20 Es
20 Es
5 x 11 or 11 x
17), which may affect printing. Please adjust your printer settings
according to the size of each page you wishRedistribution
to print. or publication of this document
by any means, is strictly prohibited.
Service Manual l
20 ES
(Begin Spec G)
LS-11a
i Redistribution or publication of this document
by any means, is strictly prohibited.
ELECTRICAL SHOCK CAN CAUSE GENERAL SAFETY PRECAUTIONS
SEVERE PERSONAL INJURY OR DEATH
• Coolants under pressure have a higher boiling point
• Remove electric power before removing protective than water. DO NOT open a radiator or heat ex-
shields or touching electrical equipment. Use rub- changer pressure cap while the engine is running.
ber insulative mats placed on dry wood platforms Allow the generator set to cool and bleed the system
over floors that are metal or concrete when around pressure first.
electrical equipment. Do not wear damp clothing
(particularly wet shoes) or allow skin surface to be • Benzene and lead, found in some gasoline, have
damp when handling electrical equipment. been identified by some state and federal agencies
as causing cancer or reproductive toxicity. When
• Use extreme caution when working on electrical checking, draining or adding gasoline, take care not
components. High voltages can cause injury or
to ingest, breathe the fumes, or contact gasoline.
death. DO NOT tamper with interlocks.
• Follow all applicable state and local electrical • Used engine oils have been identified by some state
codes. Have all electrical installations performed by or federal agencies as causing cancer or reproduc-
a qualified licensed electrician. Tag and lock open tive toxicity. When checking or changing engine oil,
switches to avoid accidental closure. take care not to ingest, breathe the fumes, or con-
tact used oil.
• DO NOT CONNECT GENERATOR SET DIRECT-
LY TO ANY BUILDING ELECTRICAL SYSTEM. • Provide appropriate fire extinguishers and install
Hazardous voltages can flow from the generator set them in convenient locations. Consult the local fire
into the utility line. This creates a potential for elec- department for the correct type of extinguisher to
trocution or property damage. Connect only use. Do not use foam on electrical fires. Use extin-
through an approved isolation switch or an ap- guishers rated ABC by NFPA.
proved paralleling device.
• Make sure that rags are not left on or near the en-
HIGH VOLTAGE GENERATOR SETS gine.
(1.9kV to 15kV) • Remove all unnecessary grease and oil from the
unit. Accumulated grease and oil can cause over-
• High voltage acts differently than low voltage. Spe- heating and engine damage which present a poten-
cial equipment and training is required to work on or tial fire hazard.
around high voltage equipment. Operation and
maintenance must be done only by persons trained • Keep the generator set and the surrounding area
and qualified to work on such devices. Improper use clean and free from obstructions. Remove any de-
or procedures will result in severe personal injury or bris from the set and keep the floor clean and dry.
death.
• Do not work on this equipment when mentally or
• Do not work on energized equipment. Unauthorized physically fatigued, or after consuming any alcohol
personnel must not be permitted near energized or drug that makes the operation of equipment un-
equipment. Due to the nature of high voltage electri- safe.
cal equipment, induced voltage remains even after
the equipment is disconnected from the power • Substances in exhaust gases have been identified
source. Plan the time for maintenance with autho- by some state or federal agencies as causing can-
rized personnel so that the equipment can be de-en- cer or reproductive toxicity. Take care not to breath
ergized and safely grounded. or ingest or come into contact with exhaust gases.
TITLE PAGE
SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Service Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Generator Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Generator Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Voltage Reconnection with Optional Instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
GENERATOR TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
Troubleshooting Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
Flow Chart A. No Build Up of AC Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
Flow Chart B. AC Output Voltage Builds Up, But is Unstable . . . . . . . . . . . . . . . . . . . 6
Flow Chart C. AC Output Voltage Builds Up, But High or Low . . . . . . . . . . . . . . . . . . 6
Flow Chart D. AC Output Voltage Builds Up, But Field Breaker Trips . . . . . . . . . . . 7
Flow Chart E. Unbalanced Generator Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . .8
ADJUSTMENTS AND TESTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
DC CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Optional Control Panel Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Engine Accessories and Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
ENGINE CONTROL SYSTEM OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
25
Starting Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Start-Disconnect Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Stopping Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Emergency Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
ENGINE CONTROL TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Troubleshooting Engine Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
CONTROL COMPONENT CHECKOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
FUEL SYSTEM / GOVERNOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30
Gasoline Carburetor Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33
Gas Mixture and Idle Speed Stop Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Electronic Governor Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
TEST EQUIPMENT A centrifugal blower, on the front end of the rotor shaft,
circulates the generator cooling air which is drawn in
Most of the test procedures in this manual can be per- through the end bell cover and discharged through an
formed with a multimeter like the Simpson Model 260 outlet at the blower end.
BRUSHLESS TORQUE TO
BLOWER
EXCITER ROTOR 130-150 FT. LBS
(176-203 N•m)
TORQUE TO
55-60 FT. LBS
(75-81 N•m)
ROTOR-
THROUGH-STUD
KEY O-RING
SEAL
ENGINE-GENERATOR
ROTATING
ADAPTER
RECTIFIER
ASSEMBLIES
STATOR- BRUSHLESS
THROUGH-STUD STATOR ROTOR EXCITER STATOR
END BELL TORQUE TO 19-21
FT. LBS (26-28 N•m)
FIGURE 1. GENERATOR
GENERATOR OPERATION
no no
Push to reset beaker. Does generator If voltage is unstable, high or low, or causes breaker
AC output voltage build up? yes to trip, see Flow Charts B, C, or D.
no
yes
Is reference voltage across TB21-1 & 2 Flash exciter field per TEST [D]. Does generator
no output voltage build up?
20 VAC or more?
yes no
Check commutating reactor L21 Disconnect stator leads 1 & 2 from TB21- 1 & 2. Is
per TEST [H]. Replace if bad. yes reference voltage across leads 20 VAC or more now?
no
Check reference transformer T21 Check diodes CR1 through CR6 on rotor per TEST [E].
per TEST [I]. Replace if bad. Replace if bad.
Is exciter field voltage across Check wiring harness for shorts per Check exciter rotor winding per
TB21-7 & 8 7.0VDC or more? no TEST [K]. Replace if bad.
TEST [N]. Replace bad wiring.
yes
Check wiring harness for opens per Check SCR’s CR13 & CR16 Check generator rotor field winding
TEST [N]. Replace bad wiring. per TEST [G]. Replace if bad. per TEST [L]. Replace if bad.
Check exciter field winding Check diodes CR12, 14, & 15 Check generator stator windings
per TEST [J]. Replace if bad. per TEST [F]. Replace if bad. per TEST [M]. Replace if bad.
no
yes
Does adjustment of Dampening Control R27 on Is voltage stable within spec at no load to full load range
VR21 per adjustment [B] result in stable voltage? yes of generator set?
no no
yes
no
no
Is jumper wire W10 connected correctly on Are generator output leads properly connected?
VR21 for desired voltage? See Figure 19 on See Figure 19 and correct if needed.
page 18 and correct if needed..
FLOW CHART D. AC OUTPUT VOLTAGE BUILDS UP, BUT FIELD BREAKER TRIPS
START
Does AC output voltage build up to 140% or Check for any loose or broken wires
more of rated voltage before breaker trips? yes or connections on VR21 assembly.
no
Check diodes CR1 through 6 in rotor Check diode CR15 on VR21 per
assembly per TEST [E]. Replace if bad. TEST [F]. Replace if bad.
Check exciter stator winding Check reference transformer T21 and connections
per TEST [J]. Replace if bad. per TEST [I]. Replace if bad.
Check exciter rotor winding per Check generator stator leads for proper
TEST [K]. Replace if bad. connection. See Figure 19, page 18.
yes
yes
yes
GENERAL
[C]
All of the following Adjustments and Tests can be per-
formed without disassembly of the generator. They
should be used for testing generator and regulator com- VOLTAGE REGULATOR CHECKOUT
ponents in conjunction with the troubleshooting flow
charts. The solid state voltage regulators (VR21) can be
checked out on the bench for proper operation or location
WARNING Troubleshooting procedures presents of faulty components. The following test equipment (one-
hazards of electrocution, asphyxiation, burns, cuts, each) is required for a proper checkout.
and other personal injury or death. Review Safety
Precautions. Service personnel must be trained and REF. DESIGNATION TEST EQUIPMENT
experienced.
S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switch
[A]
L21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reactor
F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fuse, 5 Amps
T1 . . . . . . . . . . . . . Transformer, Variable 2 Amp 0-150V
V2 . . . . . . . . . . . . . . Voltmeter, DC ± 2% of Full Scale 3,
VOLTAGE CALIBRATION ADJUSTMENT Scale 0-50 and 0-150V and 0-10V
V1 . . . . . . . Voltmeter, AC ± 2% @ 10VAC, 1% @ 150V
The calibration adjustment is made using an accurate AC R1 . . . . . . . . . . . . . . . . . . . . . . Resistor, 100-Ohm 400W
voltmeter to observe generator output voltage and to set T21 . . . . . . . . . . . . . . . . . . . Transformer, Input 315-0386
the correct no load voltage. If voltage regulator VR21
printed circuit board has been replaced, it may be neces- Transformer T21 and reactor L21 are a part of the voltage
sary to make a calibration adjustment. To obtain the cor- regulator assembly (VRA21); these are the only parts ob-
rect output voltage, proceed as follows: tainable with an Onan part number. the big 100 ohm 400
watt resistor (R1) serves as the field during checkout.
1. If set has a voltage adjust potentiometer (R22) on
the meter panel, set pointer halfway between mini- Bench Check:
mum and maximum positions.
1. Remove voltage regulator from unit according to
2. With unit running at no load, turn generator voltage
procedure given for voltage regulator replacement.
potentiometer R26 on VR21 (Figure 5) clockwise to
increase output voltage; turn R26 counterclockwise 2. Referring to Figure 5 and Table 1, connect test
to decrease output voltage. equipment to the printed circuit board VR21 termi-
nals as follows:
PIN 8 (+)
12 AMP
300 VOLT DIODE
1. Locate terminals 7 (–) and 8 (+) on voltage regulator 1. Disconnect all leads from assembly to be tested.
printed circuit board (VR21). 2. Connect one test lead to F1+ stud and connect other
2. Use a six volt dry cell battery with two clip leads and lead to CR1, CR2, and CR3 in turn; record resist-
a 12 amp, 300 volt diode as shown in Figure 6. If a ance value of each rectifier.
six volt battery is not available, a 12 volt automotive 3. Connect one lead to F2– stud and connect other
battery can be used by adding a 20-ohm resistor in lead to CR4, CR5, and CR6 in turn; record resist-
series; or a 24 volt automotive battery can be used ance value of each rectifier.
by increasing the resistance to 40-ohms.
4. Reverse ohmmeter leads from steps 2 and 3 and re-
3. After starting engine, touch positive (+) battery lead cord resistance value of each rectifier F1+ to CR1,
to the +8, and negative (–) lead to –7 terminals just CR2, and CR3 and F2– to CR4, CR5, and CR6.
long enough until voltage starts to build up or dam-
age may occur to exciter-regulator system. 5. All the resistance readings should be high in one
test and low in the other test. If any reading is high or
WARNING HAZARDOUS VOLTAGE. Touching low in both tests, rectifier assembly is defective.
uninsulated high voltage parts inside the control box
can result in severe personal injury or death. Mea- 6. Replace defective rectifier assembly with new, iden-
surements and adjustments must be done with care tical part.
to avoid touching high voltage parts. Use 24 lbs-in. (2.7 Nm) torque when tightening nuts on F1+
For your protection, stand on a dry wooden platform and F2–, and CR1 through CR6.
or rubber insulating mat, make sure your clothing
and shoes are dry, remove jewelry from your hands
and wear elbow length insulating gloves. DIGITAL
OHMMETER
TEST PROCEDURES
All of the following tests can be performed without disas-
sembly of the generator. Use the following test proce-
dures for testing generator components in conjunction
with the troubleshooting charts.
[E]
TESTING ROTATING RECTIFIERS
Two different rectifier assemblies make up the rotating
rectifier bridge assembly, Figure 7. Using an accurate
ohmmeter, test each CR using negative and positive po-
larities. Test rectifiers as follows: FIGURE 7. TESTING ROTATING RECTIFIERS
[F]
DIGITAL
TESTING OUTPUT BRIDGE DIODES OHMMETER
The output bridge rectifier diodes (Figure 8), CR12,
CR14, and CR15, are located on the voltage regulator
printed circuit board. Using an accurate ohmmeter, test
diodes CR12, CR14, and CR15 as follows:
1. Connect one ohmmeter lead to each end of diode
and observe resistance reading, Figure 9.
2. Reverse ohmmeter leads and again observe resist-
ance readings.
A good diode has a higher reading in one direction
than the other. If both readings are high, or low, diode
is defective.
3. Replace defective diodes with new, identical parts.
DIGITAL
OHMMETER
X1 X2
[J]
TESTING BRUSHLESS EXCITER STATOR
Like the generator, the brushless exciter stator (Figure
12) can be tested for open or shorted windings and
grounds.
Testing for Open or Shorted Windings:
Disconnect F1+ and F2– exciter field leads from terminal
block in generator end bell. The resistance between field
leads should be 10.98 to 13.42 ohms at 68° F (20° C).
[H]
TESTING REACTOR
The reactor assembly L21 leads are marked 1, 2, 3 and 4. MEGGER OR
Wires 1-2 and 3-4 are wound on the same iron core. INSULATION
RESISTANCE
METER
1 2
[I] [K]
TESTING REFERENCE TRANSFORMER TESTING BRUSHLESS EXCITOR ROTOR
(ARMATURE)
The transformer T21 has four leads marked H1, H2, X1,
and X2. H1-H2 are the primary leads. X1-X2 are the sec- The brushless exciter rotor (Figure 13), can be tested for
ondary leads. open or shorted windings, or grounds.
MAIN ROTOR
LEADS F1+, F2–
FIGURE 13. TESTING EXCITER ARMATURE Testing for Open or Shorted Winding:
Testing for Open or Shorted Windings: All resistance values should be within ±10% of values
specified in Table 2 at 77° F (25° C). Perform tests as fol-
Use a Wheatstone Bridge for this test. Disconnect main lows:
rotor field leads which connect to rotating rectifier assem-
blies at F1+ and F2–. Disconnect lead wires from diodes 1. Remove rotor leads F1+ and F2–0 from rotating rec-
CR1 through CR6. Test between exciter lead pairs tifier assemblies.
T1-T2, T2-T3 and T1-T3. Resistance should be 0.5 to 0.6 2. Using ohmmeter, check resistance between F1 and
at 68° F (20° C). F2 leads, Figure 15.
Testing for Grounds: 3. Replace defective rotor with new, identical part if re-
sistance readings are not within limits shown in
Use a Megger or insulation resistance meter that applies Table 2.
500 VDC or more for this test.
With all generator leads disconnected from rotating recti- DIGITAL
fiers CR1 through CR6, apply test leads between any CR OHMMETER
lead and the rotor lamination. Reading should be 1 meg-
ohm (1,000,000 ohms) or greater. If not, the exciter rotor
is questionable and might require removal for oven dry- MAIN ROTOR
ing and retest. A shorted rotor must be replaced. LEADS F1+, F2–
[L]
TESTING GENERATOR ROTOR
For these tests, use an ohmmeter on R x 100 scale.
Testing for Grounds:
On brushless type generators, check for grounds be-
tween each rotor lead and the rotor shaft, Figure 14. Per- FIGURE 15. TESTING ROTOR FOR AN OPEN CIRCUIT
form tests as follows:
TABLE 2. RESISTANCE VALUES FOR ROTORS
1. Remove rotor leads F1+ and F2– from rotating recti-
fier assemblies.
ROTOR RESISTANCE
2. Connect ohmmeter leads between F1+ and rotor
ROTOR STACK LENGTH OHMS @77° F (25° C)
shaft and between F2– and rotor shaft. Meter
should not register. 201-2984 5.8765 2.75
3. If meter registers, rotor is grounded. 201-2985 7.125 1.80
4. Replace grounded rotor with new, identical part.
Testing for Grounds: 1. Inspect all wires for breaks, loose connections, and
reversed connections. Refer to applicable wiring
Some generators have ground connections to the frame. diagram.
Check wiring diagram. 2. Remove wires from terminals at each end and using
Using an ohmmeter set at R x 100, test each stator wind- an ohmmeter, check each wire end to end for conti-
ing for shorts to laminations. A reading less than one nuity or opens.
megohm indicates a ground. 3. Using an ohmmeter, check each wire against each
of the other wires for possible shorts or insulation
Testing for Open or Shorted Windings: breaks under areas covered by wrapping material.
Test for continuity between coil leads shown in Figure 16; 4. Reconnect or replace wires according to applicable
all parts should have equal resistance. Use an accurate wiring diagram.
instrument for this test such as a Kelvin Bridge. The prop-
er resistance values for the ES generator set are given in
Table 3. All resistances should be ±10% of value shown. [O]
If any windings are shorted, open or grounded, replace
the stator assembly. Before replacing the assembly, VR21 REPLACEMENT
check the leads for broken wires or insulation.
Use the following procedure for replacing the voltage
regulator PC board.
1. Stop engine.
2. Disconnect and if necessary, label the following
wires: 3, 4, 5 or 6, 7, 8, 9, and 10.
3. Remove four screws at corners.
4. Remove used PC board.
5. Install new PC board; secure with four screws.
6. Reconnect wires removed in step 2 at the proper
terminals.
7. Place jumper W10 at proper terminals for your par-
ticular voltage code and voltage connection. See
Figures 17 and 19.
WHEATSTONE 8. Perform Voltage Calibration and Stability Adjust-
BRIDGE ment procedures [A] and [B] to obtain the correct
generator output voltage and stability with new PC
FIGURE 16. TESTING STATOR WINDINGS board in set.
STATOR STACK
LENGTH IN RESISTANCE
STATOR PHASE INCHES (mm) OHMS @68° F (20° C)
START / STOP /
REMOTE SCALE INDICATOR
SWITCH LAMPS
INDICATOR
LAMPS PHASE SELECTOR
SWITCH
CIRCUIT HOUR
BREAKERS METER
VOLTAGE REGULATOR
ASSEMBLY (GENERATOR AC)
FRONT PANEL
CONNECTOR P1
FAULT RELAY
ENGINE MONITOR
CONNECTOR P2 CIRCUIT BOARD
WATER
TEMPERATURE
SENDER (E2)
LOW ENGINE
TEMPERATURE
SWITCH (S4)
AIR GAP
END BELL
SWITCH
CONTACTS
START
no
no
Jumper battery cable B+ connection to B+ starter Check battery cables for clean and tight connections
solenoid terminal. Does engine crank? no (ref. Checkout [B]. Check B+ starter solenoid and motor-if
bad, repair or replace.
yes
yes
START
Does fuel solenoid energize when S10 is in Start Check fuel solenoid and related wiring. Repair or
position? no replace as needed.
yes
yes
Is there a spark at the spark plug? no Check ignition wiring and components.
yes
FLOW CHART C. ENGINE STARTS BUT STOPS WHEN START SWITCH IS RELEASED
START
Does K4 Power Relay stay energized when start Check all wiring to K4. Check for fault condition.
switch is released? no check if fault relay A11, K6 is energized.
yes
yes
Is there a spark at the spark plugs? no Check ignition wiring and components.
yes
yes
TROUBLESHOOTING ENGINE CONTROL breakers, DC voltage regulator, etc,. plug into the board.
If an external component is suspected of causing a prob-
Refer to Engine Control System Operation and the sche- lem, disconnect its associated jack (J1, J2 or J3) from the
matics on pages 40 and 41 when troubleshooting this board (Figures 30 and 31) and check continuity of wiring
control. Repair information is not extensive since the sol- and the component. Note some switches are NC and
id-state printed circuit board lends itself more to replace- some NO with unit at rest. Individual components can be
ment than repair. External components such as leads, checked out as referenced in “Control Component
switches, indicator lights, relays gauge senders, circuit Checkout” on page 29.
[A] [D]
BATTERY CHECKOUT RELAY CHECKOUT
Check charge condition of the battery with a hydrometer. 1. Connect 12 volts across relay coil terminals. Relay
The electrolyte specific gravity should be about 1.260 for should activate if coil is okay.
a fully charged battery at 80° F (27° C). If not, add distilled 2. Connect 12 volts to one side of relay contacts.
water to keep electrolyte at proper level and recharge the 3. Connect a voltmeter to other side of relay contact
battery. If battery will not recharge, replace it. and 12 volt source. If 12 volts appear when relay is
If the battery loses excess water, the generator charge energized, contact is okay. The 12 volt reading ap-
rate may be too high. Likewise, if battery state of charge pears in reverse order when checking normally
is not maintained, the charge rate may be too low. Refer closed (NC) contacts.
to CHARGING CIRCUIT CHECKOUT [C].
[F]
BATTERY CABLE CHECKOUT
With the starter motor operating, check the voltage drops
(1) from the battery negative post (not the cable clamp) to
the cylinder block, (2) from the battery positive post to the SWITCH CHECKOUT
battery terminal stud on the solenoid. Normally, each of
1. Remove battery B+cable.
these should be less than 0.3 volt. If extra long battery
cables are used, slightly higher voltage drops may result. 2. Place ohmmeter leads across switch.
Thoroughly clean all connections in any part of the circuit 3. Activate switch. If meter reads continuity, switch is
showing excessive voltage drop. good.
NATURAL GAS
FUEL VALVE
PRESSURE
SWITCH
LPG FUEL
REGULATOR
LPG FUEL
VALVE
FUEL
SELECTION
SWITCH PLUG IN
NATURAL GAS
SUPPLY INLET
PLUG IN LPG
SUPPLY INLET
CARBURETOR
GASOLINE FUEL
FILTER
FUEL PUMP
GASOLINE
SUPPLY INLET
LPG FLOW
ADJUSTMENT NATURAL GAS
COCK FUEL VALVE
GAS MIXER
PRESSURE
SWITCH
LPG LIQUID
CONVERTOR
FUEL
SELECTION
SWITCH
PLUG IN
NATURAL GAS
SUPPLY INLET
PLUG IN LPG
CARBURETOR
GASOLINE FUEL SUPPLY INLET
FILTER
FUEL PUMP
GASOLINE
SUPPLY INLET
Idle Speed Stop and Mixture Adjustments 4. Switch to LPG (which may be done under load) and
turn the LPG flow cock counter clockwise (richer)
1. Connect a tachometer if the set does not have a until the engine begins to miss and then clockwise
Hertz/RPM meter, start the set up on natural gas (leaner) until it again begins to miss. Then turn the
and let the engine warm up under approximately 1/4 cock to a position midway between the two extreme
rated load. positions.
AIR INLET
THROTTLE
GAS INLET LEVER
POWER MIXTURE
COCK
GAS INLET
GAIN 1
STABILITY 1
SPEED
TRIM
VIEW AA
DIP
SWITCHES
GOVERNOR
ROD
BALL STUD
GOVERNOR (MOUNTED TO CENTER
THROTTLE LEVER OF GOVERNOR LEVER)
LEVER
THROTTLE LEVER
SCREW
GOVERNOR
ROD LENGTH
49 MM
60°
AT CLOSED
THROTTLE
POSITION
No. 612-6682 sh 1 of 2
Rev. C Sys: CADAM
Modified 4/5/95
FIGURE 34. DC CONTROL (2 LIGHT) SHEET 1
No. 612-6682 sh 2 of 2
Rev. C Sys: CADAM
Modified 4/5/95
FIGURE 35. DC CONTROL (2 LIGHT) SHEET 2
No. 612-6681 sh 1 of 2
Rev. C Sys: CADAM
Modified 4/5/95
FIGURE 36. DC CONTROL (9 LIGHT) SHEET 1
No. 612-5959 sh 1 of 1
Rev. Sys: board
Modified 5/10/95
FIGURE 39. THREE PHASE GENERATOR CONTROL
No. 338-3282 sh 1 of 2
Rev. A Sys: CADAM
Modified 4/4/95
FIGURE 40. ENGINE HARNESS
LEAD TABULATION
FROM TO
STATION STATION
P1-1 CB1-1
P1-2 J1-1
P1-3 J1-5
P1-4 J1-7
P1-5 J1-9
P1-6 J1-11
M2-3 M3-3
P1-8 M2-2
P1-9 M3-2
P1-12 J1-12
P1-13 J1-4
P1-14 J1-2
P1-15 GND
CB1-1 CB2-1
M2-1 M1- (+)
M2-1 M3-1
M4-1 M3-1
M4-2 M3-3
CB13-1 CB2-1
K5-86 GND
K5-85 J1-4
K5-87 P1-13
M2-3 GND
M1- (–) M3-3