9decentralized Robust Frequency Regulation of Multi-Terminal HVDC-linked Grids
9decentralized Robust Frequency Regulation of Multi-Terminal HVDC-linked Grids
Abstract—This paper proposes a new strategy for optimal grid delivering offshore wind power to onshore power grids and
frequency regulation (FR) in an interconnected power system sharing it between interconnected regional grids [3], [4].
where regional ac grids and an offshore wind farm are linked via In HVDC technology, line-commutated converter (LCC) and
a multi-terminal high voltage direct-current (MTDC) network. In
the proposed strategy, decentralized H controllers are developed voltage source converter (VSC) have been widely used due to
to coordinate the operations of synchronous generators and MTDC their distinct characteristics. An LCC is characterized by, for
converters, thus achieving optimal power sharing of interconnected example, a high capacity for bulk power transmission, low power
ac grids and minimizing frequency deviations in each grid. To de- loss, and low installation cost [5]. However, it operates only as
velop the controllers, robust optimization problems are formulated a rectifier or an inverter that can control either dc voltage or
and solved using a dynamic model of the hybrid MTDC-linked grids
with model parameter uncertainty and decentralized control inputs dc current [6]. By contrast, a VSC can change the direction of
and outputs. The model orders of the controllers are then reduced dc current and independently control active and reactive power,
using a balanced truncation algorithm to eliminate unobservable although it has lower power rating and higher power loss even
and uncontrollable state variables while preserving their dominant when implemented in the form of modular multilevel converter
response characteris- tics. Sensitivity and eigenvalue analyses are [7]. In several projects, there is a recent interest in combining the
conducted focusing on the effects of grid measurements, parameter
uncertainty levels, and communication time delays. Comparative advantages of both LCC and VSC, developing hybrid schemes.
case studies are also carried out to verify that the proposed strategy An HVDC system can be further developed in the form of a
improves the effectiveness, stability, and robustness of real-time FR multi-terminal dc (MTDC) system [9], [10], [11], [12], [13],
in MTDC-linked grids under various conditions. [14], for example, where LCCs, grid-side VSCs (GSVSCs),
Index Terms—Grid frequency regulation, H infinity, hybrid and OWF-side VSCs (WFVSCs) are linked via a dc network
MTDC converters, offshore wind farm, optimal power sharing. to connect regional ac grids with OWFs. This enhances the
flexibility of inter-grid power delivery and sharing, thereby
facilitating the integration of large-scale OWFs with regional
I. INTRODUCTION load centers. However, due to the interconnection, each grid
USTAINABLE wind energy is critical to reducing fossil frequency is affected by power imbalances not only in the
S fuel emissions and mitigating global climate change [1].
In particular, the capacity of offshore wind farms (OWFs) is
corresponding grid but also in other grids [8], implying that
intermittent wind power causes freq- uency deviations in all
growing faster for many reasons, including a lack of suit- interconnected grids. This motivates the development of a proper
able onshore sites and better wind conditions of offshore sites strategy for power balancing in MTDC- linked grids, essentially
[2]. Meanwhile, high-voltage direct-current (HVDC) technol- requiring the coordinated control of regional power generation
ogy has been increasingly considered a promising solution for and ac-to-dc power transmission.
Several studies have been conducted on frequency regulation
(FR) in MTDC-linked grids. For example, in [9], VSCs were
Manuscript received 7 December 2021; revised 13 June 2022 and 8 August
2022; accepted 21 August 2022. Date of publication 24 August 2022; date of
droop-controlled to mitigate grid frequency deviations and dc
current version 22 June 2023. This work was supported by the National Research voltage variations resulting from wind power generation. In [10],
Foundation of Korea through Energy Cloud Research and Development Program communication-free coordination of VSC terminals was accom-
funded by the Ministry of Science, ICT under Grant NRF-2019M3F2A1073402.
Paper no. TPWRS-01886-2021. (Corresponding author: Young-Jin Kim.)
plished using a Vdc -f droop control scheme. In [11], adaptive
Jun-Soo Kim and Young-Jin Kim are with the Department of Electrical En- droop control of a VSC-MTDC system was discussed, wherein
gineering, Pohang University of Science and Technology (POSTECH), Pohang the Vdc -Idc -f characteristics of the system were analyzed to
37673, South Korea (e-mail: [email protected]; [email protected]).
Jae-Young Park is with the Korea Institute of Energy Research (KIER),
deter- mine the droop control gains. However, in [9], [10], [11],
Daejeon 34129, South Korea (e-mail: [email protected]). FR relied mainly on droop control or, equivalently, primary fre-
Oriol Gomis-Bellmunt is with the Centre d’Innovacio Tecnologica en quency control, rather than optimal secondary frequency control
Convertidors Estatics i Accionaments, Departament d’Enginyeria Electrica,
Universitat Politecnica de Catalunya, 08028 Barcelona, Spain (e-mail:
(SFC).
[email protected]). The optimal FR of MTDC-linked grids has been discussed in
Color versions of one or more figures in this article are available at recent studies (e.g., [12], [13], [14]). In [12], a model predictive
https://doi.org/10.1109/TPWRS.2022.3201316.
Digital Object Identifier 10.1109/TPWRS.2022.3201316
control (MPC) algorithm was adopted for the optimal power
0885-8950 © 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on May 06,2024 at 05:50:37 UTC from IEEE Xplore. Restrictions apply.
3280 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 38, NO. 4, JULY 2023
sharing in a VSC-MTDC system, wherein a discrete-time op- The main contributions of this paper are summarized below:
timization problem was formulated considering grid operating r To the best of our knowledge, this is the first study reporting
costs. In [13] and [14], the MPC-based power sharing was also the optimal robust FR of MTDC-linked grids using decen-
achieved to minimize the frequency deviations in the MTDC- tralized H controllers. Each H controller is designed
linked grids with only VSCs and LCCs, respectively. However, with reduced require- ment on inter-grid measurements and
in [12], [13], [14], hybrid MTDC systems were not considered. communications.
Moreover, in general, MPC is computationally intensive, be- r Hybrid MTDC-linked grids are modeled with decentral-
cause an optimization problem for MPC needs to be solved ized control inputs and outputs. For each grid, considering
directly at every time step. MPC is also likely to cause oscil- model parameter uncertainty, an optimization problem is
latory and even unstable operation of MTDC-linked grids due then formul- ated to determine the corresponding optimal
to communication time delays and model parameter uncertainty robust control gains.
[15]. Therefore, the optimal FR strategies discussed in [12], [13], r The model orders of the optimal decentralized H con-
[14] need to be further analyzed under practical conditions of trollers are reduced using a balanced truncation algorithm,
MTDC systems, for example, with regard to hybrid converters, facilitating practical applications of the proposed FR strat-
communications links, and system parameter estimates. egy.
When system parameters are uncertain, robust controllers can r The proposed strategy is comprehensively evaluated via
effectively reduce the effect of disturbance on system operation. comparison to conventional decentralized PI and H
For example, in [16], the robust dc voltage control of a VSC controller- based strategies with regard to effectiveness and
was achieved by establishing an H -mixed sensitivity function robustness against time-varying power imbalance, commu-
in a linear matrix inequality framework, wherein dc current nication failures and time delays, and different weighting
injection was set as a disturbance input. In [17], a systematic function models.
method was provided to design the H controller of a VSC for
optimal and robust control of active power and ac voltage. In [18] II. HYBRID MTDC-LINKED GRIDS
and [19], H2 and H controllers were discussed to optimally
Fig. 1 shows a schematic diagram of the proposed decen-
regulate the dc-link voltage and the converter internal energy of
tralized strategy for the optimal robust FR in MTDC-linked
an HVDC system, respectively. However, in [16], [17], [18],
grids, where regional ac grids and OWFs are interconnected
[19], robust control was applied to only a single converter;
with each other using hybrid MTDC converters (i.e., VSCs
the coordination with synchronous generators and the power
and LCCs). Each grid includes multiple synchronous generators
sharing between regional ac grids were not considered. In [19], a
(SGs), loads, and ac transmission lines, and each OWF contains
centralized optimization problem was formulated for centralized
several wind turbine generators (WTGs) using permanent mag-
and decentralized H control of the dc-link voltage in a modular
net synchro- nous generators (PMSGs). Note that for brevity,
multilevel converter when applied to a VSC-HVDC system. The
Fig. 1 illustrates an SG and a WTG. Moreover, for each WTG, a
centralized controller slightly outperformed the decentralized
back-to-back converter and its maximum-power-point-tracking
controller. However, in practice, such a centralized controller is
controller are modeled using simple equations for power balance
difficult to implement and apply for MTDC-linked grids due to
[35]. For each regional grid, a decentralized control structure is
computa- tional and communication overheads.
developed to establish the optimal control inputs for the local
This paper proposes a new decentralized strategy for optimal
controllers of the SGs and the MTDC converter and adjust
robust FR in regional ac grids that are interconnected via a hybrid
the generated and transmitted power in a coordinated manner,
MTDC system including LCCs and VSCs. For each ac grid, a
while receiving measurements from the corresponding grid and
decentralized H controller is developed for coordinated control
interconnected grids via communication systems with time de-
of generated and transmitted power, optimizing inter-grid power
lays [37], [38], [39]. Specifically, the decentralized controller k
sharing and thus minimizing frequency deviations. Specifically,
receives the measurements of ΔPgk , Δω rk , Δfk , ΔVmagk , ΔPk ,
for the proposed strategy, a dynamic model of hybrid MTDC-
and ΔVdck from grid k and the measurements of Δfj and ΔVdcj
linked grids is implemented with decentralized control inputs
from interconnected grids j k, as shown in Fig. 1 and discussed
and outputs. Given the dynamic model, a robust optimization
in Appendix.
problem for the optimal FR is formulated considering model
parameter uncertainty. The solution to the problem leads to the
optimal gain of the decentralized H controller. A balanced trun- A. Modeling of Hybrid MTDC-Linked Grids
cation algorithm is then applied to reduce the controller model Without loss of generality, this paper considers three regional
order, thus facilitating its practical implementation and the ref- ac grids and one PMSG-type OWF, all of which are linked to
erence signal generation. Sensitivity and eigenvalue analyses a dc network via two GSVSCs, one LCC, and one WFVSC.
are conducted to verify grid frequency stability in the proposed Specifically, Grids 1 and 2 are interfaced using GSVSCs and
strategy, focusing on the effects of system parameters, parameter Grid 3 is connected with LCC at the points of common coupling
uncertainty, and communication time delay. Comparative case (PCCs): i.e., n = 2 and m = 3 in Fig. 1. The GSVSCs are equipped
studies are also carried out to verify that the proposed strategy with local P-Vdc droop controllers, so that power transmitted
improves the effectiveness and robustness in reducing frequency from Grids 1 and 2 are instantaneously adjusted according to
deviations under various grid conditions. variations in the corresponding dc terminal voltages. On the
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on May 06,2024 at 05:50:37 UTC from IEEE Xplore. Restrictions apply.
KIM et al.: DECENTRALIZED ROBUST FREQUENCY REGULATION OF MULTI-TERMINAL HVDC-LINKED GRIDS 3281
Fig. 1. A schematic diagram of the proposed decentralized strategy for optimal FR in MTDC-linked grids.
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on May 06,2024 at 05:50:37 UTC from IEEE Xplore. Restrictions apply.
3282 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 38, NO. 4, JULY 2023
k, as:
with coefficient matrices augmented as: and, consequently, its frequency-domain model becomes:
A O Br rk = [Chk · (sI − Ahk )−1 · Bhk + Dhk ] · YTk . (19)
AE = , BrE = ,
As O O Kk (s)
Bw CO Specifically, for the optimal robust FR in grid k, the con-
BwE = , CE = , (14)
O O I troller k minimizes the target performance outputs Zek and
where inputs Zuk against disturbance dk . In the proposed strategy,
XE = [XT , Δfk dt, ΔVdck dt] , ∀k,
T
(15) Zek includes not only the weighted values of Δfk and Δfk
T dt but also the weighted values of ΔVdck and ΔVdck dt to
YE = [YT , Δfk dt, ΔVdck dt] , ∀k.
prevent excessive variations in dc terminal voltages during the
In (14), As is a sparse matrix with elements of ones that are optimal FR. Similarly, Zuk contains the weighted values of
ref
assigned to only the state variables Δfk and ΔVdck for all k in ΔPgk , ΔPkref , and ΔVdckref
when grid k is linked via a VSC.
ref
XE . For the case of an LCC, it consists of ΔPgk and ΔPkref .
Furthermore, We , Wu , and Wd are the weighting functions for
B. Decentralized Control Inputs and Outputs Zek , Zuk , and dk , respectively, as:
The proposed decentralized controllers are developed in the
Zek We · C̄Ek O XE XE
form of output feedback controllers, as shown in Fig. 2, so that Zk = = = [C1 D12] ,
Zuk O Wu ·I rk rk
the optimal FR in MTDC-linked grids can readily be achieved
in practice using the measurement of YE , rather than the esti- and wdrk = Wd · dk , (20)
mation of XE . In (13), YE is decentralized to YTk for the design
where C̄E k is a sparse matrix with elements of ones to extract
of the proposed controller in grid k, discussed in Section III, as:
Δfk , ΔVdck , Δfk dt, and ΔVdck dt from XE . Note that in
T
T
YTk = [YEk T
YPj ] = CTk · XE (20), C1 and D12 are additionally defined for brief notation.
Moreover, in Fig. 2, Δk (s) reflects the uncertainty in the model
= [CEk CIk CPj ]T · XE , ∀k, and j = k. (16) parameters of grid k [20], [21]: i.e., Gk (s).(1 + Δk (s)), rather
than Gk (s). In time domain, Δk (s) affects the accuracy of AE ,
In (16), YEk and YPj are the measurements delivered from BrEk , Bdrk , and CTk [see (16) and (17)]. This implies that the
grids k and j, respectively, as shown in Fig. 2. For grid k, CEk and proposed decentralized controllers are developed considering
CIk are obtained by decentralizing the upper and lower parts, uncertainty in the model parameter estimates of SGs, converters,
respectively, of CE in (14): i.e., [C O] = [CE1 , ···, CEk , ···, and ac and dc transmission lines.
CEm ]T and [O I] = [CI1 , ···, CIk , ···, CIm ]T . Moreover, in (16), Given the weighting functions and parameter uncertainty, the
YPj is a sub-vector of YEj and CPj is the corresponding sub- model of the MTDC-linked grid with the decentralized control
matrix of CEj , because the design and activation of controller k inputs and outputs [i.e., (16) and (17)] can be completed as:
do not require all of the measurement data in YEj , as discussed ẊE = A1 · XE + B1 · dk + B2 · rk , (21)
in Section III-C.
Similarly, the controller outputs or, equivalently, the reference Zk = C1 · XE + D12 · rk , (22)
signals r in (11) can be decentralized to rk : i.e., BrE ·r = YTk = C2 · XE , (23)
Σk BrEk ·rk . The reference signals rj generated by controllers
j k are regarded as disturbances for controller k. This implies where the notations are simplified as A1 = AE , B1 = Bdrk ·Wd ,
that (12) can be represented from the perspective of controller B2 = BrEk , and C2 = CTk . In frequency domain, (21) is
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on May 06,2024 at 05:50:37 UTC from IEEE Xplore. Restrictions apply.
KIM et al.: DECENTRALIZED ROBUST FREQUENCY REGULATION OF MULTI-TERMINAL HVDC-LINKED GRIDS 3283
expressed as: From (19) and (31), the time-domain control gains Ahk , Bhk ,
−1 T Chk , and Dhk in (18) also can be obtained, which is omitted
XE = (sI − A1 ) · [B1 B2 ] · [dk rk ] . (24)
here.
Using (24), (22) and (23) are then equivalently represented in In each grid, the decentralized H controller operates as the
the frequency domain as: optimal secondary frequency controller that establishes extra
power references to restore the grid frequency to a nominal value
Zk = {C1 · (sI − A1 )−1 · [B1 B2 ] + [O D12 ]} · [dk rk ]T ,
[40]. The extra references do not disturb the references of the
(25)
droop controllers, because the optimization problem (27)–(29) is
and YTk = C2 · (sI − A1 )−1 · [B1 B2 ] · [dk rk ]T . (26) formulated using the dynamic model of the MTDC-linked grids
with the droop control. This also implies that the H control gain
In other words, for the optimal robust FR, decentralized Kk (s) inherently reflects the physical operating conditions and
controller k [see (18) and (19)] should be designed to generate limits of the SGs, MTDC converters, and ac and dc networks.
rk that minimizes Zk for all unknown dk in (25), given the It further enables Kk (s) to be deterministically obtained and
measurements YTk in (26). updated for changes in the grid operating conditions, unlike
In the proposed optimal FR strategy, the decentralized control conventional non-optimal strategies wherein control gains need
gain Kk (s) for grid k is determined to minimize the H -norm of to be tuned using a trial-and-error approach.
the transfer function TZkdk from dk to Zk by solving the robust
optimization problem:
B. Model Order Reduction of Decentralized H Controllers
minTZkdk (Kk (s))∞ < γ, (27)
In general, a dynamic model of MTDC-linked grids [i.e.,
where TZkdk (Kk (s))∞ = sup σ̄(TZkdk (jω)), (28) (12)–(15)] is implemented in high dimensions including several
ω
uncontrollable and unobservable variables particularly when the
numbers of SGs, VSCs, LCCs, and WTGs are large. For the case
TZkdk (s) = G11 (s) + G12 (s)Kk (s) of Grids 1–3, discussed in Section II-A, each decentralized H
controller is designed with a model order r of 87. The full-order
· (I − G22 (s)Kk (s))−1 G21 (s), (29a)
decentralized H controllers are difficult to implement in prac-
G11 (s) = C1 · (sI − A1 )−1 · B1 , (29b) tice due to high computational burden and high sensitivity to
measurement noises. In this paper, for the practical implementa-
G12 (s) = C1 · (sI − A1 )−1 · B2 + D12 , (29c) tion, a balanced truncation algorithm [24] is applied to reduce
the model orders of the decentralized H controllers while still
G21 (s) = C2 · (sI − A1 )−1 · B1 , (29d)
preserving their dominant response characteristics. Specifically,
and G22 (s) = C2 · (sI − A1 )−1 · B2 . (29e) the optimal control gains Ahk , Bhk , and Chk of the full-order
H controller k are first converted to Ãh k = T-1 Ahk T, B̃h k =
In (27) and (28), TZkdk can be obtained as (29) by substituting
T-1 Bhk , and C̃h k = Chk T using the balancing transformation
(19) into (24)–(26). Moreover, σ̄ represents a maximum singular
matrix T, as:
value of TZkdk and γ is the performance level. In this study, a
γ-iteration method is adopted to solve the optimization problem Ahk,11 Ahk,12 Bhk,1
(27)–(29), wherein γ is repeatedly updated to a smaller value Ãhk = , B̃hk = , (32)
Ahk,21 Ahk,22 Bhk,2
until convergence [22]. For each value of γ, there exists a stable
H controller that satisfies (27) if and only if the three conditions C̃hk = Chk,1 Chk,2 . (33)
hold [23] as:
In (32) and (33), the matrix decomposition can be adaptively
X∞ = −A1 AT1 + CT1 C1 (γ −2 B1 BT1 − B2 BT2 ) ≥ 0, (30a) achieved considering the cumulative energy and number of Han-
kel singular values (HSVs). The reduced-order H controller k
Y∞ = −AT1 A1 + B1 BT1 (γ −2 CT1 C1 − CT2 C2 ) ≥ 0, (30b)
can then be determined as:
and ρ(X∞ Y∞ ) < γ 2 . (30c) ˙
X̃ hk = Ahk,11 · X̃hk + Bhk,1 · YTk
In (30c), ρ(X Y ) is the largest eigenvalue of X Y . When
γ converges, the optimal control gain Kk (s) is then determined rk = Chk,1 · Xhk + Dhk · YTk . (34)
using (30), as:
Fig. 3(a) shows the HSVs of the full-order and reduced-order
A∞ −Z∞ L∞ models of the decentralized H controllers for the MTDC-
Kk (s) = , (31a)
F∞ 0 linked grids. The HSVs were obtained for the step response to
the load demand variation by 0.1 pu in each grid, given the test
where A∞ = A1 + γ −2 B1 BT1 X∞ + B2 F∞ + Z∞ L∞ C2 , conditions discussed in Section IV-A and IV-C. Fig. 3(b) shows
(31b) the corresponding cumulative energy curves. The results of the
F∞ = −BT2 X∞ , L∞ = −Y∞ CT2 , HSV analysis indicate that the energy magnitudes of the three
decentralized H controllers are still higher than 99.9% of the
−1
and Z∞ = (I − γ −2 Y∞ X∞ ) . (31c) total energy when their model orders are reduced to r = 26, 29,
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on May 06,2024 at 05:50:37 UTC from IEEE Xplore. Restrictions apply.
3284 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 38, NO. 4, JULY 2023
(a)
(a)
(b)
(b)
(c)
Fig. 3. (a) Hankel singular values and (b) cumulative energy curves for the
optimal decentralized H controllers.
(a) (b)
(d)
(e)
and 13, respectively. This implies that the reduced-order mod- Fig. 5. Closed-loop system eigenvalues for variations in (a) Lf ranging from
0.03 mH to 1.50 mH, (b) Trh from 4 s to 10 s, (c) Ls from 0.01 pu to 0.30 pu,
els of the H controllers can successfully reflect the dynamic (d) Δ(s) from 0% to 50%, and (e) Td from 0 ms to 60 ms.
operating characteristics of the original, 87th -order models. In
other words, the reduction of the model orders to 26, 29, and
13, respectively, only marginally affects the FR performance,
while effectively mitigating the computational burden. Note that conditions. It can be seen that the elements in Bhk and Dhk
r can be set to smaller values, considering the trade-off between have values close to zero for all measurements from grid j
control performance and implementation complexity. k, apart from the measurements of Δfj and ΔVdcj . In other
words, Xhk and rk in each grid k are mainly affected by the
measurements of Δfj and ΔVdcj for grid j k. This demonstrates
C. Sensitivity and Eigenvalue Analyses
that the decentralized H controller for grid k can be effectively
The closed-loop system, shown in Fig. 2, was analyzed with designed only using the measurements of Δfj and ΔVdcj for grid
respect to the gain sensitivity and stability. Note that the anal- j k, thus mitigating the requirement for inter-grid measurement
ysis was conducted using reduced-order models of the three and communication systems and facilitating wide applications
decentralized H controllers, discussed in Section III-B. Speci- of the proposed strategy in practice.
fically, Fig. 4 shows the optimal gains of the H controllers In addition, Fig. 5 shows the eigenvalues of the closed-loop
for the GSVSC- and LCC-interfaced grids (i.e., k = 1, 2, and system with changes in system parameters, model uncertainty
3) parti- cularly with regard to the measurements from the level, and communication time delay. In Fig. 5(a)–(c), the
corresponding grid and the interconnected grids: i.e., Bhk and complex-conjugate eigenvalues move closer to the imaginary
T
Dhk for YTk = [YT Ek YT Pj ] in Fig. 2 and (18). It represents axis, implying increased overshoot and settling time, as the
the extent to which the measurements YTk affect the controller converter phase inductance Lf , the turbine time constant Trh , and
states Xhk and the reference signals rk under disturbed grid the stator inductance Ls increase from 0.03 mH to 1.50 mH, from
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on May 06,2024 at 05:50:37 UTC from IEEE Xplore. Restrictions apply.
KIM et al.: DECENTRALIZED ROBUST FREQUENCY REGULATION OF MULTI-TERMINAL HVDC-LINKED GRIDS 3285
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on May 06,2024 at 05:50:37 UTC from IEEE Xplore. Restrictions apply.
3286 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 38, NO. 4, JULY 2023
(b)
(c)
Fig. 7. Comparisons of the step responses of the small-signal model and the
comprehensive SIMULINK model of the MTDC-linked grids to ΔPL1 = 0.1 pu
and ΔPL2 = 0.15 pu: (a) f1 , (b) f2 , (c) f3 , and (d) Vdc .
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on May 06,2024 at 05:50:37 UTC from IEEE Xplore. Restrictions apply.
KIM et al.: DECENTRALIZED ROBUST FREQUENCY REGULATION OF MULTI-TERMINAL HVDC-LINKED GRIDS 3287
(b)
(c)
(d)
Fig. 9. Step responses of the (a) generated and (b) transmitted power for the
proposed and conventional strategies.
TABLE IV
COMPARISONS OF CONTINUOUS RESPONSE TEST RESULTS
Fig. 10. Responses to the continuous variations in ΔPL1–3 and ΔVW for the
proposed and conventional strategies: (a) f1 , (b) f2 , (c) f3 , and (d) Vdc .
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on May 06,2024 at 05:50:37 UTC from IEEE Xplore. Restrictions apply.
3288 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 38, NO. 4, JULY 2023
(a)
(a)
(b)
(b)
TABLE VI
COMPARISONS OF COMMUNICATION DELAY TEST RESULTS
Fig. 12. Step responses of f1 and Vdc for the (a) proposed and (b) conventional
H controllers (Cases 1 and 3) when the inter-grid communication links fail.
TABLE V
COMPARISONS OF COMMUNICATION FAILURE TEST RESULTS were directly obtained by solving the decentralized optimization
problems (27)–(29). This stands in contrast to Case 3 where the
non-optimal gains were acquired from the centralized optimiza-
tion problem. In other words, the inter-grid communication
failure more affects the non-optimal controllers, thus leading
to larger and longer overshoot responses of f1–3 and Vdc . The
case study results confirm that the proposed decentralized H
controllers are still more effective and robust in the optimal FR
against the events of inter-grid communication failure.
receiving the Δfj and ΔVdcj from grid j k. Fig. 12 shows f1 and In addition, Fig. 13 compares the step responses of f2 and f3 for
Vdc for the step responses of the MTDC-linked grids to ΔPLk variations in ΔPL1–3 by ±0.1 pu over every 40 s between Cases
= 0.1 pu for all k at t = 10 s, and Table V lists the corresponding 1 and 3, when increasing Td gradually from 20 ms to 50 ms.
numerical results. In Fig. 12(a), Case 1 enabled the smaller Table VI lists the corresponding numerical results. Note that for
deviation of f1 (and also f2 and f3 ) and the faster recovery back brevity, Td was assumed to be the same for all the decentralized
to the nominal value with smaller overshoot responses for all the H controllers, as discussed in Section III-C. As Td increased,
communication conditions than Case 3 in Fig. 12(b). Case 3 led to larger Σk fk,rms than Case 1. Moreover, in Case
Fig. 12(a) shows that in Case 1, it took approximately 3.0 s 3, Td = 50 ms led to unstable, large oscillations of f2 and f3 ;
for the frequency recovery, and the recovery time is relatively this was also the case for f1 . It was mainly because in Case 3,
smaller than in the existing SFC schemes for the real-world the centralized H control gains were simply divided for the
SG-only grids [40], but similar to the case of the previous decentralized controllers by setting the off-diagonal elements
SFC schemes for the power-electronics-interfaced grids (e.g., to zero, which reduced the maximum allowable value of the
[12] and [17]). The improved performance of Case 1 is mainly communication time delay. In other words, the eigenvalues
because the optimal gains for the decentralized H controllers moved across the imaginary axis from the LHP to the RHP
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on May 06,2024 at 05:50:37 UTC from IEEE Xplore. Restrictions apply.
KIM et al.: DECENTRALIZED ROBUST FREQUENCY REGULATION OF MULTI-TERMINAL HVDC-LINKED GRIDS 3289
Fig. 14. (a) |Δf1 |max and (b) (|Δf2 |max + |Δf3 |max )/2 for ΔPL1 (t = 5 s)
= 0.3 pu in Case 1.
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on May 06,2024 at 05:50:37 UTC from IEEE Xplore. Restrictions apply.
3290 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 38, NO. 4, JULY 2023
TABLE VIII included in each grid (i.e., 30 SGs in total), whereas it was
COMPARISONS FOR THE CIGRE BENCHMARK TEST BED
42.17 s for Case 3. Moreover, Case 1 became more time efficient
for a higher number of the SGs, compared to Case 3. The case
study results verified the computational efficiency and hence
scalability of the proposed decentralized H controllers. Note
that in Cases 1 and 3, the H controllers were designed offline
and then executed online for the real-time FR, as in Case 2.
The computational efficiency of Case 2 was not discussed here,
because the PI control gains were determined using a trial-and-
TABLE IX
COMPARISONS WITH A CONSENSUS ALGORITHM-BASED STRATEGY
error approach, rather than the optimization problem solving.
V. CONCLUSION
This paper proposes a new strategy for optimal FR in MTDC-
linked grids via coordinated, decentralized control of SGs and
hybrid converters. A dynamic model of hybrid MTDC- linked
grids was implemented considering the decentralized control
inputs and outputs. Given the dynamic model, a robust opti-
mization problem was formulated to develop a decentralized
H controller for each grid, considering the inter-grid communi-
cation systems and the model parameter uncertainty. A balanced
truncation algorithm was applied to reduce the model orders
of the decentralized H controllers, while still preserving their
dominant response characteristics. Sensitivity and eigenvalue
analyses were then conducted, focusing on the effects of inter-
grid measurement, system parameter, uncertainty level, and
communication time delay. The results of comparative case
studies verified that the proposed strategy was more effective in
Fig. 16. Computation time required to solve the optimization problems of reducing the frequency deviations in all MTDC-linked grids than
Cases 1 and 3 for an increase in the number of the SGs in each MTDC-linked
grid from 1 to 10. conventional strategies, while maintaining smaller variations in
dc network voltages. Moreover, compared to the conventional
H control strategy, the proposed strategy also improved the
The performance of the proposed optimal strategy was also effectiveness, stability, and robustness in the optimal FR of
analyzed in comparison with the conventional non-optimal strat- hybrid MTDC-linked grids under various conditions.
egy using a consensus algorithm (i.e., Case 4) [9]. Table IX
shows the test results of Cases 1 and 4 for the continuous APPENDIX
variations in ΔPL1–3 and ΔVw . Case 1 led to the significant A. Modeling of AC Grids with Hybrid Converter Interfaces
reductions of Σk Δfk,rms and ΔVdc,rms by 91.2% and 88.7%,
respectively, compared to Case 4. The improved performance of A regional ac grid includes SGs with reheat steam turbines.
Case 1 is attributable to the fact that the dynamic response capa- For each SG, a synchronous machine is modelled using the 6th -
bilities of the SGs and MTDC converters could be fully exploited order differential equations, discussed in [31]. A governor and
and optimally coordinated for fast and accurate compensation exciter are modeled using the 1st -order transfer functions, based
for the power imbalances in all grids k. By contrast, the control on [32]. The dynamic model of an SG can then be established
gains in Case 4 (and also in Case 2) need to be tuned using a as:
trial-and-error approach and hence there is a high possibility that
Ẋsg = Asg · Xsg + Bsg · rsg + Esg · Ibus , (A1)
the fast operating capabilities of the MTDC converters are not
effectively exploited. where Xsg = [ΔE q , ΔE d , Δφ1d , Δφ2q , Δδr , Δωr ,
In addition, the computational efficiency of the proposed
strategy was evaluated while gradually increasing the number Δxgov1 , Δxgov2 , Δxtur1 , Δxtur2 , ΔVf d ]T ,
of the SGs in each MTDC-linked grid. Specifically, Fig. 16 T
rsg = [ΔPgref , ΔEtref ] , and Ibus = ΔIsdq . (A2)
shows the computation time required to solve each decentralized
optimization problem [i.e., (27)–(29) for k = 1, 2, and 3] for Case Furthermore, in each grid, a phase-locked loop (PLL) is used
1. It also shows the computation time to solve the centralized to measure the grid frequency at the PCC of an MTDC converter
optimization problem [19], as discussed in Section IV-A. In Case and calculate the dq values of the PCC voltages and currents [33].
1, the optimal H control gains were determined within shorter Considering the PLL operation, an ac network is modeled as:
computation time than in Case 3. The maximum computation
time for Case 1 was estimated as 22.99 s when 10 SGs were Ẋac = Aac · Xac + Eac1 · Vac + Eac2 · Iac + Bacw · wac
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on May 06,2024 at 05:50:37 UTC from IEEE Xplore. Restrictions apply.
KIM et al.: DECENTRALIZED ROBUST FREQUENCY REGULATION OF MULTI-TERMINAL HVDC-LINKED GRIDS 3291
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on May 06,2024 at 05:50:37 UTC from IEEE Xplore. Restrictions apply.
3292 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 38, NO. 4, JULY 2023
[13] M. Mehrabankhomartash, M. Saeedifard, and S. Grijalva, “Model predic- [36] L. Wang and M. Sa-Nguyen Thi, “Stability enhancement of a PMSG–based
tive control based AC line overload alleviation by using multi–terminal DC offshore wind farm fed to a multi–machine system through an LCC–HVDC
grids,” IEEE Trans. Power Syst., vol. 35, no. 1, pp. 177–187, Jan. 2020. link,” IEEE Trans. Power Syst., vol. 28, no. 3, pp. 3327–3334, Aug. 2013.
[14] P. M. Namara, R. R. Negenborn, B. De Schutter, and G. Lightbody, [37] Y. Wang et al., “Decentralized H infinity controller design for large-scale
“Optimal coordination of a multiple HVDC link system using centralized civil structures,” Earthq. Eng. Struct. Dyn., vol. 38, no. 3, pp. 377–401,
and distributed control,” IEEE Trans. Control Syst. Technol., vol. 21, no. 2, 2009.
pp. 302–314, Mar. 2013. [38] Q. Li, F. X. Chen, M. Chen, J. M. Guerrero, and D. Abbott, “Agent-based
[15] B. -C. Jeong, D. -H. Kwon, J. -Y. Park, Y. -J. Kim, and O. Gomis- decentralized control method for islanded microgrids,” IEEE Trans. Smart
Bellmunt, “Optimal secondary control to suppress voltage fluctuations Grid, vol. 7, no. 2, pp. 637–649, Mar. 2016.
in an HVDC-linked wind farm grid,” IEEE Trans. Power Syst., vol. 37, [39] N. Yorino, Y. Zoka, M. Watanabe, and T. Kurushima, “An optimal au-
no. 4, pp. 2563–2577, Jul. 2022. tonomous decentralized control method for voltage control devices by
[16] A. Banerjee et al., “A novel explicit disturbance model–based robust using a multi-agent system,” IEEE Trans. Power Syst., vol. 30, no. 5,
damping of inter–area oscillations through MTDC grids embedded in pp. 2225–2233, Sep. 2015.
AC systems,” IEEE Trans. Power Del., vol. 33, no. 4, pp. 1864–1874, [40] Y. Rebours, D. Kirschen, M. Trotignon, and S. Rossignol, “A survey
Aug. 2018. of frequency and voltage control ancillary services—Part I: Technical
[17] L. Huang, H. Xin, and F. Döfler, “H –control of grid–connected con- features,” IEEE Trans. Power Syst., vol. 22, no. 1, pp. 350–357, Feb. 2007.
verters: Design, objectives and decentralized stability certificates,” IEEE [41] Z. Xiaodong, T. Nengling, and S. T. James, “A transient harmonic current
Trans. Smart Grid, vol. 11, no. 5, pp. 3805–3816, Sep. 2020. protection scheme for HVDC transmission line,” IEEE Trans. Power Del.,
[18] E. Sánchez–Sánchez, D. Groß, E. Prieto-Araujo, F. Dörfler, and O. Gomis- vol. 27, no. 4, pp. 2278–2285, Oct. 2012.
Bellmunt, “Optimal multivariable MMC energy–based control for dc volt- [42] A. D. Paquette and D. M. Divan, “Virtual impedance current limiting for
age regulation in HVDC applications,” IEEE Trans. Power Del., vol. 35, inverters in microgrids with synchronous generators,” IEEE Trans. Ind.
no. 2, pp. 999–1009, Apr. 2020. Appl., vol. 51, no. 2, pp. 1630–1638, Mar./Apr. 2015.
[19] S. D. Tavakoli, S. Fekriasl, E. Prieto-Araujo, J. Beerten, and O. Gomis- [43] K. Shi, W. Song, H. Ge, P. Xu, Y. Yang, and F. Blaabjerg, “Transient
Bellmunt, “Optimal H infinity control design for MMC–based HVDC analysis of microgrids with parallel synchronous generators and virtual
links,” IEEE Trans. Power Del., vol. 37, no. 2, pp. 786–797, Apr. synchronous generators,” IEEE Trans. Energy Convers., vol. 35, no. 1,
2022. pp. 95–105, Mar. 2020.
[20] D. Babazadeh and D. V. Hertem, “Study of centralized and distributed [44] T. K. Vrana, S. Dennetire, Y. Yang, J. Jardini, D. Jovcic, and H. Saad, “The
coordination of power injection in multi–TSO HVDC grid with large CIGRE B4 dc grid test system,” Electra, no. 270, pp. 10–19, Oct. 2013.
offshore wind integration,” Elect. Power Syst. Res., vol. 136, pp. 281–288, [45] H. Saad et al., “Modular multilevel converter models for electromag-
Jul. 2016. netic transients,” IEEE Trans. Power Del., vol. 29, no. 3, pp. 1481–1489,
[21] M. Aragüés-Peñalba et al., “Droop control for loss minimization in HVDC Jun. 2014.
multi-terminal transmission systems for large offshore wind farms,” Elect.
Power Syst. Res., vol. 112, pp. 48–55, Jun. 2014.
[22] K. Glover and J. C. Doyle, “State–space formulae for all stabilizing Jun-Soo Kim (Student Member, IEEE) received the B.S. degree in electrical
controllers that satisfy an H1–norm bound and relations to relations to engineering from Kyoungpook National University, Daegu, South Korea, in
risk sensitivity,” Syst. Control Lett., vol. 11, no. 3, pp. 167–172, 1988. 2019, and the M.S. degree in electrical engineering in 2021 from the Pohang
[23] J. Doyle, K. Glover, P. P. Khargonekar, and B. A. Francis, “State–space University of Science and Technology, Pohang, South Korea, where he is
solutions to standard H2 and H control problems,” IEEE Trans. Automat. currently working toward the Ph.D. degree in electrical engineering. His research
Control, vol. 34, no. 8, pp. 831–847, Aug. 1989. interests include power system control, renewable energy sources, and HVDC
[24] B. Moore, “Principal component analysis in linear systems: Controllabil- systems.
ity, observability, and model reduction,” IEEE Trans. Automat. Control,
vol. 26, no. 1, pp. 17–32, Feb. 1981.
[25] Y. Pipelzadeh, B. Chaudhuri, and T. C. Green, “Inertial response from Jae-Young Park (Member, IEEE) received the B.S. degree (Hons.) in electrical
remote offshore wind farms connected through VSC–HVDC links: A engineering from Konkuk University, Seoul, South Korea, in 2015, and the Ph.D.
communication–less scheme,” in Proc. IEEE Power Energy Soc. Gen. degree in convergence IT engineering from the Pohang University of Science and
Meeting, 2012, pp. 1–6. Technology, Pohang, South Korea, in 2022. He is currently a Senior Researcher
[26] T. Sugiyama, T. Nishiwaki, S. Takeda, and S. Abe, “Measure- with the Korea Institute of Energy Research, Daejeon, South Korea. His research
ments of synchronous machine parameters under operating condition,” interests include self-healing power systems, renewable energy resources, and
IEEE Trans. Power App. Syst., vol. PAS-101, no. 4, pp. 895–904, grid-forming power converters.
Apr. 1982.
[27] L. Wang and M. N. Thi, “Stability enhancement of a PMSG-based offshore
wind farm fed to a multi-machine system through an LCC-HVDC link,” Young-Jin Kim (Senior Member, IEEE) received the B.S. and M.S. degrees
IEEE Trans. Power Syst., vol. 28, no. 3, pp. 3327–3334, Aug. 2013. in electrical engineering from Seoul National University, Seoul, South Korea,
[28] K. Zhou et al., “Topologies and control of VSC-HVDC systems for grid in 2007 and 2010, respectively, and the Ph.D. degree in electrical engineering
connection of largescale off-shore wind farms,” in Proc. Int. Conf. Elect. from the Massachusetts Institute of Technology, Cambridge, MA, USA, in 2015.
Mach. Syst., Wuhan, China, 2008, pp. 2357–2361. From 2007 to 2011, he was with Korea Electric Power Corporation as a Power
[29] Normalized Signal Test, PJM, 2019. [Online]. Available: https://www.pjm. Transmission and Distribution System Engineer. He was also a Visiting Scholar
com/-/media/markets-ops/ancillary/reg-d.ashx with the Catalonia Institute for Energy Research in 2014, and a Postdoctoral
[30] M. Raza, E. Prieto-Araujo, and O. Gomis-Bellmunt, “Small-signal stabil- Researcher with the Center for Energy, Environmental, and Economic Systems
ity analysis of offshore ac network having multiple VSC-HVDC systems,” Analysis, Energy Systems Division, Argonne National Laboratory from 2015
IEEE Trans. Power Del., vol. 33, no. 2, pp. 830–839, Apr. 2018. to 2016. He joined the Faculty with the Pohang University of Science and
[31] P. W. Sauer and M. A. Pai, Power System Dynamics and Stability. Upper Technology, where he is currently an Associate Professor with the Department
Saddle River, NJ, USA: Prentice–Hall, 1998, pp. 95–99. of Electrical Engineering. His research interests include distributed generators,
[32] P. Kundur, Power System Stability and Control. New York, NY, USA: renewable energy resources, and smart buildings.
McGraw–Hill, 1994, pp. 341–444.
[33] J. Z. Zhou, H. Ding, S. Fan, Y. Zhang, and A. M. Gole, “Impact of
short–circuit ratio and phase–locked–loop parameters on the small–signal Oriol Gomis-Bellmunt (Fellow, IEEE) received the Degree in industrial en-
behavior of a VSC–HVDC converter,” IEEE Trans. Power Del., vol. 29, gineering from the School of Industrial Engineering of Barcelona, Technical
no. 5, pp. 2287–2296, Oct. 2014. University of Catalonia (UPC), Barcelona, Spain, in 2001, and the Ph.D. degree
[34] S. V. Bozhko, R. Blasco-Gimenez, R. Li, J. C. Clare, and G. M. Asher, in electrical engineering from the UPC in 2007. In 1999, he joined Engitrol S.L.,
“Control of offshore DFIG–based wind farm grid with line–commutated where he was a Project Engineer with Automation and Control Industry. Since
HVDC connection,” IEEE Trans. Energy Convers., vol. 22, no. 1, 2004, he has been with Electrical Engineering Department, UPC, where he is
pp. 71–78, Mar. 2007. a Professor and participates with CITCEA-UPC Research Group. Since 2020,
[35] R. Vijayapriya, P. Raja, and M. P. Selvan, “A modified active power he has been an ICREA Academia Researcher. His research interests include the
control scheme for enhanced operation of PMSG-based WGs,” IEEE fields linked with electrical machines, power electronics, and renewable energy
Trans. Sustain. Energy, vol. 9, no. 2, pp. 630–638, Apr. 2018. integration in power systems.
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on May 06,2024 at 05:50:37 UTC from IEEE Xplore. Restrictions apply.