Unit 5
Unit 5
CHAPTER 2
2.1 GENERAL
required for wind farm and grid interaction at distribution system operator
level; otherwise, it leads to long delay in connection approvals for developers
and wind turbine manufacturers. In addition, large variety of grid code
requirements, with no technical justification will make complex situation for
wind turbine manufacturers. For example, some generators will not meet the
specific grid code requirements of some countries like Germany.
to the fault duration while Denmark has the lowest short circuit time duration
Voltage drops down to 0.75 p.u have a duration of several cycles while
voltage drops down to 0.25 p.u from the rated voltage have duration of
several seconds up to minutes.
1. Generating stations
3. Sub-stations
4. Tie-lines
7. Electric supply-lines
8. Overhead lines
9. Service lines
10. Works
3. Connection Code
4. Operating Code
6. Miscellaneous
grid
2. System planning
7. Non compliance
The State Transmission Utility (STU) which has to play a key role
in the implementation of the grid code may be required to act decisively for
maintaining the grid regimes for discharging its obligations.
2. Frequency control.
These are the three main points that new grid codes must adapt for
wind farm connection. The most worrying problem that wind farms must face
is a voltage dip in the grid. The effects of transient faults may propagate over
very large geographical areas and the disconnection of wind farms under
faulty conditions could pose a serious threat to network security and security
of supply, because a great amount of wind power could be disconnected
simultaneousl Bharat Singh & Singh (2009) says
enhancement.
Indian Wind Grid Code (IWGC) contains certain rules for planning,
connection, and operation on Indian grid. The structure of Indian wind grid
code is as follows (PRDC, 2009)
Also, in the draft report of Indian wind grid code (PRDC, 2009)
contains the following aspects in the connection code i.e transmission system
voltage requirements, reactive power capability of wind farms, frequency
tolerance range, active power control, situation where wind turbines can be
disconnected from grid, situation where wind turbines must remain connected
to the grid, ability to withstand repetitive faults, protection, signals, data
communication requirements, system regarding instruments, wind farm
equipment, auxiliary supply, revenue metering, procedure for site access,
operational activities, maintenance and responsibilities for operational safety.
4. Communication requirements
In India, the LVRT requirements are applicable for the wind farms
having more than 66KV voltage penetration in the grid. It is tabulated in the
Table 2.1. (PRDC, 2009) Below this level, disconnection is allowed; On the
contrary, in India the fault occurrence in the sub transmission systems is very
frequent. At that time, thermal stress of the wind turbine is also high.
Therefore, it is necessary to disconnect from the grid like Danish grid code.
2
4
Vf
3
0 T 3000
Time (ms)
Where
Table 2.1 Fault clearing time and voltage limits of Indian grid code
Voltage (KV)
Limits
Nominal Maximum Minimum
of variation (%)
400 +5 to -10 420 360
220 +11 to -9 245 200
132 +10 to -9 145 120
110 +10 to -12.5 121 96.25
66 +10 to -9 72.5 60
33 +5 to -10 34.65 29.7
32
4. Communication requirements
Capability (ATC) for one time block in the congested corridor and loading of
transmission lines beyond operating limit.
levied for over drawl in the importing control area and at frequencies above
50 Hz. Congestion charge would be levied for under-drawl in the exporting
control area.
4. Communication requirements
Some of the problems associated with the fault are pointed out by
Athula Rajapakse et al 2009, i.e automatic reconnection of the wind power in
a particular area causes frequency problems, increasing penetrations of wind
power may increase or decrease short circuit levels and diminishing of
the power transfer capability in wind turbine generator, results in mechanical
over speeding of the machine and the turbine blades, this leads to mechanical
stress on blades and the other rotating parts.
protection and control settings. Turbine blade pitch control must be capable of
regulating the input mechanical power. During faults, fast pitch control of
blades will limit the over speeding of rotating elements. The sudden
disconnection of the wind turbine generators while the capacitor bank is still
connected can result in over voltage at the generator terminals. This is a major
protection problem related to the large wind farms.
standard IEC
61000-2-1, 1990 also voltage sag is an alternative name for the phenomenon
voltage dip (IEC 61000-2-8, 2002) (Roberto Chouhy Leborgne 2007).
This thesis focused on the first method i.e to control the d and q
axis rotor currents.
hour also boost converter integrated in dc link to maintain the dc link voltage
during voltage sag.
DFIG Grid
3
Wind 3
Turbine
Figure 2.3 M-G Set with a Flywheel for low voltage ride through
the ions from one electrode to the other (Kuldeep Sahay & Bharti Dwivedi
2009).
DFIG Grid
3
Wind 3
Turbine
SDBR
DFIG Control
Grid
3
Bypass switch
Wind 3
Turbine Resistor
Figure 2.6 shows the TCSC connected wind farm. There is TCSC
in each phase and is controlled separately and capacitors are used for reactive
power compensation. The major problem found was designing of inductor
and capacitor values for TCSC (Nitin N Joshi & Mohan 2006).
DFIG Grid
3
TCSC
Wind 3
Turbine
DFIG Grid
3
DFIG Grid
3
SVC
Wind 3
Turbine
Figure 2.9 shows the STATCOM based wind farm and Figure 2.8
shows the SVC based wind farm. Marta Molinas et al (2008) show that the
STATCOM performs better than the SVC in terms of LVRT capability if the
same rating is assumed for the devices.
DFIG Grid
3
A common dc-link of the rotor side converter (RSC) and grid side
converter (GSC) supported static compensator (STATCOM) is proposed for
the voltage ride through capability by Behera &Wenzhong Gao (2009).
DFIG Grid
3
Wind 3
Turbine
DFIG Grid
3
Wind DVR 3
Turbine Filter
DC Link
Storage DC
Unit
AC
Rotor Side Grid Side
3 Converter Converter
DC Link
DVR method affords the stable operation for the DFIG wind
turbine system under different types of grid faults (Ahmad Osman Ibrahim et
al 2011). Amutha & Kalyan Kumar (2013) proposed a DVR based method to
improve the fault ride-through capability of induction generator wind farms.
Behera et al (2010b) proposed DVR structure which is operated in such a
fashion that it does not supply or absorb any active power during the steady-
state operation. The main purpose of a DVR is to protect sensitive loads from
sags/swells and interruptions in the supply side. The capacitor supported
45
DVR, while operating in zero power mode, regulates the load voltage even
when the source and load voltages are unbalanced.
DC
AC
DFIG Grid
3
Wind SWITCH 3
Turbine
DFIG
Grid
3
SFCL
Wind 3
Turbine
controller
Cryogenic
system
SMES Unit
DFIG
Grid
3
Wind 3
Turbine
Dynamic sag corrector and compressed air energy storage are some
of the additional techniques for better LVRT (Nicolás Louzán Pérez 2003).
Generally, wind parks are located away from load centers, and therefore,
require high voltage transmission before connecting to the grid. ABB
Company uses HVdc LIGHT technology for this purpose. This voltage-fed
system has the advantages of multi-terminal capability, control of active and
reactive power independently, and mitigation of flicker or grid instability by
fast reactive energy control (Bimal K. Bose 2012).
2.11.1 Reclosing
The flow of fault current reduces the voltage at the substation bus
for that phase. The other two phases experience some increase in voltage
49
(swell). Thus, for a fault in one circuit, the customers on that phase on all
three circuits experience voltage sag until the circuit breaker is opened.
2.12 STANDARDS
the engineering principles and practices for supplying power and grounding of
sensitive electronic equipment. IEEE Standard 1250 describes the electrical
environment along with various solutions to power quality problems. IEEE
Standard 1159 is followed with a more rigorous and in depth set of definitions
for monitoring power quality.
1. Flicker
2. Switching operations
3. Harmonic analysis
Voltage quality is the main power quality problem. It has two types
i.e
1. Voltage variation
2. Flicker
Table 2.3 shows the voltage unbalance limits in the Indian wind
grid code (PRDC 2009).Voltage dips and interruptions that are reductions of
52
Voltage
Unbalance (%)
level(KV)
400 1.5
200 2
<200 3
2.13.3 Flicker