LV CABLE SIZING CALCULATION TABLE

of cable (EIT Standard 022001-22 Table


of cable (Current value in the case of 3
current conductors according to EIT
Voltage Drop
From To

Standard 022001-22 Table 5-20)


Steady State

Current Carrying capacities

Current Carrying capacities

Current Carrying capacities


Transformer / motor rating

Overall Derating Factor

of cable after derated


5-20) x Runs per Ph

Selected Cable Size


Operating Voltage

Full Load Current

Cable Length *
Laying Method

(EIT Standard 022001-22


Powerfactor

Conclusion

For Selected cable


Sl.No.

Conclusion
Table ฐ.1)

Allowed
mV/A/m

Actual
Equipment Tag. Equipment Description Equipment Tag. Equipment Description

in in in in in in in Runs in in Voltage Drop (V) in in


VA Volts Amps Amps Amps Amps Sq.mm. per Ph Mtrs mV/A/m Volts % %
1 LP-WS LP-WS PANEL LP-WS-17 LIGHTING In Wire Way 925.00 240 0.85 4.53 0.38 15 18 6.84 1C X 2.5 1 SAFE 85 18 6.94 2.89 3.00 PASS
2 LP-WS LP-WS PANEL LP-WS-12 RECEPTACLE In Wire Way 800.00 240 0.85 3.92 0.38 15 18 6.84 1C X 2.5 1 SAFE 80 18 5.65 2.35 3.00 PASS
3 LP-WS LP-WS PANEL LP-WS-28 FCU/CDU-06 In IMC Conduit 3330.00 240 0.85 16.32 1.00 20 24 24.00 1C X 4 1 SAFE 40 11 7.18 2.99 3.00 PASS

4 LP-WS LP-WS PANEL LP-WS-32 SUTTER DOOR 4,5,6 In IMC Conduit 1500.00 240 0.85 7.35 1.00 20 24 24.00 1C X 4 1 SAFE 70 11 5.66 2.36 3.00 PASS

5 LP-PP LP-PP PANEL LP-PP-19,21,23 TWO POST LIFT 4 In Wire Way 1100.00 400 0.85 1.87 0.38 15 18 6.84 3C X 2.5 1 SAFE 60 15 1.68 0.42 3.00 PASS

6 LP-PP LP-PP PANEL LP-PP-20,22,24 AIR PUMP 6 In Wire Way 2950.00 400 0.85 5.01 0.38 15 24 9.12 3C X 4 1 SAFE 55 9.5 2.62 0.65 3.00 PASS

Derating Factors for cables laid in Wire Way Wire Way

Derating factor for variation in ambient air tempperature 40 deg (see EIT Standard 022001-22 Table 5-43) 1.00

The current size of the wires in the wiring rail should use the current value in the case of 3 current conductors according to Table 5-20 or 5-27.
Without using a current reduction factor regarding the number of wires according to Table 5-8, if the total current flowing conductors do not exceed 30 wires, conductors, signal circuits, or control circuits that may have current flowing for a short period of time. It is not considered a current-carrying 0.38
conductor.

TDF for cables laid in Wire Way 0.38


WIRE WAY SIZING CALCULATION SHEET
ELECTRICAL CABLE

Cable Description
From To
Size Area of Cable.
Type
(mm²) (mm²)

LP-WS LIGHTING - 1 2x2.5 450/750V IEC01 (THW) 23.90


LP-WS LIGHTING - 3 2x2.5 450/750V IEC01 (THW) 23.90
LP-WS LIGHTING - 5 2x2.5 450/750V IEC01 (THW) 23.90
LP-WS LIGHTING - 7 2x2.5 450/750V IEC01 (THW) 23.90
LP-WS LIGHTING - 9 2x2.5 450/750V IEC01 (THW) 23.90
LP-WS LIGHTING - 11 2x2.5 450/750V IEC01 (THW) 23.90
LP-WS LIGHTING - 13 2x2.5 450/750V IEC01 (THW) 23.90
LP-WS LIGHTING - 15 2x2.5 450/750V IEC01 (THW) 23.90
LP-WS LIGHTING - 17 2x2.5 450/750V IEC01 (THW) 23.90
LP-WS LIGHTING - 19 2x2.5/2.5G 450/750V IEC01 (THW) 35.85
LP-WS LIGHTING - 21 2x2.5/2.5G 450/750V IEC01 (THW) 35.85
LP-WS LIGHTING - 23 2x2.5 450/750V IEC01 (THW) 23.90
LP-WS LIGHTING - 25 2x2.5/2.5G 450/750V IEC01 (THW) 35.85
LP-WS RECEPTACLE - 2 2x2.5/2.5G 450/750V IEC01 (THW) 35.85
LP-WS RECEPTACLE - 4 2x2.5/2.5G 450/750V IEC01 (THW) 35.85
LP-WS RECEPTACLE - 6 2x2.5/2.5G 450/750V IEC01 (THW) 35.85
LP-WS RECEPTACLE - 8 2x2.5/2.5G 450/750V IEC01 (THW) 35.85
LP-WS RECEPTACLE - 10 2x2.5/2.5G 450/750V IEC01 (THW) 35.85
LP-WS RECEPTACLE - 12 2x2.5/2.5G 450/750V IEC01 (THW) 35.85
LP-WS RECEPTACLE - 14 2x2.5/2.5G 450/750V IEC01 (THW) 35.85
LP-WS RECEPTACLE - 16 2x2.5/2.5G 450/750V IEC01 (THW) 35.85
LP-PP TWO POST LIFT 1 3x2.5/2.5G 450/750V IEC01 (THW) 47.80
LP-PP TWO POST LIFT 2 3x2.5/2.5G 450/750V IEC01 (THW) 47.80
LP-PP TWO POST LIFT 3 3x2.5/2.5G 450/750V IEC01 (THW) 47.80
LP-PP TWO POST LIFT 4 3x2.5/2.5G 450/750V IEC01 (THW) 47.80
LP-PP AIR PUMP 1 3x4/2.5G 450/750V IEC01 (THW) 57.59
LP-PP AIR PUMP 2 3x4/2.5G 450/750V IEC01 (THW) 57.59
LP-PP AIR PUMP 3 3x4/2.5G 450/750V IEC01 (THW) 57.59
LP-PP AIR PUMP 4 3x4/2.5G 450/750V IEC01 (THW) 57.59
LP-PP AIR PUMP 5 3x4/2.5G 450/750V IEC01 (THW) 57.59
LP-PP AIR PUMP 6 3x4/2.5G 450/750V IEC01 (THW) 57.59

TOTAL AREA OF CABLES. (mm²) 1,170.11

WIRE WAY SIZING CALCULATION

Solution
Total Area of Cables (mm²) 1,170.11 mm²

Selected Wire Way size 100x100 (mm²) 10,000.00 mm²

1) Using area

Using area = Total Area of Cable


Selected Wire Way size 100x100 mm.

= 1,170.11
10,000.00

= 12%

Using area of cable 12% (Using Area for Wire Way less than 20% is accepted)