Cable and Wire Way Sizing Calculation
Cable and Wire Way Sizing Calculation
Cable Length *
Laying Method
Conclusion
Conclusion
Table ฐ.1)
Allowed
mV/A/m
Actual
Equipment Tag. Equipment Description Equipment Tag. Equipment Description
4 LP-WS LP-WS PANEL LP-WS-32 SUTTER DOOR 4,5,6 In IMC Conduit 1500.00 240 0.85 7.35 1.00 20 24 24.00 1C X 4 1 SAFE 70 11 5.66 2.36 3.00 PASS
5 LP-PP LP-PP PANEL LP-PP-19,21,23 TWO POST LIFT 4 In Wire Way 1100.00 400 0.85 1.87 0.38 15 18 6.84 3C X 2.5 1 SAFE 60 15 1.68 0.42 3.00 PASS
6 LP-PP LP-PP PANEL LP-PP-20,22,24 AIR PUMP 6 In Wire Way 2950.00 400 0.85 5.01 0.38 15 24 9.12 3C X 4 1 SAFE 55 9.5 2.62 0.65 3.00 PASS
Derating factor for variation in ambient air tempperature 40 deg (see EIT Standard 022001-22 Table 5-43) 1.00
The current size of the wires in the wiring rail should use the current value in the case of 3 current conductors according to Table 5-20 or 5-27.
Without using a current reduction factor regarding the number of wires according to Table 5-8, if the total current flowing conductors do not exceed 30 wires, conductors, signal circuits, or control circuits that may have current flowing for a short period of time. It is not considered a current-carrying 0.38
conductor.
Cable Description
From To
Size Area of Cable.
Type
(mm²) (mm²)
Solution
Total Area of Cables (mm²) 1,170.11 mm²
1) Using area
= 1,170.11
10,000.00
= 12%
Using area of cable 12% (Using Area for Wire Way less than 20% is accepted)