i02848560
Voltage Regulation Note: In order to change the new voltage set point,
the “EEPROM” button must be pressed in the CDVR
SMCS Code: 4467 PC software, or the “Enter” key must be pressed in
Cat ET after the new set point is entered.
The parameters that are related to voltage regulation
are listed below. i02847614
• Voltage Set point The net result is that the generated voltage and the
output current of each generator is trimmed toward
• Generator Frequency an operating point where all generators will share
the same load current in proportion to the CT ratio,
• Knee Frequency with the little or no circulating current between them.
Droop percentage controls the amount of individual
• Integral Gain generator voltage droop (or rise) for a given amount
of CT signal.
• Derivative Gain
However, because the CT secondary circuits are all
• Proportional Gain interconnected, the CT signal seen by any individual
regulator is not representative of the actual current
• Loop Gain ßowing in that particular generator. Any display or
calculations that might use that signal as if it were
• Generator CT Current Primary Rating the actual generator current will provide erroneous
results.
• Generator CT Current Secondary Rating
Reactive voltage droop needs to be selected and an
• Load Compensation Mode enable contact needs to be closed in order to enable
cross current compensation. Refer to the Testing and
• Droop Percentage Adjusting, “Wiring Diagrams” section for a wiring
diagram of the cross current compensation circuit.
• Rated Generator Current
Cross current compensation is often used in i02847603
order to minimize circulating current ßow between
the generators that are connected in parallel. KVAR Regulation
The advantage of this operating mode is that all
generators contribute in order to establish the SMCS Code: 4467
same output voltage to the load. Cross current
compensation is only used for paralleling multiple Parameters that are related to KVAR regulation are
generator sets. Cross current compensation is not listed below.
used when paralleling with a utility.
• Rated Generator Voltage
Operation is similar to the reactive voltage droop
mode except that the secondary circuits of the current • Generator PT Primary Voltage Rating
transformers of all generators are interconnected in
a series string. Each generator is initially adjusted in • Generator PT Secondary Voltage Rating
order to provide the same output voltage.
• Voltage Setpoint
• Generator Frequency
• Knee Frequency
• Integral Gain
• Derivative Gain
RENR7941-05 15
Systems Operation Section
• VAR Set point In KVAR mode, the generator will supply a constant
amount of reactive power to the system as set by the
• VAR Integral Gain reference (KVAR) regardless of the real power output
(kW) of the generator set. The generator will supply
• VAR Loop Gain real power (kW) to the system. This is determined by
the engine governor and/or the device that is used for
When the generator is connected in parallel with sharing the load. Due to the amount of reactive power
an inÞnite bus (utility), the voltage of the generator on the utility, current overloading of the system (due
is controlled by the inÞnite bus. The voltage of the to large reactive current requirements) is possible. In
generator will change as the inÞnite bus voltage the KVAR mode, the generator can supply a Þxed
changes. It is not possible to control the system amount of reactive power to the system.
voltage when the generator is connected to an inÞnite
bus. In this instance, it is necessary for the digital For stable operation of the generator in the KVAR
voltage regulator to regulate the reactive power regulating mode, the generator must be connected
output which is supplied by the generator. There are to a utility or a system that is much larger than the
two methods for regulating the reactive power output. generator. When the breaker (tie) is closed to the
utility, connect terminal “P9-9” and terminal “P9-6” in
• KVAR Regulation order to enable the KVAR mode. When the terminal
“P9-9” and terminal “P9-6” are disconnected from
• Power Factor (PF) Regulation each other, the regulator will be in a voltage control
operating mode with the following or without the
Note: KVAR stands for Kilo-Volt-Ampere-Reactive, following: droop and line loss compensation.
which is the unit of measurement for reactive power.
i02848334
When the digital voltage regulator is in the KVAR
operating mode, the digital voltage regulator works
to produce a constant KVAR output, regardless
Power Factor Regulation
of the real power output of the generator. In this SMCS Code: 4467
case, the power factor (generator) will change when
the real power output of the generator changes. A Parameters that are related to PF regulation are
current transformer (CT) is necessary for this mode listed below.
to work. KVAR mode must be selected in software
(at the “Metering” screen in the CDVR PC software,
or under the “VAR/PF Mode Selection” screen in
• Rated Generator Voltage
the Caterpillar Electronic Technician (Cat ET). The
contact for the KVAR/PF enable must also be closed.
• Generator PT Primary Voltage Rating
Refer to the following contacts: “P9-6” and “P9-9”.
• Generator PT Secondary Voltage Rating
A remote KVAR/PF adjust toggle switch may be used
in order to Þne-tune the KVAR set point. Refer to
• Voltage Set point
the following contacts: “P9-4”, “P9-5”, and “P9-6”.
This switch may be the same switch used for remote
• Generator Frequency
voltage adjustment. When the contact for KVAR/PF
is closed, and the KVAR mode is selected, the switch
• Knee Frequency
will not affect voltage.
• Integral Gain
• Derivative Gain
• Proportional Gain
• Loop Gain
16 RENR7941-05
Systems Operation Section
• Rated Generator Current A remote KVAR/PF adjust toggle switch may be used
in order to Þne tune the PF set point. Refer to the
• Generator CT Current Primary Rating following contacts: “P9-4”, “P9-5”, and “P9-6”. The
remote KVAR/PF switch may be the same switch
• Generator CT Current Secondary Rating used for remote voltage adjustment. Raising the
PF set point will make the PF more lagging. The
• Operating Mode lagging PF is a positive PF. Lowering the PF set
point will make the PF more leading. The leading PF
• PF Set point is a negative PF. When the contact for KVAR/PF is
closed, and the PF mode is selected, then the switch
• PF Integral Gain will not adjust the voltage setting.
• PF Loop Gain Note: The KVAR/PF contact does not specify if the
CDVR is in KVAR or PF mode speciÞcally. PF mode
• Reactive Droop must be selected in software.
When the generator is connected in parallel with Note: When operating in parallel operations, make
an inÞnite bus (utility), the voltage of the generator sure that “Droop” mode is selected. The “Droop”
is controlled by the inÞnite bus. The voltage of the mode must be selected in the “Settings” screen. A
generator will change as the inÞnite bus voltage 0% droop may be selected.
changes. It is not possible to control the system
voltage when the generator is connected to an inÞnite
i02847681
bus. In this instance, it is necessary for the digital
voltage regulator to regulate the reactive power
output which is supplied by the generator. There are
Parameters
two methods for regulating the reactive power output. SMCS Code: 4467
• KVAR Regulation
General Information
• Power Factor Regulation
Parameters are pieces of information which are used
Note: KVAR stands for kilo-Volt-Ampere-Reactive, within the memory of the digital voltage regulator.
which is the unit of measurement for reactive power. Each parameter has a speciÞc range of values.
Parameters tell the digital voltage regulator how to
When the digital voltage regulator is in the power operate. Service personnel can conÞgure certain
factor operating mode, it works to produce a constant parameters to the requirements of a speciÞc site.
power factor, regardless of the real power output of ConÞguration changes the value of a particular
the generator. In this case, the reactive current will parameter. There is an upper and lower limit for
change when the real power output of the generator the value of each parameter. The limits can not be
changes. A current transformer (CT) is necessary exceeded.
for this mode to work. PF operating mode must be
selected. In order to view or conÞgure the values of the
parameters see Testing And Adjusting, “Parameter
For stable operation of the generator in the PF Viewing And ConÞguring Procedure”.
regulating mode, the generator must be connected
to a utility or system that is much larger than the
generator. When the tie breaker is closed to the
utility, connect terminals “P9-9” and “P9-6” in order
to enable the PF mode. When the terminals “P9-9”
and “P9-6” are disconnected from each other, the
regulator will be in a voltage control operating mode
with or without droop or line loss compensation as
previously described. “PF” mode must be selected in
software and the “KVAR/PF” contact must be closed.
Refer to the following contacts: “P9-6” and “P9-9”.
When the contact is not closed the regulator operates
in AVR mode.
RENR7941-05 17
Systems Operation Section
i02787341
Remote Communication
SMCS Code: 4467
g01008946
Illustration 8
Table 6
Pin Function Name Direction
1 - - N/A
2 Transmit Data TXD From Regulator
3 Receive Data RXD To Regulator
4 - - N/A
5 Signal Ground GND N/A
6 - - N/A
7 - - N/A
8 - - N/A
9 - - N/A
18 RENR7941-05
Systems Operation Section
g01136853
Illustration 9
Terminating Communication
Voltage regulator communication is terminated
by clicking “Communications” on the menu bar
and clicking “Close Comm Port”. The user will be
prompted to save the settings to the EEPROM. This
question is asked even if no changes were made
to the voltage regulator settings. When the close
command is executed (with a Yes or No to save
settings to the EEPROM), communication with the
voltage regulator is terminated. If the PC software is
exited the (by clicking “File” on the “Menu” bar and
then “Exit”) without Þrst closing communication, the
option will still be given to save the settings to the
g01392575 EEPROM.
Illustration 11
g01392576
Illustration 12
General Information
SMCS Code: 4467
g01425366
Illustration 14
Preventive Maintenance
The only preventive maintenance that is required
on the voltage regulator is to periodically check
the connections between the voltage regulator and g00241203
Illustration 15
the system. The connections must be clean and
tight. Voltage regulator units are manufactured 6V-7070 Caterpillar Digital Multimeter
using state-of-the-art, surface-mount technology.
Caterpillar recommends that no repair procedures be Caterpillar digital multimeters can be used in order
attempted by anyone other than Caterpillar dealer to measure voltage, resistance or current up to 10
technicians. amperes. RectiÞers can also be checked by using the
diode function. See Special Instruction, SEHS7734,
“Use Of The 6V-7070 And 6V-7800 Multimeter”
for the correct operation of the 6V-7070 Digital
Multimeter.
RENR7941-05 21
Testing and Adjusting Section
• CT Primary
• Power Input Frequency (Hz) - Refer to
Table 7.
Table 7
• VAR (percent of rated) - For VAR mode. 6. Start the engine. Make the Þnal adjustments, as
required.
• Power Factor - Must select Droop under
“Load Compensation Mode” for PF control. 7. Press the EEPROM button to save the settings in
the CATV.
• Soft Start Bias (percent) - A starting value
for the regulator on startup. 8. Record all settings. For more details, refer to
“Settings File” located in the “Parameter Viewing
• Soft Start Time (sec.) - For emergency and ConÞguration (Caterpillar PC Software)”
applications, this value may need to be set section.
to 2 seconds, or less.
9. Press “Get From Unit” to verify that the settings
• Knee Frequency (Hz) - Select a value that were saved.
is 0.2 to 2 Hz below rated frequency.
10. Disable communications (if desired). For more
• Slope 1 (V/Hz) - 2V per Hz suggested. details, refer to “Terminating Communications”
located in the “Remote Communication” section.
• Slope 2 (V/Hz) - Refer to Illustration 18.
c. Control Gain Settings
d. Protections Settings
g01012488
Illustration 18
The Caterpillar PC software provides the 1. Insert the CD-ROM into the CD-ROM drive of the
communication link between the voltage regulator PC.
and the user. All voltage regulator settings are
entered and read through this software. Within this 2. Click the Windows Start button and then select
software, voltage regulator settings can be saved in “Run”. In the “Open:” Þeld, enter “D:/Setup.exe”,
a computer Þle and used later in order to conÞgure where “D” is the designator letter for your PC
other units with the same settings. CD-ROM drive. Then click “OK”.
24 RENR7941-05
Testing and Adjusting Section
g01393986
Illustration 19
g01393989
Illustration 20
Systems ConÞguration screen
(1) System ConÞguration button (4) Protection Setting button (7) EEPROM button
(2) Setting Adjustment button (5) Metering/Operation button
(3) Control Gain Button (6) Get From Unit button
Each setting group has a corresponding button that Sending and Receiving Settings
can be selected to access that group of settings. See
Illustration 20. The Þve setting groups can also be When communication is enabled, voltage regulator
accessed by clicking “Screens” on the menu bar and settings can be sent or received through the PC
then selecting the desired setting group from the list. software.
Once a setting group is accessed, the individuals
settings of the group can be viewed and changed. Sending Settings
A setting is changed by clicking within the setting Settings changes are sent to the voltage regulator
Þeld and typing the setting. The minimum, maximum by two methods:
and increments (steps) for a setting are displayed on
the status bar when the cursor is placed within that 1. Type a value in the setting screen Þeld, then press
setting Þeld. A changed setting is sent to the voltage the “Enter” key.
regulator when the “Enter” key on the PC is pressed.
A setting in a Þeld with the pull down menu is sent Note: Just typing a value in the setting screen Þeld
to the voltage regulator when the setting is selected WILL NOT send that value to the CDVR. When a
from the pull down menu. value is typed in the setting screen Þeld, the “Enter”
key must also be pressed.
Receiving Settings
Voltage regulator settings are retrieved by clicking the
“Get From Unit” button (6). This causes the current
settings of the voltage regulator to be displayed on
the “settings” screen.
Setting DeÞnitions
Each of the Þve setting groups have a corresponding
screen in the PC software. The setting of each
screen are categorized by one or more tabs. In
the following paragraphs, setting are arranged and
deÞned according to the organization of the PC
application screens and tabs.
System ConÞguration
The “System ConÞguration” screen consists
of one tab labeled “ConÞguration”. Click the
“ConÞgure” button (1) in order to access the “System
ConÞguration” screen or click “Screens” on the menu
bar and click “System ConÞguration”.
RENR7941-05 27
Testing and Adjusting Section
ConÞguration Tab
g01393995
Illustration 21
Rated Voltage (V) – The rated AC generator voltage PT Secondary (V) – The secondary AC voltage
is entered in this Þeld. Voltages within the range of 90 rating of the PT is entered in this Þeld. Voltages
to 15000 VAC may be entered in 1 VAC increments. within the range of 90 and 600 VAC may be entered
in 1 VAC increments. Note: A PT is required if the
Rated Current (A) – The maximum rated AC generator is rated at more than 600 VAC. If no PT is
generator current is entered in this setting Þeld. installed, set the PT primary and PT secondary to the
Current values that are up to 9999 amperes may be expected sensed voltage.
entered in 1 ampere increments.
CT Primary – The AC current rating of the primary
Rated kVAR – This Þeld is a read-only Þeld that winding of the CT is entered in this Þeld. Current
displays the rated, calculated reactive power, based values that are up to 9999 amperes may be entered
on the values that are entered in the Rated Voltage in 1 ampere increments.
and Rated current Þelds.
CT Secondary – This Þeld is a read-only Þeld that
Frequency – This setting is used to select a nominal displays the rated value of the current that is present
system operating frequency of 50 Hz or 60Hz. at the secondary winding of the CT. This regulator is
designed for a 5 ampere secondary winding only.
PT Primary (V) – The primary AC voltage rating of
the potential transformer (PT) is entered in this Þeld. Power Input Frequency (Hz) – The frequency
Voltages within the range of 90 and 15000 VAC may value of the operating power applied to the voltage
be entered in 1 VAC increments. regulator is entered in this Þeld. This would be the
frequency of the permanent magnet generator or the
frequency of the generator in the case of self-excited
generator. Frequencies within the range of 50 to 400
Hz may be entered in 1 Hz increments. Refer to table
8 for the correct frequency values.
28 RENR7941-05
Testing and Adjusting Section
Table 8
Operating Frequency 50HZ 60HZ
Self Excited Generators 50HZ 60HZ
Permanent Magnet Generators 200HZ 240HZ
Low and Medium Voltage
6 Pole Generators 133HZ 160HZ
High Voltage 2600 Frame 200HZ 240HZ
Generators
High Voltage 2400 and 2800 150HZ 180Hz
Frame Generators
Setting Adjustments
The “Setting Adjustments” screen consists of two
tabs labeled “Setpoint” and “Startup”. Click the
“Settings” button (2) in order to access the “Setting
Adjustments” screen or click “Screens” on the menu
bar and click “Setting Adjustments”.
RENR7941-05 29
Testing and Adjusting Section
Setpoint Tab
g01009341
Illustration 22
Set point tab as seen without AVR Voltage Control and VAR/PF Control Desired Input ConÞguration (for original Þrmware).
30 RENR7941-05
Testing and Adjusting Section
g01418840
Illustration 23
Setpoint tab with AVR Voltage Control and VAR/PF Control Desired Input ConÞguration
AVR Voltage (V) – This setting Þeld is used to enter Power Factor – The Power Factor set point
the desired generator output terminal voltage. The determines the level of generator power factor
range of voltages is dependent on the value in the that is maintained by the voltage regulator when
“Voltage Adjustment Band (percent of rated)” Þeld. the voltage regulator is in the power factor mode.
Values may be entered in increments of 0.1 VAC. Settings within the range of 0.600 lagging to 0.600
leading may be entered in increments of 0.001. A
VAR (percent of rated) – The VAR set point setting in the lagging direction will have a positive
determines the level of generator VARs that are value and a setting in the leading direction will have
maintained by the voltage regulator when the digital a negative value. Before setting a leading power
voltage regulator is in the VAR mode. Percentage factor, consult the reactive capability curve for
values within the range of -100 to 100 percent may the generator being used.
be entered in increments of 0.1 percent. A setting in
the overexcited direction will have a positive value
and a setting in the under excited direction will have
a negative value.
RENR7941-05 31
Testing and Adjusting Section
AVR Voltage Control: Desired Input When operating in parallel operations, make sure
ConÞguration – “CAN Input” and “Switch” Droop mode is selected.
are the two settings that can be selected from the
drop down menu for this conÞguration. Selecting “Reactive Droop Compensation” and “Line Drop
“CAN Input” conÞgures the voltage regulator to accept Compensation” are brießy described below:
changes to the AVR voltage set point only from the
“CANbus”. If an attempt is made to change the AVR Reactive Droop Compensation - The voltage
set point with this conÞguration, from the “Settings” regulator provides a “Reactive Droop Compensation”
screen, with the use of the “Raise” or “Lower” buttons feature for three phase generators in order to
while at the “Metering” screen, and with the “Raise” assist in the sharing of reactive load during parallel
or “Lower” contacts, then the adjustment will have generator operation. The voltage regulator calculates
no effect. Selecting “Switch” conÞgures the voltage the reactive portion of the generator load using
regulator to accept changes to the AVR voltage the sensed generator output voltage and current
set point from the “Settings” screen, the “Raise” or quantities. The voltage regulator then modiÞes the
“Lower” buttons in the “Metering” screen, or by the voltage regulation set point accordingly.
use of the “Raise” or “Lower” contacts. The CANbus
will have no effect. If “CAN Input” is selected and the • A unity power factor generator load results in
CANbus communication is not available, the voltage almost no change in generator output voltage.
regulator will not automatically change to the “Switch”
setting. The user must use software to manually • A lagging power factor generator load (inductive)
change this setting to “Switch” in order to have AVR results in a reduction of generator output voltage.
voltage set point control. However, changing the
AVR set point from the “Settings” screen or using the • A leading power factor generator load (capacitive)
“Raise” or “Lower” buttons in the “Metering” screen results in an increase of generator output voltage.
will allow for changes to the AVR set point.
Droop is adjustable up to 10 percent with rated “B
VAR/PF Control: Desired Input ConÞguration – phase” line currents and 0.8 power factor. The “B
“CAN Input” and “Switch” are the two settings that phase” line currents are 5 amperes applied through
can be selected from the drop down menu for this terminals P12-1 and P12-2. The droop is adjustable
conÞguration. Selecting “CAN Input” conÞgures the with the use of the communication port(s).
voltage regulator to accept changes to the VAR/PF
voltage set point only from the “CANbus”. If an “Reactive Droop Compensation” is mutually exclusive
attempt is made to change the VAR/PF set point with to line drop compensation. These two functions work
this conÞguration, from the “Settings” screen, with opposite of one another and, therefore, cannot be
the use of the “Raise” or “Lower” buttons while at the used at the same time.
“Metering” screen, and with the “Raise” or “Lower”
contacts, then the adjustment will have no effect. In addition, the “Reactive Droop Compensation”
Selecting “Switch” conÞgures the voltage regulator to feature allows paralleling of three phase generators
accept changes to the VAR/PF voltage set point from when connected for “Cross Current Compensation”
the “Settings” screen, with the use of the “Raise” or (CCC). The CCC method of connection allows
“Lower” buttons while at the “Metering” screen, and reactive load shared between generators with very
with the “Raise” or “Lower” contacts. The CANbus little voltage droop. The droop level adjustment acts
will have no effect. If “CAN Input” is selected and the as the sensitivity adjustment when connected for
CANbus communication is not available, the voltage CCC.
regulator will not automatically change to the “Switch”
setting. The user must use software to manually Verify that the system works in reactive droop mode
change this setting to “Switch” in order to have before connecting in CCC mode.
VAR/PF voltage set point control. However, changing
the VAR/PF set point from the “Settings” screen or Note: When in CCC mode, kW and/or kVAR may
using the “Raise” or “Lower” buttons in the “Metering” indicate negative values in the “Metering” screen.
screen will allow for changes to the VAR/PF set point.
Startup Tab
g01393997
Illustration 24
34 RENR7941-05
Testing and Adjusting Section
g01012488
Illustration 25
Soft Start Bias (percent) – The Soft Start Bias Knee Frequency (Hz) – The “Knee Frequency”
setting determines the generator voltage offset setting deÞnes the value of frequency that causes
during start up as a percentage of the generator the voltage regulator to adjust the voltage set point
rated voltage. The CDVR will raise output voltage to so that the generator terminal voltage follows the
this percentage as quickly as possible. A percentage selected volts per hertz slope. A value of 45.00 to
value of 0.00 to 90.00 may be entered in increments 65.00 hertz may be entered in increments of 0.01
of 0.01 percent. hertz. “Knee Frequency” should typically be set
from 0.2 to 2 Hz less than the generator operating
Soft Start Time (sec.) – The Soft Start Time frequency. The knee frequency should be adjusted
establishes the length of time for the generator closer to the nominal frequency in applications
terminal voltage to increase to the generator rated where the generator engine and governor is slow in
voltage level from the “Soft Start Bias” percent. A recovering frequency during a transient load event.
value of 0.00 to 120.00 seconds may be entered in
increments of 0.01 seconds. If the “Under Frequency Frequency Deviation from Corner Frequency
Point” is reached before the CDVR reaches the (Hz) – This Þeld is a “read-only” Þeld. The Þxed value
“Soft Start Bias” percent, voltage will build from the is subtracted from the “Corner Frequency” value
“Soft Start Bias” percent, in a linear manner, for in order to determine when the generator under
the duration of the “Soft Start Time”. If the “Under frequency operation changes from slope 1 to slope 2.
Frequency Point” is reached after the CDVR reaches
the “Soft Start Bias” percent, voltage will build from Slope 1 (V/Hz) – When the generator frequency
the “Soft Start Bias” percent, in a linear manner, until is between the corner frequency and the corner
the “Under Frequency Point” is reached. From there, frequency minus 5 hertz, the voltage set point is
voltage will build following a “volts-per-hertz” proÞle. automatically adjusted so that the generator voltage
Refer to Illustration 25. follows volts per hertz slope 1. Slope 1 is adjusted by
this setting Þeld. A setting of zero to 10.00 may be
entered in increments of 0.01.
RENR7941-05 35
Testing and Adjusting Section
Control Gain
The “Control Gain” screen consists of a single tab
labeled “Control Gain”. Click the “Gain” button (3)
in order to access the “Control Gain” screen or click
“Screens” on the menu bar and click “Control Gain”.
36 RENR7941-05
Testing and Adjusting Section
g01009752
Illustration 26
Proportional Gain Kp – This setting selects the Increasing the value of Ki decreases the time
proportional constant stability parameter. The voltage required to reach steady state.
regulator supplies a value that is equivalent to Kp
multiplied by the error between the voltage set point Derivative Gain Kd – This setting selects the
and the actual generator output voltage. Kp values of derivative constant stability parameter. The voltage
0 to 1,000 may be entered in increments of 0.01. regulator provides an output value that is equivalent
to Kd multiplied by the derivative of the error between
If the transient response has too much overshoot, the voltage set point and the actual generator output
then Kp may be decreased. If the transient response voltage. Kd values of 0 to 1,000 may be entered in
is too slow, then Kp may be increased. increments of 0.01.
Integral Gain Ki – This setting selects the integral Increasing the value of Kd reduces transient
constant stability parameter. The voltage regulator response ringing.
supplies a value that is equivalent to Ki multiplied by
the integral of the error between the voltage set point Noise Filter Time Constant Td – This setting
and the actual generator output voltage. Ki values of selects the noise Þlter time constant and is used in
0 to 1,000 may be entered in increments of 0.01. order to reduce high frequency noise. Values of 0.00
to 1.00 may be entered in increments of 0.01.
RENR7941-05 37
Testing and Adjusting Section
PID Calculator
g01009819
Illustration 27
The PID parameters are calculated for the desired Exciter Time Constant (Te) - (Seconds) – The
system response with a settling time of about one exciter time constant (Te) can be selected from this
third of the generator time constant and about 10 pull down menu. The value displayed in this menu
percent overshoot. depend on the generator time constant (T'do) that
is selected. Available values range from one Þfth to
Excitation Control Data one half of (T'do) in 0.01 second increments. The
maximum possible exciter time constant is 3 seconds.
Gen. Information – Up to 20 characters of
descriptive text for the generator can be entered in Default Exciter Time Constant – When this box
this Þeld. When a PID record is created, this text is checked, manual selection of the exciter time
identiÞes the record. constant is disabled and Te is set at one-sixth the
value of the generator time constant (T'do). This is
Gen Time Constant (T'do) - (Seconds) – The open not recommended for SR4 and SR4B generators.
circuit generator time constant (T'do) can be selected
from this pull down menu. Time constant values AVR Control Parameters
of 1 to 15 seconds can be entered in 0.05 second
increments. Proportional Gain (Kp) – This is a read only value.
The value is calculated from the values that are
Note: Values for speciÞc generators can be obtained selected from the generator time constant (T'do) and
from the “Technical Marketing Information System”. exciter time constant (Te) pull down menus.
Table 9
Power Input to Voltage Regulator (PM /
Power Input to Exciter
SE / IE systems)
Full Forcing
Nominal Requirements
Requirements
Exciter Exciter Exciter
Number Full Full
SE/PM Input to Frequency Nominal Nominal Exciter Time
of Forcing Forcing
Voltage Regulator Range Voltage Current Resistance Constant
Phases Voltage Current
Input Input Te
Kato
70
2600/
PM to 240 Hz 3 35V 10A 3.7 ohms 0.22 sec 65V 15A
2700
105V
Frame
Kato
2800 PM 120V 90 Hz 1 50V 5A 10 ohms 0.18 sec 90V 10A
Frame
6100 PM 140V 120 Hz 3 40V 4A 10 ohms 0.22 sec 60V 10A
6100 SE 140V 60 Hz 1 40V 4A 10 ohms 0.22 sec 60V 10A
6100 IE 140V 50/180 Hz 2x1 40V 4A 10 ohms 0.22 sec 60V 10A
1400
PM 180V 200/240 Hz 3 45V 4.5A 11 ohms 0.06 sec 80V 10A
/4P
1400
IE 140V 50/180 Hz 2x1 45V 4.5A 10 ohms 0.06 sec 80V 10A
/4P
1600
PM 180V 200/240 Hz 3 60V 6A 10 ohms 0.094 sec 150V 15A
/4P
1600
IE 240 V 50/180 Hz 2x1 60V 6A 10 ohms 0.094 sec 150V 15A
/4P
1800
PM 180V 240 Hz 3 84V 4A 11 ohms 0.26 sec 190V 8.5A
/4P
1800
AREP 240V 60 Hz 1 84V 4A 11 ohms 0.26 sec 190V 8.5A
/4P
70
SR4/
PM to 240 Hz 3 35V 10A 3.7 ohms 0.22 sec 65V 15A
SR4B
105V
SR4/
SE 240V 60 Hz 1 35V 10A 3.7 ohms 0.22 sec 65V 15A
SR4B
Protection Settings
The “Protection Settings” screen consists of a single
tab labeled “Protection”. Click the “Protection” button
to access the “Protection Settings” screen or click
“Screens” on the menu bar and click “Protection
Settings”.
RENR7941-05 41
Testing and Adjusting Section
Protection Tab
g01009884
Illustration 28
“SHUTDOWN OVERRIDE” Button – This button is Generator Over voltage: Enabled – Selecting the
used to prevent excitation shutdown for any protected “Enabled” check box enables generator over voltage
function. The button displays “ENABLED” when protection. Deselecting the “Enabled” check box
selected and the button displays “DISABLED” when disables generator over voltage protection and the
the button is deselected. Enabling this button does associated settings.
not disable output drivers or “CANbus” messages.
The following protections do not rely on disabling Generator Over voltage: Fault Type – Two
excitation to cause a shutdown and, therefore, are options can be selected from this pull down menu,
not affected by the “Shutdown Override” button. “Alarm” or “Shutdown”. When “Alarm” is selected
and a generator over voltage condition is detected,
• Generator Over voltage the alarm output driver energizes, a J1939 alarm
message is sent via the “CAN” communication port,
• Generator Under voltage and the “Fault LED” will be lit constantly. For units
equipped with an RS-232 communication port, an
• Loss of Excitation (Reverse Var) Alarm fault will be annunciated via the PC software.
When “Shutdown” is selected and a generator over
• Fault Reset too long voltage condition is detected, the “Fault Shutdown”
output driver energizes, a J1939 shutdown message
Note: The position of this button cannot be saved is sent, and the “Fault LED” will ßash. For units
into the EEPROM. The default value of “Disabled” is equipped with an RS-232 communication port, a
loaded when power is cycled on the CDVR. “Shutdown” fault will be annunciated via the PC
software. The voltage regulator does NOT disable
excitation when a “Generator Over Voltage” fault
is detected.
42 RENR7941-05
Testing and Adjusting Section
Generator Over Voltage: Trip Value (percent) – Generator Under Voltage: Fault Type – Two
This setting determines the voltage threshold where options can be selected from this pull down menu,
an over voltage trip will occur. Voltage values of 105 “Alarm” or “Shutdown”. When “Alarm” is selected and
to 135 percent of the rated voltage may be entered in a generator under voltage is detected, the “Alarm”
increments of 1 percent. output driver will energize. A J1939 alarm message
is sent via the “CAN” communication port. Also,
Generator Over Voltage: Time Delay (Sec.) – This the “Fault LED” is on constantly. For units that are
setting assigns the length of time from when an equipped with an RS-232 communication port, an
over voltage condition is detected until the voltage “Alarm” fault will be annunciated via the PC software.
regulator issues an alarm or shuts down excitation. When “Shutdown” is selected and a generator
A time value of 2.0 to 30 seconds may be entered in under voltage is detected, the “Shutdown” output
0.1 second increments. driver will energize. A J1939 shutdown message is
sent via the CAN communication port. The “Fault
Reverse VAR: Enabled – Selecting the “Enabled” LED” will ßash. For units that are equipped with an
check box enables reverse VAR protection. RS-232 communication port, a “Shutdown” fault will
Deselecting the “Enabled” check box disables be annunciated via the PC software. The voltage
reverse VAR protection and the associated settings. regulator does NOT disable excitation when a
“Generator Under Voltage” fault is detected.
Note: If “Reverse VAR” protection is enabled and the
CT connections are reversed, a reverse VAR alarm Generator Under Voltage: Trip Value (percent) –
or shutdown will occur. This setting determines the level of voltage. The
value is expressed as a percentage of nominal
Reverse VAR: Fault Type – Two options can generator voltage when a generator under voltage
be selected from this pull down menu, “Alarm” or trip occurs. A value of 60 to 95 percent may be
“Shutdown”. When “Alarm” is selected and loss entered in 1 percent increments.
of excitation is detected, the alarm output driver
energizes, a J1939 alarm message is sent via Generator Under Voltage: Time Delay (Secs) –
the “CAN” communication port, and the “Fault This setting assigns the length of time from when a
LED” is lit constantly. For units equipped with an generator under voltage condition is detected until
RS-232 communication port, an alarm fault will be the voltage regulator issues an alarm or shuts down
annunciated via the PC software. When “Shutdown” excitation. A time value of 10.0 to 120.0 seconds may
is selected and loss of excitation is detected, be entered in 0.1 second increments.
the “Fault Shutdown” output driver energizes, a
J1939 shutdown message is sent via the “CAN” Over Excitation: Type – Two options can be
communication port, and the “Fault LED” ßashes. selected from this pull down menu. “Inv Time” (for
For units equipped with an RS-232 communication inverse curves) or “Threshold” (for a Þxed time delay)
port, a shutdown fault will be annunciated via the PC can be selected. The voltage regulator disables
software. The voltage regulator does NOT disable excitation when an over excitation fault is detected
excitation when a Loss of Excitation (Reverse unless a global “Shutdown Override” command is
Var) fault is detected. in effect.
Reverse VAR: Trip Value (percent) – This setting Note: Selecting “Inv Time” requires changing the
determines the level of reverse VAR ßow, expressed time setting to a suggested value of 2 (based on
as a percentage of nominal, positive VAR ßow, where the time dial settings for the SR4B Generators
a loss of excitation trip occurs. A value of 10 to 100 curve). If this value is changed, over excitation
percent may be entered in increments of 1 percent. protection may not exist.
g01119160
Illustration 29
Inverse Time Characteristic for Over Excitation Limiter
44 RENR7941-05
Testing and Adjusting Section
Metering Tab
g01010266
Illustration 30
Note: When communication is established, a GEN VOLTAGE (V): Vca – This Þeld is a read-only
“Metering” choice becomes available in the menu Þeld that displays the phase-to-phase voltage of
bar. Metering can be disabled by selecting “Disable phase C and phase A.
Metering” from this choice. When metering is
disabled, contact inputs will still work normally, but GEN VOLTAGE (V): Vavg – This Þeld is a read-only
will not indicate. “Alarms” will still work normally Þeld that displays the average value of the three
and indicate. The raise and lower buttons will still phase-to-phase voltages.
work and show a changed set point. If another tab
is selected when metering is disabled, then the GEN CURRENT (A): Ib – This Þeld is a read-only
“Metering” tab is selected, metering will become Þeld that displays the value of the current on the B
enabled automatically. phase of the generator.
GEN VOLTAGE (V): Vab – This Þeld is a read-only GEN FREQ (Hz): Freq – This Þeld is a read-only
Þeld that displays the phase-to-phase voltage of Þeld that displays the value of the frequency of the
phase A and phase B. generator voltage.
GEN VOLTAGE (V): Vbc – This Þeld is a read-only GEN POWER: kWatts – This Þeld is a read-only
Þeld that displays the phase-to-phase voltage of Þeld that displays the value of real power that is being
phase B and phase C. output from the generator.
46 RENR7941-05
Testing and Adjusting Section
GEN POWER: kVA – This Þeld is a read-only Þeld FINE ADJUSTMENT – The “Raise” and “Lower”
that displays the value of apparent power that is buttons control the Þne adjustment of the operating
being output by the generator. set point. These buttons perform the same function
as closing the appropriate set of contacts connected
GEN POWER: kVAR – This Þeld is a read-only Þeld to the “Contact Sense – Raise” input (terminal P9-5)
that displays the value of reactive power that is being and “Contact Sense - Lower” input (terminal P9-4) of
output by the generator. the voltage regulator. Each click of the “Raise” button
increases the voltage set point by 0.1 V, each click
GEN POWER: PF – This Þeld is a read-only Þeld of the “Lower” button decreases the voltage set point
that displays the value of the power factor that the by 0.1 V.
generator is operating at.
Note: The PT ratio will affect this setting.
AUX DC INPUT (V): Vaux – This Þeld is a read-only
Þeld that displays the level of dc control voltage Note: An alternate method of adjusting voltage is to
that is applied from a remote device to the voltage adjust the DC voltage between terminals “P12-3” and
regulator terminals “P12-3” (B) and “P12-6” (A). “P12-6”.
Note: The “Aux DC Input” terminals can be used as SET POINT: AVR (V) – This setting Þeld is used to
an alternate method of adjusting voltage in “AVR” enter the desired generator terminal voltage. The
mode or adjusting PF or VAR in PF or VAR mode background color of this Þeld is green when the
when used with an existing remote VAR/PF controller. voltage regulator is in AVR mode.
A DC input on these pins acts as a DC bias. When
the CDVR is in “AVR” mode, a 1 VDC change on the Note: The PT ratio will affect this setting.
terminals corresponds to a 1 percent change in the
voltage set point. A 1 VDC change gives a 10 percent SET POINT: VAR (percent of nom.) – This setting
VAR change (in “VAR” mode) and a 0.04 PF change determines the level of generator VARs maintained
(in “PF” mode). If the DC voltage is removed from by the voltage regulator when operating in VAR
the ±10 VDC control input, the operating set point mode. The background color of this Þeld is green
will return to the original value regardless of pressing when the voltage regulator is regulating the VAR set
the EEPROM button. point. A percentage value of zero to 100.0 may be
entered in 0.1 percent increments.
Note: Adding a DC voltage when the operating set
point is near the voltage adjust band limit may allow SET POINT: Power Factor – This setting determines
the regulator to operate outside of the voltage adjust the level of power factor regulation maintained by the
band. voltage regulator. The background color of this Þeld
is green when the voltage regulator is regulating the
EXCITER FIELD: Vfd (V) – This Þeld is a “read-only” power factor set point. A power factor value of –0.600
Þeld that displays the value of the exciter Þeld voltage. to 0.600 may be entered in 0.001 increments.
EXCITER FIELD: Ifd (A) – This Þeld is a “read-only” STATUS – Four indicators indicate the operating
Þeld that displays the value of the exciter Þeld current. status of the voltage regulator: “Droop”, “Line Drop”,
“Under Frequency”, and “Soft Start”.
OPERATING MODE – One of three operating modes
may be selected as active: “AVR”, “VAR”, or “PF”. The “Droop” indicator turns red when the “Reactive
When an operating mode is active, the corresponding Droop Compensation” feature is selected. The
indicator color changes from black to red for “AVR” “Reactive Droop Compensation” feature is used
mode. When an operating mode is active, the during parallel generator operation to assist in the
corresponding indicator color changes from black to sharing of reactive load.
green for the “VAR” mode and the “PF” mode.
The “Line Drop” indicator turns red when the “Line
Note: When either KVAR or PF mode are selected, Drop Compensation” feature is selected The “Line
the appropriate button must be selected and the Drop Compensation” feature is used to compensate
auxiliary breaker contact that is connected to “P9-6” for voltage drops in the lines between the generator
(KVAR/PF enable contact) and “P9-9” (contact sense and the load.
common) must be closed.
The “Under Frequency” indicator turns red when the
Note: “Droop” should be enabled whenever the generator frequency decreases below the “Knee
CDVR is operated in PF or VAR mode. The newest Frequency” setting and excitation is terminated.
version of the CDVR PC Þrmware will not allow the
operator to select PF or VAR mode unless “Droop” The “Soft Start” indicator turns red when the “Soft
is selected in the “Settings” menu Þrst. The “Droop” Start” feature is active to control the time for generator
setting can be set to 0 percent. voltage to ramp up during startup.
RENR7941-05 47
Testing and Adjusting Section
CONTACT INPUTS – Five indicators provide the • real time clock Þrst
status of the voltage regulator switch inputs: “Raise”,
“Lower”, “VAR / PF”, “Excitation Disable”, and “Fault • real time clock last
Reset”.
• occurrence count
The “Raise” indicator turns red when contact closure
at terminals “P9-5” “Contact Sense - Raise” and Note: The CDVR does not know the actual time.
“P9-6” “Contact Sense - Common” is detected. The CDVR only knows the elapsed time from CDVR
power up.
The “Lower” indicator turns red when contact closure
at terminals “P9-4” “Contact Sense - Lower” and Settings Files
“P9-6” “Contact Sense - Common” is detected.
Caterpillar PC software enables you to print a list of
The “Var/PF” indicator turns red when contact closure voltage regulator settings, save voltage regulator
at terminals “P9-9” “Contact Sense - Var/PF Enable”
settings in a Þle, and open a settings Þle in order
and “P9-6” “Contact Sense - Common”is detected.
to upload those settings to a voltage regulator. A
settings Þle may also be opened and edited with any
The “Excitation Disable” indicator turns red when
text editing software.
contact closure at terminals “P9-7” “Contact Sense
– Excitation Disable” and “P9-6” “Contact Sense -
Common” is detected.
• code
• description
• service meter hours Þrst
• service meter hours last
48 RENR7941-05
Testing and Adjusting Section
g01394300
Illustration 31
Print Icon
g01016740
Illustration 32
RENR7941-05 49
Testing and Adjusting Section
g01016741
Illustration 33
g01394035
Illustration 34
Save Icon
It is recommended that the settings for the voltage Uploading the Settings Files to the
regulator be saved to a Þle. In order to save setup Voltage Regulator
time when conÞguring multiple units with the same
settings, the saved settings can be uploaded to other A voltage regulator settings Þle downloaded from a
voltage regulator units. voltage regulator or created within the PC software
can be uploaded to multiple voltage regulator units.
A settings Þle can also be created in the PC software Only a voltage regulator settings Þle with a “.dv2”
without being connected to a voltage regulator. The extension can be uploaded to a voltage regulator
settings of the desired screens can be changed. The unit. Before uploading a Þle, communication must be
settings can then be saved to a Þle. Once a settings initiated with the voltage regulator that is to receive
Þle is created, the Þle can be edited with the use of the settings. See Systems Operation, “Remote
any text editing software. The Þle can then be saved Communication”.
for uploading.
The upload process is started by clicking the open
A settings Þle is created by clicking the save icon icon or clicking “File” on the menu bar and then
(1) or by clicking “File” on the menu bar and then clicking “Open”. An “Open” dialog box is then
clicking “Save”. When the command is given, a “Save displayed where the desired settings Þle is navigated
As” dialog box is displayed where the settings are to and selected. Clicking “Open” uploads the settings
assigned a Þle name and then saved. All voltage Þle. The default settings for the CDVR are stored in a
regulator settings Þles are automatically given a Þle called “Defaults.DV2” in the “CDVR PC Software”
“.dv2” extension. folder on the PC.
Table 10
CDVR PC Software Settings
Rated kVAR (@ 0.8 Power Factor): 75
Sensing Mode: 1 (0=Single-Phase, 1=Three-Phase)
Rated Generator Frequency: 0 (0=60 Hz, 1=50 Hz)
Rated Generator Voltage: 120 (Volts)
Generator PT Primary Voltage Rating: 120 (Volts)
Generator PT Secondary Voltage Rating: 120 (Volts)
Generator CT Primary Current Rating: 600 (Amps)
Generator CT Secondary Current Rating: 5 (Amps)
Rated Generator Current: 600 (Amps)
Power Input Frequency: 60 (Hz)
g01408125
Illustration 35
Upload Embedded Software
g01408132
Illustration 37
g01408133
Illustration 38
g01408135
Illustration 39
g01408137
Illustration 40
Serial Number Change
g01408138
3. Click on the “Flash Memory” button. Refer to
Illustration 41 Illustration 43.
11. Once the transfer is complete, the device
information is displayed in the right hand column
of the “Embedded Program Loader”. Refer to
Illustration 42. The displayed program version
number indicates the version and the date of the
Þrmware that was just loaded.
g01408140
Illustration 42
CDVR Information After Upload
• CDVR
• Caterpillar Electronic Technician software (Cat ET)
• Power to the CDVR
56 RENR7941-05
Testing and Adjusting Section
g01425391
Illustration 43
g01425392
Illustration 44
RENR7941-05 57
Testing and Adjusting Section
i02848566
• Communication Adapter II
Follow the steps below in order to program the
voltage regulator with Cat ET:
g01112560
Illustration 46
Connect button
g01113063
Illustration 47
ConÞguration tool
g01113076
Illustration 48
Available ECM's
g01113082
Illustration 49
ConÞguration group
g01113121
Illustration 50
Parameter selection
g01113102
Illustration 51
Change Parameter Value
g01113109
Illustration 52
Disconnect button
The following items are needed to view metering Follow the steps below in order to view metering
parameters in the CDVR with Cat ET: parameters in the CDVR with Cat ET.
g01425537
b. If the response is oscillatory or has a large
Illustration 53 amount of overshoot, decrease Ki or Kd.
3. Various status groups will be available. Refer to c. If the desired response is still not achievable,
Illustration 54. Click on a status group in order to proceed to Step 3.
display the parameters in that group.
3. If T'do and Te are known, use the PID calculator in
order to obtain the starting PID values. If T'do is
known but Te is not known, use the PID calculator
with the default exciter time constant (Te = T'do/6).
If the desired response is not obtainable with
these PID values, proceed to Step 4.
4. In order to set up custom groups, double click The desired rise time should be based on how
on “Temporary Group”. Double click on the fast you want the combined generator and CDVR
parameters that are desired in order to add them to respond. In most application, this will be in the
to the group. range of 0.5 seconds to 1 second. Once Kp is
adjusted, increase Ki in order to get the desired
5. Click “OK” again to enable the group. response. If overshoot or if ringing occurs, reduce
Ki and then increase Kp, Ki, and Kd. Keep the
ratio constant.
62 RENR7941-05
Testing and Adjusting Section
Note: Many people use a load application or If a “Generator Undervoltage” fault has occurred, a
rejection test in order to adjust the voltage regulator. generator undervoltage condition has been detected
If available, use an inductive load. A resistive load at the generator voltage sensing input(s) of the
is not the best way to adjust the voltage regulator's voltage regulator in excess of the programmed
PID values. If the only load available is a resistive threshold for longer than the programmed time delay.
load, beware that the engine governor's or speed Refer to the Testing and Adjusting, “Low Voltage -
governor's response will signiÞcantly affect the Troubleshoot” section.
voltage regulator's performance.
If the“ Fault Reset” contact input is closed for more
than 10 seconds, a “Fault Reset Too Long” fault has
i02848548
occurred. Remove the short across the “Fault Reset”
Troubleshooting contact input.
STOP.
RENR7941-05 63
Testing and Adjusting Section
2. Verify that the generator is running at rated speed. 8. Verify that the common alarm/Shutdown LED
indicator on the voltage regulator is not ßashing.
OK – If the generator is spinning at rated speed,
go to step 3. OK – If no protective fault has caused the
excitation to be turned off, go to step 15.
NOT OK – If the generator is not at rated speed,
increase generator speed to the rated value. NOT OK – If the LED indicator is ßashing, open
communications with the voltage regulator to
STOP. determine if a protective shutdown fault has
occurred that would cause excitation to be turned
3. The digital voltage regulator is PMG power or off. If protective shutdown fault has occurred that
Shunt powered. would cause excitation to be turned off, go to step
9.
PMG power – Proceed to step 4.
9. If an Exciter Diode Monitor (EDM) fault has
Shunt Powered – Proceed to step 5. occurred, stop the machine, insure that the power
input to the voltage regulator is removed, and
4. Check for correct input power to the voltage unplug “P6” on the voltage regulator.
regulator. Refer to SpeciÞcation, “Electrical”, for
input power requirements. a. Refer to the generator manual for instructions
on checking the rotating exciter diodes. Have
OK – If voltage is present, go to step 5. the rotating exciter diode assembly checked for
open or shorted diodes. If an open or shorted
NOT OK – If PMG voltage is not present, refer to diode is present in the rotating exciter diode
the generator manual for the repair procedures assembly, refer to the generator manual for
and check for an open circuit. instructions on how to replace the rotating
rectiÞer assembly.
STOP.
b. After repairs are complete, reset the voltage
5. Verify that the residual voltage applied to the regulator by momentarily closing the Fault
power input is at least 6 VAC. Reset contact or by cycling 24 VDC control
power.
OK – If the applied voltage is 6 VAC or greater,
go to step 6. c. The generator may be restarted. If there is
no problem with the rotating exciter diode
NOT OK – If the applied voltage is less than 6 assembly, the EDM trip value may be set
VAC, refer to the generator manual and ßash the too low. An EDM fault may occur with good
generator Þeld. Install blocking diodes in series rotating exciter diodes under varying loads if
with the battery in order to prevent damage to the the trip level is set too low. Set the EDM trip
voltage regulator and/or the battery. level to a value greater than the RMS ripple
current present in the exciter Þeld under normal
STOP. operating conditions in order to prevent a false
trip.
6. Verify that the fuse is not open.
d. Reconnect “P6”. Reset the voltage regulator by
OK – If no fuses are open, go to step 8. momentarily closing the Fault Reset contact or
by cycling 24 VDC control power.
NOT OK – Replace any fuses that are open.
e. The generator may be restarted. If an Exciter
STOP. Diode Monitor (EDM) fault has not occurred,
go to step 10.
7. Verify that the CDVR is connected to 24VDC
control power. 10. If an Over Excitation fault has occurred, stop
the machine and have the generator and/or load
OK – If CDVR is connected to 24VDC control conditions checked for a generator or load fault
power, go to step 8. that could cause excessive exciter Þeld current to
ßow. Also have the system checked for loose or
NOT OK – Connect CDVR to 24VDC control open connections to the voltage regulator sensing
power. inputs. Any faults must be repaired.
STOP.
64 RENR7941-05
Testing and Adjusting Section
a. After repairs are complete, reset the voltage 12. If a Field Overcurrent fault has occurred, stop
regulator by momentarily closing the Fault the machine and have the generator and/or load
Reset contact or by cycling 24 VDC control conditions checked for a generator or load fault
power. that could cause excessive exciter Þeld current to
ßow. Also have the system checked for loose or
b. The generator may be restarted. If no generator open connections to the voltage regulator sensing
or load fault has occurred and there are no inputs. A Field Overcurrent fault is detected when
loose or open connections to the sensing output current from the voltage regulator exceeds
inputs of the voltage regulator, verify that the approximately 28 A.
Over Excitation trip level and the delay settings
are properly adjusted for the generator. OK – If a Field Overcurrent fault has not occurred,
go to step 13.
c. Set the Over Excitation trip level slightly above
the requirement of the application but not so NOT OK – Any fault must be repaired. After
high as to render the protection ineffective or repairs are complete, reset the voltage regulator
damage the system. by momentarily closing the Fault Reset contact or
by cycling 24 VDC control power. The generator
d. Reset the voltage regulator by momentarily may be restarted.
closing the Fault Reset contact or by cycling
24 VDC control power. STOP.
e. The generator may be restarted. If the Over 13. If an Internal Memory Failure fault has occurred,
Excitation fault still exists, the instantaneous try resetting the voltage regulator by momentarily
trip value of 28 Amperes may have been closing the Fault Reset contact or by cycling 24
reached by a faulty diode. The EDM virtual fault VDC control power.
LED will not indicate in this case since there is
a 5 second delay associated with the EDM fault STOP. – If an Internal Memory fault has not
protection. Go to Step 9. If an Over Excitation occurred, go to step 14.
fault has not occurred, go to step 11.
NOT OK – If after resetting the voltage regulator
Note: SR4 and SR4B generators may require up another Internal Memory Failure occurs, replace
to 12 Amperes for full load excitation. A 10 second the voltage regulator.
delay is needed in order to insure 300 percent short
circuit current requirements. STOP.
11. If a Loss of Sensing fault has occurred, stop the 14. If an Internal Watchdog Failure fault has occurred,
machine and have the system checked for loose reset the voltage regulator by momentarily closing
or open connections to the voltage sensing inputs the Fault Reset contact or by cycling 24 volt
of the voltage regulator. control power.
a. Have the generator and/or load conditions OK – If an Internal Watchdog Failure fault has not
checked for a generator or load fault that could occurred, go to step 15.
cause the sensed voltage to be low.
NOT OK – If after resetting the voltage regulator
b. If the generator is equipped with voltage another Internal Watchdog Failure fault occurs,
transformers for stepping the generator voltage replace the voltage regulator.
down to levels usable by the voltage regulator,
verify that the transformers are functional and STOP.
that any transformer fuses are not open.
15. Replace the voltage regulator unit. If replacing
c. If transformer fuses are found to be open, the voltage regulator unit does not correct the
replace the fuses. problem, go to step 16.
d. Any faults must be repaired. After repairs 16. There is a problem with the generator. Refer to
are complete, reset the voltage regulator by the generator manual to troubleshoot the problem.
momentarily closing the Fault Reset contact or
by cycling 24 VDC control power.
STOP.
OK – If the voltage adjustment is correct, go to 7. Verify that the sensing potential transformer (if
step 2. used) has the correct turns ratio and is operating
correctly.
NOT OK – If the voltage adjustment is too low,
adjust the voltage to the correct setpoint. OK – If the sensing potential transformer is
operating correctly, go to step 8.
STOP.
NOT OK – If the turns ratio of the sensing
2. Verify that the underfrequency setpoint (knee potential transformer is incorrect, replace the
frequency) is not greater than the generator sensing potential transformer.
frequency.
STOP.
OK – If the underfrequency setpoint is correct,
go to step 3. 8. Low generator output voltage may occur when
operating in droop mode with an inductive load.
NOT OK – If the underfrequency setpoint is too If the low voltage condition is not caused by the
high, adjust the setpoint below the rated generator droop function, go to step 9.
frequency.
9. Replace the voltage regulator.
STOP.
STOP.
1. Verify that the voltage adjustment is not set too Unstable Voltage -
high.
Troubleshoot
OK – If the voltage adjustment is correct, go to
step 2. SMCS Code: 4467-035
STOP.
STOP.
The terminals and heat sinks are live at hazardous 3. Verify the following parameters are programmed
voltages when power is applied and for up to 8 as follows:
minutes after power is removed.
• Rated voltage (V) equals the generator rated
voltage
1. Verify that the governor for the engine is operating
properly. • PT primary (V) equals the generator winding
rated voltage
OK – If the governor is operating properly, go to
step 2. • PT secondary (V) equals the generator sensed
voltage
NOT OK – If the governor is not operating
properly, refer to the engine manual in order to Go to step 5.
troubleshoot the problem.
4. Verify the following parameters are programmed
STOP. as follows:
2. Verify that the sensing and input power leads are • Rated voltage (V) equals the generator rated
connected securely. voltage
OK – If the sensing or input power lead • PT primary (V) equals the generator rated
connections are secure, go to step 3. voltage
NOT OK – If the sensing or input power leads are • PT secondary (V) equals the generator rated
not connected securely, tighten the connections. voltage
STOP. Go to step 5.
3. Verify that the voltage regulator stability range is 5. Verify that the Þeld winding inputs to the CDVR
set to the proper range. are not partially or completely shorted.
OK – If the stability range setting is correct, go OK – If winding inputs are ok, go to Step 6.
to step 4.
NOT OK – If winding inputs not ok, repair winding
NOT OK – If the stability range setting is incorrect, input fault. Check the system again.
reset the stability range.
STOP.
STOP.
6. Check exciter for proper resistance value.
4. Verify that the stability level is properly set. If the
stability level is not properly set, reset the stability OK – If exciter resistance value is ok, go to Step
level. 7.
i02847363
5. Verify that regulation is not being affected by 2. Verify that the voltage regulator line drop setting
normal droop operation. If droop operation is not is not adjusted to 0%. If the line drop setting is
affecting regulation, go to step 6. adjusted to 0%, increase the set point above 0%.
If the line drop setting is adjusted to above 0%,
6. Verify that regulation is not being affected by go to step 3.
normal line loss compensation. If line loss
compensation is not affecting regulation, then 3. Check for an open in the circuit connected to
replace the voltage regulator. voltage regulator terminals P12-1 and P12-2
and CT2. If there is an open circuit, repair as
On new applications and when commissioning, check necessary. If there is not an open circuit, go to
the PID value. If the voltage ßuctuates at steady-state step 4.
“No Load” or “Full Load”, reduce Kg or if at 1.0 reduce
Kp. Recalculate PID in calculator. 4. Verify that all connections are correct according
to Testing and Adjusting, “Wiring Diagrams”. If
Note: Self Excited (shunt powered) generators connections are incorrect, correct the problem. If
will have a greater input power voltage than PMG connections are correct, go to step 5.
generators. This will require lower gain settings (Kg
Þrst then Kp if necessary) on comparably sized 5. Verify that the load that is being applied to the
machines. Adjust the Kg values Þrst, then Kp values generator for droop testing is not a purely resistive
to reach acceptable steady-state and transient load. If only a resistive load is being applied to the
responses. generator, apply an inductive load and retest. If the
load being applied to the generator is inductive,
go to step 6.
i02847675
No Line Loss Compensation - 6. Verify that the current sensing transformer that
is being used is compatible with the voltage
Troubleshoot regulator. For example, a current sensing
transformer with a 1 ampere output rating would
SMCS Code: 4467-035 produce very little droop since the voltage
regulator has a 5 ampere current transformer
input. If the current transformer input is incorrect,
replace the current sensing transformer for
compatibility. If the current transformer input is
correct, go to step 7.
i02822626
No Voltage Droop -
Troubleshoot
g01425633
Illustration 60 SMCS Code: 4467-035
i03213854
Wiring Diagrams
SMCS Code: 4467; 7566
g01425818
Illustration 62
Math Model - Per Unit Block Diagram for Rotating RectiÞer Excitation System.
Vs – Sensing Voltage
Kg – Programmed Gain
Kp – Proportional Gain
Ki – Integral Gain
Kd – Derivative Gain
Td – Derivative Time
Vr – Regulated Voltage
Ke – Exciter Gain
g01015474
Illustration 63
Typical Connections for PMG Power Input, ABC Rotation, and Three Phase Voltage Sensing
Notes:
(A) 52a contact required only for Var/PF (F) The ±10 VDC input provides adjustment (I) When generator rotation is ACB, the
control. Var/PF enabled only when 52a of output. connections for the CTB should be
is closed, inactive when open. (G) Three-phase PMG is shown. For reversed.
(B) When excitation disable switch is open, single-phase, remove P6-3 connection.
excitation is enabled. For HV machines using 2 single phase
(C) When fault reset switch is momentarily PMGs in series, connect PMG leads
closed, any shutdown fault is reset. 2 and 3 together, and connect leads 1
(D) S1 (SPST, spring return to center-off and 4 to CDVR pins P6-1 and P6-2,
position) adjusts CAT Digital Voltage respectively.
Regulator setpoint. (H) Sensing potential transformer is required
(E) Alarm Driver and Shutdown Fault Driver if line voltage exceeds 600 VAC.
are normally off.
RENR7941-05 73
Testing and Adjusting Section
g01015488
Illustration 64
Typical Connections for Shunt Power Input, ABC Rotation, and Single Phase Voltage Sensing
Notes:
(A) 52a contact required only for Var/PF (D) S1 (SPST, spring return to center-off (G) Sensing potential transformer is required
control. Var/PF enabled only when 52a position) adjusts CAT Digital Voltage if line voltage exceeds 600 VAC.
is closed, inactive when open. Regulator setpoint. (H) When generator rotation is ACB, the
(B) When excitation disable switch is open, (E) Alarm Driver and Shutdown Fault Driver connections for the CTB should be
excitation is enabled. are normally off. reversed.
(C) When fault reset switch is momentarily (F) The ±10 VDC input provides adjustment
closed, any shutdown fault is reset. of output.
74 RENR7941-05
Testing and Adjusting Section
g01408526
Illustration 65
Typical Connections for a SE, L-N Directly Connected Power Input, ABC Rotation, and Single Phase Voltage Sensing (Generator less than 480V)
Notes:
(A) 52a contact required only for Var/PF (D) S1 (SPST, spring return to center-off (G) Sensing potential transformer is required
control. Var/PF enabled only when 52a position) adjusts CAT Digital Voltage if line voltage exceeds 600 VAC.
is closed, inactive when open. Regulator setpoint. (H) When generator rotation is ACB, the
(B) When excitation disable switch is open, (E) Alarm Driver and Shutdown Fault Driver connections for the CTB should be
excitation is enabled. are normally off. reversed.
(C) When fault reset switch is momentarily (F) The ±10 VDC input provides adjustment
closed, any shutdown fault is reset. of output.
RENR7941-05 75
Testing and Adjusting Section
g01015546
Illustration 66
Typical Connections for Shunt Power Input, ABC Rotation, and Three Phase voltage Sensing
Notes:
(A) 52a contact required only for Var/PF (D) S1 (SPST, spring return to center-off (G) Sensing potential transformer is required
control. Var/PF enabled only when 52a position) adjusts CAT Digital Voltage if line voltage exceeds 600 VAC.
is closed, inactive when open. Regulator setpoint. (H) When generator rotation is ACB, the
(B) When excitation disable switch is open, (E) Alarm Driver and Shutdown Fault Driver connections for the CTB should be
excitation is enabled. are normally off. reversed.
(C) When fault reset switch is momentarily (F) The ±10 VDC input provides adjustment
closed, any shutdown fault is reset. of output.
76 RENR7941-05
Testing and Adjusting Section
g01015576
Illustration 67
Typical Connections for PMG Power Input, ABC Rotation, and Single Phase Voltage Sensing
Notes:
(A) 52a contact required only for Var/PF (F) The ±10 VDC input provides adjustment (I) When generator rotation is ACB, the
control. Var/PF enabled only when 52a of output. connections for the CTB should be
is closed, inactive when open. (G) Three-phase PMG is shown. For reversed.
(B) When excitation disable switch is open, single-phase, remove P6-3 connection.
excitation is enabled. For HV machines using 2 single phase
(C) When fault reset switch is momentarily PMGs in series, connect PMG leads
closed, any shutdown fault is reset. 2 and 3 together, and connect leads 1
(D) S1 (SPST, spring return to center-off and 4 to CDVR pins P6-1 and P6-2,
position) adjusts CAT Digital Voltage respectively.
Regulator setpoint. (H) Sensing potential transformer is required
(E) Alarm Driver and Shutdown Fault Driver if line voltage exceeds 600 VAC.
are normally off.
RENR7941-05 77
Testing and Adjusting Section
g01425819
Illustration 68
Typical Connections for PMG Power Input, ABC Rotation, and Single Phase Voltage Sensing
Notes:
(A) 52a contact required only for Var/PF (F) The ±10 VDC input provides adjustment (I) When generator rotation is ACB, the
control. Var/PF enabled only when 52a of output. connections for the CTB should be
is closed, inactive when open. (G) Three-phase PMG is shown. For reversed.
(B) When excitation disable switch is open, single-phase, remove P6-3 connection.
excitation is enabled. For HV machines using 2 single phase
(C) When fault reset switch is momentarily PMGs in series, connect PMG leads
closed, any shutdown fault is reset. 2 and 3 together, and connect leads 1
(D) S1 (SPST, spring return to center-off and 4 to CDVR pins P6-1 and P6-2,
position) adjusts CAT Digital Voltage respectively.
Regulator setpoint. (H) Sensing potential transformer is required
(E) Alarm Driver and Shutdown Fault Driver if line voltage exceeds 600 VAC.
are normally off.
78 RENR7941-05
Testing and Adjusting Section
g01112935
Illustration 69
Typical Connections for Internal Excitation Power Input, ABC Rotation, and Three Phase Voltage Sensing
Notes:
(A) 52a contact required only for Var/PF (D) S1 (SPST, spring return to center-off (G) Sensing potential transformer is required
control. Var/PF enabled only when 52a position) adjusts CAT Digital Voltage if line voltage exceeds 600 VAC.
is closed, inactive when open. Regulator setpoint. (H) When generator rotation is ACB, the
(B) When excitation disable switch is open, (E) Alarm Driver and Shutdown Fault Driver connections for the CTB should be
excitation is enabled. are normally off. reversed.
(C) When fault reset switch is momentarily (F) The ±10 VDC input provides adjustment
closed, any shutdown fault is reset. of output.
RENR7941-05 79
Testing and Adjusting Section
g01112701
Illustration 70
Typical Connections for PMG Power Input, ABC Rotation, and Single Phase Voltage Sensing (Generator Less Than 600 Volts)
Notes:
(A) 52a contact required only for Var/PF (F) The ±10 VDC input provides adjustment (I) When generator rotation is ACB, the
control. Var/PF enabled only when 52a of output. connections for the CTB should be
is closed, inactive when open. (G) Three-phase PMG is shown. For reversed.
(B) When excitation disable switch is open, single-phase, remove P6-3 connection.
excitation is enabled. For HV machines using 2 single phase
(C) When fault reset switch is momentarily PMGs in series, connect PMG leads
closed, any shutdown fault is reset. 2 and 3 together, and connect leads 1
(D) S1 (SPST, spring return to center-off and 4 to CDVR pins P6-1 and P6-2,
position) adjusts CAT Digital Voltage respectively.
Regulator setpoint. (H) Sensing potential transformer is required
(E) Alarm Driver and Shutdown Fault Driver if line voltage exceeds 600 VAC.
are normally off.
80 RENR7941-05
Testing and Adjusting Section
g01112717
Illustration 71
Typical connections for PMG power input and three phase direct voltage sensing
(generator less than 600 volts)
Notes:
(A) 52a contact required only for Var/PF (D) S1 (SPST, spring return to center-off (H) Sensing potential transformer is required
control. Var/PF enabled only when 52a position) adjusts CAT Digital Voltage if line voltage exceeds 600 VAC. For HV
is closed, inactive when open. Regulator setpoint. machines using 2 single phase PMGs
(B) When excitation disable switch is open, (E) Alarm Driver and Shutdown Fault Driver in series, connect PMG leads 2 and 3
excitation is enabled. are normally off. together, and connect leads 1 and 4 to
(C) When fault reset switch is momentarily (F) The ±10 VDC input provides adjustment CDVR pins P6-1 and P6-2, respectively.
closed, any shutdown fault is reset. of output. (I) When generator rotation is ACB, the
(G) Three-phase PMG is shown. For connections for the CTB should be
single-phase, remove P6-3 connection. reversed.
RENR7941-05 81
Testing and Adjusting Section
g01429193
Illustration 72
Typical connections for cross current compensation
82 RENR7941-05
Testing and Adjusting Section
g01429203
Illustration 73
Typical connections for cross current compensation (two CDVR's).
RENR7941-05 83
Testing and Adjusting Section
g01429204
Illustration 74
Typical connections for cross current compensation (one CDVR and one DVR).
84 RENR7941-05
Testing and Adjusting Section
g01112822
Illustration 75
Typical connections for a manual voltage control
RENR7941-05 85
Index Section
Index
C Parameter Viewing and ConÞguration (Caterpillar PC
Software) ............................................................. 23
Cross Current Compensation ................................ 14 Changing Settings.............................................. 24
Flash the CDVR Using Cat ET Software ........... 55
Installing the Caterpillar PC Software ................ 23
D Sending and Receiving Settings ........................ 25
Setting DeÞnitions .............................................. 26
Dimensions.............................................................. 7 Settings Files ..................................................... 47
Starting Caterpillar PC Software ........................ 24
Uploading Embedded Firmware Using the CDVR
E PC Software ..................................................... 52
Parameters ............................................................ 16
Electrical .................................................................. 4 General Information ........................................... 16
Poor Voltage Regulation - Troubleshoot................ 68
Power Factor Regulation ....................................... 15
G
K
T
KVAR Regulation................................................... 14
Table of Contents..................................................... 3
Testing and Adjusting ............................................ 20
L Testing and Adjusting Section ............................... 20
Troubleshooting..................................................... 62
Line Loss Compensation ....................................... 12 Alarm or Shutdown Faults.................................. 62
Loading and Stopping ProÞle ................................. 11
Low Voltage - Troubleshoot................................... 65
U
P
W
Parameter Viewing and ConÞguration (Caterpillar
Electronic Technician).......................................... 57 Wiring Diagrams .................................................... 71
Viewing Metering Parameters Using Cat ET
Software ........................................................... 60
86 RENR7941-05
Index Section
RENR7941-05 87
Index Section
©2009 Caterpillar Cat, Caterpillar, their respective logos, “Caterpillar Yellow” and the Power edge Printed in U.S.A.
All Rights Reserved trade dress, as well as corporate and product identity used herein, are trademarks
of Caterpillar and may not be used without permission.